Tiêu đề IEC 61347-2-6:2000 - Part 2-6: Particular requirements for d.c. supplied electronic ballasts for aircraft lighting
Trường học International Electrotechnical Commission
Chuyên ngành Electrotechnical standards
Thể loại quy chuẩn quốc tế
Năm xuất bản 2000
Định dạng
Số trang 36
Dung lượng 308,24 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 7.1 Marquages obligatoires (14)
  • 7.2 Informations à fournir, le cas échéant (14)
  • 7.1 Mandatory marking (15)
  • 7.2 Information to be provided, if applicable (15)

Nội dung

Microsoft Word 1347 2 6f ed1 doc NORME INTERNATIONALE CEI IEC INTERNATIONAL STANDARD 61347 2 6 Première édition First edition 2000 10 Appareillages de lampes – Partie 2 6 Prescriptions particulières p[.]

Marquages obligatoires

Les ballasts doivent être marqués d’une manière claire et durable, conformément aux prescriptions de 7.2 de la CEI 61347-1, avec les marquages obligatoires suivants:

– points a), b), e), f), k) et l) de 7.1 de la CEI 61347-1, conjointement avec

– indication du type et du courant nominal du coupe-circuit, si nécessaire.

Informations à fournir, le cas échéant

In addition to the mandatory markings mentioned above, the following information, if applicable, must be provided on the ballast or included in the manufacturer's catalog or an equivalent document.

– points h), i), j) et n) de 7.1 de la CEI 61347-1, conjointement avec

– une indication précisant si le ballast est protégé contre l’inversion de polarité de l’alimentation;

– une indication précisant que le ballast est prévu seulement pour usage dans les avions.

8 Protection contre le contact accidentel avec les parties actives

Les prescriptions de l’article 10 de la CEI 61347-1 s'appliquent.

Les prescriptions de l’article 8 de la CEI 61347-1 s'appliquent.

10 Dispositions en vue de la mise à la terre

Les prescriptions de l’article 9 de la CEI 61347-1 s'appliquent.

Les prescriptions de l’article 11 de la CEI 61347-1 s'appliquent, à l’exception de la prescription de valeur de résistance d’isolement de 7 MΩ pour l’isolation renforcée.

Les prescriptions de l’article 12 de la CEI 61347-1 s'appliquent.

13 Essai d'endurance thermique des enroulements

Les prescriptions de l’article 13 de la CEI 61347-1 ne s'appliquent pas.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Mandatory marking

Ballasts shall be clearly and durably marked, in accordance with the requirements of 7.2 of

IEC 61347-1, with the following mandatory markings:

– items a), b), e), f), k) and l) of 7.1 of IEC 61347-1, together with

– indication of type and current rating of the fuse, if applicable.

Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall be given either on the ballast, or be made available in the manufacturer’s catalogue or similar:

– items h), i), j) and n) of 7.1 of IEC 61347-1, together with

– indication whether the ballast is proof against supply voltage polarity;

– indication that the ballast is for aircraft use only.

8 Protection against accidental contact with live parts

The requirements of clause 10 of IEC 61347-1 apply.

The requirements of clause 8 of IEC 61347-1 apply.

The requirements of clause 9 of IEC 61347-1 apply.

The requirements of clause 11 of IEC 61347-1 apply, with the exception of the 7 MΩ insulation resistance requirement for reinforced insulation.

The requirements of clause 12 of IEC 61347-1 apply.

13 Thermal endurance test for windings

The requirements of clause 13 of IEC 61347-1 are not applicable.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Le ballast doit supporter sans défaillance toute impulsion de tension provenant de la source de tension.

Compliance is verified through the following test, which is divided into two applicable sections: a) Long-duration voltage impulses that are generally not significantly weakened by traditional inductance/capacitance input filters.

When operating the ballast at the maximum voltage of its nominal range and at an ambient temperature of 25 °C, in conjunction with an appropriate number of lamps, the ballast must withstand the specified voltage spikes listed in Table 1, which are superimposed on the supply voltage and share the same polarity.

Tableau 1 – Impulsions de tension de longue durée

Impulsion de tension Nombre d’impulsions Valeur de crête

Largeur de l'impulsion à mi-hauteur ms

3 Egale à la tension de référence

A circuit designed for generating and applying long-duration pulses is illustrated in Figure G.2 of IEC 61347-1 Additionally, short-duration voltage pulses can typically be attenuated by conventional input filters that utilize inductance and capacitance.

