Concentrically braced frames, which are designed to these higher ductility stan-dards, can be designed for smaller seismic design forces and are called special concentricallybraced frame
Trang 2LATERAL-FORCE DESIGN 9.21
FIGURE 9.11 Photograph of crack through the column flange and
into the column web or panel zone of connection.
of these buildings collapsed and there was no loss of life, but the economic loss was siderable This unexpected damage has caused a new evaluation of the design of momentframe connections through the SAC Steel Project SAC is a joint venture of SEAOC, ATC(Applied Technology Council), and CUREE (California Universities for Research in Earth-quake Engineering), and the joint venture is funded by FEMA This work is still in progress,but it is clearly leading structural engineers in new directions in the design of special steelmoment frame buildings The work shows that great ductility is possible, but it also showsthat the engineer must exercise great care in the selection and design of members and con-nections The requirements that are evolving for special moment frames are briefly sum-marized in Art 9.7.1
con-Concentric braced frames, defined in Art 9.4, economically provide much larger
strength and stiffness than moment-resisting frames with the same amount of steel Thereare a wide range of bracing configurations, and considerable variations in structural perform-ance may result from these different configurations Figure 9.12 shows some concentricbracing configurations The braces, which provide the bulk of the stiffness in concentricallybraced frames, attract very large compressive and tensile forces during an earthquake As aresult, compressive buckling of the braces often dominates the behavior of these frames The
pinched cyclic force-deflection behavior shown in Fig 9.9b commonly results, and failure
of braces may be quite dramatic Therefore, concentrically braced frames are regarded asstiffer, stronger but less ductile than steel moment-resisting frames In recent years, researchhas shown that concentrically braced frames can sustain relatively large inelastic deformationwithout failure if greater care is used in the design and selection of the braces and the braceconnections Concentrically braced frames, which are designed to these higher ductility stan-dards, can be designed for smaller seismic design forces and are called special concentricallybraced frames Different design provisions are required for ordinary concentrically bracedframes and special concentrically braced frames These are summarized in Art 9.7.2
Eccentric braced frames, defined in Art 9.4, can combine the strength and stiffness of
concentrically braced frames with the good ductility of moment-resisting frames Eccentricbraced frames incorporate a deliberately controlled eccentricity in the brace connections (Fig.9.13) The eccentricity and the link beams are carefully chosen to prevent buckling of thebrace, and provide a ductile mechanism for energy dissipation If they are properly designed,
eccentric braced frames lead to good inelastic performance as depicted in Fig 9.9c, but they
require yet another set of design provisions, which are summarized in Art 9.7.3
Dual systems, defined in Art 9.4, may combine the strength and stiffness of a braced
frame and shear wall with the good inelastic performance of special steel moment-resisting
frames Dual systems are frequently assigned an R value and seismic design force that are
Trang 39.22 SECTION NINE
FIGURE 9.12 Typical configurations of concentric braced frames.
intermediate to those required for either system acting alone Design provisions provide limitsand recommendations regarding the relative stiffness and distribution of resistance of the twocomponents Dual systems have led to a wide range of structural combinations for seismicdesign Many of these are composite or hybrid structural systems However, steel frameswith composite concrete floor slabs are not commonly used for developing seismic resistance,even though composite floors are commonly used for gravity-load design throughout theUnited States
9.7 SEISMIC-DESIGN LIMITATIONS ON STEEL FRAMES
A wide range of special seismic design requirements are specified for steel frames to ensurethat they achieve the ductility and behavior required for the structural system and the designforces used for the system Use of systems with poor or uncertain seismic performance isrestricted or prohibited for some applications Most of these requirements are specified inthe ‘‘Seismic Provisions for Structural Steel Buildings’’ of the AISC These provisions areeither adopted by reference or they are directly incorporated into the UBC and NEHRPprovisions However, UBC also includes supplemental provisions and clarifications whichsupplement the AISC provisions This article will provide a summary of the provisions formoment-resisting frames, concentrically braced frames and eccentrically braced frames forseismic applications It should be noted that the 1992 AISC seismic provisions are directly
Trang 49.7.1 Limitations on Moment-Resisting Frames
Structural tests have shown that steel moment-resisting frames may provide excellent tility and inelastic behavior under severe seismic loading Because these frames are fre-
Trang 5duc-9.24 SECTION NINE
quently quite flexible, drift limits often control the design The UBC recognizes this ductility
and assigns R⫽8.5 to special moment-resisting frames (Art 9.4)
Slenderness Requirements. Special steel moment-resisting frames must satisfy a range ofslenderness requirements to control buckling during the plastic deformation in a severe earth-
quake The unsupported length, L b, of bending members must satisfy
2500 r y
F y where ryis the radius of gyration about the weak axis of the member andF yis the specifiedminimum yield stress, ksi, of the steel The objective of this limit is to control lateral torsionalbuckling during plastic deformation under cyclic loading The flanges of beams and columnsmust have a slenderness less than
bƒ 52
2 tƒ 兹F y where bƒand tƒare the flange width and thickness, respectively The purpose of this require-ment is to control flange buckling during the plastic deformation expected in a severe earth-quake The webs of members must satisfy
P u and Pyare the factored applied compressive load and the yield load of the member,is
the resistance factor, and d and tw are the depth and web thickness of the member Theselatter equations are required to control web buckling during the plastic deformation expectedduring a severe earthquake These limits are somewhat more conservative than the normalcompactness requirements for steel design, because of the greater ductility demand of seismicloading
Seismic Loads for Columns. The columns and column splices must be designed for thepossibility of uplift and extreme compressive load combinations Two special factored loadcombinations are required for this purpose when the factored axial load on the columnexceeds 40% of the nominal capacity For axial compression, columns should have thestrength to resist
1.0 P DL⫹0.5 P LL⫹0.2 P S⫹ ⍀P HE (9.22)and for axial tension
where PDL, PLL, PS and PHE are the column loads due to dead load, live load, snow load,
Trang 6con-tions as depicted in Fig 9.14a The conneccon-tions were used because experiments performed
20 to 30 years ago indicated that good ductility was achieved with such connections ever, as noted in Art 9.6, cracking occurred in a number of these connections during theNorthridge earthquake The cracking was more frequently noted in new buildings and inbuildings with relatively heavy members There are a number of probable contributing factors
How-to this observed damage, and the building codes have responded How-to these facHow-tors First, thedamage was more common in buildings where the lateral resistance was concentrated inlimited portions of the structure, since this concentration produces larger member sizes Theredundancy factor described in Art 9.4 was partly motivated by this observation Second,the expected yield stress of modern structural steels often widely exceeds the nominal yieldstress This limits the ability to control the yield mechanism during severe seismic loadingand thus, may increase the potential for cracking and brittle modes of failure As a result,
the AISC seismic design provisions now include an expected strength factor, R y, defined as
the ratio of the expected yield stress, F ye , to the specified yield stress, F y:
F ye
F y
ThisR yvalue can be established through testing or, in the absence of test data, specification
defined values of between 1.1 and 1.5 are provided Ryis used to evaluate both the uncertainty
in material properties and how this affects the seismic performance of the building.Many other issues including the weld electrode, the basic connection geometry, and theconstruction practices used, are believe to have contributed to the observed damage TheSAC Steel Project was started to address these issues and its goals are to develop reliablemethods of seismic design, repair, and retrofit for steel moment frames This project iscompleting a wide range of experimental and analytical research regarding the seismic per-formance of steel frame buildings The work is still in progress, but significant recommen-dations are forthcoming However, ‘‘Interim Guidelines: Evaluation, Repair, Modificationand Design of Welded Steel Structures’’ and ‘‘Interim Guidelines Advisory No 1’’ by FEMA(FEMA 267 and 267A) include many recommendations arrived at to date regarding specialsteel moment-resisting frame connections It is expected that a number of new and improvedconnection types will be prequalified by this research work However, for the present, thestructural engineer is left with a great deal of responsibility regarding the acceptability ofconnections for special steel moment-resisting frames In general, the UBC and the AISCseismic provisions permit the use of a wide range of connections, but require that prototypeconnection tests be completed to verify seismic performance of the connection before it isused in construction This testing requires time and the cost is not inconsequenttial However,the testing may often produce significant savings in the final construction cost and it relievesthe engineer of considerable uncertainty regarding the seismic performance of the building.The testing may be avoided, if past test results of the selected connection with the samegeneral member sizes as used in the subject building, can be provided
In this environment, the coverplated connection depicted in Fig 9.14b and the reduced beam section depicted in Fig 9.14c are being used with some frequency since there is a
reasonable experimental data base for both connection types The coverplated connectionsignificantly strengthens the connection with the goal of forcing yielding into the beam atthe end of the coverplate This modification has worked very well in a number of past tests,but it is an expensive connection and there also have been a few undesirable fractures withthis connection The reduced beam section cuts away a portion of the beam flange at a shortdistance from the welded flange connection so that yielding occurs within the reduced flange
Trang 79.26 SECTION NINE
FIGURE 9.14 Typical beam-to-column connectoins for special moment-resisting frames (a) Typical Northridge connection (b) Typical coverplated connection (c) Typical reduced beam section connection.
