Cơ bản về bảo vệ hệ thống điện Protection system is a complete arrangement of protection equipment and other devices required to achieve a specified function based on a protection principal. Protection equipment is a collection of protection device ( relay, fuse, etc.) excluded are device such as CT’s, CB’s, contactor, etc. Protection scheme is a collection of protection equipment providing a defined function and including all equipment required to make the scheme work (i.e. relays, CT’s, CB’s Batteries, etc.)
Trang 1POWER SYSTEM
PROTECTION
Fundamentals of
Protection Practice
Trang 2Why power system need the
protection system?
Severe disruption to normal routine of modern
society is likely if power outages are frequent or
prolonged
Many items of equipment are very expensive,
and the complete power system represent a very
large capital investment
Fault may represent a risk to life and/or property
Why power system need the
protection system?
5 Other
3 Control equipment
10 Instrument transformer
12 Transformer
15 Busbar
10 Underground Cable
45 Overhead line
% of faults Type of equipment
Trang 3Why power system need the
protection system?
2 Other
5 Series Fault
10
Three Phase Short
Circuit
5 Two Phase Short Circuit
18 Two Phase to Earth
60 One Phase to Earth
% of fault Type of faults
What can the protection system do?
Increase emphasis on reliability and
security of supply.
Prevent the diverse items of equipment
from the severe damage by detect and
disconnect elements of the power system.
Trang 4More fundamental
However, is the power system should operate
in a safe manner at all times No matter how well
designed, faults will always occur on a power
system
The provision of adequate protection is
therefore on integral part of power system
design
As requirements of reliability and economic are
largely opposed, power system design is
inevitable a compromise
Protection System
Protection system is a complete arrangement of
protection equipment and other devices required to
achieve a specified function based on a protection
principal.
Protection equipment is a collection of protection device
( relay, fuse, etc.) excluded are device such as CT’s,
CB’s, contactor, etc.
Protection scheme is a collection of protection
equipment providing a defined function and including all
equipment required to make the scheme work (i.e
relays, CT’s, CB’s Batteries, etc.)
Trang 5Protective Relay
Relay maybe classified according to the
technology used
electromechanical
static
digital
numerical
The different type have somewhat different
capabilities due to limitations of technology
used
Type of protective relay
a relay that responds to single quantity
a relay that responds to several quantities
a single relay containing several elements, each responding
independently to a different quantity
I >
I >
ANSI / IEC Relay Symbols
59N Neutral point
displacement relay 32
Directional
overpower relay
59 Overvoltage relay 27
Undervoltage
relay
55 Power factor relay 26
Overtemperature
relay
51V
Voltage restrained/controlled overcurrent relay 21
Distance relay
51N
Definite time earth fault overcurrent relay 14
Underspeed relay
51G
Inverse time earth fault overcurrent relay 12
Overspeed relay
IEC 60617 ANSI
Description IEC60617
ANSI Description
ω >
ω <
Z <
θ >
U<
P>
U I>
cos ϕ >
U>
U rsd>
Trang 6O I
ANSI / IEC Relay Symbols
87 Differential relay
81O Overfrequency relay 51
Inverse time
overcurrent relay
81U Underfrequency relay 50
Instantaneous
overcurrent relay
79 Autoreclose relay 49
Thermal relay
78 Phase angle relay 47
Negative sequence
voltage relay
67N Directional earth fault relay 46
Negative sequence
relay
67 Directional
overcurrent relay 37
Undercurrent relay
64 Earth-fault relay 37
Underpower relay
IEC 60617 ANSI
Description IEC 60617
ANSI Description
P<
I<
I 2<
U 2<
I>>
I >
I >
I >
I >
ϕ<
f<
f>
Id>
Zones of Protection
To limit the extent of power system that is
disconnected when a fault occur
G
Zone 1 Zone 2 Zone 3 Zone 4
Zone 4 Zone 6
Zone 5
Trang 7G
Zones of Protection
Ideally the zones of protection should overlap So that no part
of the power system is left un protected.
The point of connection of the protection with the power
system usually defines the zone and corresponds to the
location of CT’s.
