device, wall mounted Duplex receptacle outlet, Isolated ground, wall mounted Duplex receptacle outlet, split wired, wall mounted Duplex special purpose outlet Emergency outlet, ‘wall
Trang 1Quick guide Residential Wiring Diagrams,
Codes, And Symbols
traveler wires j{ evelor wires:
XÃ Ales to light
Sway switch with light at end
Outlet symbols Duplex receptacle outlet with GFI or GFC! device, wall mounted
Duplex receptacle outlet, Isolated ground, wall mounted Duplex receptacle outlet, split wired, wall mounted Duplex special purpose outlet Emergency outlet,
‘wall mounted Garbage disposal outlet, wall mounted
General outiet,
Trang 2
Electrical circuits
microwave 240-volt circuit
oven circuit for electric stove
5'
TUB/SHOWER OVER 1/2" W.P GYP BRD 42" WALL
1/2" W.P
\
RA 24"x24" DBL DOMED ©
| \\ 30" ibe ~—.k_ INSULATED TEMP
| (KNEE SPACE GLASS SKYLIGHT
h
Trang 3—@®) BLANKED OUTLET MOMENTARY CONTACT
FAN OUTLET S, : THREE WAY SWITCH 5 OUTLET Seo REMOTE CONTROL
3H” = 3 SINGLE, TRIPLEX, ETC Se mmaAmmmmn
S FOUR WAY SWITCH
WITH PULL SWITCH S ELECTROLIER SWITCH WPF
E ® SPECIAL PURPOSE
S SWITCH AND PILOT LAMP
VAPOR DISCHARGE —* @) FLOOR OUTLET POWER PANEL
SWITCH € KEY OPERATED SWITCH
K
EXIT QUXET € og CIRCUIT BREAKER
Trang 4Electrical Wiring Diagrams
Simple outlet circuit middle of : | end of
=) circuit
tie all ground wires together
Trang 5Pigtail GFCI Outlets
Fas irk
Attach to terminal
pigtail off
‘e)molgeell
Trang 6Single switch before light
Trang 73-way switch with light in center
Trang 9trance to breaker box
Trang 11Cable Sizes
30-Amps 20-Amps 15-Amps 10-Amps 7-Amps
3-wire armored cable
UF cable
Trang 12Electric 120/240V Two #6 hot wires @ @
range 50 amps and a #8 neutral wire 129/240V 120/240V
The following rules apply to 15A & 20A receptacles on 120V circuits They do
not apply to 240V receptacles or to 30A 120V receptacles
L] AII bathroom receptacles [3802.1] {210.8A1}
LJ All garage & accessory building receptacles [3802.2] {210.8A2}?"
LJ All receptacles in unfinished basements EXC [3802.5] {210.8A5}?"
Permanently installed fire or burglar alarm system [3802.5X3] {210.8A5X}
The 2005 NEC and the 2006 IRC have exceptions for receptacles in garages
and unfinished basements that are not readily accessible or that serve applianc-
es not easily moved from one place to another, such as freezers A receptacle
for a single appliance under that exception must be a single receptacle, and for
two such appliances a duplex receptacle can be used
L] All outdoor receptacles EXC [3802.3] {210.8A3}
Receptacles for snow melting & deicing equipment on dedicated branch
circuit if located so they are not readily accessible _ [38 02.8X] {210.8A3X}
L] Equipment plugged into receptacles installed under above exception
req’s GFPE protection in plug cap [4001.7] {426.28}
L] All receptacles in crawlspaces at or below grade level _[3802.4] {210.8A4}
L] All receptacles serving kitchen counters F30 [3802.6] {210.8A6}
L] Receptacles within 6ft of outside edge of laundry, utility,
or wet bar sinks [3802.7]? {210.8A7}
(] Receptacles in boathouses [3802.8] {210.8A8}
Trang 13Residential Electrical Guidelines
240-volt outlet, wall mounted 240-volt outlet, clothes wall mounted
240-volt outlet, range, wall mounted Clothes washer outlet,
wall mounted Dishwasher outlet, wall mounted
Duplex receptacle outlet,
te
Here are a few typical guidelines that apply to residential work These are NOT legal interpretations
of any one code, so check with your local authority before starting work
Duplex receptacle outlet, floor mounted Duplex receptacle outlet, wall mounted
dditional 240-
Duplex receptacle outlet
with GFI/GFCI device, wall
mounted One lighting/convenience outlet circuit should be for every 575 square feet of floor space in a house
Any bathroom or garage outlet within 6' of a sink must be Ground-Fault Circuit Interrupter (GFCI) protected All kitchen
outlets for countertop must be GFCI protected Bedroom outlets should be Arc-Fault Circuit Interrupter (AFC!) protected
Duplex special purpose
outlet, key letter or abbrev., or indicate NEMA
config Emergency outlet, wall mounted
Garbage disposal outlet, wall mounted
General outlet, ceiling
mounted General outlet, wall mounted
Junction box, ceiling mounted
At least one GFCI outlet is required in an unfinished basement, as well as most outdoor outlets Exceptions include inacces- =<
sible outlets like those in a garage or behind a refrigerator eS
Any point along the bottom of a wall (which is 2' or wider) must be within 6' of an outlet The 6' distance cannot be measured | _*
across a doorway or fireplace And the outlet must be within 5 1/2' of the floor (This cuts down on extension cord use, espe- @®
cially across doorways, fireplaces and similar openings )
room, hallway, stairway
light switch must control
, for example) or ar
Rough-in Electrical i
In a new house, addition or major remodeling project, cable and boxes are "roughed-in"
before the walls are insulated and drywalled
dunction box, wall
mounted
Notching walls and drilling holes
STUDS
Actual ; NOTCHED Dimensions
