UNIFIED FACILITIES CRITERIA UFC DIESEL ELECTRIC GENERATING PLANTS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED... 16 January 2004 UNIFIED FACILITIES CRITERIA UFC GENERAL ELECT
Trang 1UNIFIED FACILITIES CRITERIA (UFC)
DIESEL ELECTRIC
GENERATING PLANTS
APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED
Trang 216 January 2004 UNIFIED FACILITIES CRITERIA (UFC)
GENERAL ELECTRIC GENERATING PLANTS
Any copyrighted material included in this UFC is identified at its point of use
Use of the copyrighted material apart from this UFC must have the permission of the
copyright holder
U.S ARMY CORPS OF ENGINEERS (Preparing Activity)
NAVAL FACILITIES ENGINEERING COMMAND
AIR FORCE CIVIL ENGINEERING SUPPORT AGENCY
Record of Changes (changes indicated by \1\ /1/ )
Change No Date Location
Trang 3UFC 3-540-04N
16 January 2004 FOREWORD
The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides
planning, design, construction, sustainment, restoration, and modernization criteria, and applies
to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance with USD(AT&L) Memorandum dated 29 May 2002 UFC will be used for all DoD projects and work for other customers where appropriate All construction outside of the United States is
also governed by Status of forces Agreements (SOFA), Host Nation Funded Construction
Agreements (HNFA), and in some instances, Bilateral Infrastructure Agreements (BIA.)
Therefore, the acquisition team must ensure compliance with the more stringent of the UFC, the SOFA, the HNFA, and the BIA, as applicable
UFC are living documents and will be periodically reviewed, updated, and made available to
users as part of the Services’ responsibility for providing technical criteria for military
construction Headquarters, U.S Army Corps of Engineers (HQUSACE), Naval Facilities
Engineering Command (NAVFAC), and Air Force Civil Engineer Support Agency (AFCESA) are responsible for administration of the UFC system Defense agencies should contact the
preparing service for document interpretation and improvements Technical content of UFC is the responsibility of the cognizant DoD working group Recommended changes with supporting rationale should be sent to the respective service proponent office by the following electronic
form: Criteria Change Request (CCR) The form is also accessible from the Internet sites listed below
UFC are effective upon issuance and are distributed only in electronic media from the following source:
Hard copies of UFC printed from electronic media should be checked against the current electronic version prior to use to ensure that they are current
AUTHORIZED BY:
DONALD L BASHAM, P.E
Chief, Engineering and Construction
U.S Army Corps of Engineers
DR JAMES W WRIGHT, P.E
Chief Engineer Naval Facilities Engineering Command
KATHLEEN I FERGUSON, P.E
The Deputy Civil Engineer
DCS/Installations & Logistics
Department of the Air Force
Dr GET W MOY, P.E
Director, Installations Requirements and Management
Office of the Deputy Under Secretary of Defense (Installations and Environment)
Trang 416 January 2004
i
CONTENTS
Page CHAPTER 1 INTRODUCTION
Paragraph 1-1 PURPOSE AND SCOPE 1-1
1-2 APPLICABILITY 1-1 1-2.1 General Building Requirements 1-1 1-2.2 Safety 1-1 1-2.3 Fire Protection 1-1 1-2.4 Antiterrorism/Force Protection 1-1 1-3 REFERENCES 1-2
APPENDIX A MIL-HDBK 1003/11.……… ……… A-1
Trang 5UFC 3-540-04N
16 January 2004
1-1
CHAPTER 1 INTRODUCTION
1-1 PURPOSE AND SCOPE This UFC is comprised of two sections
Chapter 1 introduces this UFC and provides a listing of references to other Tri-Service documents closely related to the subject Appendix A contains the full text copy of the previously released Military Handbook (MIL-HDBK) on this subject This UFC serves as criteria until such time as the full text UFC is developed from the MIL-HDBK and other sources
This UFC provides general criteria for the design of diesel electric generating plants
