9.1.1 Conduction Almost all the types of transformers are either oil or gas filled, and heat flows fromthe core and windings into the cooling medium.. The heat dissipation from the trans
Trang 1Cooling Systems
The magnetic circuit and windings are the principal sources of losses andresulting temperature rise in various parts of a transformer Core loss, copper loss
in windings (I2R loss), stray loss in windings and stray loss due to leakage/high
current field are mainly responsible for heat generation within the transformer.Sometimes loose electrical connections inside the transformer, leading to a highcontact resistance, cause higher temperatures Excessive temperatures due toheating of curb bolts, which are in the path of stray field, can damage gaskets(refer to Chapter 5) The heat generated due to all these losses must be dissipatedwithout allowing the core, winding and structural parts to reach a temperaturewhich will cause deterioration of insulation If the insulation is subjected totemperatures higher than the allowed value for a long time, it looses insulatingproperties; in other words the insulation gets aged, severely affecting thetransformer life There are two principle characteristics of insulation: dielectricstrength and mechanical strength The dielectric strength of insulation aged in oilremains high up to a certain temperature after which it drops rapidly At this pointthe insulation material becomes brittle and looses its mechanical strength Thus, it
is primarily the mechanical strength which gets affected by the highertemperatures and aging, which in turn affects the dielectric strength Hence, thedielectric strength alone cannot always be depended upon for judging the effect oftemperature on the insulation [1]
Accurate estimation of temperatures on all surfaces is very critical in the design
of transformers to decide the operating flux density in core and current densities inwindings/connections It helps in checking the adequacy of cooling arrangementsprovided for the core and windings It also helps in ensuring reliable operation ofthe transformer since the insulation life can be estimated under overloadconditions and corrective actions can be taken in advance
Trang 2The values of maximum oil and winding temperatures depend on the ambienttemperature, transformer design, loading conditions and cooling provided Thelimits for ambient temperature and the corresponding limits for oil temperaturerise and winding temperature rise are specified in the international standards Asthe ambient temperature varies from one country to another, the limits could bedifferent for different countries For example in IEC 60076–2 (second edition:1993), a maximum ambient temperature of 40°C is specified with a limit on topoil temperature rise of 60°C In a country where the maximum ambienttemperature is 50°C, the top oil temperature rise limit may be correspondinglyreduced to 50°C If the installation site is more than 1000 m above the sea level,the allowable temperature rise for transformers is reduced as per the guidelinesgiven in the standards because of the fact that air density reduces with theincrease in altitude lowering the effectiveness of cooling Altitude basicallyaffects the convective heat transfer (because of lower buoyancy effect) and notthe radiation A corresponding reverse correction is applied when the altitude offactory location is above 1000 m and the altitude of installation site is below
1000 m
In oil cooled transformers, the oil provides a medium for both cooling andinsulation Heat from core, windings and structural components is dissipated bymeans of the oil circulation The heat is finally transmitted either to atmosphericair or water In the subsequent sections, modes of heat transfer and theirapplication in different cooling configurations in a transformer are discussed
9.1 Modes of Heat Transfer
The heat transfer mechanism in a transformer takes place by three modes, viz.conduction, convection and radiation In the oil cooled transformers, convectionplays the most important role and conduction the least important Rigorousmathematical treatment for expressing these modes of heat transfer is quitedifficult and hence designers mostly rely on empirical formulae
9.1.1 Conduction
Almost all the types of transformers are either oil or gas filled, and heat flows fromthe core and windings into the cooling medium From the core, heat can flowdirectly, but from the winding it flows through the insulation provided on thewinding conductor In large transformers, at least one side of insulated conductors
is exposed to the cooling medium, and the heat flows through a small thickness ofthe conductor insulation But in small transformers the heat may have to flowthrough several layers of copper and insulation before reaching the coolingmedium
The temperature drop across the insulation due to the conduction heat transfermechanism can be calculated by the basic thermal law:
Trang 3(9.4)where η=5.67×10-8W/(m2 °K4) is the Stephan-Boltzmann constant, E is surface emissivity factor, A R is surface area for radiation in m2, T s is average temperature of
radiating surface in °K, and T a is ambient air temperature in °K
Surface emissivity is a property, which depends on several factors like surfacefinish, type of paint applied on the surface, etc When the emissivity factor is lessthan unity, the effective radiating surface is correspondingly less (as indicated bythe above equation) For tank and radiators painted with grey colour havingemissivity of 0.95, the effective radiating area is usually assumed to be that ofoutside envelope without introducing much error
Trang 49.1.3 Convection
The oil, being a liquid, has one important mechanical property that its volumechanges with temperature and pressure [3] The change of volume withtemperature provides the essential convective or thermosiphon cooling Thechange of volume with pressure affects the amount of transferred vibrations fromthe core to tank
