a How much field current is required to make V T equal to 2300 V when the generator is running at no load?. c How much field current is required to make V T equal to 2300 V when the gene

Trang 1

( )

2 640 V 1280 V

Since the machine is ∆-connected, 1280 V L=Vφ= V

4-4 A three-phase Y-connected 50-Hz two-pole synchronous machine has a stator with 2000 turns of wire per

phase What rotor flux would be required to produce a terminal (line-to-line) voltage of 6 kV?

SOLUTION The phase voltage of this machine should be Vφ=V L/ 3=3464 V The induced voltage per phase in this machine (which is equal to Vφ at no-load conditions) is given by the equation

4-5 Modify the MATLAB program in Example 4-1 by swapping the currents flowing in any two phases What

happens to the resulting net magnetic field?

SOLUTION This modification is very simple—just swap the currents supplied to two of the three phases

% M-file: mag_field2.m

% M-file to calculate the net magetic field produced

% by a three-phase stator

% Set up the basic conditions

bmax = 1; % Normalize bmax to 1

freq = 60; % 60 Hz

w = 2*pi*freq; % angluar velocity (rad/s)

% First, generate the three component magnetic fields

t = 0:1/6000:1/60;

Baa = sin(w*t) * (cos(0) + j*sin(0));

Bbb = sin(w*t+2*pi/3) * (cos(2*pi/3) + j*sin(2*pi/3));

Bcc = sin(w*t-2*pi/3) * (cos(-2*pi/3) + j*sin(-2*pi/3));

% Calculate Bnet

Bnet = Baa + Bbb + Bcc;

% Calculate a circle representing the expected maximum

% value of Bnet

circle = 1.5 * (cos(w*t) + j*sin(w*t));

% Plot the magnitude and direction of the resulting magnetic

% fields Note that Baa is black, Bbb is blue, Bcc is

% magneta, and Bnet is red

% Plot the four magnetic fields

plot([0 real(Baa(ii))],[0 imag(Baa(ii))],'k','LineWidth',2);

plot([0 real(Bbb(ii))],[0 imag(Bbb(ii))],'b','LineWidth',2);

Trang 2

106

plot([0 real(Bcc(ii))],[0 imag(Bcc(ii))],'m','LineWidth',2);

plot([0 real(Bnet(ii))],[0 imag(Bnet(ii))],'r','LineWidth',3); axis square;

When this program executes, the net magnetic field rotates clockwise, instead of counterclockwise

4-6 If an ac machine has the rotor and stator magnetic fields shown in Figure P4-1, what is the direction of the

induced torque in the machine? Is the machine acting as a motor or generator?

SOLUTION Since τind=kBR×Bnet, the induced torque is clockwise, opposite the direction of motion The machine is acting as a generator

4-7 The flux density distribution over the surface of a two-pole stator of radius r and length l is given by

Trang 3

SOLUTION The total flux under a pole face is given by the equation

d

φ= BA

Under a pole face, the flux density B is always parallel to the vector dA, since the flux density is always

perpendicular to the surface of the rotor and stator in the air gap Therefore,

B dA

φ=

A differential area on the surface of a cylinder is given by the differential length along the cylinder (dl)

times the differential width around the radius of the cylinder (rdθ)

( )( )

dA= dl rdθ where r is the radius of the cylinder

Therefore, the flux under the pole face is

Trang 4

108

4-8 In the early days of ac motor development, machine designers had great difficulty controlling the core losses

(hysteresis and eddy currents) in machines They had not yet developed steels with low hysteresis, and were not making laminations as thin as the ones used today To help control these losses, early ac motors

in the USA were run from a 25 Hz ac power supply, while lighting systems were run from a separate 60 Hz

ac power supply

(a) Develop a table showing the speed of magnetic field rotation in ac machines of 2, 4, 6, 8, 10, 12, and

14 poles operating at 25 Hz What was the fastest rotational speed available to these early motors?

(b) For a given motor operating at a constant flux density B, how would the core losses of the motor

running at 25 Hz compare to the core losses of the motor running at 60 Hz?

(c) Why did the early engineers provide a separate 60 Hz power system for lighting?

P

=The resulting table is

The highest possible rotational speed was 1500 r/min

(b) Core losses scale according to the 1.5th power of the speed of rotation, so the ratio of the core losses

at 25 Hz to the core losses at 60 Hz (for a given machine) would be:

Trang 5

Chapter 5: Synchronous Generators

5-1 At a location in Europe, it is necessary to supply 300 kW of 60-Hz power The only power sources

available operate at 50 Hz It is decided to generate the power by means of a motor-generator set consisting of a synchronous motor driving a synchronous generator How many poles should each of the two machines have in order to convert 50-Hz power to 60-Hz power?