Nominal Dimensions NOTE: Insulation can be put up then removed for an inspection, but inspection must be
done before the walls are sealed by a vapor barrier and wallboard DRILLED
Make sure wall switches are located with proper respect to door swing,
and wall outlets will not conflict with tile, cabinets, lockers, casework, or
Each box should stick out a little past the framing so its front will be flush
with — or set back just a fraction from — the drywall
Notches should represent less than 25% of the joist depth (see Notched / 25% above) Holes should represent less than 60% of the joist depth (see Drilled / 60% above)
You can use a scrap piece of drywall to set boxes out the right distance `
Some boxes even have a pre-formed %" reference line for quick installation |
: Non-Load-Bearing Walls
Drill or notch the framing to allow for the cable/wiring to run between
boxes, down into the under-floor crawl spaces, up into the ceiling, as well
as through studs (Most rooms have either an attic above or a basement/
crawlspace below Drill holes so cable runs horizontally through joists.)
the joist depth (see Notched / 40% above)
A heavy-duty right-angle drill with a 1" bit is the tool for this job Wall holes
drilled at about knee-height will be just right for outlets Holes through ` JOISTS
Ceiling joists and wall plates will be a bit harder; that's where the right-angle | Notches must represent less than 1/6th of the depth of the joist
drill comes in really handy
Notches should represent less than 40% of
boxes (See "Pulling Cable," inside.)
Drilled holes in joists must not be within 2 inches of an outside edge of the joist Pull wire/cable into each box; clip, clamp and cap
Drilled holes must represent less than 1/3rd of the overall depth of the joist
Use metal reinforcing plates (nailing plates) at all points where the drilled
hole is less than 1%" from either outside edge of a stud or joist Nailing
plates are required over all notches
Trang 14
Cable Checklist
Cabling must be installed and supported properly It also must be protected from
physical damage and from electrical damage
PULLING CABLE
"Running cable’ or "pulling cable" is a bit more involved than it sounds
Bends in Romex must not be made too sharply Bending cable incorrectly can
weaken the outer sheathing as well as the insulation on the individual conduc-
tors The radius of the curve of the inner edge of any bend must not be less than
five times the diameter of the cable A correct installation will result in a "jug
handle."
| Getting cable to cooperate can be frustrating and time consuming So
_ it helps to be patient and a bit creative
-check your circuit diagrams before running any cable Also
Cable must be fastened to the framing every 4-1/2 feet, using staples, cable ties,
straps, hangers, or similar fittings
note where you can double-up runs anywhere by pulling two atonce
Flat cables (e.g., 14/2 Romex or 12/2 Romex) must not be stapled on edge ulling wire through conduit, or even when pulling nonmetal-
Flat cables may be installed on top of one another and fastened with one staple,
so long as one flat side of one cable is against the framing member and the |
other flat side is against the flat side of the next cable (Two cables should not
be placed side-by-side and fastened with one staple; this can damage the cable
insulation.)
thed cable through holes in studs, joists, etc., "fish tape" can
ough holes, hooked to the cable or wire, and pulled back to
ll cable is to start at the last fixture in the run, pull
Where cable runs through wood framing members, it must be no closer than
1-1/4 inches to the nearest edge of the framing member When this clearance
cannot be maintained, a nailing plate must be added for protection In cases
where a framing member is notched to accommodate electrical cabling, a nailing
plate is always required
complete the run, and then start pulling it
Where cable runs through metal studs, plastic grommets must be inserted in ail |
holes, whether those holes are manufactured or field-drilled The plastic grom-
met must cover all metal edges of the hole, to provide physical protection as the
cables are pulled through the metal studs
g runs, you may need to return to the
to feed more cable through Two people
tangle or bind If you feel re-
Openings around penetrations through walls, floors, and ceilings must be filled
with an approved fire-stopping material (Some locales require fire-stopping
Cabling must be secured within 12" of every nonmetallic box that's larger than
2%" x 4" vice panel, leave a foot or so of
and the box/spool end for
All cables that run into metal or plastic boxes must be protected from abrasion
This can be accomplished by using connectors that have smooth openings for
the cabling to go through or by simply making sure a short section of the cable
sheathing extends past the clamping mechanism of a cable clamp
All cables that run into metal or plastic boxes must be secured to the boxes Com-
monly, this is done using internal or external clamps
Account for the voltage drop that can be caused by long runs of cable Try to limit
drop to less than 3% (See Voltage Drop table.)
