Voltage Stress Related Failures in Extruded Insulation Voltage Stress Related Failures in Extruded Insulation z Overloads, defects or weak spots in insulation lead to chemical breakdown
Trang 2What Is Partial Discharge?
Electrotechnical Commission (IEC) International Standard 60270, Section 3.1 published in 2000, the definition of Partial Discharge is:
“Localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot
occur adjacent to a conductor.”
Trang 3IEC 60270 Section 3.1 Notes
z “Partial discharges are in general a
consequence of local electrical stress concentrations in the insulation or on the surface of the insulation…”
z “Corona is a form of partial discharge that
occurs in gaseous media around conductors which are remote from solid or liquid
insulation…”
z “Partial discharges are often accompanied by emission of sound, light, heat, and chemical reactions…”
Trang 4Paper-Insulated Lead Cable
Paper-Insulated Lead Cable
Trang 5Extruded MV Cable Construction
Trang 6EPR Cable Construction
Trang 7EPR Insulation in Cable Accessories
Cones and other Cable Accessories are
manufactured from an EPR compound because
of it’s great resistance to treeing and the effects
of corona discharge around terminations and
splices.
Trang 8Types of Cable Failures
Insulation
Trang 9Laminar Cable Insulation Failure
Picture Provided By Pirelli Wire
Trang 10Laminar Cable Insulation Failure
Picture Provided By Pirelli Wire
Tape removed showing electrical treeing
Trang 11Voltage Stress Related Failures in
Extruded Insulation
Voltage Stress Related Failures in
Extruded Insulation
z Overloads, defects or weak spots in insulation lead to
chemical breakdown of the insulation, producing thermal runaway leading to decreased Insulation Resistance,
increased leakage current and failure
z Design, manufacturing or workmanship results in voids or contamination which produce Partial Discharge and
ultimate failure
z Water Trees Form and convert to Electrical Trees and
lead to ultimate failure
Trang 12Voltage Stress Related Failures in
Extruded Insulation
Voltage Stress Related Failures in
trees Water Trees lead to decreased insulation resistance and very slight increase in leakage
current Water Trees do not directly produce
failure.
produce Partial Discharge and ultimate failure.
Trang 13Water Trees
Trang 15Bowtie Trees [9]
Bowtie Tree in XLPE Bowtie Tree in EPR
Trang 16Water Tree Conversion [2]
and/or switching.
result in power dissipation in the water channels existing in insulation sufficient to raise the
temperature of the water and increase pressure
in the water tree channel.
support partial discharge.
Trang 17Water Treeing
HMWPE Insulation
Picture Provided By General Cable XLPE Insulation
Picture Provided By General Cable
Trang 18Water Tree Conversion
z PD Inception voltage is exceeded by lightning and other surges causing a PD in voids
z Voltage drops to below PD Extinction voltage and PD
stops
z Each occurrence at which PD occurs causes the size and geometry of the insulation void to change Lowering the
PD inception and extinction voltages
z When PD extinction voltage drops below system nominal voltage, PD’s are continuous leading to electrical tree
formation and ultimate insulation failure
Trang 19Water Tree Conversion
Trang 20Insulation Failure
Picture Provided By Pirelli Wire
Trang 21Failures in Cable Accessories
occur in terminations, splices and other cable accessories.
Accessories are predominantly involve Partial Discharge Deterioration caused by voids,
contaminants and workmanship problems.
Trang 22The Partial Discharge Process
ACOUSTICS HEAT/CHEMICAL
REACTIONS
Trang 23IEEE Standard 400-2001 Notes:
IEEE Standard 400-2001 Notes:
z “Partial discharge measurement is an important method of assessing the quality of the insulation
of power cable systems…”
z “A partial discharge is an electrical discharge
(formation of a streamer or arc) that does not
bridge the entire space between two electrodes.”
z Partial discharges may occur in a “void…at a
contaminant…or at the tip of a well-developed water tree ”
Trang 24The Partial Discharge Process
Microscopic spaces (“voids”) may be formed
in insulation systems due to water tree
growth, aging, installation or manufacturing
defects Continued stress and overvoltages
can initiate PD in voids.
Heat and other forms of energy released by PD cause erosion of the internal surface of the void.
Continued erosion forms channels that develop into so-called electrical trees in the insulation.
Insulation
System
Failure
Continued PD produces further erosion until the electrical tree bridges the insulation.
