It is Part 2 of a two-partStandard, as follows:AS 2220 Emergency warning and intercommunication systems in buildings AS 2220.1 Part 1: Equipment design and manufacture AS 2220.2 Part 2:
Trang 1Licensee
Conditions of use
This is a licensed electronic copy of a document where copyright is owned or managed by
Standards Australia International Your licence is a single user licence and the document may not
be stored, transferred or otherwise distributed on a network You may also make one paper copy
of this document if required
Web Check-up
AS 2220.21989 Emergency warning and intercommunication systems in buildings
-System design, installation and commissioning
Licensed to LUU MINH LUAN on 25 Feb 2002
Trang 2AS 2220.2—1989
Emergency warning and intercommunication systems in buildings
Part 2: System design, installation and commissioning
Trang 3Intercommunication Systems in Buildings It was approved on behalf of the Council
of Standards Australia on 4 May 1989 and published on 11 September 1989
The following interests are represented on Committee BD/56:
Association of Consulting Engineers, AustraliaAustralian Assembly of Fire AuthoritiesAustralian Fire Protection AssociationAustralian Uniform Building Regulations Coordinating CouncilBuilding Owners and Managers Association of AustraliaCommonwealth Fire Board
Department of Administrative Services — Construction GroupDepartment of Defence
Electrical Contractors Association of AustraliaFire Protection Industry Association of AustraliaInsurance Council of Australia
Public Works Department, New South WalesPublic Works Department, Victoria
Safety Institute of AustraliaTelecom Australia
Review of Australian Standards To keep abreast of progress in industry, Australian Standards are subject
to periodic review and are kept up to date by the issue of amendments or new editions as necessary It is important therefore that Standards users ensure that they are in possession of the latest ed ition, and any amendments thereto.
Full details of all Australian Standards and related publications will be found in the Standards Australia Catalogue of Publications; this information is supplemented each month by the magazine ‘The Australian Standard’, which subscribing members receive, and which gives details of new publications, new editions and amendments, and of withdrawn Standards.
Suggestions for improvements to Australian Standards, addressed to the head office of Standards Australia, are welcomed Notification of any inaccuracy or ambiguity found in an Australian Standard should be made without delay in order that the matter may be investigated and appropriate action taken.
This Standard was issued in draft form for comment as DR 85304.
Trang 4AS 2220.2—1989
Emergency warning and intercommunication systems in buildings
Part 2: System design, installation and commissioning
First published as part of AS 2220—1978.
AS 2220—1978 (in part) revised and redesignated
Trang 5PREFACEThis Standard was prepared by Standards Australia’s Committee on EmergencyWarning and Intercommunication Systems in Buildings It is Part 2 of a two-partStandard, as follows:
AS 2220 Emergency warning and intercommunication systems in buildings
AS 2220.1 Part 1: Equipment design and manufacture
AS 2220.2 Part 2: System design, installation and commissioning (this Standard) This Standard together with AS 2220.1 supersede AS 2220—1978, Emergency warning and intercommunication systems for buildings and provide more detailed requirements
than AS 2220—1978 although not differing in the overall intent of that Standard
AS 1851, Maintenance of fire protection equipment, Part 10: Emergency warning and intercommunication systems specifies the periodic inspection and maintenance
requirements of the emergency warning and intercommunication systems designed andinstalled in accordance with this Standard
Copyright STANDARDS AUSTRALIA Users of Standards are reminded that copyright subsists in all Standards Australia publications and software Except where the Copyright Act allows and except where provided for below no publications or software produced by Standards Australia may be reproduced, stored in a retrieval system in any form or transmitted by any means without prior permission in writing from Standards Australia Permission may be conditional on an appropriate royalty payment Requests for permission and information on commercial software royalties should be directed to the head office of Standards Australia.
Standards Australia will permit up to 10 percent of the technical content pages of a Standard to be copied for use exclusively in-house by purchasers of the Standard without payment of a royalty or advice to Standards Australia.
