Power-system stability is a term applied to alternating-current electric power systems, denoting a condition in which the various synchronous machines of the system remain in synchronis
Trang 1MATLAB-based transient
stability analysis of a power system
A PROJECT
ON:-MD SAMAR AHMAD (807056)
MUKESH KUMAR (807057) ADITYA SAHAY (807007)
JYOTI MAYEE PANI (807042)
PROJECT MENTOR:- Dr.C.K.Panigrahi
Trang 2By:-1) ABSTRACT
3) LITERATURE RIVIEW &
MOTIVATION OF THE PRESENT
5) CASE STUDY
8) CASE STUDY OF A MACHINE NINE-BUS SYSTEM
THREE-9) SIMULINK
10) REFERENCES
CONTENTS:
Trang 3Power-system stability is a term applied to
alternating-current electric power systems, denoting a
condition in which the various synchronous machines of the system remain in synchronism, or "in step," with each other Conversely, instability denotes a condition involving loss of synchronism, or falling "out of step."
Occurrence of a fault in a power system causes transients To stabilize the system load flow analysis is done Actually in
practice the fault generally occurs in the load side As
we controlling load side which will lead to complex problem in order avoid that we are controlling the
generator side
A MATLAB simulation has been carried out
to demonstrate the performance of the three-machine nine-bus system.
ABSTRACT
Trang 4 BACK GROUND
The classical model of a multi machine may be used to study the stability of
a power system for a period of time during which the system dynamic
response is dependent largely on the kinetic energy in the rotating
masses
The classical three-machine nine-bus system is the simplest model
used in studies of power system dynamics and requires of minimum
amounts of data Hence such studies can be connected in a relatively short time under minimum cost
Among various method of load flow calculation Newton Raphson method is
chosen for calculation of load flow study If the oscillatory response of a power system during the transient period following disturbance is damped and the system settles in a finite time to a new steady operating condition, we say the system is stable If the system is not stable, it is
considered unstable This primitive definition of stability requires that the system oscillations should be damped This condition is
sometime called asymptotic stability and means that the system contains inherent forces that tend to reduce oscillation
INTRODUCTION
Trang 5 In recent years, energy, environment, right-of-way, and cost problems
have delayed the construction of both generation facilities and new transmission lines, while the demand for electric power has
continued to grow This situation has necessitated a review of the
traditional power system concepts and practices to achieve greater
operating flexibility and better utilization of existing power systems
Transient stability of a transmission is a major area of
research from several decades Transient stability restores the
system after fault clearance Any unbalance between the
generation and load initiates a transients that causes the rotors of the
synchronous machines to “swing” because net accelerating torques are exerted on these rotors If these net torques are sufficiently large to cause some of the rotors to swing far enough so that one or more
machines “slip a pole” and synchronism is lost So the calculation of
transient stability should be needed A system load flow analysis is required for it .The transient stability needs to be enhanced to optimize the load ability of a system, where the system can be loaded
closer to its thermal limits
LITERATURE RIVIEW & MOTIVATION
OF THE PRESENT WORK
Trang 6 Occurrence of fault may lead to instability in a
system or the machine fall out of synchronism Load flow study should be done to analyze the transient stability of the power system If the system can’t
sustain till the fault is cleared then the fault in-stabilize the whole system If the oscillation in rotor angle around the final position go on increasing and the change in angular
speed during transient condition go on increasing then system never come to its final position The unbalanced condition
or transient condition may leads to instability where the machines in the power system fall out of
synchronism Calculation of load flow equation by
Newton Raphson method, Runge Kutta method, and
decoupled method gives the rotor angle and initial condition.
PROBLEM STATEMENT
Trang 7 Each generator operates at the same synchronous speed
and frequency of 50 hertz while a delicate balance between
the input mechanical power and output electrical power is
maintained
Whenever generation is less than the actual consumer
load, the system frequency falls On the other hand,
whenever the generation is more than the actual load, the
system frequency rise The generators are also
interconnected with each other and with the loads
they supply via high voltage transmission line.
An important feature of the electric power system is that
electricity has to be generated when it is needed because
it cannot be efficiently stored Hence using a
sophisticated load forecasting procedure generators are scheduled for every hour in day to match the load
In addition, generators are also placed in active
standby to provide electricity in times of emergency This is referred as spinning reserved.