Trang 8pre-LATERAL-FORCE DESIGN 9.27
FIGURE 9.15 Forces acting on a column and beam in the panel zone in a typical moment-resisting
connection during seismic loading Forces in (a) are equivalent to those in (b).
area, well before large stresses develop at the welded connection This alternative has alsoperformed well, but testing is in progress to evaluate the effects of composite slabs and thelateral-torsional stability of the reduced section These and other alternatives are discussed
in the FEMA 267 documents, and partial design procedures are provided there At the end
of the SAC Steel Project, a number of different steel frame connections will likely be qualified for use in seismic design by structural engineers These will clearly include anumber of different bolted connections as well as welded connections However a study ofthese connections is incomplete and the design procedures for the connections are not fullydeveloped As a result, the structural engineer must currently rely on the experimental eval-uation requirements of the seismic design specification
pre-Other Connection and Frame Issues. While many issues of connection design are nowloosely defined because of the Northridge damage, some important issues are still welldefined in the seismic specifications Seismic bending moments in the beam cause largeshear stresses in the column web in the panel zone of the connection (Fig 9.15) The panel-zone shear strength, kips, may be computed from
Equation (9.25) takes into account the fact that the strength of the panel zone is enhanced
by the strength and stiffness of the column flanges, and that panel- zone yielding providesgood, stable energy dissipation and inelastic performance Also, this equation encouragespanel-zone yielding over many other types of plastic deformation Equation (9.25), however,permits some plastic deformation of the panel zone at loads well below the design load,
since V is sometimes considerably larger than the panel-zone yield capacity,
Trang 99.28 SECTION NINE
If the panel zone does not have the capacity required by Eq (9.25), a doubler plate (Fig
9.14a) or thicker column web is required A minimum thickness t zfor the combined doublerplate and column web is prescribed:
d z⫹w z
90
where d z and w zare the depth between continuity plates and width between column flanges
in the panel zone Doubler plates must be stitched to the web of the column with plug welds
to prevent local buckling of the plate, otherwise d zcannot be included in Eq (9.27).Panel-zone requirements often control the lateral resistance of steel moment-resistingframes However, this may cause some difficulties for structural designers The UBC requirescomputation of the story drift due to panel-zone deformation, and there is no clear, simplemethod for calculating story drift in frames dominated by panel-zone yielding
Special moment-resisting frames provide superior performance when yielding due to vere seismic loading occurs in the beams rather than the columns This strong-column, weak-beam behavior is required, except in special cases To ensure this behavior, the followingrelationship must be satisfied, except as indicated below
se-兺Z (F c yc⫺ƒ )a
兺Z F b yb where Z b and Z c are the plastic section modulus, in3, of the beam and the column Thisrequirement need not be met when ƒa⬍ 0.3F vcfor all load combinations, except for thosespecified by Eqs (9.22) and (9.23), and any of the following conditions hold:
1 The joint is at the top story of a multistory frame with fundamental period greater than
0.7 second
2 The joint is in a single-story frame.
3 The sum of the resistances of the weak-column joints is less than 20% of the resistances
for a specific story in the total frame and the sum of the resistances of the weak-columnjoints in a specific frame is less than 33% of the resistances for the frame
Research suggests that yielding of the columns results in concentration of damage in thestructural frames (Fig 9.10) and reduces the available ductility in the structure while in-creasing the ductility demand However, many structural configurations quite naturally lead
to weak-column, strong-beam behavior In addition, the issue is further complicated by cern that panel-zone yielding may lead to an equivalent of weak-column, strong-beam be-havior even though Eq (9.28) is satisfied
con-Ordinary Moment Frames. Some steel moment-resisting frames, known as ordinary ment frames, are not designed to satisfy all of the preceding conditions In many cases, theseframes are used in less seismically active zones Sometimes, however, they are used inseismically active zones with larger seismic design forces; that is, they are designed with
mo-R⫽4.5 As a result, the design forces would be nearly twice as large as required for specialmoment frames, but the detailing requirements are reduced Ordinary moment-resistingframes must satisfy some of the requirements noted above, depending upon the seismic zoneand the design forces in the structure
9.7.2 Limitations on Concentric Braced Frames
Concentric braced steel frames are much stiffer and stronger than moment-resisting frames,and they frequently lead to economical structures However, their inelastic behavior is usually
Trang 10LATERAL-FORCE DESIGN 9.29
inferior to that of special moment-resisting steel frames (Art 9.6) One reason is that thebehavior of concentric braced frames under large seismic forces is dominated by buckling.Furthermore, the columns must be designed for tensile loads and foundation uplift as well
as for compression
Figure 9.12 shows some of the common bracing configurations for concentric bracedframes Seismic design requirements vary with bracing configuration
X bracing, for example, usually is very slender and has large tensile capacity and little
compressive buckling capacity It may be an economical design for lateral loads, but itpermits concentration of inelastic deformations, and energy dissipation during major earth-quakes is poor As a result, X bracing is restricted to use in less seismically active zones orvery short structures in more active zones
K bracing causes yielding in the columns during severe seismic loading One diagonal
is in compression while the other is in tension, and the compression diagonal buckles wellbefore the tensile brace yields The buckling introduces large shears and bending moments
in the columns As a result, K bracing is prohibited in the more seismically active regions.Because of these considerations, diagonal and chevron bracing are the primary systemsfor major structures in seismically active regions of the United States
Chevron bracing (V or inverted V, shown in Fig 9.12) causes beam yielding during
severe seismic excitation, whereas K bracing causes column yielding Beam flexure withchevron bracing induces deformations of floors during a major earthquake but provides ad-ditional energy dissipation, which may improve the seismic response during major earth-quakes
Diagonal bracing acts in tension for lateral loads in one direction and in compression
for lateral loads in the other direction The ‘‘Uniform Building Code’’ requires that thedirection of the inclination of bracing with the diagonal bracing system be balanced, sincebraces have much larger capacity in tension than in compression
Buckling of Bracing. In general, the energy dissipation of concentric braced frames isstrongly influenced by postbuckling brace behavior This is quite different for slender bracesthan for stocky braces For example, the compressive strength of a slender brace is muchsmaller in later cycles of loading than it is in the first cycle In addition, very slender bracesoffer less energy dissipation but are able to sustain more loading cycles and larger inelasticdeformation than stocky braces In view of this, the slenderness ratio of bracing is limited,to
L 720
r 兹f y where L is the unsupported length, in; r is the least radius of gyration, in; and Fyis the yieldstress, ksi