Standards Australia will also permit the inclusion of its copyright material in computer software programs for no royalty payment provided such programs are used exclusively in-house by the creators of the programs.
Care should be taken to ensure that material used is from the current edition of the Standard and that it is updated whenever the Standard is amended or revised The number and date of the Standard should therefore be clearly identified.
The use of material in print form or in computer software programs to be used commercially, with or without payment, or in commercial contracts is subject to the payment of a royalty This policy may be varied by Standards Australia at any time.
Trang 6Page
FOREWORD 4
SECTION 1 SCOPE AND GENERAL 1.1 SCOPE 5
1.2 REFERENCED DOCUMENTS 5
1.3 DEFINITIONS 5
SECTION 2 EMERGENCY WARNING SYSTEMS 2.1 GENERAL REQUIREMENTS 6
2.2 FUNCTIONAL REQUIREMENTS 6
2.3 OPERATIONAL REQUIREMENTS 7
SECTION 3 EMERGENCY INTERCOMMUNICATION SYSTEM 3.1 SEPARATION 8
3.2 LOCATION OF WARDEN INTERCOMMUNICATION POINT (WIP) 8
SECTION 4 POWER SUPPLY 4.1 GENERAL 8
4.2 POWER SUPPLY CONNECTION 8
4.3 BATTERIES 8
SECTION 5 INSTALLATION 5.1 GENERAL 9
5.2 WIRING 9
5.3 TERMINATIONS AT LOUDSPEAKERS 9
5.4 EQUIPMENT PROTECTION 9
5.5 INSTALLATION OF BATTERIES 9
5.6 EMERGENCY NOTICES 9
5.7 OPERATING INSTRUCTIONS 12
5.8 INSTALLER’S STATEMENT 12
SECTION 6 COMMISSIONING 6.1 GENERAL CHECKS 13
6.2 SPECIFIC CHECKS 13
6.3 DOCUMENTATION 13
APPENDICES A HAZARD-RESISTANT WIRING COMPONENTS 14
B TYPICAL METHOD OF OPERATION AND RESPONSE OF PERSONNEL 15
C SEALED BATTERIES 16
D REPORT OF TESTS FOR SEALED BATTERIES 18
E COMMISSIONING TEST REPORT 19
F EMERGENCY WARNING AND INTERCOMMUNICATION SYSTEMS STANDARD FORM OF INSTALLER’S STATEMENT 20
G EMERGENCY WARNING AND INTERCOMMUNICATION SYSTEMS CERTIFICATE 21
H EMERGENCY WARNING AND INTERCOMMUNICATION SYSTEMS SYSTEM INFORMATION 22
Trang 7An emergency warning and intercommunication system is installed in a building for thepurpose of enabling the orderly evacuation of the building in the event of an emergency Toachieve this aim, it is essential that the emergency warning and intercommunication systemhas the following capabilities as appropriate:
(a) Provision for manual and automatic activation
(b) On activation, the ability to alert wardens with an audible alarm (A visual alarm mayalso be required)
(c) Where both an emergency warning system and an emergency intercommunicationsystem are required to comply with AS 2220, these systems are integrated to provide
a positive means of intercommunication between the House Warden and the variousfloors or Zone Wardens to enable the orderly evacuation of the building
(d) Emission of audible or visible signals or both that will either (i) alert the occupants; or
-(ii) order the occupants to vacate the building
(e) Ease of operation
(f) Continuous operation under conditions of hazards
COPYRIGHT
Trang 8STANDARDS AUSTRALIA
Australian Standard Emergency warning and intercommunication systems in buildings
Part 2: System design, installation and commissioning
SECTION 1 SCOPE AND GENERAL
1.1 SCOPE This Standard sets out the performance
requirements for the design, installation, and
commissioning of emergency warning and
intercommunication systems installed in buildings
NOTE: The method of operation of the emergency warning and
intercommunication system (EWIS) and the response of personnel
are indicated in Appendix B.
