1. Trang chủ
  2. » Luận Văn - Báo Cáo

Iec 60331-3-2009.Pdf

54 1 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Tests for electric cables under fire conditions – Circuit integrity – Part 3: Test method for fire with shock at a temperature of at least 830 °C for cables of rated voltage up to and including 0,6/1,0 kV tested in a metal enclosure
Trường học International Electrotechnical Commission
Chuyên ngành Electrical Safety Standards
Thể loại Standards Document
Năm xuất bản 2009
Thành phố Geneva
Định dạng
Số trang 54
Dung lượng 1,16 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 5.1 Test equipment (10)
  • 5.2 Metal enclosure (15)
    • 5.2.1 Material and dimensions (15)
    • 5.2.2 Metal enclosure selection (15)
  • 5.3 Test ladder and mounting (15)
  • 5.4 Source of heat (16)
    • 5.4.1 Burner (16)
    • 5.4.2 Flow meters and flow rates (17)
    • 5.4.3 Verification (18)
  • 5.5 Shock producing device (18)
  • 5.6 Positioning of source of heat (19)
  • 5.7 Continuity checking arrangements (19)
  • 5.8 Fuses (19)
  • 6.1 Test specimen preparation (19)
  • 6.2 Test specimen mounting (20)
  • 7.1 Test equipment and arrangement (20)
  • 7.2 Electrical connections (20)
  • 7.3 Flame and shock application (22)
  • 7.4 Electrification (22)
  • 8.1 Flame application time (23)
  • 8.2 Acceptance criteria (23)

Nội dung

IEC 60331 3 Edition 1 0 2009 05 INTERNATIONAL STANDARD NORME INTERNATIONALE Tests for electric cables under fire conditions – Circuit integrity – Part 3 Test method for fire with shock at a temperatur[.]

Test equipment

The test equipment includes a metal enclosure made from a straight stainless steel tube with a circular cross-section, through which the test specimens are drawn This enclosure is mounted on a test ladder, consisting of a steel framework securely fastened to a rigid support The setup features a heat source in the form of a horizontally mounted ribbon burner, along with a shock-producing device Additionally, a test wall equipped with thermocouples is used to verify the heat source, while a continuity checking arrangement and fuses ensure safety and proper function during testing.

A general arrangement of the test equipment is shown in Figures 1, 2, 3 and 4

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

1 shock producing device 4 ribbon gas burner

2 steel ladder 5 fixed vertical element

Figure 1 – Schematic diagram of test configuration

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Dimensions in millimetres (dimensions are approximate)

Figure 2 – Recommended method of mounting the metal enclosure to the test ladder

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

1 entry for air 4 horizontal steel test ladder

2 rubber bush 5 entry for propane gas

Figure 3 – Plan view of fire test equipment

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

1 shock producing device H horizontal distance of metal enclosure centre line from burner face

2 steel test ladder V vertical distance of metal enclosure centre line from centre line of burner

4 centre line of burner face

Figure 4 – End elevation of fire test equipment (not to scale)

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Metal enclosure

Material and dimensions

The enclosure is made from a straight stainless steel tube with a circular cross-section, manufactured to be free of surface irregularities It measures (1,300 ± 50) mm in length and adheres to the specific dimensions outlined in Table 1.

NOTE AISI grades 304 and 316 have been found to be suitable materials for the enclosure

Metal enclosure selection

The particular metal enclosure shall be selected using the criteria given in 6.2.

Test ladder and mounting

The test ladder shall consist of a steel framework as shown in Figure 1 The vertical elements of the ladder shall be fixed at (400 ± 20) mm spacing The test ladder shall be

(1 200 ± 100) mm long and (600 ± 50) mm high, and the total mass of the test ladder shall be

(18 ± 1) kg Ballast, if required, shall be placed on the steel supports

Angle iron measuring approximately 45 mm in width and 6 mm in thickness, with appropriately cut slots for securing bolts or saddles, is an ideal material for ladder construction.

The metal enclosure shall be rigidly mounted centrally on the test ladder, as shown in Figure 2

Suitably sized saddles or U-bolts are recommended for fixing on the vertical elements

NOTE 2 It is important that the fixings are tight enough to prevent vertical movement of the metal enclosure whilst allowing longitudinal expansion of the metal enclosure

Each horizontal element must have a mounting hole located within 200 mm from each end, with the exact position and diameter determined by the specific supporting bush and framework used The test ladder should be secured to a rigid support using four bonded rubber bushes with a hardness of 50–60 Shore A, placed between the ladder's horizontal steel elements and the support framework, as illustrated in Figures 1 and 3, to allow movement under impact.

