This PSCAD/EMTDC model can be used to evaluate the DFIG WT performances under different operating modes, control schemes and the grid integration capabilities.. 2.1 Aerodynamic modelling
Trang 1Published in IET Renewable Power Generation
Received on 10th August 2012
Revised on 21st November 2012
Accepted on 17th December 2012
doi: 10.1049/iet-rpg.2012.0222
ISSN 1752-1416 Doubly-fed induction generator wind turbine
modelling for detailed electromagnetic system
studies
Ting Lei, Mike Barnes, Meliksah Ozakturk
Power Conversion Group, University of Manchester, M1 0QD, UK
E-mail: Ting.lei-2@postgrad.manchester.ac.uk
Abstract: Wind turbine (WT) technology is currently driven by offshore development, which requires more reliable, multi-megawatt turbines Models with different levels of detail have been continuously explored but tend to focus either on the electrical system or the mechanical system This study presents a 4.5 MW doubly-fed induction generator (DFIG) WT model with pitch control The model is developed in a simulation package, which has two control levels, the WT control and the DFIG control Both a detailed and a simplified converter model are presented Mathematical system block diagrams of the closed-loop control systems are derived and verified against the simulation model This includes a detailed model of the DC-link voltage control– a component which is usually only presented in abstract form Simulation results show that the output responses from the two models have good agreement The grid-side converter control with several disturbance inputs has been evaluated for three cases and its dynamic stiffness affected by operating points are presented In addition, the relation of pitch controller bandwidth and torsional oscillation mode has been investigated using a two-mass shaft model This model can be employed to evaluate the control scheme, mechanical and electrical dynamics and the fault ride-through capability for the turbine
1 Introduction
The trend of future wind turbine (WT) installations moving
offshore is stimulating the need for high reliability and ever
larger WTs in order to minimise cost Two WT concepts
currently used are considered to be suitable for the
multi-megawatt offshore installations – the doubly-fed
induction generator (DFIG) WT and the permanent magnet
synchronous generator WT [1] Currently the former with a
capacity up to 5 MW has the largest market share
Increasingly comprehensive studies need to be carried out
to evaluate the control strategies and system dynamic
behaviour These studies require accurate models
DFIG WTs have been investigated for many years [2–10]
In most of these, the converters are simplified as controllable
voltage or current sources with only fundamental frequency
components, which makes it impossible to implement a
detailed study of power converter dynamics The drive-train
is often treated as a lumped-mass system, which means the
induced torsional oscillations are neglected
In this paper, a PSCAD/EMTDC-based DFIG WT model
with two control levels is provided The DFIG control level
involves the rotor-side converter (RSC) control and the
grid-side converter (GSC) control The WT control level
involves the pitch control and the optimum torque tracking
[4] Mathematical analysis of each individual control system
is carried out and the mathematical blocks (MB) have been
verified against PSCAD/EMTDC simulation results Two
converter representations, with and without IGBT switches are used here, which are referred to as the full switched model (FSM) and the switch-averaged model (SAM) They both have been implemented for observing GSC control performances where the DC-link dynamic is involved The latter is used to demonstrate the WT mechanical responses such as rotor speed and pitch angle to wind speed changes Finally, a multi-mass shaft model is added to investigate the correlation of the pitch mechanism and shaft torsional modes This PSCAD/EMTDC model can be used to evaluate the DFIG WT performances under different operating modes, control schemes and the grid integration capabilities