Note that this document does not constitute a detailed technical design, maintenance or operations manual, and is issued as a general guide to the
considerations associated with design of economical, efficient and environmentally acceptable heating plants
1-2 APPLICABILITY This UFC applies to all Navy service elements and
Navy contractors; Army and Air Force service elements should use the appropriate references cited in paragraph 1-3 below; all other DoD agencies may use either
document unless explicitly directed otherwise
1-2.1 GENERAL BUILDING REQUIREMENTS All DoD facilities must comply
with UFC 1-200-01, Design: General Building Requirements If any conflict occurs
between this UFC and UFC 1-200-01, the requirements of UFC 1-200-01 take
precedence
1-2.2 SAFETY All DoD facilities must comply with DODINST 6055.1 and
applicable Occupational Safety and Health Administration (OSHA) safety and health standards
NOTE: All NAVY projects, must comply with OPNAVINST 5100.23 (series), Navy
Occupational Safety and Health Program Manual
If any conflict occurs between this UFC and OPNAVINST 5100.23, the requirements of OPNAVINST 5100.23 take precedence
1-2.3 FIRE PROTECTION All DoD facilities must comply with UFC 3-600-01,
Design: Fire Protection Engineering for Facilities If any conflict occurs between this
UFC and UFC 3-600-01, the requirements of UFC 3-600-01 take precedence
1-2.4 ANTITERRORISM/FORCE PROTECTION All DoD facilities must
comply with UFC 4-010-01, Design: DoD Minimum Antiterrorism Standards for
Buildings If any conflict occurs between this UFC and UFC 4-010-01, the requirements
of UFC 4-010-01 take precedence
Trang 6UFC 3-540-04N
16 January 2004 1-3 REFERENCES The following Tri-Service publications have valuable
information on the subject of this UFC When the full text UFC is developed for this subject, applicable portions of these documents will be incorporated into the text The designer is encouraged to access and review these documents as well as the
references cited in Appendix A
1 US Army Corps of Engineers
Commander AFETL98-2, Clean Air Act Amendments
ATTN: CEIM-IM-PD Required for Electric Generators and
2803 52nd Avenue Power Plants
Hyattsville, MD 20781-1102 USACE TM 5-685, Operation, Maintenance
(301) 394-0081 fax: 0084 and Repair and Repair of Auxiliary
Generators
26 August 1996
For Evaluation Only.
Copyright (c) by Foxit Software Company, 2004
Trang 7A-1
APPENDIX A MIL-HDBK 1003/11 DIESEL ELECTRIC GENERATING PLANTS
Trang 813 OCTOBER 1987
MILITARY HANDBOOK
DIESEL-ELECTRIC GENERATING PLANTS
AMSC N/A
DISTRIBUTION STATEMENT A APPROVED FOR PUBLIC RELEASE: DISTRIBUTION IS
UNLIMITED
AREA FACR
Trang 9PAGE ii INTENTIONALLY BLANK
Trang 10ABSTRACT
This handbook provides basic design guidance which has been developed from extensive reevaluation of facilities It is intended for use by
experienced architects and engineers The criteria presented is for the design of stationary diesel-electric generating plants for prime and
standby/emergency duty Planning factors are provided for plants
incorporating the cogeneration of steam and/or hot-water for other uses Changes required for utility interconnections, equipment applications and the types of waste-heat recovery cycles available for cogeneration are also provided Data and criteria required for design of diesel-electric
generating plants include information on the service category and the types
of diesel prime movers, generators and utility interfaces available, sources
of power and fuels available, other plant location factors, advantages and disadvantages of various plant ownership options, and electrical and thermal loads anticipated Design criteria are included for diesel-engine
auxiliaries and foundations, voltage ratings, generators and exciters,
control wiring and components, piping, insulation, corrosion protection, and for various other design factors Guidance is provided to assist in the design of different types of plant construction and of nonstandard plants.
iii