The compressive strength of bracing members must also be limited to 80% of the factorednominal compressive capacity, c P n, of the brace computed by the normal AISC LRFD
design procedure This reduction in compressive capacity is applied because of the loss ofcompressive resistance expected during cyclic loading after the initial buckling cycles How-ever, the reduction is not used in the evaluation of the maximum forces that can be transferred
to adjacent members
Bracing, contributing most of the lateral strength and stiffness to frames, resists most ofthe seismic load It is tempting, for economy, to design bracing as tension members only,since steel is very efficient in tension However, this results in poor inelastic behavior undersevere earthquake loading, a major reason for excluding X bracing from seismically activeregions On the other hand, more energy is dissipated in a brace yielding in tension than in
a brace buckling in compression As a result, all bracing systems must be designed so that
at least 30%, but no more than 70%, of the base shear [Eq (9.5)] is carried by bracingacting in tension, while the balance is carried by bracing acting in compression
Trang 119.30 SECTION NINE
The overall and local slenderness of bracing is important The ratio b / t of width to
thickness of single-angle struts or double-angle braces that are separated by stitching ments is limited to
t 兹F y where b and t are the flange width and thickness of the angle, respectively The slenderness
of bracing for hollow rectangular and circular tubes of high strength steel are likewise limited
Strength of Connections. The strength of the connections should be stronger than themembers themselves This assures that the energy dissipation occurs in the members ratherthan the connections For ordinary concentrically braced frames, this is achieved by firstassuring that the connections are capable of developing the brace forces produced by theload combinations given in Eqs (9.22) and 9.23) with the overstrength factor,⍀, of 2.0 Inaddition, the connections must be designed to resist the maximum tensile strength of thebrace considering the full uncertainty of the yield stress in the brace members This is
accomplished by assuring that the connection resistance also exceeds Ry F y A g, where Agis
the gross area of the brace and Ry and Fy are as defined in the moment-resisting framediscussion (Eq 9.24)
Selection of R. Once concentric bracing is selected for seismic design, the force reduction
factor, R, must be chosen The discussion to this point has focused on ordinary braced frames, which have R⫽5.6, and also have the fewest restrictions on their application This R value
is somewhat smaller than that permitted for special steel moment-resisting frames, becauseconcentrically braced frames are known to be dominated by brace buckling As a result,their resistance may deteriorate and the brace may fracture under seismic loading There aretwo major options for improving the behavior of concentrically braced frames First, they
may be used as a dual system with a special steel moment-resisting frame, and R⫽ 6.5.With this system, the moment frame must be able to resist the loads which are at least 25%
of the total seismic design base shear In addition, both the braced frame and the momentframe must be able to resist their appropriate portion of the loading in accordance with theirrelative stiffness The braced frame is usually much stiffer than the moment frame, so thatthis requirement effectively means that the dual system has a greater total resistance thanrequired by the basic design equations A second alternative is the recently developed specialconcentrically braced frame The seismic performance of concentrically braced frames can
be improved if the brace can tolerate larger inelastic deformations without excessive rioration and brace or connection fracture However, additional special detailing requirements
dete-are needed to achieve this improvement If these additional requirements dete-are satisfied, R⫽
6.4 for special concentrically braced frames, and R ⫽ 7.5 with dual systems of specialconcentrically braced frames and special steel moment frames
Trang 12LATERAL-FORCE DESIGN 9.31
Special Concentrically Braced Frames. Special concentrically braced frames require thatthe braced frame satisfy the requirements summarized above, but a few more restrictiverequirements are added to ensure improved ductility of the system The slenderness of brac-ing members must be limited to
K L 1000
r 兹F y where K, L and r are the effective length coefficient, the brace length, and the controlling
radius gyration of the bracing The bracing must be compact, and there is no reductionapplied to the compressive load capacity as used for ordinary concentrically braced frames.The requirements for the stitching of the members are somewhat more restrictive, and astrength analysis of the bracing member is required to ensure that the connections haveadequate strength to fully develop the bracing members It should be noted that the provisionsfor special concentrically braced frames were considerably more restrictive than the provi-sions for ordinary braced frames in previous versions of the seismic design specifications.However, recent changes to the seismic design specifications such as the expected yield
strength factor, R y, and the overstrength factor, ⍀, have narrowed the differences betweenspecial and ordinary braced frames As a result, the special concentrically braced frame is
an incresingly attractive option
9.7.3 Eccentric Braced Frames
These combine the strength and stiffness of a concentric braced frame with the inelastic
performance of a special moment-resisting frame (Fig 9.9c) The UBC permits use of an R
of 7 or 8.5 for an eccentric braced frame This results in seismic design forces comparable
to those required for special moment-resisting frames if the fundamental period of vibration
is the same However, braced frames are invariably stiffer than moment-resisting frames ofsimilar geometry and have a shorter period This results in a somewhat larger design loadthan for special moment-resisting frames under comparable conditions (C W Roeder, and
E P Popov, ‘‘Eccentrically Braced Steel Frames for Earthquakes,’’ Journal of Structural Division, March 1978, American Society of Civil Engineers.)
General Requirements for Ductility. There are a number of special design provisions thatmust be satisfied by eccentric braced frames As defined in Art 9.4, a link must be provided
at least at one end of each brace The link beam should be designed so that it is the weaklink of the structure under severe seismic loading This is done by selecting the size of thesteel section and the length of the link beam to match seismic-load design requirements.The weak link is assured by the requirement that the brace be designed for a force at least1.25 times the brace force necessary to yield the link beam considering the expected yield
strength (Ry F y) Yielding or buckling of the columns must also be avoided Therefore, the
column must be designed for the combined axial force of 1.1 times the sum of the yieldforces for all link beams considering the expected yield strength In addition, the columnsmust be designed for the normal factored load combinations from the AISC LRFD Speci-fication These brace and column design forces are needed to ensure that the brace andcolumn do not buckle as the link beam strain hardens during inelastic deformation
Link Beam. Eccentrically braced frames develop good inelastic behavior because yielding
in the link beam occurs well before brace buckling or inelastic deformation of the columns,and this yielding permits large inelastic deformations and great energy dissipation duringsevere earthquakes The link beam may yield in shear, flexure or a combination of the twodepending upon the size of the beam and the length of the link The normal yield shear of
Trang 139.32 SECTION NINE
FIGURE 9.16 Typical connection details and stiffener arrangement for an eccentric braced frame.
