• Plant effect on grid • Grid effect on plant • Interconnection requirements are typically imposed at the PCC Point of Common Coupling • Impacts at the PCC are a function of: • Diversity
Trang 1Power Systems & Energy Course:
Power Quality Issues with Large-Scale Renewable Plants
Jason MacDowell
Trang 2Power Quality – Renewable Plant Perspective
• Power quality is a two way street!
• Plant effect on grid
• Grid effect on plant
• Interconnection requirements are typically imposed
at the PCC (Point of Common Coupling)
• Impacts at the PCC are a function of:
• Diversity of the individual WTGs/PV arrays
• Characteristics of the collector system
• Characteristics of the transmission grid
Trang 3Power Quality Basics
Undervoltages:
Notch – less than one cycle duration
Dip – duration of a few cycles
Sag – duration of seconds to minutes
Interruption – reduction to zero for seconds to minutes
Overvoltages:
Spike – less than one cycle duration
Swell – duration of cycles or more
Waveform Distortion:
Harmonics – steady-state distortion affecting every cycle
integral multiples of operating frequency
Interharmonics – non-integral multiples of operating frequency
Noise – random high-frequency signals
Frequency Shift – variations in frequency through time
Flicker – cyclic or random variations in voltage magnitude
Trang 4Flicker is caused by repetitive variations in voltage – can be
irritant to utility customers
15 1
House Pumps Sump Pumps Air-Conditioning Equipment Domestic Refrigerators Oil Burners
Single Elevator Heights Y-delta Changes
on Generator Sets X-Ray Equipment
Elevator-Motor-Arc Furnace Flashing Signs Arc-W elders Manual Spot-W elders Sews Group Elevators
Reciprocating Pumps Compressors Automatic Spot-W elders
1 3 6 10 20
Border Line of Visibility
Border Line of Irritation
Trang 5Flicker in Wind Plant Applications
– Wind turbulence, gusting
– Drive-train oscillations
– Blades passing tower
– Induction generator close-in inrush
eliminates issue
could be required to meet tight grid specs
Trang 6Flicker in Large PV Plants
• Cloud shadow passage potentially can cause significant
voltage variation
– Frequency of variations usually not sufficient to be technically
considered “flicker” unless variations are very large
– Very large voltage variations would be unacceptable for other reasons
• Output of PV plants becomes smoother as plant rating
increases
– Finite size of cumulus clouds that cause the most intermittent
shadowing
– Output of very large plants approaches (1 - %overcast)*Pclear_sky
• Plant level voltage regulation can readily mitigate voltage
Trang 7Non-Repetitive Voltage Change
– Typically 1% - 2% for frequent events – Some codes relax limits to 3% for infrequent events
– Capacitor/reactor bank switching – Transformer energization
– Feeder switching – Interconnecting HV cable switching
Trang 8Voltage Transients Affecting Grid
– Ringing oscillations, usually at several hundreds of Hz
– Severity depends on point-on-wave of energization
– Synchronized switching -switch closes near voltage zero
– Ideally, eliminates transient – Experience has been that switchgear must operate often to “keep
in training”
– Impedance preinsertion
– Resistor preinsertion (breakers) – Lossy inductor (circuit switchers)
Trang 9What are Harmonics?