Zones of Protection
Unit protection will result in the boundary being a clearly
define close loop.
Zone maybe un restricted, the extent or reach will depend on
measurement of the system quantities.
G
G
Trang 8Principal of Protection
Reliability
Operate under all required condition, and refrain from
operating when so required.
Incorrect operation can be attributed to one of
Incorrect design / setting
Design: Due consideration must be given to the nature, frequency and duration of fault, all relevant parameters of the power system and type of protection equipment used.
Setting: The setting are chosen for protection relays and system which take in to account the primary system, fault, load levels etc The characteristic of power system changes with time change in load etc Therefore, setting value of relay may need to be checked at suitable intervals
to ensure that are still appropriate
Principal of Protection
Incorrect installation / testing
Installation: The complexity of interconnections of many systems and their relationship to the remainder
of the installation may make checking difficult.
Deterioration in service
The time between operations of protection relays maybe years rather than days During this period defects may have developed unnoticed until revealed
by the failure of the protection to respond to a power system fault For this reason, relays should be regularly tested in order to check for correct functioning
Trang 9Principal of Protection
Selectivity
To trip only those circuit breakers whose operation is
required to isolate the fault The property of selectivity
tripping is also called ‘discrimination’ and is achieved
by two general methods.
Time Grading
Protection systems in successive zones are arranged to
operate in times that are graded through the sequence of
equipments so that upon the occurrence of a fault although a
number of protection equipments respond, only those relevant
to the faulty zone complete the tripping function The others
make incomplete operations and then reset.
Principal of Protection
Unit Systems
The protection systems that respond only fault conditions
occurring with in a clearly defined zone, it does not
involve time grading, is relatively fast in operation The
speed of response is substantially independent of fault
severity.
Trang 10Principal of Protection
Stability
The ability of protection system to remain
unaffected by conditions external to the
protected zone, for example through load
current and external fault conditions
Principal of Protection
Speed
The function of protection systems is to isolate faults
on the power system as rapidly as possible.
The main objective is to safeguard continuity of supply by
removing each disturbance before it lead to widespread loss
of synchronism and consequent collapse of power system
As the loading on a power system increase the phase shift
between voltages and different busbars on the system also
increases, and therefore so does the probability that
synchronism will be lost when system is disturbed by a fault,
protection must thus operate as quickly as possible.
Trang 11Principal of Protection
However speed of operation must be
weighed against economy
Distribution circuits which do not
normally require a fast fault clearance, are
usually protected by time-graded systems
Generating plant and EHV systems
require protection gear of highest attainable
speed
Principal of Protection
Sensitivity
This is a term frequently used when referring
to the minimum operating level ( current,
voltage, power etc.) of relays or complete
protection scheme
Trang 12Primary and Back-Up Protection
The reliability of a power system has been
discussed earlier, including the use of more than
primary ( or main ) protection system operating
in parallel
In the event of failure or non-availability of
the primary protection some other means of
ensuring that the fault is isolated must be
provided These secondary systems are referred
to as ‘back-up protection’
Back-Up Protection
Local back-up protection
This is achieved by protection which detect an
un-cleared primary system fault at its own
location and which then trip its own circuit
breakers, e.g time-graded over current relay
Trang 13Back-Up Protection
A B D
E
C
+ +
Local back-up protection
Back-Up Protection
A B
C
D
E
+ +
-Local back-up protection ( Breaker failure relay )
Trang 14Back-Up Protection
Remote back-up protection
This is provided by protection that detects an
un-cleared primary system fault at a remote
location and then issue a local trip command
e.g the second or third zones of distance
relay
Back-Up Protection
F
R1 R2
R3
1 2
3
Current
Time
R 1
R 2
R 3
fault
T1
T2
T3
Trang 15Back-Up Protection
The extent and type of back-up protection
applied will naturally be related to the failure
risks and relative economic importance of the
system
For distribution systems where fault clearance times
are not critical, time delayed remote back-up
protection maybe adequate.
For EHV systems, where system stability is at risk
unless a fault is cleared quickly, multiple primary
protection systems, operating in parallel and possibly
of different type ( e.g distance and unit protection )
will be used to ensure fast and reliable tripping.