The heat dissipation from the core and windings occurs mainly due toconvection When a heated surface is immersed in a fluid, heat flows from thesurface to the cooling medium Due to increase in the fluid temperature, itsdensity (or specific gravity) reduces The fluid (oil) in oil-cooled transformers,rises upwards and transfers its heat to outside ambient through tank andradiators The rising oil is replaced by the colder oil from the bottom, and thusthe continuous oil circulation occurs The convective heat transfer is expressed
by the relationship:
where Q is heat flow in W, h is heat transfer coefficient in W/(m2 °C), A is surface
area in m2, and temperatures T surface and T fluid are in °C Since h depends on both
geometry as well as fluid properties, its estimation is very difficult However, a lot
of empirical correlations are available, which can be used in majority of designcalculations In one such correlation, the heat dissipated per unit surface area isexpressed as equal to a constant multiplied by temperature rise raised to anempirical coefficient
The heat dissipation from the transformer tank to ambient air occurs similarlybut the warmed air after cooling does not come back and its place is occupied bynew quantity of fresh air In the case of tank, heat dissipation by convection andradiation mechanisms are comparable since the surface area available for theconvective cooling is same as that for the radiation cooling The heat dissipated bythe tank through the convection and radiation is also usually calculated byempirical relations in which the resultant effect of both the mechanisms is takeninto account
9.2 Cooling Arrangements
9.2.1 ONAN/OA cooling
In small rating transformers, the tank surface area may be able to dissipate heatdirectly to the atmosphere; while the bigger rating transformers usually requiremuch larger dissipating surface in the form of radiators/tubes mounted directly onthe tank or mounted on a separate structure If the number of radiators is small,they are preferably mounted directly on the tank so that it results in smaller overalldimensions
Trang 5When number of radiators is large, they are mounted on a separate structure andthe arrangement is called as radiator bank The radiators are mounted on headers,which are supported from the ground In this case, strict dimensional control ofpipes and other fittings is required in order to avoid oil leakages.
Oil is kept in circulation by the gravitational buoyancy in the closed-loopcooling system as shown in figure 9.1 The heat developed in active parts is passed
on to the surrounding oil through the surface transfer (convection) mechanism.The oil temperature increases and its specific gravity drops, due to which it flowsupwards and then into the coolers The oil heat gets dissipated along the coldersurfaces of the coolers which increases its specific gravity, and it flowsdownwards and enters the transformer tank from the inlet at the bottom level.Since the heat dissipation from the oil to atmospheric air is by natural means (thecirculation mechanism for oil is the natural thermosiphon flow in the coolingequipment and windings), the cooling is termed as ONAN (Oil Natural and AirNatural) or OA type of cooling
In the arrangement consisting of radiator banks, higher thermal head can beachieved by adjusting the height of support structures The thermal head can bedefined as the difference between the centers of gravity of fluids in the tank andradiator bank Although it is difficult to get higher thermal head for the case oftank mounted radiators, reasonable amount of thermal head is achieved by thearrangement shown in figure 9.2 When the radiators are mounted at higherheight, the buoyancy effect on the cooling-loop increases resulting in increase
of the rate of oil flow and heat dissipation in the cooling equipment However,
it is to be noted that the increase in flow rate results in increased frictionalpressure loss, thereby offsetting the thermal head gained by the heightdifference
Figure 9.1 ONAN cooling
Trang 69.2.2 ONAF/FA cooling
As the transformer rating increases, the total loss to be dissipated also increases.One way of increasing the heat transfer is to increase the heat transfer coefficientbetween the radiator outside surface and air (equation 9.5) In this equation, for a
radiator T surface corresponds to its outside wall surface temperature However, the
temperature drop across the radiator plate is very small, hence T surface can beconsidered as the oil temperature itself If fans are used to blow air on to thecooling surfaces of the radiators, the heat transfer coefficient is significantlyincreased For a given set of ambient air temperature and oil temperature, acompact arrangement is possible since less number of radiators is required to coolthe oil This type of cooling is termed as ONAF (Oil Natural and Air Forced) or FAtype of cooling
If there is a particular case in which either ONAN or mixed ONAN/ONAFcooling can be specified; the ONAN cooling has the following advantages(although it may take more space):
- it is more reliable as no cooler controls are involved and it requires lessmaintenance
- the cost increase due to extra radiators is, to a large extent, compensated bythe reduction in cost due to the absence of fans and control system
- it is particularly useful when low noise transformers are required Absence offans makes it easier to achieve the required low noise level
- there is no cooler loss
- winding losses also reduce (although marginally) because of lower winding
Figure 9.2 Arrangement for higher thermal head
Trang 7temperature rise at fractions of rated load as compared to the mixed cooling.most of the time, when load on the transformer is less than its full rating,temperature rise inside the transformer is low and its life increases (gain oflife).