the link beam is the lesser of Ypor 2 Mp/ e In this expression, Mp, is the normal link beam
plastic moment (Mp⫽Z F y ) and e is the clear span eccentricity of the link beam The plastic shear capacity, Vp, of the link beam is
where d, tƒ, and t ware the depth, flange thickness and web thickness of the link beam Thenominal yield shear and moment of the link beam may require further reduction if the axialforce in the link beam exceeds 15% of the yield axial force, but this can occur only undervery special conditions with specific brace configurations Link beams where
1.6 M p
V p
are controlled by shear yield behavior, and they have a maximum plastic link rotational angle
of 0.08 radians Link beams where
Stiffeners and Lateral Support of the Link Beam. The link beam is subject to both highbending stress, high shear stress and significant inelastic deformation As a result, it musthave lateral support to both the top and bottom flanges at both ends of the link beam Thelateral supports must have adequate resistance to develop 6% of the expected flange force
(Ry F y bƒtƒ) The beam must also satisfy all of the web and flange slenderness requirementspreviously noted for special moment resisting frames Full depth web stiffeners are alsorequired at each end of the link beam as illustrated in Fig 9.16 The high shear stress in theweb of the link beam results in the potential for web buckling during large inelastic cycles,and intermediate web stiffeners are also likely to be required as shown in Fig 9.16 Spacing
s for intermediate stiffeners for link beams with link rotation angle of 0.08 radians is
Trang 14LATERAL-FORCE DESIGN 9.33
d
5When the link rotation angle is 0.02 radians or less,
d
5For link beams with link rotation angle between 0.02 and 0.08 radians, the spacing must bedetermined by interpolation The web stiffeners must all be full depth stiffeners, however,the intermediate stiffeners may sometimes be lighter than the end stiffeners
Beam Outside the Link. Special considerations are also required for the beam outside thelink The beam outside the link must be designed for forces which are 1.1 times those caused
by the brace force necessary to yield the link beam considering the expected yield stress (Ry
F y) of the link beam Lateral support and slenderness requirements are required for the beamoutside the link
Eccentrically Braced Frames in Dual Systems. The preceding discussion has covered
ec-centrically braced frames with R⫽7.0 Eccentrically braced frames may also be designed
as part of dual systems with special moment-resisting frames and R⫽8.5 With dual systems,the special moment-resisting frame must be able to resist loads which are at least 25% ofthe total seismic design base shear In addition, both the eccentrically braced frame and themoment frame must be able to resist their appropriate portion of the loading in accordancewith their relative stiffness
General Comments. Doubler plates and holes or penetrations are not permitted in the linkbeams The connections must be strong enough to develop fully the plastic capacity of thelink beams Link beams that are directly connected to columns require the same experimentalverification as is presently required for special steel moment-resisting frames
Eccentrically braced frames are a rational attempt to design steel structures that fullydevelop the ductility of the steel without loss of strength and stiffness due to buckling Thedesign of these frames is somewhat more complicated than that of some other steel frames,but eccentric braced frames offer advantages in economical use of steel and seismic per-formance that cannot be duplicated by other systems
9.8 FORCES IN FRAMES SUBJECTED TO LATERAL LOADS
The design loads for wind and seismic effects are applied to structures in accordance withthe guidelines in Arts 9.2 to 9.5 Next, the structure must be analyzed to determine forcesand moments for design of the members and connections Member and connection designproceeds quite normally for wind load design after these internal forces are determined, butseismic design is also subject to the detailed ductility considerations described in Arts 9.6and 9.7 This is required for preliminary design and for interpretation and evaluation ofcomputer results Approximate methods are based on physical observations of the response
of structures to applied loads Two such methods are the portal and cantilever methods, oftenused for analyzing moment-resisting frames under lateral loads
The portal method is used for buildings of intermediate or shorter height In this method,
a bent is treated as if it were composed of a series of two-column rigid frames, or portals.Each portal shares one column with an adjoining portal Thus, an interior column serves asboth the windward column of one portal and the leeward column of the adjoining portal
Trang 159.34 SECTION NINE
FIGURE 9.17 Eight-story moment-resisting frame subjected to static lateral loading.
Horizontal shear in each story is distributed in equal amounts to interior columns, whileeach exterior column is assigned half the shear for an interior column, since exterior columns
do not share the loads of adjacent portals If the bays are unequal, shear may be apportioned
to each column in proportion to the lengths of the girders it supports When bays are equal,the axial load in interior columns due to lateral load is zero
Inflection points (points of zero moment) are placed at midheight of the columns andmidspan of beams This approximates the deflected shapes and moment diagrams of thosemembers under lateral loads The location of the inflection points may be adjusted for specialcases, such as fixed or pinned base columns, or roof beams and top-story columns, or otherspecial situations On the basis of the preceding assumptions, member forces and bendingmoments can be determined entirely from the equations of equilibrium As an example, Fig.9.17 indicates the geometry and loading of an eight-story moment-resisting frame, and Fig.9.18 illustrates the use of the portal method on the upper stories of the frame The framehas two interior columns So one-third of the shear in each story is distributed to the interiorcolumns and half of this, or one-sixth, is distributed to the exterior columns (Fig 9.18) Theother member forces are computed by equations of equilibrium on each subassemblage Forexample, for the subassemblage at the top of the frame in Fig 9.18, setting the sum of themoments equal to zero yields
Trang 16FIGURE 9.18 Forces at midspan of beams and midheight of columns in the frame of Fig 9.17 as determined
by the portal method.
Trang 17FIGURE 9.19 Drift of a moment-resisting frame
assumed for analysis by the cantilever method.
The cantilever method is used for tall
buildings It is based on the recognition thataxial shortening of the columns contributes
to much of the lateral deflections of suchbuildings (Fig 9.19) In this method, thefloors are assumed to remain plane, and theaxial force in each column is assumed to beproportional to the distance of the columnfrom the centroid of the columns Inflectionpoints are assumed to occur at midheight ofthe columns and at midspan of the beams.The internal moments and forces are deter-mined from equations of equilibrium, as withthe portal method The determination of theforces and moments in the members at thetop floors of the frame in Fig 9.17 is illus-trated in Fig 9.20 The lateral forces causeoverturning moments, which induce axialtensile and compressive forces in the col-umns Therefore,
A4⫽ ⫺A7 and A5⫽ ⫺A6 (9.43)Since the exterior columns are 3 times as farfrom the centroid of the columns as the in-terior columns,
Trang 18FIGURE 9.20 Cantilever method of determining the forces at midspan of beams and midhheight of columns
in the frame of Fig 9.17.