The paper is structured as follows Section 2 presents the component modelling and equations Sections 3 and 4 then elaborate the DFIG-level and WT-level control systems, respectively, as well as the mathematical analysis and simulation results Section 5 concludes the main results
2 System modelling
A schematic diagram of the DFIG WT and its overall control systems are illustrated in Fig 1 The turbine rotor is connected to the DFIG through a shaft system The generator rotor is fed from the grid through a back-to-back converter which handles only the slip power (up to 30% of the rated power)
www.ietdl.org
Trang 22.1 Aerodynamic modelling
The aerodynamic model can be described by the equation of
aerodynamic power or torque generated as the wind passes the
turbine blades [11]
Pa=r
2pR2
aCp(l, b)v3w (1)
Ta=r
2pR3 a
Cp(l, b)
withρ is the air density (kg/m3
), Rais the radius of the rotor (m), vwis the wind speed upstream the rotor (m/s) andωris
the rotor speed (rad/s) The power coefficient Cp is a
function of the tip speed ratio λ and the pitch angle β
(deg.), for which the numerical approximation in [9] is used
l =vrRa
1
li=l + 0.08b1 −b03.035
Cp(l, b)= 0.22 116l
i
− 0.4b − 5
e− 12.5/ l( ( )i ) (5)
2.2 Induction generator modelling
The DFIG machine equations have been described in [5,9]
Note that in Fig 1, the currents are set as outputs from the
stator and rotor If generation convention is considered, the
set of machine equations can be derived as
vs= −Rsis+dcs
dt + jvscs (6)
vr = −Rrir+dcr
dt + j vs− vr
cs= −Lsis− Lmir (8)
cr = −Lrir− Lmis (9)
with v is the voltage (kV), R is the resistance (Ω), i is the current (kA), ωsis the synchronous electric speed (rad/s), ψ
is the flux linkage (Wb), Lm is the mutual inductance between stator and rotor windings (H ) The subscripts s and
r denote the stator and rotor quantities
2.3 Back-to-back converter modelling Two voltage source inverters (VSI) are connected back-to-back via a DC-link to comprise the converter This enables bidirectional power flow In Fig 2, the FSM is presented with all the IGBT switches and a PWM frequency of 4.5 kHz This model provides a deeper insight
of the converter dynamics over a short time scale
In the SAM, the converter is presented as two current-controlled voltage sources coupled through a DC-link The DC-dynamics are based on the power balance between the RSC and GSC, which generates two current disturbances from the VSIs feeding into the DC-link The SAM is suitable for inspecting the mechanical dynamics over a longer time scale without the disturbance from the switching noise
2.4 Shaft system modelling The shaft system has been presented as six, three, two and lumped-mass models in other research [12], among which the lumped and two-mass shaft models are often used to study the electric behaviours of the DFIG It is suggested in [11] that for a generator with shaft stiffness lower than 3 pu/el rad, a two- mass shaft model should be considered PSCAD/EMTDC provides the standard models of the wound rotor induction machine and the multi-mass shaft They can be interfaced with WT aerodynamic model and pitch controller as shown in Fig.3 The performances of the two-mass shaft model are investigated in Section 4 If not specified, the analysis refers to the lumped shaft model with
a SAM converter in the paper
The model performances during single or three-phase fault conditions are presented in Fig.4, where the stator and rotor voltages subject to significant changes when the grid voltages drop to 0 for 100 ms
Fig 1 DFIG WT model and its overall control systems
Trang 33 DFIG control
The control system has been shown in Fig.1, in which two
control levels are identified based on different bandwidths
The DFIG control consists of the RSC control and the GSC
control The former is used to provide decoupled control of
the active and reactive power while the latter is mainly used
to ensure a constant voltage on the DC-link [5,7]
3.1 RSC control
Stator-flux orientation is used for the RSC control in which
the stator flux is collinear with the d-axis and the other
