Short-Circuit CalculationsWhen the current flow path is directed correctly, the pres-sure of the source voltage forces normal current magnitudes to flow through the load impedances.. In
Trang 1Short-Circuit Calculations
When the current flow path is directed correctly, the pres-sure of the source voltage forces normal current magnitudes
to flow through the load impedances During this time, the insulation surrounding the energized conductors prevents current from flowing through any path other than through the load impedance In this situation, the load impedance is large enough to limit the current flow to “normal” low val-ues in accordance with Ohm’s law:
E I Z
Problems arise, however, when the conductor insulation fails, permitting a shortened path for electron flow than
through the load impedance If the shortened path, or short circuit (also known as a fault), permits contact between a
phase conductor and an equipment grounding conductor,
this is known as a ground fault, or a phase-to-ground fault.
If, however, the shortened path instead permits contact between two or three phase conductors, then it is known as
a phase-to-phase fault.
If a solid connection is made between the faulted phase con-ductor and the other phase wire or the equipment grounding
conductor, then the short circuit is identified as a bolted fault.
5
179 v
Copyright 2001 by The McGraw-Hill Companies, Inc Click here for Terms of Use
Trang 2In bolted faults, little or no arcing exists, the voltage drop across the very low impedance of the almost-nonexistent arc
is very low, and the fault current is of high magnitude
If an arcing connection is made between the faulted phase conductor and the other phase wire or the equipment grounding conductor, then the short circuit is identified as an
arcing fault, with its associated lowered fault current flow In
certain systems, this arcing fault current can be so low that
it is not recognizable as a problem to the upstream overcur-rent device During such events, excessive heat buildup around the arc can occur, causing further damage to the oth-erwise sound electrical system or starting fires in nearby structures or processes Even though the fault may be small, heat energy flows from it over time to the surroundings, eventually causing high temperatures High temperatures applied to most wire insulation systems cause plastic defor-mation and failure, frequently resulting in an even more severe short circuit than the original one It is because of this consideration that everything possible must be done to inter-rupt current flow to a fault as soon as possible after the beginning of the fault or to limit fault current flow in some way, such as with transformers or grounding resistors Considering that fault current can reach several hundred thousand amperes, interrupting fault current flow can be a formidable task, so one rating of circuit breakers and fuses intended to interrupt fault currents is the ampere rating that each can interrupt These device ampere ratings fre-quently are given in terms of symmetrical current values (providing for no direct-current offset) or in terms of asym-metrical current values that include provision for direct-cur-rent (dc) offset The relative amount of dc offset and resulting asymmetrical current value multiplier used to multiply by the symmetrical current value are related to the
X/R value of the system at the point of the fault With a
highly resistive circuit having little reactance, the difference between the symmetrical and asymmetrical current values are minimal (there could be no difference at all), but with a highly reactive system containing only a small resistance value, the asymmetrical current value could be a multiple of three to five times the symmetrical value, or higher
Trang 3Large values of current cause large magnetic forces When fault current flows through switchgear or a circuit breaker, the bus bars therein are attracted to one another and then are forced apart from one another at a frequency
of 50 or 60 times per second depending on the frequency of the power source This equipment must be braced to with-stand these forces, and this bracing is rated and is called the
withstand rating of the equipment Thus a circuit breaker
must be rated in full-load amperes for normal operation, it must have a withstand rating, and it must have an inter-rupting rating
The interrupting rating of a circuit breaker depends largely
on how fast its contacts can operate to begin to interrupt the current flow in the circuit A breaker that is extremely fast, with a contact parting time of, say, one cycle, must be able to
interrupt much more current in a system with a large X/R
value than would a slower breaker Fuses, on the other hand, are able to open and interrupt fault current in less than 14
cycle, so fuses must carry accordingly greater ratings Although the calculation of the asymmetrical current val-ues from the symmetrical current valval-ues is important, most of the short-circuit calculation work goes into determining the symmetrical short current availability at the prospective fault point in the electrical power system This symmetrical current calculation normally is done for a phase-to-phase fault, with the knowledge that this is normally the most demanding case Rarely (only where the fault occurs near very large electrical machines having solidly grounded wye connections) does the phase-to-ground fault exceed the phase-to-phase fault in cur-rent availability Therefore, concentration is on the phase-to-phase fault for the electrical power system with the largest expected quantity of rotating machines that will exist on the system in the foreseeable future
Short-circuit currents present a huge amount of destruc-tive energy that can be released through electrical systems under fault conditions These currents can cause serious damage to electrical systems and to equipment or nearby persons Protecting persons and electrical systems against damage during short-circuit conditions is required by the
National Electrical Code (Secs 110-9 and 110-10).