SOLUTION The speed of a synchronous machine is related to its frequency by the equation

120 e

m

f n

5-2 A 2300-V 1000-kVA 0.8-PF-lagging 60-Hz two-pole Y-connected synchronous generator has a

synchronous reactance of 1.1 Ω and an armature resistance of 0.15 Ω At 60 Hz, its friction and windage losses are 24 kW, and its core losses are 18 kW The field circuit has a dc voltage of 200 V, and the maximum I F is 10 A The resistance of the field circuit is adjustable over the range from 20 to 200 Ω The OCC of this generator is shown in Figure P5-1

(a) How much field current is required to make V T equal to 2300 V when the generator is running at no load?

(b) What is the internal generated voltage of this machine at rated conditions?

(c) How much field current is required to make V T equal to 2300 V when the generator is running at rated conditions?

(d) How much power and torque must the generator’s prime mover be capable of supplying?

(e) Construct a capability curve for this generator

Note: An electronic version of this open circuit characteristic can be found in file

p51_occ.dat, which can be used with MATLAB programs Column 1 contains field current in amps, and column 2 contains open-circuit terminal voltage in volts

Trang 6

From the OCC, the required field current is 5.9 A

(d) The input power to this generator is equal to the output power plus losses The rated output power is

Trang 7

core 18 kW

P =stray (assumed 0)

P =

IN OUT CU F&W core stray 870.4 kW

P =P +P +P +P +P =Therefore the prime mover must be capable of supplying 175 kW Since the generator is a two-pole 60 Hz machine, to must be turning at 3600 r/min The required torque is

r1

rad2s60

min1r/min3600

kW2.175

τ

m P

(e) The rotor current limit of the capability curve would be drawn from an origin of

2

3 3 1328 V

4810 kVAR1.1

S

V Q X

φ

ΩThe radius of the rotor current limit is

3 3 1328 V 1537 V

5567 kVA1.1

A E

S

V E D

X

φ

ΩThe stator current limit is a circle at the origin of radius

% Get points for stator current limit

theta = -95:1:95; % Angle in degrees

rad = theta * pi / 180; % Angle in radians

s_curve = S * ( cos(rad) + j*sin(rad) );

% Get points for rotor current limit

orig = j*Q;

theta = 75:1:105; % Angle in degrees

rad = theta * pi / 180; % Angle in radians

r_curve = orig + DE * ( cos(rad) + j*sin(rad) );

% Plot the capability diagram

Trang 8

112

plot( [-1500 1500],[0 0],'k');

plot( [0,0],[-1500 1500],'k');

% Set titles and axes

title ('\bfSynchronous Generator Capability Diagram');

The resulting capability diagram is shown below:

5-3 Assume that the field current of the generator in Problem 5-2 has been adjusted to a value of 4.5 A

(a) What will the terminal voltage of this generator be if it is connected to a ∆-connected load with an impedance of 20 30 ∠ ° Ω ?

(b) Sketch the phasor diagram of this generator

(c) What is the efficiency of the generator at these conditions?

(d) Now assume that another identical ∆-connected load is to be paralleled with the first one What happens to the phasor diagram for the generator?

(e) What is the new terminal voltage after the load has been added?

(f) What must be done to restore the terminal voltage to its original value?

SOLUTION

(a) If the field current is 4.5 A, the open-circuit terminal voltage will be about 2385 V, and the phase

voltage in the generator will be 2385 / 3=1377 V

The load is ∆-connected with three impedances of 20 30 ∠ ° Ω From the Y-∆ transform, this load is equivalent to a Y-connected load with three impedances of 6.667 30 ∠ ° Ω The resulting per-phase equivalent circuit is shown below:

Trang 9

+ -

A A

E I

Trang 10

A A

E I

(f) To restore the terminal voltage to its original value, increase the field current I F

5-4 Assume that the field current of the generator in Problem 5-2 is adjusted to achieve rated voltage (2300 V)

at full load conditions in each of the questions below

(a) What is the efficiency of the generator at rated load?

(b) What is the voltage regulation of the generator if it is loaded to rated kilovoltamperes with

Trang 11

(a) This generator is Y-connected, so I L=I A At rated conditions, the line and phase current in this generator is

P =

IN OUT CU F&W core stray 870.4 kW

P =P +P +P +P +P =OUT

Trang 12

(e) For this problem, we will assume that the terminal voltage is adjusted to 2300 V at no load

conditions, and see what happens to the voltage as load increases at 0.8 lagging, unity, and 0.8 leading power factors Note that the maximum current will be 251 A in any case A phasor diagram representing the situation at lagging power factor is shown below:

Trang 13

By the Pythagorean Theorem,

Vφ = EX I

The MATLAB program is shown below takes advantage of this fact

% M-file: prob5_4e.m

% M-file to calculate and plot the terminal voltage

% of a synchronous generator as a function of load

% for power factors of 0.8 lagging, 1.0, and 0.8 leading

% Define values for this generator

EA = 1328; % Internal gen voltage

I = 0:2.51:251; % Current values (A)

R = 0.15; % R (ohms)

X = 1.10; % XS (ohms)

% Calculate the voltage for the lagging PF case

VP_lag = sqrt( EA^2 - (X.*I.*0.8 - R.*I.*0.6).^2 )

