Current available communication protocols with FX2 FX IBMS Billing Help Desk Maintenance Management Alarm Management Client PC Intranet Internet SM S OA network Facility Booking FX BEMS
Trang 1savic-net FX Integration System Construction Guide
会社名入力
日付入力
Trang 2manufacture
Trang 31 Current available communication
protocols with FX2
FX IBMS
Billing Help Desk
Maintenance Management
Alarm Management
Client PC
Intranet Internet
SM S
OA network
Facility Booking
FX
BEMS
BMS Network (Ethernet, 100Mbps)
SMS DSS EDS
IDS
SCS
Building Wide IT Network Infrastructure
(Ethernet, 100Mbps) SDS
ACC
BACnet IP
BACnet IP Modbus TCP Modbus RTU
Sub systems
SCS
Infilex
(DDC)
Infilex
IP type (DDC)
CCTV System
Fire Alarm System
Lighting System
Public Address System
Car Park System
Lift/Escalator System
Modbus Device
Modbus RTU
LonTalk Modbus TCP
Modbus RTU
Trang 42 Communication protocol checklist
for each manufacture
BACnet IP BACnet
MS/TP
Modbus TCP
Modbus
CNA '
Quantum Carrier TRANE YORK
Communication Protocols Equipments Manufactures
Chiller IBMS
YORK VRV DAIKIN Lighting Panasonic
LG産電
Schneider CIRCUTOR GE
Janitza M-System Mitsubishi SATEC Schneider GE
Mitsubishi Edwards
Power Meter
Power Monitoring
PLC
Edwards GST(China) NOHMI Notifier Simplex Public Address TOA Car Park
Lift / Escalator
FA System TOP Server
Installed Possible, but not installed
Need to discuss Impossible Fire Alarm
Trang 53 Selection guide of communication
protocols
installed to an actual project is our first priority.
to communicate with first manufactures or products for Yamatake.
your projects BSC is still considering to use 3rd party software for OPC.
Trang 64 Special remarks of BACnet system
BACnet if other BACnet protocols like BACnet Ethernet, BACnet MS/TP, etc are required
Get a Protocol Implementation Conformance Statement (PICS) of the
Get a Protocol Implementation Conformance Statement (PICS) of the
product on the other end of the communication as soon as possible and confirm their BACnet communication specifications like the protocol
revision, network type and object types, etc
Get the object list on the other end of the communication for our system
engineering
a Estimate one or more SCS for the exclusive use of BACnet processing when
FX2 has trending function or time program for other manufacturer’s products.
b Estimate SCOL Management function (BSY45310Z0502) when FX2 has
trending function for other manufacturer’s objects FX2 needs SCOL program (analog copy output) to convert SCS external data of manufacturer’s objects
to dummy points.
Trang 7・ Objects reading / writing
・ Alarm event sending
・ Device monitoring
5 Case study of BACnet (NOHMI)
< System name >
Integlex fire alarm system
< Protocol revision >
ANSI/ASHRAE 135-2004
Client PC B-OWS(MIS)
ANSI/ASHRAE 135-2004
< Information type and objects>
Fire representative information
(BV)
Fir alarm status (BI)
Exhaust-gas protection
equipments running status (MI)
B-BC (SCS)
B-BC BACnet IP
(MI)
Exhaust-gas protection control
status (MO)
Device information (Device)
Notification-Class
< Function >
Fire alarm monitoring
Fire Alarm System
Trang 8・ Objects reading / writing
・ Alarm scan (every 2
min.)
・ Device monitoring
5 Case study of BACnet (TRANE)
< System name >
< Protocol revision >
Client PC B-OWS(MIS)
< Objects >
< Function >
B-BC (SCS)
B-AAC (BCU) BACnet IP
Chiller Plant Control System
Trang 95 Case study of BACnet (DAIKIN)
< System name >
D-BACS
< Protocol revision >
ANSI/ASHRAE 135-2004
Client PC B-OWS(MIS)
・ Objects reading / writing
・ Alarm scan (every 2 min.)
・ Device monitoring
< Objects >
Accumulator
AI/AO/AV
BI/BO/BV
Device
MI/MO
Notification-Class
< Function >
Status / alarm monitoring
BACnet IP
B-ASC (BACnet Gateway)
monitoring
B-BC (Exclusive SCS for BACnet) Status / alarm monitoring
Time program
Event program
Analog measurement /
setting
Trending
VRV System
・ External data
collection
(for trending)
・ Time program
(Exclusive SCS for BACnet)
Trang 106 Special remarks of Modbus system
and Modbus Plus cannot be supported with FX2.
other end of the communication as soon as possible and confirm the possibility of communication with FX2.
one Modbus devices has 99 points in maximum Add one more Modbus device in case of using over 100 points per Modbus Modbus device in case of using over 100 points per Modbus device.
MB3170.
http://www.moxa.com/product/MGate_MB3170_3270.htm
Trang 117 Case study of Modbus (Power
Meter)
< Function >
Current
Client PC MIS
Current
Voltage
Power
Power Factor
Frequency
BACnet IP
SCS with Modbus
Modbus TCP
Modbus Gateway
Power Meter Modbus RTU
Trang 127 Case study of Modbus (Panasonic)
< System name >
< Function >
Client PC
MIS
Modbus TCP
Individual Load
Control
256 circuits But maximum 99 points per controller for SCS makes a priority.
Group Control
BACnet IP
SCS with Modbus
Modbus Gateway
OPIU (Modbus_IFU)
Group Control
Pattern Control
Dimmer Load Control
System Status Monitor
Lighting Control System Modbus RTU