Trang 4Not only should short-circuit studies be performed when a facility electrical system is first designed, but they also should be updated when a major modification or renovation takes place and no less frequently than every 5 years Major changes would include a change by the electrical utility, a change in the primary or secondary system configuration within the facility, a change in transformer size or imped-ance, a change in conductor lengths or sizes, or a change in the motors that are energized by a system
When modifications to the electrical system increase the value of available short-circuit current, a review of overcur-rent protection device interrupting ratings and equipment withstand ratings should be made This may entail replacing overcurrent protection devices or installing current-limiting devices such as current-limiting fuses, current-limiting circuit breakers, or current-limiting reactors The key is to know, as accurately as possible, how much short-circuit current is available at every point within the electrical power system
Sources of Short-Circuit Current
Every electrical system confines electric current flow to
select-ed paths by surrounding the conductors with insulators of var-ious types Short-circuit current is the flow of electrical energy that results when the insulation barrier fails and allows cur-rent to flow in a shorter path than the intended circuit In nor-mal operation, the impedances of the electrical appliance loads limit the current flow to relatively small values, but a short-cir-cuit path bypasses the normal current-limiting load imped-ance The result is excessively high current values that are limited only by the limitations of the power source itself and by the small impedances of the conductive elements that still remain in the path between the power source and the short-circuit point Short-short-circuit calculations are used to determine how much current can flow at certain points in the electrical system so that the electrical equipment can be selected to with-stand and interrupt that magnitude of fault current In short-circuit calculations, the contribution of current sources is first determined, and then the current-limiting effects of
Trang 5imped-ances in the system are considered in determining how much current can flow in a particular system part
There are three basic sources of short-circuit currents:
■ The electrical utility
■ Motors
■ On-site generators
There are two types of motors that contribute short-circuit current:
■ Induction motors
■ Synchronous motors
Between these sources of short-circuit current and the point
of the short circuit, various impedances act to limit (impede) the flow of current and thus reduce the actual amount of short-circuit current “available” to flow into a short circuit Naturally, the value of these impedances is different at every point within an electrical system; therefore, the magnitudes
of short-circuit currents available to flow into a short circuit
at different places within the electrical system vary as well Several calculation methods are used to determine short-circuit currents, and reasonably accurate results can be derived by system simplifications prior to actually perform-ing the calculations For example, it is common to ignore the impedance effect of cables except for locations where the cables are very long and represent a large part of the overall short-circuit current path impedance Accordingly,
in the most common form of short-circuit calculations, short-circuit current is considered to be produced by gener-ators and motors, and its flow is considered to be impeded only by transformers and reactors
The Ability of the Electrical Utility System to
Produce Short-Circuit Current
By definition, the source-fault capacity is the maximum out-put capability the utility can produce at system voltage
Trang 6Generally, this value can be gotten from the electrical
utili-ty company by a simple request and is most often given in amperes or kilovoltamperes
Suppose that the utility company electrical system inter-face data are given as
MVASC 2500 at 138 kilovolts (kV) with an X/R
7 at the interface point
For this system, the utility can deliver 2,500,000 kilo-voltamperes (kVA) ÷ [138 kV(兹3苶)], or a total of 10,459 sym-metrical amperes (A) of short-circuit current
The short-circuit value from the electrical utility company will be “added to” by virtue of contributions from the on-site generator and motor loads within the plant or building elec-trical power system That is, the short-circuit value at the interface point with the electrical utility will be greater than just the value of the utility contribution alone
Short-Circuit Contributions of On-Site
Generators
The nameplate of each on-site generator is marked with its
subtransient reactance X d ″ like this This subtransient
val-ue occurs immediately after a short circuit and only contin-ues for a few cycles For short-circuit current calculations, the subtransient reactance value is used because it produces the most short-circuit current
Determining how many kilovoltamperes an on-site genera-tor can contribute to the short-circuit current of an electrical power system is a simple one-step process, solved as follows:
Short-circuit kVA
For example, a typical synchronous generator connected to
a 5000 shaft horsepower (shp) gas turbine engine is rated at
7265 kVA, and its subtransient reactance X d″ is 0.17 The
generator kVA rating
d ″ rating
Trang 7problem is to determine the short-circuit output capabilities
of this generator Thus
Short-circuit kVA 42,735 kVA
Note that when more than one source of short-circuit cur-rent is present in a system, the resulting amount of short-cir-cuit kilovoltamperes available to flow through a short cirshort-cir-cuit
is simply the arithmetic sum of the kilovoltamperes from the