1.2 REFERENCED DOCUMENTS The following
documents are referred to in this Standard:
AS
1088 Hearing aids
1088.4 Part 4: Magnetic field strength in
audio-frequency induction loops forhearing aid purposes
1259 Sound level meters
1530 Methods for fire tests on building materials,
components and structures1530.4 Part 4: Fire-resistance test of elements of
construction
1670 Automatic fire detection and alarm systems —
S y s t em d es i g n , i n s t al l a t i o n , a n dcommissioning
1851 Maintenance of fire-protection equipment
1851.10 Part 10: E m e r g e n c y w a r n i n g a n d
intercommunication systems
1981 Stationary batteries of the lead-acid pasted
plate type
2036 Manually operated fire alarm call points
2191 Stationary batteries of the lead-acid Plante
positive plate type
2220 Emergency warning and intercommunication
systems for buildings2220.1 Part 1: Equipment, design and manufacture
2293 Emergency evacuation lighting in buildings2293.1 Part 1: Design and installation
2676 Installation and maintenance of batteries in
buildings
3000 SAA Wiring RulesBS
6387 Specification for performance requirements for
cables required to maintain circuit integrityunder fire conditions
1.3 DEFINITIONS For the purpose of this Standard,
the definitions given in AS 2220.1 and the followingapply:
1.3.1 Fire compartment — a fire-isolated compartment
or enclosure constructed of fire-resistant materials
1.3.2 Fire-resistance level (FRL) — the ability of an
element of construction, component or structure to fulfilfor a stated period of time the required structuraladequacy, integrity, thermal insulation and other expectedduty specified during exposure to a fire test specified in
AS 1530.4
1.3.3 Fire resisting — an element of construction,
component or structure which, by requirement of theRegulatory Authority, has a specified fire resistance
1.3.4 Main equipment — equipment essential to the
operation of the system including, control equipment,amplification equipment and power supply modules
COPYRIGHT
Trang 9SECTION 2 EMERGENCY WARNING SYSTEMS
2.1 GENERAL REQUIREMENTS.
2.1.1 Emergency control panels (ECPs).
2.1.1.1 Location The master emergency control panel
(MECP) and any additional emergency control panels
(ECPs), that may be required, shall be installed in an
approved location complying with the following
requirements:
(a) The ECP area shall be secure and relatively isolated
acoustically The ambient noise level at the ECPs
shall not exceed 70 dB(A)
NOTE: This Standard expects the ambient noise level to be
assessed taking into consideration the unusual circumstances of
an emergency For example, during a fire, it is expected that a
fire brigade booster pump may be operating outside the building,
thereby increasing the noise level in the lobby area above 70
dB(A) The lobby area in this case, would be unsuitable for the
ECP, unless provisions are made for its isolation.
(b) Access to the ECPs shall not be obstructed, nor
shall any ECP obstruct the evacuation of the
building
NOTES:
1 It is not recommended to locate any ECP in an area where
a high level of activity is expected during an emergency evacuation.
2 In the event of an emergency, operators of the system, and
most particularly the house warden are expected to make a series of decisions over a short time It has been established that a suitable environment, as well as a system that is easy
to operate, play an important role in the successful handling
of the emergency, and hence, the safety of occupants.
3 Safe manning should be possible under anticipated
conditions of hazard and emergency.
(c) ECPs shall be located so that visible indications
shall remain readily distinguishable, under all
ambient lighting conditions
2.1.1.2 Physical working environment The following
requirements shall apply:
(a) Lighting Emergency lighting shall be provided as
required in accordance with AS 2293.1
(b) Ventilation When batteries are located inside the
ECP cubicle, adequate ventilation in accordance
with AS 2676 shall be provided
(c) Workspace. The personnel workspace shall be
arranged so as to minimize distraction by peripheral
activities, and its plan dimensions shall be not less
than those specified in Figure 2.1
2.1.2 Additional facilities A notice shall be provided
at every ECP location, giving essential instructionsnecessary to ensure the correct use of the equipment, theterminology being understandable by non-technicalpersonnel
NOTE: It is recommended that a telephone be provided in the vicinity of the MECP.