rotor quantities are converted to this frame The equations
of the electric torque and the stator reactive power can be
found in [5], which are modified here using generator
convention,
Te=3 2
Lm
Lsscsir q (10)
Qs= −3
2
2
√
Vs
Lss cs−3
2
2
√
VsLm
Lss ir d (11) where Vsis the stator phase voltage in rms
Resolving (6)–(9), splitting the rotor voltage in d–
q-components and neglecting the statorflux transients (dψs/
dt = 0) gives
vr d∗ = −Rrir d− Lc
dir d
dt + vslipLcir q (12)
v∗r q= −Rrir q− Lc
dir q
dt − vslipLcir d+ vslip
Lm
Lsscs (13) where
vslip= vs− vr, Lc= Lrr−L2m
Lss
The MB diagram of RSC control is depicted in Fig 5, where the decoupling of d–q control-loops is achieved by adding the feed-forward compensation after the inner-loop
PI controller Reactive power control is cascaded with d-current control loop and electric torque control is cascaded with q-current control loop The estimated quantities are marked by ‘^’ to distinguish them from the real quantities
In PSCAD/EMTDC, the DFIG WT is connected to the grid through a step-up transformer Parameters used in the model are tabulated in appendix The DFIG is set to the speed control mode with a nominal rotor speed
Responses from the MB are compared with PSCAD/ EMTDC simulations (‘PCD’), applying the same reference signals (Ref) In Fig 6, the plots are resulted from a step input of Q∗s, Te∗, i∗r d, i∗r q at the four control loops separately Note that in the lower plots, the time scale is smaller since the bandwidth of the current-loop is much higher than the power loops It can be observed that the curves ‘MB’ and ‘PCD’ have a good agreement, indicating that the mathematical model can describe the software model accurately for this case
3.2 GSC control of the DC-link
In GSC control, the q-component controls the DC-link voltage and the d-component controls the reactive power Positive current is considered from the grid to the converter
Fig 3 Turbine rotor, two-mass shaft and DFIG model
arrangements in PSCAD/EMTDC
Fig 2 Two converter models
Upper: FSM, lower: SAM
www.ietdl.org
Trang 4Thus the voltage equations in the d–q frame are expressed as
vg d= Rgscig d+Lgscdig d
dt − vsLgscig q+ eg d (14)
vg q= Rgscig q+ Lgsc
dig q
dt + vsLgscig d+ eg q (15)
As shown in Fig.7, the inner-loop control of the GSC consists
of d–q loops with similar structure The DC control loop
Fig 4 Model performances under fault conditions
Left: single-phase fault, right: three-phase fault
Fig 5 Decoupled control block diagrams of the RSC
a Inner-loop control system
b Outer-loop control system
Trang 5should be cascaded with q-current control loop, the small
signal model of which will be illustrated in the following
paragraphs
Aligning the grid voltage to the q-axis (vg_d= 0) and
applying power invariant principle to the DC and ac points
Pc=3
2vg qig q= Vdcidc g= Vdcidc r (16)
The dynamics equation of capacitor (Fig 2) can be
described as
CdVdc
dt = idc g+ idc r (17)
Combining (16) into (17) and eliminating term idc_g
dVdc
dt =idc r
C +3vg qig q
Taking partial derivatives of all variables
D ˙Vdc= 1
CDidc r+ 3
2CKVDig q+ 3
2CKGDvg q
− 3
KV=Vg q0
Vdc0 and KG=ig q0
Vdc0
For steady state
Vdc0idc r0= −1.5vg q0ig q0 (20)
The power change of the converter is then
DPc= Vdc0Didc r+ DVdcidc r0
= Vdc0Didc r− 1.5KVKGDVdc
(21)
Fig 6 Mathematical veri fication of the RSC control
Upper: outer-loop step response, lower: inner-loop step response
Fig 7 GSC control block diagrams
Upper: current control loops, lower: small signal model of DC-link control loop
www.ietdl.org
Trang 6Equation (19) is the small signal model of DC-link The
subscript‘0’ denotes a particular operating point From the
equation, DC-voltage dynamics are affected by several
components: the first two terms are the injected currents at
the DC-link, which will charge or discharge the capacitor;
the last two terms reflect the impact of grid voltage and
DC-voltage changes In the closed-loop control system,
[Fig 7and (19)], the first and third terms can be treated as
external disturbances that cause the change of DC-voltage,
while the second term is the controlled current obtained