When operating the ballast at the maximum voltage of its nominal range and at an ambient temperature of 25 °C, in conjunction with an appropriate number of lamps, the ballast must withstand the specified voltage spikes listed in Table 2, which are superimposed on the supply voltage and share the same polarity.

Tableau 2 – Impulsions de tension de courte durộe (10 às ou moins)

3 Egale à huit fois la tension de référence

Adapted circuits for measuring pulse energy and for generating and applying short-duration pulses are illustrated in Figure G.1 of IEC 61347-1 and Figure 1 of this standard.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

The ballast shall withstand without failure any pulses originating from the power source.

Compliance is evaluated through a two-part test, both sections of which are relevant The first section involves long-duration pulse voltages that are typically not significantly reduced by standard inductor/capacitor input filters.

When operating at the maximum rated voltage and with the correct number of lamps in an ambient temperature of 25 °C, the ballast must endure the specified number of pulse voltages, as outlined in table 1, superimposed with the same polarity on the supply voltage, without experiencing any failures.

Table 1 – Long-duration pulse voltages

Pulse voltage Number of voltage pulses Peak value

Pulse width at half-peak ms

A circuit designed for generating and applying long-duration pulses is illustrated in figure G.2 of IEC 61347-1 Additionally, short-duration pulse voltages are typically subject to attenuation by standard inductor/capacitor input filters.

At the maximum rated voltage and with the correct number of lamps in an ambient temperature of 25 °C, the ballast must endure the specified number of pulse voltages, as outlined in table 2, applied with the same polarity on the supply voltage without experiencing any failures.

Table 2 – Short-duration pulse voltages (10 às or less)

Period between Number of voltage pulses Peak value

Pulse energy mJ each pulse s

NOTE Suitable circuits for measuring pulse power and for producing and applying short-duration pulses are shown in figure G.1 of IEC 61347-1 and in figure 1 of this standard.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Les ballasts ne doivent pas devenir dangereux lorsqu'ils fonctionnent en conditions anormales à la tension maximale de leur plage nominale de tensions.

Under abnormal conditions, a functioning regime is characterized by one or more of the following scenarios: a) the lamp or one of the lamps is not inserted; b) the lamp fails to ignite due to a broken cathode; c) the lamp does not ignite even though the cathode circuits are intact (lamp deactivated); d) the lamp operates, but one of its cathodes is deactivated or broken (rectifying effect).

La conformité est vérifiée par l'essai suivant.

Each of the abnormal conditions mentioned must be applied, with the ballast operating for 1 hour according to the manufacturer's instructions (including cooling elements if specified), at the upper limit of the temperature range for which the ballast was designed.

In the experiment simulating operation with a deactivated lamp, a resistor must replace each cathode The resistance value should be derived from the nominal operating current of the lamp, as specified in the appropriate lamp characteristic sheets of IEC 60081 and IEC 60901, and incorporated into the following equation: × Ω.

I n est le courant nominal de fonctionnement de la lampe.

Pour les lampes ne figurant pas dans la CEI 60081 et la CEI 60901, les valeurs déclarées par le fabricant doivent être utilisées.

To test the rectifier effect on a DC-powered electronic ballast, the circuit shown in Figure 2 should be utilized The lamp must be connected to the midpoint of the appropriate equivalent resistances The rectifier's polarity should be set to create the most unfavorable operating conditions If necessary, the lamp should be ignited using a suitable ignition device Additionally, polarity inversion should be considered.

Lorsqu'un ballast est déclaré comme pouvant supporter l'inversion de polarité de la tension d'alimentation, il doit être essayé comme suit.

Ballasts designed to operate on voltage sources that may be subjected to transients and surges must be powered for 1 hour under a reverse polarity voltage equal to the maximum value of their rated voltage range, using one or more suitable lamps.

– Durant cette période, le ballast doit supporter sans défaillance un nombre d'impulsions de tension superposées à la tension d'alimentation et de même polarité, telles qu'elles sont spécifiées au tableau 2.

Au cours et à la fin des essais spécifiés aux points a) à e), le ballast ne doit pas présenter de défauts compromettant la sécurité ni émettre de fumée.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

The ballast shall not impair safety when operated under abnormal conditions at the maximum value of the rated voltage range.

Abnormal working conditions occur when certain issues arise with lamps, including situations where a lamp is not inserted, a lamp fails to start due to a broken cathode, a lamp remains inactive despite intact cathode circuits, or a lamp operates while one of its cathodes is deactivated or damaged, leading to a rectifying effect.

Compliance is checked by the following test.

Ngày đăng: 17/04/2023, 11:42