2.1.3 Interconnection of alarm systems The main
equipment shall be interconnected with the fire indicatorpanel (FIP) where provided An isolation facility shall beincorporated, to prevent automatic actuation of theemergency warning system under test conditions Anyother alarm system connected to the emergency warningsystem shall have a similar facility
Isolation of alarm-initiating signalling lines shall raise afault indication as specified in AS 2220.1
2.2.3 Output of loudspeakers At any location within
the signal reception area, the A-weighted sound pressurelevel of the audible signals, measured with the timeweighting ‘F’ (fast), shall exceed by a minimum of 10
dB the noisiest background sound pressure levelaveraged over a period of 60 s This level shall be notless than 65 dB and not more than 105 dB These valuesare to be determined in accordance with AS 1259.For audible signals intended to arouse sleepingoccupants, the sound pressure level signals shall be notless than 75 dB when measured at the sleeping position(see Note)
The sound pressure level shall not fall by more than 6
dB when tested under battery-powered operation (seeClause 4.3.2)
Trang 10Loudspeakers installed within the vicinity of any ECP or
WIP shall not inhibit the normal operation of the system
NOTE: The 75 dB signal level may not be adequate to wake all
sleeping occupants.
2.2.4 Visible signals. Where the background
A-weighted noise level exceeds 95 dB, visible signals
shall be installed The number and disposition of visible
signalling devices, shall be such as to ensure visibility in
the required areas, and the intensity of the visible signals
shall ensure perception by the occupants They shall
comply with the requirements for visible signals in AS
2220.1
Visible signalling devices shall be provided with suitable
identification, e.g signs or symbols giving the
appropriate instructions
2.3 OPERATIONAL REQUIREMENTS.
2.3.1 Initiation In addition to manual operation from
an ECP and any automatic activation, provision shall be
made to manually actuate the EWS from within each
evacuation zone This shall be achieved by either
-(a) one or more red manual call points, complying with
AS 1603.5, as part of the fire alarm system; or
(b) one or more white emergency alarm initiating
devices, complying with AS 2220.1
Both red and white devices shall not be present withinthe same evacuation zone
NOTE: The regulatory authority may have specific requirements which could limit the number of alarm initiating devices which can
be installed within one evacuation zone.
2.3.2 Duration of alert signal The alert signal shall
continue on until manual control of the system is taken
or, if not responded to within a prescribed time frominitiation, the signal shall be automatically replaced by anevacuation signal The prescribed time shall beestablished to suit the particular building but it shall notexceed 10 min For buildings with 6 or more evacuationzones, the automatic execution of the evacuation shall bearranged, so that the affected evacuation zones areevacuated first and the other evacuation zones areevacuated in a logical order of priority