Trang 25Why Test for Partial Discharges?
z Partial discharge testing can detect:
– Insulation defects that may have occurred during cable system installation or the manufacturing process
– Insulation deterioration due to normal service operating conditions
z Partial discharge testing is a PREDICTIVE qualitative analysis tool that can warn of a potential upcoming system failure.
z The Partial Discharge testing program can locate problem areas
(cable, splices, and/or terminations) in a cable system.
z Partial discharge test results can be trended over time.
z Unlike traditional High Potential Testing, partial discharge testing is not destructive to an insulation system (Hipot testing is typically a
“go-no-go” test the cable either fails or it doesn’t) In addition, “even
massive insulation defects in extruded dielectric insulation cannot be detected with DC ” according to the IEEE 400-2001 standard.
Trang 26AEIC PARTIAL DISCHARGE
Trang 27Historical Testing Methods
Trang 28Off-Line Testing Techniques
Off-Line Testing Techniques
and in some cases, completely removed from the distribution system.
voltage, and if necessary raising the voltages
above the normal operation voltage.
voltage also minimizes noise, reducing the need for filtering and intense data interpretation.
Trang 29High Potential Testing - DC
IEEE, Electric Power Research Institute (EPRI), Insulated Cable
Engineers Association (ICEA), and Association of Edison Illuminating Companies (AEIC) all agree on the following:
• “DC High Potential Maintenance Testing on aged (XLP) cables can damage the cable resulting in premature failure”
• “High Voltage DC Tests continue to be useful tests to check systems before they are placed in service When used as maintenance tests the possibility of damage to the cable should be considered.”
• “Cable Manufacturer’s must be consulted to determine acceptable voltage levels and recommendations typically include to test at your own risk”
Trang 30High Potential Testing - DC
• IEEE 400-2001 standard:
• " even massive insulation defects in extruded
dielectric insulation cannot be detected with DC at
the recommended voltage levels."
In other words not only is DC High Potential testing likely destructive for field-aged extruded cables, but it may not tell you a darn thing
Trang 31High Potential Testing - DC
WHAT’S THE BOTTOM LINE
SKIP??????????
QUIT DC HIPOT
TESTING
Trang 32Power Factor/Dissipation Factor Testing
z Effective in locating weaknesses in insulation and
potential hazards before impending failure
z Not a “Go-No-Go” Test
z Testing does not overstress the insulation and can
determine if the insulation is slowly degrading through trending
z Testing limited to relatively short lengths of cables
z Not effective in detecting localized faults as the length of cable increases
Trang 33Very Low Frequency (VLF) Testing
z VLF - High Potential Testing
– VLF damages the insulation less than DC Testing and has the
capability of locating potential failure sites.
– VLF has the advantage of portability with low energy
requirements, which results in much smaller test sets.
z VLF Partial Discharge Testing
– Voltage is raised to above the PD inception voltage to cause PD
to occur PD is then locatable using Time Domain PD Detection methods.
– Cable must be disconnected to test.
Trang 34In-Service Testing Techniques
In-Service Testing Techniques
z Has the obvious advantage that the cable is not put at any additional risk from the test
z Technique has the advantage that the cable is not
removed from service, leaving it energized as it is for normal operation
z Removes the potential for damage due to
inappropriate switching and yields no system
contingency problems
Trang 35Ultrasonic PD Testing
accessory is not directly buried or is at least
physically accessible
are extremely short wave in nature, fairly
directional and easy to isolate from background noise
Trang 36On-Line Partial Discharge Testing System for Cable Systems
On-Line Partial Discharge Testing
System for Cable Systems
z There is zero down time associated with On-Line PD
testing because the the test is performed at normal
operating voltage Testing involves no external voltage or current sources
z Test equipment measures PD produced at voltages of
2400 volts and greater.
z The system is independent of load current.
z It is non-invasive testing that does not inject current into the system, nor does it subject the system to excessive voltage levels.
z Method is 100% destructive and 100%
non-invasive.
Trang 37On-Line Partial Discharge Testing
System
On-Line Partial Discharge Testing
System
Two Part System Study
z Partial Discharge activity is
recorded from several Points
of Attachment (POA’s) along
the length of each cable run.
z If possible, the sensors are
clamped around all three
phases at once.
z In general, it is preferred to
attach sensors every 500 ft
z Partial Discharge data is processed utilizing pattern recognition software and analysis.
z Analysis is used to formulate a final report, which details findings
z Final Report detailing the analysis
of system is delivered
Trang 38The ETI On-Line Partial Discharge
Testing System
The ETI On-Line Partial Discharge
Testing System
SPECTRUM ANALYZER
LAPTOP COMPUTER
3-PHASE AC CABLE COAXIAL CABLE
PD SENSOR
CUSTOMER FINAL TESTING REPORT
HISTORICAL TRENDING
DATABASE
DIAGNOSTIC AND REPORT GENERATION SOFTWARE
SCHEDULED MAINTENANCE
SOFTWARE
Trang 39Partial Discharge Testing Equipment
z Custom made split core
sensors, are placed
around all three phases of
the cable (if possible).
z Sensors sense RF
Current and convert to a
millivolt (mV) output.
z Several images of partial
discharge activity are
recorded at several Point
of Attachments (POA’s)
along the length of the
cable.