various sources, and the total equivalent kilovoltamperes from
all these sources is simply the arithmetic sum of the individ-ual equivalent kilovoltampere values
For example, if two of the preceding 7625-kVA, 138-kV synchronous generators are cogenerating into an electrical power system that is also supplied from an electrical utility whose capabilities on the generator side of the utility trans-former are 300 million voltamperes (MVA), how many total fault kilovoltamperes are available at the terminals of the generator? The answer is
Total kVA 2 (42,735 kVA) 300,000 kVA 385,470 kVA
It is worthwhile to note that the kilowatt rating of the
gen-erator set is not used in this calculation Instead, the
kilo-voltampere rating of the electrical dynamo in the generator set is used because it (not the engine) determines how many short-circuit kilovoltamperes can be delivered momentarily into a fault This is so because most of the fault current is quadrature-component current having a very lagging power factor Another way of saying this is that the fault current does little work because of its poor power factor, and the size
of the engine determines the kilowatt value of real work the generator set can do
Short-Circuit Contributions of Motors
The nameplate of each motor is marked with its locked-rotor code letter as well as with its rated continuous full-load current
7265 kVA
Trang 8and horsepower The locked-rotor value occurs immediately on motor energization and also immediately after a short circuit After a short circuit, this large amount of current flow through the motor only continues for a few cycles (even less time with induction motors) Unless specific information about the indi-vidual motor locked-rotor current characteristics is known, normally, a value of six times the motor full-load current is
assumed Dividing 100 percent current by 600 percent current produces the normally assumed X ″ motor value of 0.17 It is
this value that is used to determine the short-circuit power contribution of a motor or group of motors The characteristics
of small induction motors limit current flow more than those
of larger motors; therefore, for calculations involving motors smaller than 50 horsepower (hp), the 0.17 value must be increased to 0.20 In addition, the approximation that 1 hp equals 1 kVA normally can be made with negligible error,
par-ticularly with motors of less than 200 hp
Determining the short-circuit contribution from a motor is
a simple one-step process solved as follows:
Short-circuit power
(Note: 1 hp 1 kVA for this calculation.)
Unless specific values of subtransient reactance or motor locked-rotor code letter are known, for motors of 50 hp and less, use 0.20 for the subtransient reactance For individual motors or groups of motors producing 50 hp and more, use 0.17 for the subtransient reactance Always assume that 1
hp 1 kVA.
For example, a typical 460-volt (V) motor is rated at 40 hp Determine the short-circuit contribution of this motor Thus
Short-circuit power 200 kVA
If there were 10 identical motors of this same rating con-nected to one bus, then their total short-circuit contribution
at the bus would be 10 200 kVA 2000 kVA.
40 kVA
0.20
motor horsepower rating
Trang 9Note that for motors of 50 hp or larger, the X d″ rating of 0.17 should be used For example, a typical 4.16-kV motor is rated at 2000 hp Determine the short-circuit power contri-bution of this motor
Setting 1 hp equal to 1 kVA, we get
Short-circuit power 11,764 kVA
If all the short-circuit current contributors were at the same voltage, then short-circuit currents simply could be added to one another to determine the total amount avail-able to flow in a system However, because transformers greatly lessen the flow of fault current and also change volt-ages, the impact of transformers must be considered, and fault values transported through transformers must be cal-culated in terms of power instead of amperes
Let-Through Values of Transformers
For any transformer, the maximum amount of power (the fault capacity) that the transformer will permit to flow from one side of the transformer to the other side, in kilovoltam-peres, is calculated as
Let-through power
For example, a 2000-kVA transformer has a nameplate impedance of 6.75 percent, and its voltage ratings are 13.8 kV-277/480 V, three phase Find the maximum amount of power that this transformer can let through if it is energized from an infinite power source The answer is
Let-through power
2000 29,630 kVA
0.0675
transformer kilovoltampere rating
%Z/100
transformer kilovoltampere rating
2000 kVA
Trang 10If the power source upstream of the transformer is not infinite, then the amount of power that would be available
on the load side of the transformer would be less, and it is calculated using admittances as follows:
■ Utility short-circuit power is UP, and its admittance is 1/UP.
■ Maximum transformer let-through is T, and its admit-tance is 1/T.
■ Net power from the utility let through the transformer P
is calculated as
P
Where the utility can supply 385,000 kVA, the amount that the preceding 2000-kVA, 6.75 percent impedance trans-former can let through, or admit, is calculated as
Let-Through Values of Reactors
Similar to a transformer coil in its current-limiting charac-teristics, a reactor is a series impedance used to limit fault current In a three-phase circuit, there are normally three identical reactor coils, each connected in series with the phase conductors between the source and the electrical load The amount of power that a reactor will let through from an infinite power source to a short circuit on the output termi-nals of the reactor is calculated as
Let-through power
1000 (phase-to-phase kilovolt circuit rating)reactor impedance in ohms per phase 2
1
(1/385,000) (1/29,630)
1
(1/UP) (1/T)