1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

EXH600 air cooled heat exchangers

4 291 0

Đang tải... (xem toàn văn)

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Định dạng
Số trang 4
Dung lượng 38,17 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

This section provides general design guidelines for air cooled exchangers (also called air coolers). See API Standard 661 for air cooler nomenclature and illustrations and for mechanical design requirements. General Design Considerations Design Air Temperature Tube Side Design Viscosity Plugging Headers Layout Draft Fans Fins Winterization Estimating Rules of Thumb

Trang 1

Chevron Corporation 600-1 December 1989

600 Air Cooled Heat Exchangers

Abstract

This section provides general design guidelines for air cooled exchangers (also called air coolers) See API Standard 661 for air cooler nomenclature and illustra-tions and for mechanical design requirements

610 General Design Considerations 600-2

611 Design Air Temperature

612 Tube Side Design

613 Viscosity Plugging

614 Headers

615 Layout

Trang 2

600 Air Cooled Heat Exchangers Heat Exchanger and Cooling Tower Manual

610 General Design Considerations

Air cooled exchangers are used to cool or condense low viscosity fluids They are usually designed by the manufacturer The HTRI ACE computer program may be used to rate air coolers and condensers, if air rate is known Fan design and rating is beyond the scope of the ACE program

611 Design Air Temperature

Design air temperature is usually selected as the dry bulb temperature that is exceeded about 150 hours per year during the hottest 4 consecutive months This corresponds to meeting design performance 98+% of the year, but not for a few hours a day during the hottest days

Evaluated weather data can be obtained from the following sources:

• “Evaluated Weather Data for Cooling Equipment Design,” by Fluor Products Company, 1958

• “Army, Navy and Air Force Manual Engineering Data,” by Departments of the Army, the Navy, and the Air Force, April 1, 1963

• “Evaluated Weather Data for Cooling Equipment Design, Addendum No 1, Winter and Summer,” by Fluor Products Company, 1964

Consult ETD Engineering Analysis Division if these or other weather data sources are not readily available

Air cooling process streams to about 20°F over the design ambient temperature, or higher, is economic Water cooling or refrigeration is used if lower process tempera-tures are required

612 Tube Side Design

Tube side design for air coolers and shell and tube exchangers involves the same principles Economic tube side velocities given in Section 220 and process side heat transfer coefficient given in Section 481 apply to air coolers Estimating rules of thumb specific to air coolers are given in Section 660 below

613 Viscosity Plugging

Cooling viscous fluids is usually not practical in air coolers because of viscosity plugging The viscosity of viscous oil usually increases rapidly with decreasing temperature Air side maldistribution inevitably causes some tubes to run cooler than others This increases the viscosity in the cooler tube and therefore reduces flow through that tube, which causes further cooling and more flow reduction The result of this temperature-viscosity-flow effect is to virtually stop flow in some tubes and force flowing tubes into the turbulent flow regime, if the viscous oil pumps can develop the needed head Otherwise, flow essentially stops

Trang 3

Heat Exchanger and Cooling Tower Manual 600 Air Cooled Heat Exchangers

Air coolers should not be used when the tube side outlet Reynolds number (defined

in Appendix B) is less than 2000

Air recirculation described in Section 650 may be used to air cool fluids that become very viscous or freeze near ambient temperatures Tempered water cooling described in Section 330 is an alternative

614 Headers

Most air coolers have header plugs opposite each tube on each end to facilitate inspection and cleaning Removable cover plates on each header is an alternative but is not economic and rarely used

615 Layout

Air-cooled exchangers usually have four rows of staggered tubes Six rows are sometimes used for large process temperature range Aligned tube rows are never advantageous because of significant air side channeling and temperature maldistri-bution

Air-cooled exchangers are often mounted over pipeways to minimize plant real estate Pipeway mounted units are usually 30 feet long Shorter bundles are common for grade mounted units

More than one bundle (service) may be in the same bay with a common pair of fans, if overcooling some of the services is not a concern If overcooling is a poten-tial problem, adjustable louvers for that bundle can be used, or the service can be built as a separate unit with dedicated fans

620 Draft

Forced draft is required when the maximum outlet air temperature is higher than the manufacturer’s rated temperature of the fans or the auto-variable fan pitch control hubs Operation with the fans off and during steam out should be consid-ered The air outlet temperature is approximately the same as the process inlet temperature when fans are off, and same as the steam temperature during steam out The plenum of induced draft units acts like a stack and produces a significant “fans-off” duty The “fans-“fans-off” performance of forced draft units is negligible

Induced draft is sometimes specified for a column overhead condenser where temperatures permit Induced draft is normally considered if overcooling during rain storms is a problem or if design relief loads would be reduced by the superior fans off performance of induced draft units Rain affects the full bundle in forced draft units and only about half the bundle in induced draft units

When the above considerations do not govern draft, the manufacturer usually decides Induced draft provides better air flow distribution than forced draft;

however, induced draft fans must move a greater volume of (heated) air than forced draft These effects are not large

Trang 4

600 Air Cooled Heat Exchangers Heat Exchanger and Cooling Tower Manual

630 Fans

There should be at least two fans per bundle with the fans covering at least 40 percent of the bundle Half of the fans are usually autovariable pitch fans During the summer, the manual fan is on and the autovariable fan adjusts air flow to control duty During the winter, the manual fan is usually shut off Auto-variable fan pitch control is usually justified by fan power savings rather than control needs, but serves both functions Fan blades are usually aluminum or plastic The best plastic fan blades are good to about 350°F Auto-variable fan pitch control hubs may have rubber seals that limit temperature to about 250°F

640 Fins

Fins are almost always aluminum Three fin types are commonly used: footed, inte-gral (extruded) and imbedded Maximum process inlet temperatures for these fin types are 250°F, 550°F, and 750°F, respectively API 661, Section 5.1, describes these fin types in more detail

650 Winterization

Winterization is required for air coolers with fluids that may become immobile under expected winter conditions due to freezing, pour point problems or the viscosity plugging phenomenon described in Section 610 Winterization usually means building an enclosure around the air cooler with provisions to recirculate a portion of the outlet air back to the inlet A steam coil under the bundle is also normally provided to heat up the bundle if the fluid in the bundle ever becomes immobile Winterization of air coolers is discussed in detail in API Recommended Practice 632 (not included in this manual)

660 Estimating Rules of Thumb

Air coolers usually have four layers of 1-inch O.D tubes with 10, 5/8-inch high fins per inch, arranged in a 2-1/2-inch pitch equilateral triangular layout The ratio of fin surface to bare outside surface (bos) is about 20:1; the required plot space is about

200 ft2 per 1000 ft2bos; the air rate is about 600 lb/hr/ft2bos; the installed fan power

is about 20 hp per 1000 ft2bos; and the air side heat transfer coefficient is about 175 Btu/hr ⋅ °F ⋅ ft2⋅bos

Note that the installed fan power (“pumping power”) is four times higher than that normally used for other types of heat exchangers This is because air cooler design

is limited by warm weather operation Annual average fan power is usually about one fourth of the design value

Ngày đăng: 31/10/2017, 00:10

TỪ KHÓA LIÊN QUAN