Thus, in cases where the ONAN rating is 75% or more (it is closer to the ONAFrating), ONAN cooling can be specified instead of mixed ONAN/ONAF coolingbased on cost-benefit analysis
There are two typical configurations for mounting fans in ONAF cooling Onemethod is to mount the fans below the radiators, which blow air from bottom totop Larger capacity fans can be used since it is easy to design the supportstructures for them In this system the fans can be either supported directly fromthe radiators or they can be ground mounted Care should be taken that the fansmounted on radiators do not produce appreciable vibrations Usually, sufficientsurface of radiators is covered in the air-flow cone created by the fan; theremaining surface is taken to be naturally cooled In the second method, fans aremounted on the side of radiators These fans are relatively smaller in sizecompared to the first arrangement since the number of fans is usually more for thisconfiguration Both the configurations have their own advantages anddisadvantages, particular selection depends on the specific design requirement
9.2.3 OFAF/FOA cooling
As discussed previously, the flow rate inside the windings under ONAN andONAF cooling arrangements is governed by the natural balance between theviscous resistance and the thermosiphon pressure head Normally this flow rate isrelatively low Because of this, the heat carrying (or dissipating) capacity of the oil
is low The heat carrying capacity can be defined as
(9.6)
where Q is heat flow in W, m is mass flow rate in kg/s, C p is specific heat in J/(kg
°C), and temperatures T out and T in are in °C For the given transformer oil inlet (T in)
and top oil (T out) temperatures, the only way to increase the heat dissipationcapability is to increase This necessitates the use of an external pump to circulatethe oil in high rating transformers Also, in order to get a higher heat transfer rate,
fans have to be always operating at the radiator sections m This type of cooling is
called as OFAF (Oil Forced and Air Forced) or FOA cooling There are basicallytwo types of pump designs: axial flow in-line type and radial flow type forcirculating oil against low and high frictional head losses respectively The axialflow type is used with mixed cooling (ONAN/ ONAF/OFAF) since it offers lessresistance when switched-off The radial flow type pumps, which offer very highresistance to oil flow under the switched-off condition, are used with oil-to-airheat exchangers (unit cooler arrangement) or oil-to-water heat exchangers in
Trang 8which no natural cooling is provided The head required to be developed for thesetwo types of compact heat exchangers is quite high and the radial flow pump cancater to this requirement quite well.
In OFAF cooling arrangement, when fans are mounted on the sides ofradiators, they should be uniformly distributed over the radiator height, whereasfor ONAF cooling more fans should be mounted at the top of radiator height This
is because in OFAF condition, the temperature difference between top and bottomportions of radiators is small as compared to that under ONAF condition.When the oil is forced into the transformer (figure 9.3), its flow is governed bythe least resistance path as well as the buoyancy Hence, part of the oil may notenter either windings or core, and may form a parallel path outside these two.Thus, the top oil temperature may reduce because of the mixture of hot oil comingfrom the windings and the cool oil coming from the pump This in turn reduces theeffectiveness of radiators The heat dissipation rate can be improved if the oil isforced (by use of pumps) and directed in the windings through the predeterminedpaths as shown in figure 9.4 This type of cooling is termed as ODAF (Oil Directedand Air Forced) type of cooling ODAF type of cooling is used in most of the largerating power transformers One disadvantage of ODAF cooling is the increasedpressure loss because of the ducting system used for directing the oil flow Foreach winding, the oil flow rate is required to be determined accurately In theabsence of proper oil flow rates, an unreasonable temperature rise will result.Additionally, any blockage or failure of the ducting system leads to highertemperature rise
Generally, the higher the pump capacity (and the greater the oil velocity) thehigher the rate of heat dissipation is Hence, during the early development, therewas a general trend for using higher capacity pumps permitting higher loss density(use of higher current density in windings and/or higher flux density in core),leading to lower material cost and size of transformers The trend continued till anumber of large transformers failed due to the phenomenon called staticelectrification (explained in Section 9.6) Hence, the oil pump capacity should bejudiciously selected
Trang 99.2.4 Unit coolers
As mentioned earlier, sometimes OFAF cooling is provided through the use ofcompact heat exchangers when there is space constraint at site In this small boxtype structure, an adequate surface area is provided by means of finned tubes.Usually, about 20% standby cooling capacity is provided Disadvantage of thesecoolers is that there is only one rating available (with running of fans and pumps)
If the system of fans and pumps fails (e.g., failure of auxiliary supply), ONANrating is not available Hence, the continuity of auxiliary supply to fans and pumps
is required to be ensured
9.2.5 OFWF cooling