- R.*I.*0.8 - X.*I.*0.6;

VT_lag = VP_lag * sqrt(3);

% Calculate the voltage for the leading PF case

VP_lead = sqrt( EA^2 - (X.*I.*0.8 + R.*I.*0.6).^2 )

- R.*I.*0.8 + X.*I.*0.6;

VT_lead = VP_lead * sqrt(3);

% Calculate the voltage for the unity PF case

VP_unity = sqrt( EA^2 - (X.*I).^2 );

title ('\bfTerminal Voltage Versus Load');

xlabel ('\bfLoad (A)');

ylabel ('\bfTerminal Voltage (V)');

legend('0.8 PF lagging','1.0 PF','0.8 PF leading');

Trang 14

118

5-5 Assume that the field current of the generator in Problem 5-2 has been adjusted so that it supplies rated

voltage when loaded with rated current at unity power factor (You may ignore the effects of R A when answering these questions.)

(a) What is the torque angle δ of the generator when supplying rated current at unity power factor?

(b) When this generator is running at full load with unity power factor, how close is it to the static stability

limit of the machine?

Thus the torque angle δ = 11.4°

(b) The static stability limit occurs at δ = 90° This generator is a very long way from that limit If we ignore the internal resistance of the generator, the output power will be given by

3sin

A S

V E P X

=

and the output power is proportional to sinδ Since sin 11.4° =0.198, and sin 90° =1.00, the static stability limit is about 5 times the current output power of the generator

5-6 A 480-V 400-kVA 0.85-PF-lagging 50-Hz four-pole ∆-connected generator is driven by a 500-hp diesel

engine and is used as a standby or emergency generator This machine can also be paralleled with the normal power supply (a very large power system) if desired

(a) What are the conditions required for paralleling the emergency generator with the existing power

system? What is the generator’s rate of shaft rotation after paralleling occurs?

Trang 15

(b) If the generator is connected to the power system and is initially floating on the line, sketch the resulting

magnetic fields and phasor diagram

(c) The governor setting on the diesel is now increased Show both by means of house diagrams and by

means of phasor diagrams what happens to the generator How much reactive power does the generator supply now?

(d) With the diesel generator now supplying real power to the power system, what happens to the generator

as its field current is increased and decreased? Show this behavior both with phasor diagrams and with house diagrams

SOLUTION

(a) To parallel this generator to the large power system, the required conditions are:

1 The generator must have the same voltage as the power system

2 The phase sequence of the oncoming generator must be the same as the phase sequence of the

power system

3 The frequency of the oncoming generator should be slightly higher than the frequency of the

running system

4 The circuit breaker connecting the two systems together should be shut when the above conditions

are met and the generator is in phase with the power system

After paralleling, the generator’s shaft will be rotating at

120 50 Hz120

1500 r/min4

e m

f n

(c) When the governor setpoints on the generator are increased, the emergency generator begins to supply

more power to the loads, as shown below:

(d) With the generator now supplying power to the system, an increase in field current increases the

reactive power supplied to the loads, and a decrease in field current decreases the reactive power supplied

to the loads

Trang 16

V T

5-7 A 13.8-kV 10-MVA 0.8-PF-lagging 60-Hz two-pole Y-connected steam-turbine generator has a

synchronous reactance of 12 Ω per phase and an armature resistance of 1.5 Ω per phase This generator is operating in parallel with a large power system (infinite bus)

(a) What is the magnitude of E A at rated conditions?

(b) What is the torque angle of the generator at rated conditions?

(c) If the field current is constant, what is the maximum power possible out of this generator? How much

reserve power or torque does this generator have at full load?

(d) At the absolute maximum power possible, how much reactive power will this generator be supplying or

consuming? Sketch the corresponding phasor diagram (Assume I F is still unchanged.)

SOLUTION

(a) The phase voltage of this generator at rated conditions is

13,800 V

7967 V3

Trang 17

The magnitude of E A is 12,040 V

(b) The torque angle of the generator at rated conditions is δ = 17.6°

(c) Ignoring R A , the maximum output power of the generator is given by

V E P

X

φ

ΩThe power at maximum load is 8 MW, so the maximum output power is three times the full load output power

(d) The phasor diagram at these conditions is shown below:

A A

The generator is actually consuming reactive power at this time

5-8 A 480-V, 100-kW, two-pole, three-phase, 60-Hz synchronous generator’s prime mover has a no-load speed

of 3630 r/min and a full-load speed of 3570 r/min It is operating in parallel with a 480-V, 75-kW, pole, 60-Hz synchronous generator whose prime mover has a no-load speed of 1800 r/min and a full-load speed of 1785 r/min The loads supplied by the two generators consist of 100 kW at 0.85 PF lagging

four-(a) Calculate the speed droops of generator 1 and generator 2

(b) Find the operating frequency of the power system

(c) Find the power being supplied by each of the generators in this system

(d) If V T is 460 V, what must the generator’s operators do to correct for the low terminal voltage?

SOLUTION The no-load frequency of generator 1 corresponds to a frequency of