TRANSIENT STABILITY
Trang 8• The power system is routinely subjected to a
variety of disturbances Even the act of switching on an appliance in the house can be regarded as a disturbance
• However, given the size of the system and the scale
of the perturbation caused by the switching of an appliance in comparison to the size and capability of the interconnected system, the effects are not
measurable Large disturbance do occur on the system These include severe lightning strikes, loss of transmission line
carrying bulk power due to overloading
• The ability of power system to survive the transition
following a large disturbance and reach an acceptable
operating condition is called transient stability
TRANSIENT STABILITY(cont.)
Trang 9The physical phenomenon following a large disturbance can be
described as
follows:-•Any disturbance in the system will cause the imbalance between the
mechanical power input to the generator and electrical power output of the generator to be affected As a result, some of the generators will
tend to speed up and some will tend to slow down.
• If, for a particular generator, this tendency is too great, it will no longer
remain in synchronism with the rest of the system and will be
automatically disconnected from the system This
phenomenon is referred to as a generator going out of step.
TRANSIENT STABILITY(cont.)
Trang 10Transient instability refers to the condition where there is a
disturbance on the system that causes a disruption in the
synchronism or balance of the system The disturbance can be a number of types of varying degrees of severity:
• The opening of a transmission line increasing the X L of the
system
• The occurrence of a fault decreasing voltage on the system (The
voltage at the fault goes to zero, decreasing all system voltages in the area.)
• The loss of a generator disturbing the energy balance and
requiring an increase in the angular separation as other generators
adjust to make up the lost energy
• The loss of a large block of load in an exporting area
TRANSIENT INSTABILITY
Trang 11Acceleration or deceleration of these large generators
causes severe mechanical stresses
Generators are also expensive Damage to generators
results in costly overhaul and long downtimes for repair As a
result, they are protected with equipment safety in mind
As soon as a generator begins to go out-of-step, sensor in the system
sense the out-of-step condition and trip the generators In addition, since the system is interconnected through transmission lines, the imbalance in the generator electrical output power and mechanical input power is reflected in a change in the flows of power on
transmission lines
As a result, there could be large oscillations in the flows on the
transmission lines as generator try to overcome the imbalance and their output swing with respect to each other
EFFECT OF TRANSIENT INSTABILITY
Trang 12ELEMENTARY VIEW OF TRANSIENT STABILITY
Consider the very simple power system of Fig
2.2, consisting of a synchronous generator
supplying power to a synchronous motor over
a circuit composed of series inductive
reactance X
Each of the synchronous machines may be
represented, at least approximately, by a
constant voltage source in series with a
constant reactance
Thus the generator is represented by EG and
XG ; and the motor, by EM and XM
Upon combining the machine reactance and
the line reactance into a single reactance, we
have an electric circuit consisting of two
constant-voltage sources, EG and EM,
connected through reactance
X =X G + XL + XM
Trang 13It is shown that the power transmitted from the generator to the motor depends upon the phase difference δ of the two voltages EG and EM Since these voltages are generated by the flux produced by the field windings of the machines, their
phase difference is the same as the electrical angle between the
Trang 14 The electromechanical equation describing the relative motion of the rotor load angle (δ) with respect to the stator field as a function of time is known
Pt = Shaft power input corrected for rotational loss
Pu = Pm sin(δ)=electric power output corrected for rotational losses
Pm= amplitude of power angle curve
δ = rotor angle with respect to a synchronously rotating referance
SWING EQUATION
Trang 15EQUAL AREA CRITERION
• (lim δo,δ1) ∫ Pa (d δ ) =A1 (positive area);
• (lim δ1,δ2) ∫ Pa (d δ) =A2 (negative area);
Trang 16A 1= Area of acceleration
A2= Area of deceleration
If the area of acceleration is larger than the area of deceleration, i.e.,
A 1 > A2 The generator load angle will then cross the point δm, beyond which the electrical power will be less than the mechanical power forcing the
accelerating power to be positive
The generator will therefore start accelerating before is slows down
completely and will eventually become unstable If, on the other hand, A1< A2, i.e., the decelerating area is larger than the accelerating area, the machine will decelerated completely before accelerating again
The rotor inertia will force the subsequent acceleration and deceleration areas
to be smaller than the first ones and the machine will eventually attain the steady state If the two areas are equal, i.e., A 1 = A 2 , then the accelerating area is equal
to decelerating area and this is defines the boundary of the stability limit
EQUAL AREA CRITERION (cont.)