Trang 199.38 SECTION NINE
Analysis of Dual Systems. Approximate analysis of braced frames can be performed as ifthe bracing were a truss However, many braced structures are dual systems that combinemoment-resisting-frame behavior with braced-frame behavior Under these conditions, anapproximate analysis can be performed by first distributing the lateral forces between thebraced-frame and moment-resisting-frame portions of the structure in proportion to the rel-ative stiffness of the components Braced frames are commonly very stiff and normally wouldcarry the largest portion of the lateral loads
Once the initial distribution of member and connection forces and moments is completed,
a preliminary design of the members can be performed At this time, it is possible to alyze the structure by any of a number of linear-elastic, finite-element methods, for whichcomputer programs are available
rean-While many major, existing structures were designed without benefit of computer analysistechniques, it is not advantageous to design modern buildings for wind and earthquakeloading without this capability It is needed to predict realistic structural response to windloading and to evaluate occupant comfort, as well as for dynamic design for seismic loading,especially for buildings of unusual geometry Both the seismic and wind load provisions inthe ‘‘Uniform Building Code’’ result in local anomalies in the distribution of design forcesdue to the distribution of mass, stiffness, or local wind pressure, and many elements such
as slabs and diaphragms may distribute large forces from one load element to another Thecombination of these factors results in the requirement for finite-element analysis
9.8.2 Nonlinear Analysis of Structural Frames
Although nonlinear analysis is not commonly used for structural design, it is important forseismic design for several reasons First, while the seismic-design provisions of variousbuilding codes rely on linear-elastic concepts, they are based on inelastic response Seismicbehavior of structures during major earthquakes depends on nonlinear material behaviorcaused by yielding of steel and cracking of concrete The reduced stiffness due to yieldingmakes the stability of structures of great concern, and ensuring stability requires consider-ation of geometric nonlinearities Nonlinear analysis permits treatment of these stability ef-
fects with P⫺ ⌬ moments (Fig 9.21)
Second, design methods such as load-and-resistance-factor design encourage use of ible, partly restrained (PR) connections Such connections are inherently nonlinear in theirresponse Hence, it is necessary to analyze structures with attention to the contribution ofconnection flexibility Further nonlinearity may occur due to the effects of connection flex-
flex-ibility on frame stability and P ⫺ ⌬ moments These nonlinear effects are not commonlyconsidered in design at present However, computer programs are available to model nonlin-ear frame behavior and their use is growing
9.9 MEMBER AND CONNECTION DESIGN FOR LATERAL LOADS
Wind loads on steel structures are determined by first establishing the pressure distributions
on structures after considering the appropriate design wind velocity, the exposure condition,and the local variation of wind pressure on the structure (Art 9.2) Then, the wind loads onframes and structural elements are determined by distributing the wind pressure in accord-ance with the tributary areas and relative stiffness of the various components
Seismic design loads are determined by the static-force or dynamic methods With thestatic-force method, the total base shear is determined by Eq (9.5) It is distributed to bentsand structural elements by simple rules combined with considerations of the distribution ofmass and stiffness (Art 9.4) With the dynamic method, the total range of dynamic modes
Trang 20LATERAL-FORCE DESIGN 9.39
FIGURE 9.21 Sidesway of a two-story frame subjected to horizontal and vertical loads (a)
Position of deflected structure for drift ⌬; (b) curves show relationship of horizontal force and drift
with and without the P⫺ ⌬ effect.
of vibration are considered in determination of the base shear This is distributed to the bentsand components in accordance with the mode shapes For both wind and seismic loading,forces and moments in members and connections can be first estimated by approximateanalysis techniques (Art 9.8.1) They may be ultimately computed by finite-element or otherstructural analysis techniques
Once member and connection forces and moments are determined, design for lateral loads
is similar to design for other loadings
Connections used for wind loading run the full range of unrestrained (pinned), fullyrestrained (FR), or partly restrained (PR) connections PR connections are frequently usedfor wind loading design, because they are economical and easily fabricated and constructed.Connections used in seismic design are normally unrestrained or FR connections PRconnections have less seismic resistance than the members they are connecting, and therefore
Trang 21of PR connections in seismic design Nevertheless, they offer many advantages and may beeconomical for use in less seismically active regions, rehabilitation projects, and perhaps, inthe future, major seismic regions.
Wind loading design is based on elastic behavior of structures, and strength considerationsare adequate for design of wind connections Seismic design, in contrast, utilizes inelasticbehavior and ductility of structures, and many design factors must be taken into accountbeyond the strength of the members and connections These requirements are intended toassure adequate ductility of structures Code provisions attempt to assure that inelastic de-formations occur in members rather than connection (Art 9.7)
Designs for wind and seismic loading often use floor slabs and other elements to distributeloads from one part of a structure to another (Fig 9.22) Under these conditions, the slabs
Trang 22LATERAL-FORCE DESIGN 9.41
FIGURE 9.23 Typical gusset-plate connections at a column (a)
With braces above and below the joint; (b) with a brace only below
the joint.
Trang 239.42 SECTION NINE
and other elements act as diaphragms These may be considered deep beams and are subject
to loadings and behavior quite different from that encountered in gravity-load design It isimportant that this behavior be considered, and it is particularly important that the connectionbetween the diaphragms and the structural elements be carefully designed These connectionsoften involve a composite connection between a steel structural member and a concrete slab,wall, or other component The design rules for these composite connections are not as well-defined as those for most steel connections However, there is general agreement that theconnections should be designed for the largest forces to be transferred at the interface Also,the design should recognize that large groups of shear connectors or other transfer elements
do not necessarily behave as the sum of the individual elements
Braced frames, which are economical systems for resisting both wind and earthquakeloadings, frequently require large gusset plates in connections (Fig 9.23) Different modelsfor predicting the resistance of these connections may produce very different results andfurther research is needed to define their behavior Hence, it is likely that there will becontinuing changes in the design models for connections for lateral-load design (SeeSec 5.)
Models used for design of connections should satisfy the equations of equilibrium, ensuresupport for maximum loads and deformations that are possible for connections, and recognizethat large groups of connectors do not always behave as the sum of the individual connectors
Trang 24This section presents information on the design of structural members that are cold-formed
to cross section shape from sheet steels Cold-formed steel members include such products
as purlins and girts for the construction of metal buildings, studs and joists for light mercial and residential construction, supports for curtain wall systems, formed deck for theconstruction of floors and roofs, standing seam roof systems, and a myriad of other products.These products have enjoyed significant growth in recent years and are frequently utilized
com-in some shape or form com-in many projects today Attributes such as strength, light weight,versatility, non-combustibility, and ease of production, make them cost effective in manyapplications Figure 10.1 shows cross sections of typical products
10.1 DESIGN SPECIFICATIONS AND MATERIALS
Cold-formed members for most application are designed in accordance with the Specification for the Design of Cold-Formed Steel Structural Members, American Iron and Steel Institute, Washington, DC Generally referred to as the AISI Specification, it applies to members cold-
formed to shape from carbon or low-alloy steel sheet, strip, plate, or bar, not more than
1-in thick, used for load carry1-ing purposes 1-in build1-ings With appropriate allowances, it can
be used for other applications as well The vast majority of applications are in a thicknessrange from about 0.014 to 0.25 in
The design information presented in this section is based on the AISI Specification and its Commentary, including revisions being processed The design equations are written in
dimensionless form, except as noted, so that any consistent system of units can be used Asynopsis of key design provisions is given in this section, but reference should be made tothe complete specification and commentary for a more complete understanding
The AISI Specification lists all of the sheet and strip materials included in Table 1.6 (Art.
