Warranty and LiabilityWinCC S7-1200/ S7-1500 Warranty and Liability Note The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping
Trang 1Configuration Example 10/2014
WinCC Connection to
S7-1200 and S7-1500
WinCC V7.3
Trang 2Warranty and Liability
WinCC S7-1200/ S7-1500
Warranty and Liability
Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality The Application Examples do not represent customer-specific solutions They are only intended
to provide support for typical applications You are responsible for ensuring that the described products are used correctly These Application Examples do not relieve you of the responsibility to use sound practices in application, installation, operation and maintenance When using these Application Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described We reserve the right to make changes to these Application Examples at any time and without prior notice If there are any deviations between the recommendations provided in these Application Examples and other Siemens publications – e.g Catalogs – the contents of the other documents have priority
We do not accept any liability for the information contained in this document Any claims against us – based on whatever legal reason – resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded Such an exclusion shall not apply in the case of mandatory liability, e.g under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”) The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health The above provisions do not imply a change of the burden of proof to your detriment
Any form of duplication or distribution of these Application Examples or excerpts hereof is prohibited without the expressed consent of Siemens Industry Sector
Security
informa-tion
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks They are important components in a holistic industrial security concept With this in mind, Siemens’ products and solutions undergo continuous development Siemens recommends strongly that you regularly check for product updates
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g., cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept Third-party products that may be in use should also be considered For more information about industrial security, visithttp://www.siemens.com/industrialsecurity
To stay informed about product updates as they occur, sign up for a product-specific newsletter For more information, visit
http://support.automation.siemens.com
Trang 3Table of Contents
Table of Contents
Warranty and Liability 2
1 Task 4
2 Solution 5
2.1 Overview 5
2.2 Hardware and software components 7
2.2.1 Validity 7
2.2.2 Components used 7
3 Configuration and Settings 9
3.1 Loading AS symbols from an existing S7-1500 program 9
3.2 Loading AS messages from an existing S7-1500 program 15
4 References 18
5 History 18
Trang 41 Task
WinCC S7-1200/ S7-1500
Figure 1-1
S7-1500
S7-1200
WinCC V7.3 Encrypted
process connection
Process connection
Introduction
The task is to provide process tags and AS messages of S7-1200 and S7-1500 in WinCC V7.3
It is to be possible to establish a protected HMI connection to S7-1500
Trang 52 Solution
2.1 Overview
2.1 Overview
Setup
The following scheme shows the most important components of the solution:
Figure 2-1
S7-1500
S7-1200
PROFINET IE
WinCC V7.3
SIMATIC S-1200, S7-1500 Channel
Description
WinCC V7.3 provides the communication channel "SIMATIC S7-1200, S7-1500 Channel" for communication with S7-1200 and S7-1500 CPUs
Communication to S7-1200 and S7-1500 can be realized with absolute addressing and since WinCC V7.3 also with symbolic addressing
Between WinCC V7.3 and S7-1500, a protected communication connection can be established
Characteristic features
· Access to the symbolic addresses and CPU alarming is effected via the online connection to the CPU only
· Offline configuration is only possible for the absolute addresses
Note Currently, no raw data tags can be used via the
"SIMATIC S7-1200, S7-1500 Channel"
Trang 62 Solution
2.1 Overview
WinCC S7-1200/ S7-1500
Features of the communication to S7-1200 and S7-1500
· Cyclic reading of tags
· Chronological reporting (program alarm)
· Loading of AS messages (S7-1500)
· Password protection
· Time synchronization
· Use of S7-1200/S7-1500 tags in WinCC – Export/Import function
1) Export of the tags from TIA Portal (only absolute addressing) 2) Import to WinCC via the WinCC Configuration Studio
· Loading of AS symbols
Delimitation
This application does not contain a description of:
· Configuration of S7-1500 in TIA Portal
· Installation of SIMATIC TIA Portal and WinCC V7.3 Basic knowledge of these topics is assumed
Assumed knowledge
Basic knowledge of WinCC V7.3 and SIMATIC TIA Portal is assumed
Trang 72 Solution
2.2 Hardware and software components
2.2 Hardware and software components
2.2.1 Validity
This application is valid for
· STEP 7 from V13
· WinCC V7.3
· S7-1200 (from firmware V2.2)
· S7-1500
2.2.2 Components used
The application was created with the following components:
Hardware components
Table 2-1
S7-1516-3 PN/DP 1 6AG1516-3AN00-7AB0 Alternatively, any other
S7-1500 or S7-1200 can be used Development
system
1 PC for configuration of
controller and WinCC.