2.3.3 Use of the system for non-emergency purposes.
The emergency warning system may be used as apaging-background music system under non-emergencyconditions, provided that -
(a) the equipment is designed to override ancilliaryfunctions under emergency conditions as specified
in AS 2220.1;
(b) the capacity of the battery charger as specified in
AS 2220.1 will provide sufficient current toaccommodate the additional load; and
(c) the system integrity is maintained
COPYRIGHT
Trang 11SECTION 3 EMERGENCY INTERCOMMUNICATION SYSTEM
3 1 S E P A R A T I ON T h e emer g en cy
intercommunication system shall be separate from the
Telecom Australia system and from any other
communication system
3.2 LOCATION OF WARDEN
INTER-COMMUNICATION POINT (WIP) A WIP shall be
located on each level, or, where a floor is divided into
two or more evacuation zones, in each evacuation zone
The requirements for the position of each point are
similar to those given in Clause 2.1.1.1 for the ECP,
with the additional requirements that it
shall be convenient to a fire-isolated escape route, ormeans of egress, and in a position in the level orevacuation zone, that will permit control of and egressfrom the associated area
If the WIP handset is enclosed within any other cabinet,
it must be assured that the 80 db(A), audible signal,when measured at 1 m from the apparatus is maintained
as specified in AS 2220.1
WIPs shall be mounted at a height between 1200 mmand 1800 mm above floor level
SECTION 4 POWER SUPPLY
4.1 GENERAL The system shall be energized from a
reliable source of supply and shall be connected in
accordance with AS 3000 The power source shall be—
(a) an a.c supply from an electricity authority or a
source equal in quality and reliability; and
(b) batteries, as specified in Clause 4.3, which shall
supply the necessary power to the system in the
event of mains input power failure
4.2 POWER SUPPLY CONNECTION The system
shall be directly connected to the line side of the nearest
electrical distribution board and it shall be separately
protected by a circuit breaker or fuse The circuit breaker
or fuse shall be clearly labelled, to indicate that it
c o n t r o l s t h e e m e r g e n c y w a r n i n g ( a n d
intercommunication) system No other load or equipment
shall be connected to the circuit
4.3 BATTERIES.
4.3.1 General Batteries shall be of a type specially
designed for continuous float charging conditions, and
shall comply with the performance requirements of one
or more of the following, as appropriate:
(a) Lead-acid pasted type batteries (see AS 1981)
(b) Lead-acid Plante positive plate type batteries (see
AS 2191)
(c) Sealed batteries (see Appendix C)
Sealed batteries which cannot be recharged after a total
discharge to zero volts are not acceptable
Cells which require the addition of electrolyte during
service shall be provided with means of visual inspection
of the electrolyte for maximum and minimum levels, and
low electrolyte alarm indication
NOTES:
1 Batteries which have a memory effect or cyclic discharge/charge requirements are considered unsuitable.
2 For requirements on the installation, of batteries, see Section 5.
4.3.2 Battery capacity The capacity of the batteries
shall be, in the event of mains input power failure,capable of maintaining the system in normal working(quiescent) condition for at least 8 h After which,sufficient capacity shall remain to operate the emergencywarning and intercommunication system including allaudible and visible signals at the specified outputs, for aperiod not less than 90 min and within the temperaturerange specified in AS 2220.1
NOTE: When calculating the capacity of the battery required to power the system, consideration needs to be given to:
(a) The available capacity of the battery at the beginning and at its end of life.
(b) The reduction in capacity due to low ambient temperature (c) The reduction in capacity when discharging at the 1.5-hour rate compared to the 10-hour rate.
The above considerations will lead to a required capacity
of between 1.5 and 2 times the capacity at the 10-hourrate
4.3.3 Battery connections The connecting leads to the
battery shall be clearly labelled to reduce the possibility
of reverse connections to the battery
Two types of external connections are acceptable:(a) Bolted lugs for centrally located battery supplies; or(b) Quick connector type connectors for distributedbattery supply
(See also AS 2220.1 for requirements forbattery protection.)
COPYRIGHT
Trang 12SECTION 5 INSTALLATION
5.1 GENERAL. The emergency warning and
intercommunication system shall be installed in a manner
that will enable the fulfilment of the design requirements
of the equipment as outlined in AS 2220.1
5.2 WIRING.
5.2.1 General The wiring shall comply with AS 3000
with conductor cross-sectional area not less than
0.75 mm2
, and Clauses 5.2.2 and 5.2.3, and shall bededicated to the emergency warning and
intercommunication system (EWIS) functions only The
installation wiring of the system shall be carried out by
licensed electrical contractors
5.2.2 Wiring protection. Wiring, forming part of
emergency warning and intercommunication systems and
where required under Table 5.1 and as typically shown
in Figure 5.1, shall be of such materials and so installed
that the system shall be capable of operating under
conditions of hazard for at least 90 min The following
shall be deemed to comply with the required protection:
(a) Wiring that complies with Appendix A
(b) Wiring that is enclosed in a form of construction
that enables the wiring to fulfil the test conditions
given in Paragraph A3, Appendix A, provided that
no power services wiring is contained in such
enclosure
Cabling systems and their protective enclosures shall be
installed in the manner used in the prototype that
qualified for the specified test performance (See
Appendix A.)