1.4) as applicable steels, as well several of the plate steels included in Table 1 (A36, A242,A588, and A572) A283 and A529 plate steels are also included, as well as A500 structuraltubing (Table 1.7) Other steels can be used for structural members if they meet the ductilityrequirements The basic requirement is a ratio of tensile strength to yield stress not less than1.08 and a total elongation of at least 10% in 2 in If these requirements cannot be met,alternative criteria related to local elongation may be applicable In addition, certain steelsthat do not meet the criteria, such as Grade 80 of A653 or Grade E of A611, can be used
Trang 2510.2 SECTION TEN
FIGURE 10.1 Typical cold-formed steel members.
for multiple-web configurations (roofing, siding, decking, etc.) provided the yield stress istaken as 75% of the specified minimum (or 60 ksi or 414 MPa, if less) and the tensile stress
is taken as 75% of the specified minimum (or 62 ksi or 428 MPa if less) Some exceptionsapply Suitability can also be established by structural tests
10.2 MANUFACTURING METHODS AND EFFECTS
As the name suggests, the cross section of a cold-formed member is achieved by a bendingoperation at room temperature, rather than the hot rolling process used for the heavier struc-tural steel shapes The dominant cold forming process is known as roll-forming In thisprocess, a coil of steel is fed through a series of rolls, each of which bends the sheetprogressively until the final shape is reached at the last roll stand The number of roll standsmay vary from 6 to 20, depending upon the complexity of the shape Because the steel isfed in coil form, with successive coils weld-spliced as needed, the process can achieve speeds
up to about 300 ft / min and is well suited for quantity production Small quantities may beproduced on a press-brake, particularly if the shape is simple, such as an angle or channelcross section In its simplest form, a press brake consists of a male die which presses thesteel sheet into a matching female die
In general, the cold-forming operation is beneficial in that it increases the yield strength
of the material in the region of the bend The flat material between bends may also show
an increase due to squeezing or stretching during roll forming This increase in strength isattributable to cold working and strain aging effects as discussed in Art 1.10 The strengthincrease, which may be small for sections with few bends, can be conservatively neglected
Alternatively, subject to certain limitations, the AISI Specification includes provisions for using a section-average design yield stress that includes the strength increase from cold-
forming Either full section tension tests, full section stub column tests, or an analyticalmethod can be employed Important parameters include the tensile-strength-to-yield-stress
Trang 26COLD-FORMED STEEL DESIGN 10.3 TABLE 10.1 Safety Factors and Resistance Factors Adopted by the AISI Specification
Category
ASD safety factor, ⍀
LRFD resistance factor,
Flexural members
(a) Bending strength
Sections with stiffened or partially stiffened compression flanges 1.67 0.95
Beams having one flange through-fastened to deck or sheathing (C- or Z-sections) 1.67 0.90 Beams having one flange fastened to a standing seam roof system 1.67 0.90 (b) Web design
Shear strength controlled by yielding (Condition a, Art 10.12.4) 1.50 1.00 Shear strength controlled by buckling (Condition b or c, Art 10.12.4) 1.67 0.90
Stiffeners
Combined axial load and bending
(b) Arc spot welds
Connected part, longitudinal loading
Trang 2710.4 SECTION TEN
TABLE 10.1 Safety Factors and Resistance Factors Adopted by the AISI Specification (Continued )
Category
ASD safety factor, ⍀
LRFD resistance factor, (e) Flare groove welds
(b) Tension strength on net section
* F u is tensile strength and F syis yield stress.
ratio of the virgin steel and the radius-to-thickness ratio of the bends The forming operationmay also induce residual stresses in the member but these effects are accounted for in theequations for member design
10.3 NOMINAL LOADS
The nominal loads for design should be according to the applicable code or specificationunder which the structure is designed or as dictated by the conditions involved In the absence
of a code or specification, the nominal loads should be those stipulated in the American
Society of Civil Engineers Standard, Minimum Design Loads for Buildings and Other tures, ASCE 7 The following loads are used for the primary load combinations in the AISI Specification:
Struc-D ⫽ Dead load, which consists of the weight of the member itself, the weight of allmaterials of construction incorporated into the building which are supported by the mem-ber, including built-in partitions; and the weight of permanent equipment
E⫽Earthquake load
L⫽Live loads due to intended use and occupancy, including loads due to movable objectsand movable partitions and loads temporarily supported by the structure during mainte-
nance (L includes any permissible load reductions If resistance to impact loads is taken
into account in the design, such effects should be included with the live load.)
Trang 28COLD-FORMED STEEL DESIGN 10.5
L r⫽Roof live load
S⫽Snow load
R r⫽Rain load, except for ponding
W⫽Wind loadThe effects of other loads such as those due to ponding should be considered when signif-icant Also, unless a roof surface is provided with sufficient slope toward points of freedrainage or adequate individual drains to prevent the accumulation of rainwater, the roofsystem should be investigated to assure stability under ponding conditions
10.4 DESIGN METHODS
The AISI Specification is structured such that nominal strength equations are given for various
types of structural members such as beams and columns For allowable stress design (ASD),the nominal strength is divided by a safety factor and compared to the required strengthbased on nominal loads For Load and Resistance Factor Design (LRFD), the nominalstrength is multiplied by a resistance factor and compared to the required strength based onfactored loads These procedures and pertinent load combinations to consider are set forth
in the specification as follows
10.4.1 ASD Requirements
ASD Strength Requirements. A design satisfies the requirements of the AISI Specification
when the allowable design strength of each structural component equals or exceeds therequired strength, determined on the basis of the nominal loads, for all applicable loadcombinations This is expressed as
where R⫽ required strength
R n⫽ nominal strength (specified in Chapters B through E of the Specification)
⍀ ⫽safety factor (see Table 10.1)
R n/⍀ ⫽allowable design strength
ASD Load Combinations In the absence of an applicable code or specification or if the
applicable code or specification does not include ASD load combinations, the structure andits components should be designed so that allowable design strengths equal or exceed theeffects of the nominal loads for each of the following load combinations:
Trang 29in-10.6 SECTION TEN
Composite Construction under ASD For the composite construction of floors and roofs
using cold-formed deck, the combined effects of the weight of the deck, the weight of thewet concrete, and construction loads (such as equipment, workmen, formwork) must beconsidered
10.4.2 LRFD Requirements
LRFD Strength Requirements. A design satisfies the requirements of the AISI Specification
when the design strength of each structural component equals or exceeds the requiredstrength determined on the basis of the nominal loads, multiplied by the appropriate loadfactors, for all applicable load combinations This is expressed as
where Ru⫽required strength
R n⫽nominal strength (specified in chapters B through E of the Specification)
⫽resistance factor (see Table 10.1)
R n⫽design strength
LRFD Load Factors and Load Combinations In the absence of an applicable code or
specification, or if the applicable code or specification does not include LRFD load nations and load factors, the structure and its components should be designed so that designstrengths equal or exceed the effects of the factored nominal loads for each of the followingcombinations:
Several exceptions apply:
1 The load factor for E in combinations (5) and (6) should equal 1.0 when the seismic load
model specified by the applicable code or specification is limit state based
2 The load factor for L in combinations (3), (4), and (5) should equal 1.0 for garages, areas
occupied as places of public assembly, and all areas where the live load is greater than
Composite Construction under LRFD For the composite construction of floors and roofs
using cold-formed deck, the following additional load combination applies:
where DS⫽weight of steel deck
C W⫽weight of wet concrete
C⫽construction load (including equipment, workmen, and form work but excludingwet concrete
Trang 30COLD-FORMED STEEL DESIGN 10.7
10.5 SECTION PROPERTY CALCULATIONS
Because of the flexibility of the manufacturing method and the variety of shapes that can bemanufactured, properties of cold-formed sections often must be calculated for a particularconfiguration of interest rather than relying on tables of standard values However, properties
of representative or typical sections are listed in the Cold-Formed Steel Design Manual, American Iron and Steel Institute, 1996, Washington, DC (AISI Manual ).