Trang 40Partial Discharge Testing Equipment
z Data from the sensors are fed through a coaxial cable, through an amplifier to a Spectrum
Analyzer
z The Spectrum Analyzer is used to evaluate the
magnitude patterns and frequencies of any partial discharge activity at the POA
z Partial discharge waveforms are captured for
analysis by our partial discharge analysis software and engineers
z Any obvious PD activity may be relayed to the
customer before leaving the site
Trang 41Partial Discharge Predictions
z Characteristics of PD in electrical trees differ from those in spherical voids
z The pulse shapes, rise and fall times, width, and
amplitude depend on the applied field in the insulation
z Voids are identifiable by single discharges occurring each half cycle
z Electrical Trees are branchlike with the PD’s proceeding in steps along the branch Trees are identifiable by multiple discharge pulses occurring per half cycle
Trang 42PD Characteristics
Trang 43PD Characteristics
Trang 44PD Characteristics
Trang 45PD Characteristics
Electrical Treeing Electrical Treeing
Trang 46PD Characteristics
Electrical Treeing Electrical Treeing
Trang 47Final Partial Discharge Report
The data is then used to electronically generate a final report
that details the severity and location of partial discharge
activity PD activity is then classified into the following
category(s) and appropriate recommendations made.
Severity Level Classifications
Level A-Low levels of Partial Discharge activity occurring No
necessary actions at this time Retest in 3 years.
Level B-Moderate levels of Partial Discharge activity occurring Retest
within 12-18 months to monitor & trend PD activity.
Level C-High levels of Partial Discharge activity occurring Prioritized
repair or replacement is recommended.
Trang 48Final Partial Discharge Report
z Software has been developed for pattern
recognition and conversion of data to usable format Software significantly reduces the
amount of time required to generate a final report
z Reports can show the severity level of any
observed partial discharge activities, where they are located, recommended testing
intervals, other recommended actions, etc
z In addition, the final report can provide the actual data used to formulate our
recommendations.
Trang 49Partial Discharge Analysis
z All data recorded while on-site
is scrutinized to uncover any pending problems within the tested system, and analyze their severities and locations.
z A comparative analysis is generated from the data gathered while on-site This comparative analysis allows for prioritization/planning of cable replacements, scheduling
repairs, etc
Trang 50Success Stories
- St Louis Correctional Facility
– Tuesday - Identified “Level C” Y-Splice located in PMH feeding 5KV Padmount Transformer -
Recommended Prioritized Replacement
– Friday - Y-Splice violently fails before facility could replace causing unplanned outage
• 5KV Distribution System was less than 2 years old and
failure determined to be workmanship related on the Splice
Trang 51Y-Success Stories
-Bellamy Creek Correctional Facility
– Performed On-Line Partial Discharge Testing to establish baseline data for facility upon completion of Acceptance
Testing.
– 15KV Distribution System Passed Acceptance Testing that consisted of AC High Potential Testing
– On-Line Partial Discharge Testing found a workmanship
defect at a Transformer Termination which was not found by High Potential Testing.
Trang 53– Identified “Level C” splice located in Tap Box on roof of
facility Repairs were not scheduled until July Outage 2003 – Cable Splice failed Dec 2002 causing 48 hr loss of plant production.
Trang 54Success Stories
– Performed On-Line Partial Discharge Testing to determine condition of 34.5KV Distribution cables and accessories
– Testing was performed during normal plant
production with zero down time
– Several areas requiring prioritized attention were identified
– Replaced pothead connection with attached
results
Trang 55Primcor Refinery - 8/2002 (Initial Test)
Trang 56Primcor Refinery - 8/2002 (Initial Test)
Trang 57Primcor Refinery - 2/2003 (After Repairs)
Trang 58Primcor Refinery - 2/2003 (After Repairs)
Trang 60z On-Line Partial Discharge Testing is a
non-invasive, non-destructive, predictive test
z Final report generated which provides
interpretations and recommended actions
Trang 61Insulation Magazine, Vol 16, No 5
Conditions”, IEEE Trans PD-13, No 2, April 1998, pp 310 - 315
Magazine, Vol 11, No 2
No 5
AC Impulse Breakdown of Model EPR and TR-XLPE Cables as a Function of Wet Electrical Aging”, PES ICC, April 2002
of the IEEE Conference on Electrical Insulation and Dielectric Phenomena pp 547-551 (also submitted for review to Trans PD.)
Insulation Magazine, Vol 8, No 2
Voltage Solid Dielectric Cables”, IEEE Electrical Insulation Magazine, Vol 9, No 6