Separate runs of cable/wire are required for bedroom outlets (so they can be
provided with Arc-Failure Circuit Interrupter (AFC!) protection The same is true
for any other circuits requiring AFCI or GFCI protection
"Hot" wire In an outlet, itis always
"Ground" or "grounding" wire In an
"Second hot" wire in a 3-way outlet
CIRCUIT TYPE
wired to the narrow spade or brass-colored terminal
outlet, it is always wired to the green terminal
Often called the "traveler."
"Neutral" wire In an outlet, it is always wired to the wide spade or silver-colored terminal
Trang 15
M v
Electrical Switch Symbols
Fused switch, wall mounted
Fused safety switch
xxAF= frame size
xxAT= trip size
Key controlled switch,
Manual motor switch,
with thermal overloads
wall mounted
Momentary contact Intermittent
switch, wall mounted
Motion detector sensor
Photoelectric switch
Pilot/remote light switch
load off, wall mounted
Pilot/remote light switch
load on, wall mounted
Remote control switch
receiver, wall mounted
Ceiling pull switch
ceiling mounted
Chain pull switch
Circuit breaker switch,
Dimmer switch, wall mounted
Disconnect safety switch
Door, closet, or jamb switch
Double pole switch, wall mounted
Electric eye, relay
Electric eye, source
Enclosed circuit breaker
xxAF= frame size
xxAT= trip size
Evaporative cooler switch
3-switches, fan, pump,
speed controller, wall mounted
Explosion proof switch
wall mounted
Flourescent light dimmer
switch, wall mounted
Four-way switch, wall mounted
Three-way switch, wall mounted
Timer or motor switch with thermal overload wall mounted Time clock switch Variable speed or volume control switch, wall mounted
Wall bracket pull switch
Weather proof circuit
breaker, wall mounted Weather proof switch, wall mounted Cable tray Conduit turning up Conduit turning down Conduit with capped end Emergency circuit Exposed circuit Homerun to panel letters indicate panel numbers indicate circuits
Plug in or feeder bus
Trang 16Exat light, wall mounted
arrow indicates exit
Exit light, recessed
wall mounted
Exit light, shaded area
indicates number of faces shown, arrow indicates exit
no arrow when directly
over an exit door
Flourescent fixture, ceiling mounted
Flourescent lighting fixture,
O Flourescent lighting fixture,
p pendant style, ceiling mount Same as above, wall mount
Flourescent lighting fixture
recessed style
ceiling mount Flourescent lighting fixture surface mount with outlet
box, ceiling mount Flourescent lighting fixture
on critical branch circuit
Bit Fiourescent | ® | on emergency circuit Mel lighting fixture
Trang 17Flourescent fixtures continuous row
Illuminated house number,
wall mount
Incandescent lighting fixture,
ceiling mounted
bank, urued caling routed
Incandescent lighting fixture,
chandelier, ceiling mounted
(Oy @ controlled by low voltage switch relay in box, wail mounted
Incandescent lighting fixture,
Œˆ letter in triangle is reference
to key, ceiling mounted
Incandescent lighting fi :
mimoriveray lights, wall mounted
Incandescent lighting fixture,
multiple flood lights,
KAR Wea mounted
Incandescent lighting fixture,
OO recessed, ceiling mounted
5 Incandescent lighting fixture,
fixture, ceiling mounted
Incandescent lighting fixture, rough-in only, ceiling mounted Incandescent lighting fixture,
spot light, ceiling mounted Incandescent lighting fixture,
heat tamp, ceiling mounted
Incandescent llighting standard
uppercase = key, number= 4k circuit number, switch contro! Ơ
@:+o@
Incandescent lighting fixture
surface directional light wall mounted
incandescent lighting
fixture, track lighting
Incandescent lighting fixture
MN underwater recessed, bottom fixture
=r Incandescent lighting fixture
underwater recessed, wall mounted
® underwater Incandescent lighting fixture
up beam (ar bottom mounted
( Oy) Incandescent lighting fixture
(S=) watitan
LÔ On va nương
Trang 18Outlet Symbols
220-volt outlet, wall mounted 220-volt outlet, clothes dryer wall mounted
220-voit outlet, range,
Blanked (unused) quad
outlet, wall mounted
©0943
Clothes washer outlet, wall mounted
Combination switch and double
outlet, receptacle, wall mounted
Combination switch and single outlet receptacle, wall mounted
Dishwasher outlet wall mounted Drop cord
Trang 19@eoojn”®92
Outlet symbols
Duplex receptacle outlet
with GFI or GFCI device,
wall mounted
Duplex receptacle outlet,
isolated ground, wall mounted
Duplex receptacle outlet,
split wired, wall mounted
Duplex special purpose outlet Emergency outlet,