The hardware requirements for STEP 7 and WinCC apply.
Software components
Table 2-2
WinCC V7.3 1 6AV63.1- 7-3
TIA Portal STEP 7 V13 Professional
1 6ES7822-1 03- Alternatively, TIA Portal
STEP 7 V13 Basic can be used for S7-1200.
NOTE Use the SIMATIC NET V12 installation being enclosed to WinCC V7.3 if no
STEP 7 or TIA Portal is installed on the computer (With it the communication drivers are installed.)
Sample files and projects
The following list includes all files and projects that are used in this example
Trang 82 Solution
2.2 Hardware and software components
WinCC S7-1200/ S7-1500
Table 2-3
color_filling_station.zip Getting Started
S7-1500 101908495_WinCC_S71200_S71500_Chanel_de.pdf This document.
Trang 93 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
3.1 Loading AS symbols from an existing S7-1500 program
This section describes the configuration of tags in WinCC with optimized block access to the address range in the S7-1500 automation system
Table 3-1
Create a new WinCC project or open an existing one.
Open Tag Management.
Enter the IP address, access point, and product family.
3 Add a SIMATIC S7-1200, S7-1500 Channel.
Trang 103 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
WinCC S7-1200/ S7-1500
4 Right-click and add a "New Connection".
5 Right-click and open the "Connection parameters".
Enter the new IP address of your S7-1500 or S7-1200 here.
Trang 113 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
6 Optional: Realize a protected connection to S7-1500 by entering a password.
Note
Password protection is only provided by S7-1500 CPUs Further information is available in the manual:
"SIMATIC S7-1500 Automation System > Protection > Configuring access protection for the CPU " \3\
Start WinCC Runtime.
Trang 123 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
WinCC S7-1200/ S7-1500
Right-click on the connection and go to "AS Symbols -> Read from AS" to read out the symbols of the S7-1500.
These are read now.
Confirm the message with OK.
Trang 133 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
9 The symbols of the S7-1500 are now listed under "AS Symbols":
10 By checking the "Access" check box, the tags with symbolic addressing are
automatically created.
11 These are now displayed on the "Tags" tab together with their properties.
Trang 143 Configuration and Settings
3.1 Loading AS symbols from an existing S7-1500 program
WinCC S7-1200/ S7-1500
12 You can change the tag name on the "Tags" and "AS Symbols" tabs.
Note If modifications are made to the controller, it is necessary to execute the
"Read from AS" command again
Note If WinCC Runtime is stopped and Tag Management is closed, neither the
symbolic addressing nor the "AS Symbols" tab is displayed any longer Both can be displayed in Tag Management again with the "Read from AS" command
Trang 153 Configuration and Settings
3.2 Loading AS messages from an existing S7-1500 program
3.2 Loading AS messages from an existing S7-1500
program
Table 3-2
1 Open the "Alarm logging" editor.
Trang 163 Configuration and Settings
3.2 Loading AS messages from an existing S7-1500 program
WinCC S7-1200/ S7-1500
2 Under "AS Messages", right-click on the connection "NewConnection_1" to
open the context menu.
3 Click on "Load from AS" to import the system messages.
Trang 173 Configuration and Settings
3.2 Loading AS messages from an existing S7-1500 program
4 Now the tabs "AS Messages" and "AS Text lists" are available.
Note Loading the AS messages is only possible with an S7-1500
Trang 184 References
WinCC S7-1200/ S7-1500
Table 4-1
\1\ Siemens Industry Online Support
http://support.automation.siemens.com
\2\ Download page of the entry
http://support.automation.siemens.com/WW/view/en/101908495
\3\ S7-1500 Manual;
Access Protection
https://www.automation.siemens.com/mdm/default.aspx?DocVersionI d=63956397195&TopicId=62467847691
Table 5-1
V1.0 10/2014 First version