from the negative feed-back loop, trying to return
DC-voltage to its operating point On the other hand, the
first and last terms constitute the converter power change,
as shown in (21) With KG being negative, the last term is
actually a positive feedback term that counteracts with the
controlling term, introducing an energy buffer effect
respectively
The plots of SAM and FSM show that the mean value of the FSM matches with the SAM PWM switching is presented in the current waveform but not apparent in the DC-voltage waveform because of the smoothing effect All the plots from MBs of DC-voltage control can match with the software simulations except the MB_full Since there is
no change in the converter (ΔPc= 0), the terms ΔVdc and
Δidc_r will counteract each other and must be considered together in this case, as shown in (21) The effect of
Δvg_qcan be ignored if the grid is assumed to be stiff Case B and C: The DC-voltage responses to a Te-step and grid voltage sag are shown in the lower two plots of Fig.9 In both cases, the DC reference value is set to be constant The disturbance signal idc_ris the main factor that causes the output DC-voltage change, which is illustrated in the upper plots It can be observed that the mean value of FSM is lower than the SAM because of the switching losses in the IGBTs The contributions of two other disturbance inputs are evaluated
as shown in the lower plots Three curves from MBs are shown, which are the MB with all the three disturbance terms, the one neglecting the term ΔVdc and the one neglecting the term Δvg_q In case B, the MB response will slightly deviate from the software simulation if ΔVdcis not considered, which plays a more important role thanΔvg_qin the DC-dynamics However, the term Δvg_q shows more
Fig 8 Mathematical veri fication of the GSC control
Upper: case A – DC-loop step response, lower: current-loop step response
Fig 9 DC-control disturbance factor analyses for different cases
Left: case B – Te steps from 1.2 to 1.3 pu, right: case C – Grid voltage drops to 80% of nominal value
Trang 7impact in case C, because of significant grid voltage
oscillations
In normal WT operating condition, case B is the most
common situation, where the reference electric torque or
power changes because of a wind speed change The grid
disturbance-term Δvg_q can be ignored Now the dynamic
stiffness (DS) [13] of DC-link system can be evaluated for
varying operating points This describes the resistance of
the system to a certain disturbance Considering only the
key disturbance input Δidc_r, resulting from the change of
input powerΔP
DS=DVDP
dc
=Vdc0Didc r
DVdc
= Vdc0Cs+ 1.5vg q0 KG+ KP
+1.5vg q0Ki s (22)
Fig 10 illustrates the DS when varying two parameters’
operating points, Vdc0and vg_q0, respectively, both of which
are changed from 0.7 to 1.3 times of their nominal values
The DS is only sensitive to Vdc0 for higher frequencies
because of the first term in (22) and it is sensitive to vg_q0
for middle and low frequencies because of the other two
terms As is shown in thefigure, the higher the DC-voltage
or the grid voltage is, the higher the system DS will be
Software simulations have been presented in Fig.11, where
the DS of the system has been evaluated for three different
Vdc0 and the electric torque is oscillating at 150 Hz with
0.2 pu amplitude
4 WT control
4.1 Controller development
For the WT control, the system measures the rotor speed and
uses it to generate references both to the pitch system of the
WT and to the DFIG control level (Fig 1) There are two different control algorithms for this control level At lower wind speeds, the pitch angle remains at the optimum value (0 degrees) and the optimum torque will be tracked according to a pre-defined curve [11]
Tgopt= Koptv2
At higher wind speeds, the pitch control is activated to remove excessive power extracted from wind The two control modes sometimes work together to regulate the WT
in the high wind region [4, 12, 14] The model presented here considers the case where the two controllers operate independently for their respective regions A non-linear transfer function is employed to generate the torque-speed look-up table