Because the cross section of a cold-formed section is generally of a single thickness of
steel, computation of section properties may be simplified by using the linear method With
this method, the material is considered concentrated along the centerline of the steel sheet
and area elements are replaced by straight or curved line elements Section properties are calculated for the assembly of line elements and then multiplied by the thickness, t Thus, the cross section area is given by A⫽L⫻t, where L is the total length of all line elements; the moment of inertia of the section is given by I ⫽ I⬘ ⫻ t, where I⬘ is the moment ofinertia determined for the line elements; and the section modulus is calculated by dividing
I by the distance from the neutral axis to the extreme fiber, not to the centerline of the
extreme element As subsequently discussed, it is sometimes necessary to use a reduced or
effective width rather than the full width of an element.
Most sections can be divided into straight lines and circular arcs The moments of inertiaand centroid location of such elements are defined by equations from fundamental theory aspresented in Table 10.2
10.6 EFFECTIVE WIDTH CONCEPT
The design of cold-formed steel differs from heavier construction in that elements of
mem-bers typically have large width-to-thickness (w / t) ratios and are thus subject to local
buck-ling Figure 10.2 illustrates local buckling in beams and columns Flat elements in pression that have both edges parallel to the direction of stress stiffened by a web, flange,
com-lip or stiffener are referred to as stiffened elements Examples in Fig 10.2 include the top flange of the channel and the flanges of the I-cross section column.
To account for the effect of local buckling in design, the concept of effective width isemployed for elements in compression The background for this concept can be explained
as follows
Unlike a column, a plate does not usually attain its maximum load carrying capacity atthe buckling load, but usually shows significant post buckling strength This behavior isillustrated in Fig 10.3, where longitudinal and transverse bars represent a plate that is simplysupported along all edges As the uniformly distributed end load is gradually increased, thelongitudinal bars are equally stressed and reach their buckling load simultaneously However,
as the longitudinal bars buckle, the transverse bars develop tension in restraining the lateraldeflection of the longitudinal bars Thus, the longitudinal bars do not collapse when theyreach their buckling load but are able to carry additional load because of the transverserestraint The longitudinal bars nearest the center can deflect more than the bars near theedge, and therefore, the edge bars carry higher loads after buckling than do the center bars.The post buckling behavior of a simply supported plate is similar to that of the gridmodel However, the ability of a plate to resist shear strains that develop during buckling
also contributes to its post buckling strength Although the grid shown in Fig 10.3a buckled
into only one longitudinal half-wave, a longer plate may buckle into several waves as
illus-trated in Figs 10.2 and 10.3b For long plates, the half-wave length approaches the width b.
After a simply supported plate buckles, the compressive stress will vary from a maximumnear the supported edges to a minimum at the mid-width of the plate as shown by line 1 of
Trang 3110.8 SECTION TEN
TABLE 10.2 Moment of Inertia for Line Elements
Source: Adapted from Cold-Formed Steel Design Manual, American Iron and Steel Institute, 1996,
Washington, DC.
Trang 32COLD-FORMED STEEL DESIGN 10.9
FIGURE 10.2 Local buckling of compression elements (a) In beams; (b) in
columns (Source: Commentary on the Specification for the Design of
Cold-Formed Steel Structural Members, American Iron and Steel Institute, Washington,
DC, 1996, with permission.)
Fig 10.3c As the load is increased the edge stresses will increase, but the stress in the
mid-width of the plate may decrease slightly The maximum load is reached and collapse isinitiated when the edge stress reaches the yield stress—a condition indicated by line 2 of
Fig 10.3c.
The post buckling strength of a plate element can be considered by assuming that afterbuckling, the total load is carried by strips adjacent to the supported edges which are at auniform stress equal to the actual maximum edge stress These strips are indicated by the
dashed lines in Fig 10.3c The total width of the strips, which represents the effective width
of the element b, is defined so that the product of b and the maximum edge stress equals
the actual stresses integrated over the entire width The effective width decreases as theapplied stress increases At maximum load, the stress on the effective width is the yieldstress
Thus, an element with a small enough w / t will be able to reach the yield point and will
be fully effective Elements with larger ratios will have an effective width that is less thanthe full width, and that reduced width will be used in section property calculations.The behavior of elements with other edge-support conditions is generally similar to thatdiscussed above However, an element supported along only one edge will develop only oneeffective strip
Equations for calculating effective widths of elements are given in subsequent articles
based on the AISI Specification These equations are based on theoretical elastic buckling
theory but modified to reflect the results of extensive physical testing
Trang 3310.10 SECTION TEN
FIGURE 10.3 Effective width concept (a) Buckling of grid model; (b) buckling of plate; (c) stress distributions.
Trang 34COLD-FORMED STEEL DESIGN 10.11
10.7 MAXIMUM WIDTH-TO-THICKNESS RATIOS
The AISI Specification gives certain maximum width-to-thickness ratios that must be adhered
to
For flange elements, such as in flexural members or columns, the maximum flat
width-to-thickness ratio, w / t, disregarding any intermediate stiffeners, is as follows:
Stiffened compression element having one longitudinal edge connected to a web or flangeelement, the other stiffened by
(a) a simple lip, 60
(b) other stiffener with IS⬍I a, 90 (c) other stiffener with ISⱖI a, 90
Stiffened compression element with both longitudinal edges connected to other stiffenedelements, 500
Unstiffened compression element, 60
In the above, ISis the moment of inertia of the stiffener about its centroidal axis, parallel to
the element to be stiffened, and Iais the moment of inertia of a stiffener adequate for theelement to behave as a stiffened element Note that, although greater ratios are permitted,
stiffened compression elements with w / t⬎250, and unstiffened compression elements with
w / t⬎30 are likely to develop noticeable deformations at full design strength, but ability todevelop required strength will be unaffected
For web elements of flexural members, the maximum web depth-to-thickness ratio, h / t,
disregarding any intermediate stiffeners, is as follows:
Unreinforced webs, 200Webs with qualified transverse stiffeners that include (a) bearing stiffeners only, 260(b) bearing and intermediate stiffeners, 300
10.8 EFFECTIVE WIDTHS OF STIFFENED ELEMENTS
10.8.1 Uniformly Compressed Stiffened Elements
The effective width for load capacity determination depends on a slenderness factordefinedas
where k ⫽plate buckling coefficient (4.0 for stiffened elements supported by a web along
each longitudinal edge; values for other conditions are given subsequently)
ƒ⫽maximum compressive stress (with no safety factor applied)
E⫽Modulus of elasticity (29,500 ksi or 203 000 MPa)
Trang 3510.12 SECTION TEN
FIGURE 10.4 Illustration of uniformly compressed stiffened element (a) Actual element; (b) stress on effective element (Source: Specification for the Design of Cold-Formed Steel Structural Members, Amer-
ican Iron and Steel Institute, Washington, DC, 1996, with permission.)