Trang 17curves of all the machines of a system will show whether the
machines will remain in synchronism after a disturbance In a multi machines system , the output and hence the accelerating power of each machine depend upon the angular positions –and also upon the angular speeds-of all the machines of the system
POINT-BY-POINT SOLUTION OF THE SWING EQUTION
Trang 18i. M1(d2 δ)1 /dt2) =Pi1 – PU1 (δ1 , δ2 , δ3 , dδ1 /dtdt , dδ2 /dtdt , dδ3 /dtdt )
ii.M2(d2 δ)2 /dt2) =Pi2 – PU2 (δ1 , δ2 , δ3 , dδ1 /dtdt , dδ2 /dtdt , dδ3 /dtdt )
iii.M3(d2 δ)3 /dt2) =Pi3 – PU3 (δ1 , δ2 , δ3 , dδ1 /dtdt , dδ2 /dtdt , dδ3 /dtdt )
Formal solution of such a set of equations is not feasible even the simplest
case.so we go for point to point solution which is most feasible and widely
used way of solving the swing equations such solution which are also called step by step solutions ,are applicable to the numerical solution of all sorts of differential equations Good accuracy can be attained and the computational are simple
In a point by point solution one or more of the variables are assumed either to
be constant or to vary according to assumed laws throughout a short interval
of time ∆t , so that as a result of the assumptions made the equations can be solved for the changes in the other 2variables during the same time interval Then, from the values of the other variables at the end of the interval, new value can be calculated for the variables which were assumed constant These new value are then used in the next time interval
In a multi-machine system ,there
are three simultaneous differential equations likes :-
Trang 19
In applying the point by point method to the solution of
swing equations, it is customary to assume that the accelerating power is constant during each time constant during each time
interval, although it has different values in different variables.
The point by point solution of swing curve consists of two
processes which are carried out
alternately:- The first process is the computational of the angular positions,
and perhaps also of the angular speeds at the end of the time
interval from a knowledge of the positions and speeds at the
beginning of the interval and the accelerating power assumed
constant for interval
The second process is the computational of the accelerating
power of each machine from the angular position of all machines
of the system The second process requires knowledge of network solution.
Methods of solution of swing
equations:
Trang 20 Dividing the time interval t in n intervals
From equations (1) &(2)
Trang 21 The equations 3,4,5&6 are suitable for point-by-point calculation.
the preceding interval can be calculated as
δn - δn-1 = ∆δn ;
or, δ n-1 - δ n-2 = ∆δ n-1 ;
or, ωn -1 - ωn-2 = ∆ωn-1 ; From equation (5)
∆ ω n-1 = (P a(n-2) ∆t /dtM); ………….(10) using eq (9) &(10)
∆ δn = ∆δn-1 + ∆t Pa(n-2) ∆t /dtM +(Pa(n-1) - Pa(n-2)) (∆t ) 2 /dt2M;
Or, ∆t(ω δn = ∆t(ωδn-1 +(Pa(n-1) + Pa(n-2)) (∆t(ωt )2/2M; …… (final eq for point by point soln.)
Mathematical derivation for computational algorithm
Trang 22
A synchronous machine performing oscillation of small amplitude with respect to an infinite bus ,its power output may be assumed to be directly proportional to its angular
displacement from the infinite bus considering a 50 cycle machine for which H = 2.7
Mj-per Mva And which is operating in the steady state with input and output of 1.00
pu and angular displacement of 45 o (elec.) with respect to an infinite bus Upon
occurrence of a fault ,we assume that the input remains constant and that output is given
The inertial constant is
M = H /dt(pi*f) =2.7/dt(pi*50) = 017188( unit power sec 2 per elec.rad )
or ,M = H/dt(180*f) =0.30micro ( unit power sec 2 per elec.deg )