The pitch controller with full-non-linear plant model is illustrated as in Fig 12a The actuator introduces a lag between the actual pitch angle and the commanded pitch from the PI controller This controller is designed with a bandwidth of one-magnitude-order smaller than the electric torque control loop The actuator time constant is τ = 0.2 s
Jt is the total rotational inertia The wind speed vw acts as the external disturbance experienced by turbine rotor and the generator torque Tg is treated as an internal disturbance signal on the shaft system and it is fixed at the rated value for the higher wind speed region
The system model should be linearised in order to evaluate its control performance The linearisation process of different mass systems has been performed in [15] and this methodology is applied in [16] to design the PI controller Here the method is extended to lower wind speed region and will be justified by software simulations
At a particular operating pointωr0,β0, vw0, the aerodynamic torque can be expressed as
Ta= Ta vr0, u0, vw0
+ gDvr+ zDb + hDvw (24)
Fig 10 DS at different operating points
Fig 11 Software simulation of DC-link DS in response to Te oscillations
www.ietdl.org
Trang 8g =∂Ta
∂vr , z =∂Ta
∂b, h =∂v∂Twa The rotor dynamics can be described as
Jtdvr
For the higher wind speed region Tg= Ta0, therefore
D ˙vr = ADvr+ BDb + BdDvw (26)
where A =γ/Jt, B =ζ/Jt, C =η/Jt,
For the lower wind speed region
Tg= Tg0+ 2Koptvr0△vr (27) where Tg0= Ta0, eliminating the pitch controller
D ˙vr= (A − C)Dvr+ BdDvw (28) with C = 2Koptωr_0/J
These two linear models are depicted in Figs.12b and c For the WT-level control simulation, the induction machine should be held in torque control mode after the initial transient to interface with the aerodynamic model The system responses at two operating points (op) are shown in Fig.13, where
Op1: vw0= 15 m/s,ωr0= 1.2 pu,β = 10°
Op2: vw0= 9 m/s,ωr0= 0.78 pu,β = 0°
On the left plots, as wind rises, the pitch angle increases in order to maintain the rotor speed within the threshold (denoted
as‘Thr’) On the right plots, the pitch angle is maintained at 0 degrees despite of the wind speed change The rotor speed increases proportionally with the wind speed, to maintain the optimum tip-speed ratio The very low response is because
of the large system inertia In both cases, the results from
‘PCD’ and ‘MB’ match very well With the lumped-mass shaft model, no torsional oscillations are presented even though the pitch controller is relatively fast
a Pitch control with full-non-linear plant model
b Linearised control model for higher wind speed region
c Linearised control model for lower wind speed region
Fig 13 Mathematical veri fication of the WT-level control
left: 0.5 m/s v w step at op 1, right: 0.5 m/s v w step at op 2
Trang 94.2 Controller coordination
To illustrate the relation of pitch controller bandwidth region and the turbine torsional mode, the responses of a two-mass
WT model to a wind step is simulated for different pitch controller bandwidths Results are obtained by stepping the wind speed from 13 to 14 m/s, as shown in Fig.14
Significant mechanical oscillations are presented in the rotor speed and pitch angle, which are known as torsional oscillations The torsional frequency of the WT can be calculated from [11]
fT = 1 2p
Ksv0(Hturbine+ Hgenerator) 2HturbineHgenerator
= 2.55 Hz (29)
where Ks is the shaft stiffness (pu/el rad), ω0 is the synchronous electric speed (rad/s), H is the moment of inertia (s)
In Fig.14, lower pitch bandwidth can produce smoother but slower response and can result in longer over speed Torsional oscillations occur as the pitch bandwidth approaches 0.2 Hz, where the controller bandwidth begins to interfer the shaft natural frequency The responses will become unstable if a
Fig 14 Torsional oscillations observed for a two-mass drive-train
system at different controller bandwidths
Fig 15 Electrical oscillations induced by torsional modes – a comparison of both shaft models