Where cables or enclosures penetrate fire-resisting walls
or floors, suitable sealing materials shall be installed to
comply with building regulations
5.2.3 Integrity of circuits Wiring between ECPs, main
equipment rack, FIP, evacuation zone loudspeaker
groups, emergency alarm device and WIPs, shall be
arranged so that a short-circuit or open-circuit within a
cable in any zone shall not affect the normal operation of
other evacuation zones as defined in Sections 2 and 3
5.2.4 Fault monitoring. Where fault monitoring of
signal wiring is required, end of line termination devices
shall be provided so that open-circuit or short-circuit
faults can be detected and raise an alarm at the MECP
5.2.5 Joints and terminations Joints in conductors
shall not be permitted except in long runs Joints and
terminations shall be made only in a suitable enclosed
terminal box or strip employing fixed terminations
Joints and terminations associated with the vertical riser
cables shall be made within the associated fire-isolated
duct
5.2.6 Separation from other systems The wiring of
the EWIS and its associated extra-low voltage circuits
shall be kept separate and distinct from power and light
circuits (see segregation of wiring systems in AS 3000)
Where a duct system is used a separate channel or chase
shall be provided
5.3 TERMINATIONS AT LOUDSPEAKERS.
5.3.1 Connection facilities required Each incoming
and outgoing conductor of the same potential shall be
connected to a separate screw or clamping facility.Terminal blocks shall be securely fixed to theloudspeakers Terminals shall not be exposed to viewand shall only be accessible with the use of tools
5.3.2 Terminals, design and construction Terminals
shall be of copper or copper alloy and suitable for theapplication Terminals shall be designed andproportioned so that a connection made will not slackenoff or overheat under normal conditions of use Clamptype terminals shall be designed so that the conductorscan be rigidly and effectively clamped between metalsurfaces Clamping devices with screws, which screwdirectly into conductors, shall not be used
5.3.3 Stress on conductor terminals Conductors shall
be so supported and connected that there will be noundue mechanical stress on either the conductors or theterminals to which they are connected
5.4 EQUIPMENT PROTECTION.
5.4.1 Main equipment The main equipment shall be
located in a secure, fire-isolated area within the building.The area shall be free of stored combustible material andignition sources, i.e., areas such as electrical switchrooms, store rooms and similar, are not acceptable
In existing buildings without fire compartments the mainequipment shall be located in an area presenting the leastrisk to the continued operation of the equipment in anemergency
5.4.2 Distributed equipment Equipment installed in
a fire compartment or evacuation zone, servicing otherthan the installed fire compartment or evacuation zone,
is not acceptable, except where the distributed equipment
is installed in a fire compartment in accordance with therequirements for main equipment
5.4.3 Loudspeakers Loudspeakers shall bepermanently fixed in position
5.5 INSTALLATION OF BATTERIES.
5.5.1 General Batteries shall be located in accordance
with AS 2676 and installed in accordance with themanufacturer’s recommendations
5.5.2 Battery enclosures Batteries shall be secured
from unauthorized persons by a locked door The keyshall be identical with other keys required for access tocontrol and indication equipment as specified in
AS 2220.1
Non-sealed batteries shall be located in a separateenclosure sealed from other parts of the equipment Theenclosure shall be protected against corrosion adequatelyventilated, and be of such a size as will permit easyaccess for battery inspection and maintenance withoutneed to disconnect individual cells or batteries
5.6 EMERGENCY NOTICES. Notices providinginstructions to be followed in case of emergency, shall
be positioned adjacent to each ECP and WIP
NOTE: The text of the notice is not specified in this Standard as this depends on the type of building, type of system, and evacuation procedures.
COPYRIGHT