Đây là tài liệu chỉ dẫn tính toán lựa chọn chống sét cho tủ điện trung thế trong nhà Selection surge arresster for indoor medium voltage Switchgear. Step 1: Define technical parameters of system Maximum operation voltage of system Um = (1.05÷1.1Ur) In Vietnam, Um =1.1Ur Define earth fault factor:
Trang 1GUIDE FOR SURGE ARRESTOR
SELECTION
Trang 2History Records
No Revision
ELECTRIC AND ESTIMATION TEAM
2
Trang 31 Scope
2 Introduction
3 Define condition service
4 Calculating and selection for rated voltage
5 Selection for normal discharge current
6 Example
3 ELECTRIC AND ESTIMATION TEAM
Trang 41 Scope
This document applies to non-linear
metal-oxide resistor type surge arrester without
spark gaps designed to limit voltage
surges on A.C power circuits
ELECTRIC AND ESTIMATION TEAM
4
Trang 5• A Define condition service • B Calculating for rated voltage
ELECTRIC AND ESTIMATION TEAM
5 This document will be pressent 3 steps to select a SA as below:
• C Selection for normal discharge current
Trang 6A Define condition service
- Indoor or outdoor
- Temperature of environment
- Atitude above sea level: this information is
very important to calculating operating
voltage
Etc…
ELECTRIC AND ESTIMATION TEAM
6
Trang 7B Calculating for rated voltage
• Step 1: Define technical parameters of
system
- Maximum operation voltage of system
Um = (1.05÷1.1Ur)
In Vietnam, Um =1.1Ur
- Define earth fault factor:
ELECTRIC AND ESTIMATION TEAM
7
4 wiring repeat grounded system 1.25~
1.35
3 wiring- Solidly-Grounded System 1.4
3 wiring- High impedance-Grounded System 1.73
3 wiring- - Delta-Grounded System 1.73
- Define temporary over voltage:
Utov = Ke * Um/ √3
Trang 8B Calculating for rated voltage
• Step 2: Define continuously operation
voltage: COV (MCOV)
- Uc ≥ Um/ √3
ELECTRIC AND ESTIMATION TEAM
8
• Step 3: Define overvoltage withstand
capability
- Insulated neutral: t ≥ 2h
- Solidly grounded neutral: t = 10s
Trang 9C Selection for normal discharge current
- We select normal discharge current
following 2 table of IEC 60099 standard
ELECTRIC AND ESTIMATION TEAM
9
Trang 10C Selection for normal discharge current
ELECTRIC AND ESTIMATION TEAM
10
Trang 11Example 1: Selection SA for
system:22kV-25kA-solidly grounded (EVN project)
- Um = 1.1 * 22 = 24 (kV)
- Utov = 1.4 * 24/ √3= 19.42kV
- Uc ≥ 24/ √3 = 13.87
- Base on protective characteristics table, we
select SA 18kV with Uc = 15.3kV
ELECTRIC AND ESTIMATION TEAM
11
Trang 12- Define time duration:
T = Utov/Uc = 19.42/13.87 = 1.27
So, we easily to see in TOV curver the
time duration is 1000s >10s It satisfy
withstand condition requirement
- Following table 15 we will select the
normal discharge current is 10kA
- Conclusion : SA-18kV-10kA
ELECTRIC AND ESTIMATION TEAM
12
Trang 13Example 2: Selection SA for system:10kV-50kA-3 wiring- High impedance-Grounded System
(MONG DUONG project)
- Um = 1.1 * 10 = 11 (kV)
- Utov = 1.73 * 11/ √3= 11kV
- Uc ≥ 11/√3 = 6.35kV
- Base on protective characteristics table, we can select SA 9kV with Uc = 7.65
- Define time duration:
T = Utov/Uc = 11/7.65 = 1.43
We see in TOV curve the time duration approximate 70s < 2h It does not satisfy withstand condition requirement So we will select SA 10 kV, Uc = 8.4
T = Utov/Uc = 11/8.4 = 1.3
We see in TOV curve the time duration approximate 1000s It satisfy
Following table 15 we will select the normal discharge current is 10kA
Conclusion : SA-10kV-10kA
(So, in my opinion, we select SA 9kV for Mong Duong project is wrong.)
ELECTRIC AND ESTIMATION TEAM
13
Trang 14Example 3: Selection SA for system:6.6kV-25kA-3 wiring- High impedance-Grounded System
(SAMSUNG project)
- Um = 1.1 * 6.6 = 7.2 (kV)
- Utov = 1.73 * 7.2/ √3= 7.2kV
- Uc ≥ 7.2/√3 = 4.15kV
- Base on protective characteristics table, we can select SA 6kV with Uc = 5.1
- Define time duration:
T = Utov/Uc = 7.2/5.1 = 1.4
We see in TOV curve the time duration approximate 70s < 2h It does not satisfy withstand condition requirement So we will select SA 9 kV, Uc = 7.65
T = Utov/Uc = 7.2/7.65 = 0.9
We see in TOV curve the time duration > 10000s It satisfy
Following table 15 we will select the normal discharge current is 10kA
Conclusion : SA-9kV-10kA
(We bought SA 6kV for Sam Sung project is wrong Now, they are storing at inventory :D)
ELECTRIC AND ESTIMATION TEAM
14
Trang 15THANKS FOR WATHCHING
ELECTRIC AND ESTIMATION TEAM
15