Fig 16 Controller adjustment and coordination
www.ietdl.org
Trang 10be four to ten times faster than the outer-loop so that they
can be treated separately The speed of GSC DC-link control
fGSC_DCneeds to be no smaller than the RSC current control
loop fRSC_i in order achieve instant power transfer and
minimise the voltage transients on the capacitor Owing to
very large inertia of the WT rotor, the electrical controller
system will not excite the shaft torsional mode even when
their bandwidths are very close The controllers are adjusted
as in Fig 16, from which their constants can therefore be
obtained based on the MB diagrams
5 Conclusions
With future WTs moving towards offshore, very large turbines
will be installed making the reliability more critical
Comprehensive studies on the WT behaviours and control
systems are needed in order to improve their design and
operation This paper presents a complete DFIG WT model
and its overall control systems The interaction of the WT
control level with the DFIG control level has been presented
in the paper A FSM with IGBTs and a SAM are
implemented The former is suitable for detailed studies of
short-time transient behaviours while the latter is more
sensible for investigating mechanical responses over a longer
time scale Mathematical models of individual control-loops
are developed and tested The results are consistent with the
PSCAD/EMTDC simulations These are used to adjust the
controller bandwidth and damping in the software model DS
of DC-link to power changes is analysed for different
operating points Analysis shows that higher stiffness can be
achieved by increasing the grid voltage or the DC-link
voltage It can be observed that torsional oscillations may be
excited by a fast pitch controller This indicates the two-mass
shaft model is necessary for studying the controller
coordination especially when pitch control is involved What
is more, it can induce electrical oscillations and may further
impose stresses on power electronics or grid stability
6 Acknowledgment
The authors thank the Engineering and Physical Sciences
Research Council for supporting this work through grant
no EP/H018662/1– Supergen ‘Wind Energy Technologies’
7 Peña, R., Clare, J.C., Asher, G.M.: ‘Doubly fed induction generator using back-to-back PWM converters and its application to variable speed wind-energy generation ’, IEEE Proc Elecr Power Appl., 1996,
143, (3), pp 231–241
8 Slootweg, J.G., de Haan, S.W.H., Polinder, H., Kling, W.L.: ‘General model for representing variable speed wind turbines in power system dynamics simulation ’, IEEE Trans Power Syst., 2003, 18, (1),
pp 144 –151
9 Slootweg, J.G., Polinder, H., Kling, W.L.: ‘Dynamic modelling of a wind turbine with doubly fed induction generator ’ IEEE Proc on Power Engineering Society, Vancouver, BC, Canada, 2001
10 Todd, R.: ‘High power wind energy conversion systems’ EngD thesis, University of Manchester, 2006
11 Akhmatov, V.: ‘Analysis of dynamic behaviour of electrical power systems with large amount of wind power ’ PhD thesis, Ørsted DTU, Technical University of Denmark, 2003
12 Muyeen, S.M., Ali, M.H., Takahashi, R., et al.: ‘Comparative study on transient stability analysis of wind turbine generator system using different drive train models ’, IET Renew Power Gener., 2007, 1, (2),
pp 131 –141
13 Lorenz, R.D., Schmidt, P.B.: ‘Synchoronized motion control for process automation ’ Industry Applications Society Annual Meeting, October
1989, pp 1693 –1698
14 Bossany, E.A.: ‘The design of closed loop controllers for wind turbines’, Wind Energy, 2000, 3, (3), pp 149–163
15 Wright, A.D.: ‘Modern control design for flexible wind wurbines’ Report no TP-500-35816, NREL, 2004
16 Wright, A.D., Fingersh, L.J.: ‘Advanced control des1ign for wind turbines-part 1: Control design, implementation, and initial tests ’ Report no TP-500-42437, NREL, 2008
8 Appendix
Parameters that are used in the DFIG WT model
spring constant (K s ) 0.7 pu/el.rad generator self-damping 0.032 pu
stator voltage (L –L, RMS) 1 kV stator/rator turns ratio 1