voltages superimposed on the system
– Frequencies are multiples of normal system frequency
– Interharmonics are non-integral multiples
Trang 10Harmonic Sources in Renewable Plants
controlled rotor resistance induction generators)
Trang 11– High frequency; are easily filtered
– Random phase superposition self-cancels much of the
harmonics produced in a plant with many WTGs/inverters
• All rotating machines produce a small amount of harmonics due to winding configuration
• WTG harmonics do not usually require action in collector
system design
PWM Waveforms
(Illustration only)
Trang 12GE Test Data
Actual values may be less; it is hard to discriminate harmonics from WTG from harmonics flowing into WTG from grid distortion
Trang 13Harmonic Performance Specifications
IEEE 519 specifies the following limits for “dispersed generation”:
I THD
• Voltage specifications might also be made (individual, and RSS)
• Need to consider impact on wind plant equipment as well:
– Transformers
– Capacitors
Trang 14Harmonics Injected by Plant Into Grid
Zgrid
PCC
I PCC
“Infinite” Bus
Trang 15Impedances at Harmonic Frequencies
– Inductive impedance increases with frequency
– Capacitive impedances (negative) decrease in absolute value with
frequency
components affected by eddy current losses
Inductive Impedance Capacitive Impedance
L f j
R jX
R
Z L 2
C f
j jX
Trang 16L
f I
Z Z
Z
Z I
C L
C L
j
I Z
Z
Z I
C L
C inj
grid
Trang 17Resonant Amplification, with Damping
• Resonant frequency unchanged
• Magnitude of resonant amplification is reduced
• In a realistic system, harmonic voltages and currents can be greatly amplified
j R C f
jR L
f I
j R C f
j I
Trang 18f
0 5 10 15
If
f
Current amplification factor
Trang 19The Grid as a Harmonic Source
– Due to nonlinear loads, P-E devices, transformers
– Greatest at 3rd, 5th, and 7th harmonic
• Good data requires extended-duration monitoring
• IEEE-519 sets “recommended practice” for utilities:
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Vh VTHD
69 – 161 kV 1.5% 2.5%
> 161 kV 1.0% 1.5%
Trang 20Harmonics Injected by Grid Into Plant
ZgridPCC
V Harm
I PCC
I WTG
Trang 21Resonant Amplification of Grid Harmonics
– Substation transformer + capacitor banks & cable
charging
– Can amplify grid distortion
• Problems caused by excess harmonics in collector system
h cap
Z Z
V I
C L
c h
coll
Z Z
Z V
Trang 22HARMONIC ANALYSIS
Trang 23Harmonic Analysis Software Tools
Steady-state phasor analysis – one frequency at a time
• Time-domain modeling tools are not needed
• Some time-domain tools also perform phasor analysis (e.g., EMTP, ATP)
Capability to represent frequency-dependent characteristics of network components
• XL = 2fL XC =-1/(2fC)
• Long-line characteristics of cables and overhead lines
• Frequency-dependent damping characteristics are extremely important
Must handle a large
number of configurations
Trang 24Source Characteristics of WTGs/Inverters
Modern PV inverters and wind turbines do not look like an ideal harmonic current source
• Internal filters are in shunt
• VSC bridge appears like:
– Ideal current source at low frequency (within controller bandwidth)
– Ideal voltage source at high frequency (f >> controller bandwidth)
– Complex transition of characteristics in between
• Shunt impedance of machine
Norton equivalent is the preferred representation
• Source magnitude spectrum depends on operating point
• Equivalent shunt source impedance is a complex function of frequency – does not conform to simple models
Trang 25WTG representation (Internal Distortion)
• Doubly-fed asynchronous generator machine
• Low distortion energy:
– Converter operated with high switching frequency
– Converter rating is a fraction of turbine rating
• Small distortion filter within the turbine to absorb most of the
distortion energy created by the converter.
Trang 26WTG representation and field WTG measurements
• Machine presents a shunt impedance to the grid that will
absorb distortion currents
• Most of measured distortion currents are due to external
sources
• Harmonic current measurements are severely affected by
distortion of external sources
Harmonic measurement
point
Trang 27WTG representation – Norton Equivalent
• Study assumptions based on
physics of the system
• Realistic system distortion
Trang 28Grid Impedance at Harmonic Frequencies
• Transmission grid impedance is important
to both studies of:
– Ambient distortion amplification in the
Trang 29MITIGATING HARMONICS
Trang 30Mitigating Grid Harmonic Amplification
– Selection of transformer impedances and capacitor bank ratings
– This option is limited by the wide range of tunings possible
– Avoid certain operating configurations
– E.g., start up WTGs on one feeder before switching in another feeder, on startup
– Detune shunt capacitors
– Add inductor in series with capacitor – Capacitor cannot resonate at a frequency higher than the frequency defined by the L-C combination
– Typical to select L-C to resonant at 4.8 th harmonic
• Filter out harmonics
– Complex design
Trang 31Harmonic Filter Topologies
Single-Tuned
Filter
1 10 10 0 1 103 1 10410
0.1 1 10
Trang 32Practical Filter Design Considerations
– Tuning taps on inductors
– Variable inductors
– Temperature variations (capacitors)
– Component failures (capacitors)
– System frequency variation
– Component aging
Filter design must be sufficiently robust to meet design objectives for expected variations
Trang 33• Harmonic system studies should be based on realistic
converter modeling guidelines
• Wind/Solar plant equipment can create resonances
(Shunt Caps), particularly to grid distortion If shunt
capacitors are required, consider de-tuning
• If filters are needed, design must be sufficiently robust
to meet design objectives for expected variations.