CHAPTER 19 Serial Communications All of the manufacturers provide units designed for digital serial communica-tions.. For this reason, each of the manufacturers provides serial data comm
Trang 1CHAPTER 19 Serial Communications
All of the manufacturers provide units designed for digital serial communica-tions The great majority of applications will be found to require the speed and efficiency of serial data transfer For this reason, each of the manufacturers provides serial data communications as an integral part of its base system Each of the standard turnkey systems incorporate RS-485 multidrop communications designed for direct computer interface This fact alone should be enough to convince those still wed to
4 to 20 mA interfaces of the inefficiencies of such an approach If it were cheaper
or easier to follow that path, at least some of the manufacturers would be doing so
A INTERFACE
All of the units provide a standard RS-485 interface This allows for multiple units to be connected to a single-twisted shielded-pair cable The number of counters that can be connected to the system depends on the number of instrument addresses available, and the limitations of the data collection software All of the manufacturers allow for up to 32 units More units may be added to each system, but will have to
be placed on a separate RS-485 network
ARTI, Chemtrac, Met One, and IBR provide RS-232 access to the particle counter This allows individual parameters to be set without connecting to the
RS-485 network Only one unit may be connected at a time on an RS-232 network Chemtrac provides a separate connector, while Met One and IBR require moving a couple of jumpers to switch from RS-485 to RS-232
RS-485 communications can be conducted over two- or four-wire cabling Two-wire communications involves transmitting and receiving data over the same pair
of wires, while the four-wire arrangement keeps transmission and receiving lines separate There is no difference in speed, as the units do not transmit and receive at the same time ARTI, Met One, and Chemtrac are designed to operate on a two-wire arrangement, although the Chemtrac unit may also be operated in four-two-wire L1306/frame/pt03 Page 163 Friday, June 23, 2000 2:16 PM
© 2001 by CRC Press LLC
Trang 2164 A PRACTICAL GUIDE TO PARTICLE COUNTING
mode by removing jumpers on the printed circuit board IBR requires a four-wire connection The only difference in these arrangements is the slightly higher cost of four-conductor cabling
B PROTOCOLS
Each of the available units communicates data by way of a unique protocol When a standard turnkey system is installed, the protocol is not important from the user’s standpoint Only when the particle counters are to be tied into SCADA or a data collection system does the protocol come into play
Only ARTI and Chemtrac use protocols developed to simplify interface with third-party equipment ARTI has implemented the Modbus RTU protocol, which is supported by almost all of the available SCADA software packages Chemtrac uses
a modified version of the optomux protocol While the standard optomux protocol
is supported by many SCADA packages, not all of the commands are included The standard optomux protocol provides for minimums, maximums, and averages to be transmitted by the field hardware, whereas the SCADA software programs perform these tasks themselves Often these commands are left out of the driver packages that come standard with the SCADA software Unfortunately, the particle counters make use of these commands for other data functions, and so the drivers are not fully compatible However, since many of the commands are functional, the existing drivers can be modified to support these commands, as opposed to being written from scratch
Certainly at some point, other units will be designed to communicate via more widely accepted protocols Most of these will be built around popular programmable logic controller (PLC) protocols such as Modbus, since the amount of data commu-nicated is rather large, and fits the format of the PLC
The individual protocols are too complex to provide within this book Met One includes detailed information on protocols in their standard equipment manuals The other manufacturers should be able to provide this information on request L1306/frame/pt03 Page 164 Friday, June 23, 2000 2:16 PM