For flexural members, when initial yielding is in compression, ƒ⫽F y , where Fyis the yieldstress; when the initial yielding is in tension, ƒ⫽the compressive stress determined on thebasis of effective section For compression members, ƒ⫽column buckling stress
The effective width is as follows:
10.8.2 Stiffened Elements with Stress Gradient
Elements with stress gradients include webs subjected to compression from bending alone
or from a combination of bending and uniform compression For load capacity determination,
the effective widths b1 and b2 illustrated in Fig 10.5 must be determined First, calculatethe ratio of stresses
where ƒ1and ƒ2are the stresses as shown, calculated on the basis of effective section, with
no safety factor applied In this case ƒ1is compression and treated as⫹, while ƒ2can beeither tension (⫺) or compression (⫹) Next, calculate the effective width, b e, as if theelement was in uniform compression (Art 10.8.1) using ƒ1for ƒ and with k determined as
Trang 36COLD-FORMED STEEL DESIGN 10.13
FIGURE 10.5 Illustration of stiffened element with stress gradient (a) Actual element; (b) stress on fective element varying from compression to tension; (c) stress on effective element with non-uniform com- pression (Source: Specification for the Design of Cold-Formed Steel Structural Members, American Iron
ef-and Steel Institute, Washington, DC, 1996, with permission.)
Trang 3710.14 SECTION TEN
FIGURE 10.6 Illustration of uniformly compressed unstiffened element (a) Actual element; (b) stress
on effective element (Source: Specification for the Design of Cold-Formed Steel Structural Members,
American Iron and Steel Institute, Washington, DC, 1996, with permission.)
10.9 EFFECTIVE WIDTHS OF UNSTIFFENED ELEMENTS
10.9.1 Uniformly Compressed Unstiffened Elements
The effective widths for uniformly compressed unstiffened elements are calculated in the
same manner as for stiffened elements (Art 10.8.1), except that k in Eq 10.4 is taken as
0.43 Figure 10.6 illustrates the location of the effective width on the cross section
10.9.2 Unstiffened Elements and Edge Stiffeners with Stress Gradient
The effective width for unstiffened elements (including edge stiffeners) with a stress gradient
is calculated in the same manner as for uniformly loaded stiffened elements (Art 10.9.1)
except that (1) k in Eq 10.4 is taken as 0.43, and (2) the stress ƒ3is taken as the maximumcompressive stress in the element Figure 10.7 shows the location of ƒ3 and the effectivewidth for an edge stiffener consisting of an inclined lip (Such lips are more structurallyefficient when bent at 90⬚, but inclined lips allow nesting of certain sections.)
10.10 EFFECTIVE WIDTHS OF UNIFORMLY COMPRESSED
ELEMENTS WITH EDGE STIFFENER
A commonly encountered condition is a flange with one edge stiffened by a web, the other
by an edge stiffener (Fig 10.7) To determine its effective width for load capacity nation, one of three cases must be considered The case selection depends on the relation
determi-between the flange flat width-to-thickness ratio, w / t, and the parameter S defined as
For each case an equation will be given for determining Ia, the moment of inertia required for a stiffener adequate so that the flange element behaves as a stiffened element, ISis themoment of inertia of the full section of the stiffener about its centroidal axis, parallel to the
element to be stiffened A⬘Sis the effective area of a stiffener of any shape, calculated bymethods previously discussed The reduced area of the stiffener to be used in section property
calculations is termed AS and its relation to A⬘S is given for each case Note that for edgestiffeners, the rounded corner between the stiffener and the flange is not considered as part
of the stiffener in calculations The following additional definitions for a simple lip stiffener
illustrated in Fig 10.7 apply The effective width dS⬘ is that of the stiffener calculated cording to Arts 10.9.1 and 10.9.2 The reduced effective width to be used in section property
Trang 38ac-COLD-FORMED STEEL DESIGN 10.15
FIGURE 10.7 Illustration of element with edge stiffener (a) Actual element; (b) stress on effective element and stiffener (Source: Specification for the Design of Cold-Formed Steel Structural Members, American Iron and Steel
Institute, Washington, DC 1996, with permission.)
calculations is termed dS and its relation to dS⬘is given for each case For the inclined stiffener
of flat depth d at an angleas shown in Fig 10.7,
Trang 3910.16 SECTION TEN
n
where n⫽1 / 2, C2⫽I S / I a , and C1⫽2⫺C2 The coefficients C1and C2give the proportion
of the effective width to be placed along either edge of the flange, Fig 10.7 The plate
buckling coefficient k aand other terms are determined as follows:
For a simple lip stiffener with 140⬚ ⱖ ⱖ40⬚ and D / wⱕ0.8 (see Fig 10.7),
The following are calculated as for Case II, but with n⫽1 / 3: C1, C2, b, k, dS, and AS.
For all cases, effective width for deflection determination is calculated in the same mannerexcept that stresses are calculated at service load levels based on the effective section at thatload
10.11 TENSION MEMBERS
The nominal tensile strength, Tn, of an axial loaded tension member is the smallest of three
limit states: (1) yielding in the gross section, Eq 10.22; (2) fracture in the net section awayfrom the connections, Eq 10.23; and (3) fracture in the net section at connections (Art.10.18.2)
where Ag is the gross cross section area, An is the net cross section area, Fy is the design
yield stress and Fuis the tensile strength
As with all of the member design provisions, these nominal strengths must be divided
by a safety factor,⍀, for ASD (Art 10.4.1) or multiplied by a resistance factor,, for LRFD (Art 10.4.2) See Table 10.1 for⍀andvalues for the appropriate member or connection category.
10.12 FLEXURAL MEMBERS
In the design of flexural members consideration must be given to bending strength, shearstrength, and web crippling, as well as combinations thereof, as discussed in subsequentarticles Bending strength must consider both yielding and lateral stability In some appli-cations, deflections are also an important consideration
Trang 40COLD-FORMED STEEL DESIGN 10.17
10.12.1 Nominal Strength Based on Initiation of Yielding
For a fully braced member, the nominal strength, Mn, is the effective yield moment based
on section strength:
where Seis the elastic section modulus of the effective section calculated with the extreme
fiber at the design yield stress, Fy The stress in the extreme fiber can be compression or
tension depending upon which is farthest from the neutral axis of the effective section Ifthe extreme fiber stress is compression, the effective width (Art 10.8–10.10) and the effective
section can be calculated directly based on the stress Fyin that compression element ever, if the extreme fiber stress is tension, the stress in the compression element depends onthe effective section and, therefore, a trial and error solution is required (Art 10.22)
How-10.12.2 Nominal Strength Based on Lateral Buckling
For this condition, the nominal strength, Mn, of laterally unbraced segments of singly-, bly-, and point-symmetric sections is given by Eq 10.25 These provisions apply to I-, Z-, C-, and other singly-symmetric sections, but not to multiple-web decks, U- and box sections.
dou-Also, beams with one flange fastened to deck, sheathing, or standing seam roof systems aretreated separately The nominal strength is
M e ⫽Elastic critical moment calculated according to (a) or (b) below:
(a) For singly-, doubly-, and point symmetric sections:
M e⫽C r A b o 兹 ey tfor bending about the symmetry axis (10.29)