For most of the transformers installed in hydropower stations, where there isabundance of water, oil-to-water heat exchangers are used As the surface heattransfer coefficient of water is more than air, such type of cooling results insmaller radiators This type of cooling is termed as water forced (WF) cooling.Depending on the type of oil circulation, the transformer cooling system is termed
as OFWF or ODWF type of cooling During operation, it is very important toensure that the oil pressure is always more than the water pressure so that thepossibility of water leaking into the oil is eliminated A dedicated differentialpressure gauge and the corresponding protection circuit are used to trip thetransformer if a specific value of pressure difference between the oil and water isnot maintained during the operation
9.3 Dissipation of Core Heat
As the transformer core size increases, it becomes more important to decide thepositions of cooling ducts in it These cooling ducts (shown in figure 9.5) reduceboth the surface temperature rise of the core relative to that of oil and thetemperature rise of the interior of the core relative to that at the surface
Figure 9.5 Core cooling ducts
Trang 10It is necessary to maximize core area (net iron area) to get an optimum design.The cooling ducts reduce the core area, and hence their number should be asminimum as necessary This requires accurate determination of temperatureprofile of the core and effective placement of the cooling ducts The complicatedgeometry of the boundary surface between the core and oil, and the anisotropy ofthe thermal conductivity of the laminated core are some of the complexitiesinvolved in the computations A general formulation of the approximated two-dimensional problem of temperature distribution in rectangular cores subjected tolinear boundary conditions (thermal resistance being independent of heat flow andoil temperature) is given in [4] The method described in [5] solves the two-dimensional problem by transforming Poisson’s equation of heat conduction intoLaplace’s equation The method can be applied to any arbitrary shape due to use of
a functional approximation The paper also reports the use of electrical analogmethod which uses the analogy between electrical potential difference andtemperature difference, between electrical current and heat flow, and betweenelectrical conductivity and thermal conductivity The calculation of temperaturedistribution in the transformer core is a complex three-dimensional problem withnon-uniform heat generation Furthermore, the thermal properties of core areanisotropic in the sense that the thermal conductivity along the plane oflaminations is quite different from that across them The problem can be solved byusing three-dimensional finite element thermal formulation with the anisotropicthermal material properties taken into account
The surface of core is normally in contact with the insulation (between coreand frame) Hence, the limit on the core surface temperature is the same as that forthe windings For the interior portions of the core which are in contact with onlythe oil (film), the limit is 140°C In most cases, the temperature differencebetween the core interior (e.g., mid-location between two cooling ducts) andsurface is about 15 to 20°C
9.4 Dissipation of Winding Heat
Radial spacers (pressboard insulations between disks/turns) cover about 30 to40% of the winding surface, making the covered area ineffective for theconvective cooling The arrangement is shown in figure 9.6 Thus, although higherspacer width may be required from the short circuit withstand considerations, it iscounterproductive for cooling Hence, while calculating the gradients, only theuncovered winding surface area is taken into account
Heat from the covered winding area is transferred to the uncovered area bythermal conduction process increasing thermal load on the uncovered surfaces.Contrary to the width of radial spacer, cooling is improved with the increase in itsthickness Hence, radial spacers may not be required from insulationconsiderations in low voltage windings, but they are essential for providing thecooling ducts
Trang 11The required spacer thickness bears a specific relationship with the radial depth ofwinding For a given radial depth, a certain minimum thickness of radial spacers isrequired for effective cooling (otherwise resistance to oil flow in the duct betweentwo disks/turns is higher and the oil largely flows through the axial ducts at insideand outside diameters resulting in higher temperature rise at the middle portion ofthe radial depth).
When the winding radial depth is quite high, the usual practice of providingtwo axial ducts at the inside and outside diameters (along with the radial ducts)may not be enough Hence, some manufacturers provide an additional axialcooling duct in the middle of the radial depth as shown in figure 9.7, so that thethickness of the radial spacers can be lower With this arrangement, the axial spacefactor of the winding improves (due to reduction of insulation along the windingheight), but the radial space factor worsens Hence, the design and dimensioning
of the axial and radial spacers have to be judiciously done, which may also depend
on the manufacturing practices
Axial ducts play an important role in dissipation of heat from the windings Thehigher the axial duct width, the better the oil flow conditions are; this is more validfor windings without radial ducts In large transformers with radial cooling ductsbetween disks/turns, thicknesses of the axial ducts (at the inside and outsidediameters of the winding) and radial ducts decide the oil velocity within thewinding and the rate of heat dissipation
Figure 9.6 Effect of radial spacers on cooling