NOTE 3 A typical rubber bush, which has been found to be suitable, is shown in Figure 5

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Figure 5 – Typical rubber bush for supporting the test ladder

Source of heat

Burner

The heat source should be a ribbon-type propane gas burner with a nominal burner face length of 500 mm and a Venturi mixer, with a recommended centre-feed design The burner face width must be 10 mm, featuring three staggered rows of drilled holes approximately 1.32 mm in diameter, spaced 3.2 mm apart, as illustrated in Figure 6 Additionally, small pilot holes milled on each side of the burner plate are allowed to maintain the flame.

Guidance on the choice of a recommended burner system is given in Annex B

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

NOTE Round holes, 1,32 mm in diameter, on centres 3,2 mm from one another, staggered in three rows and centred on the face of the burner Nominal burner face length 500 mm

Flow meters and flow rates

Mass flow meters/controllers should be used as the means of controlling accurately the input flow rates of fuel and air to the burner

NOTE 1 Rotameter type flow meters may be used as an alternative, but are not recommended Guidance on their use, and the application of appropriate correction factors is given in Annex C of IEC 60331-11:1999

NOTE 2 Figure 7 shows an example of a rotameter type system

For the purposes of this test, the air shall have a dew point not higher than 0 °C

The flow rates used for the test shall be as follows:

– air: (160 ± 8) l/min at reference conditions (1 bar and 20 °C) or (3 267 ± 163) mg/s ;

– propane: (10,0 ± 0,4) l/min at reference conditions (1 bar and 20 °C) or (319 ± 13) mg/s

NOTE 3 The purity of the propane is not defined Industrial grades that contain impurities are allowed, provided that the calibration requirements are achieved

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

6 screw valve (6 A = alternative position) 14 compressed air cylinder

7 pilot feed 15 screw valve on pilot feed

Figure 7 – Schematic diagram of an example of a burner control system using rotameters

Verification

The burner and control system shall be subject to verification following the procedure given in

Shock producing device

The shock-producing device is made from a mild steel round bar measuring 25 ± 0.1 mm in diameter and 600 ± 5 mm in length It is freely pivoted on an axis parallel to the test ladder, positioned in the same horizontal plane and located 200 ± 5 mm from the ladder's upper edge The pivot axis divides the bar into two unequal lengths, with the longer segment specified accordingly.

The ladder must withstand an impact from a bar measuring (400 ± 5) mm in length, which is dropped from an angle of (60 ± 5)° to the horizontal The bar falls under its own weight and strikes the upper edge of the ladder precisely at its midpoint, as illustrated in Figures 1 and 4.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Positioning of source of heat

The burner face must be positioned in the test chamber at a minimum height of 200 mm above the chamber floor or any solid mounting block, and it should be placed at least 500 mm away from any chamber wall to ensure proper testing conditions.

The burner must be positioned centrally relative to the metal enclosure, maintaining a horizontal distance of (H ± 2) mm from the burner face to the enclosure's center and a vertical distance of (V ± 2) mm from the burner centerline to the enclosure's center, as illustrated in Figure 4.

The precise burner location for cable testing must be identified by following the verification procedure outlined in Annex A, which specifies how to determine the values of H and V to be used.

NOTE The burner should be rigidly fixed to the framework during testing so as to prevent movement relative to the metal enclosure.

Continuity checking arrangements

During the test, a continuity check current is passed through all conductors of the test specimen(s) using a three-phase star-connected or single-phase transformer with sufficient capacity This setup ensures the test voltage is maintained up to the maximum allowable leakage current, guaranteeing accurate and reliable testing results.

NOTE 1 Due note should be taken of the fuse characteristics when determining the power rating of the transformer

This current shall be achieved by connecting, at the other end of the sample, a suitable load and an indicating device (e.g lamp) to each conductor, or group of conductors

NOTE 2 A current of 0,25 A at the test voltage, through each conductor or group of conductors, has been found to be suitable.

Fuses

Fuses used in the test procedure in Clause 7 shall be of type DII, complying with IEC 60269-3

Alternatively, a circuit-breaker with equivalent characteristics may be used

Where a circuit-breaker is used, its equivalent characteristics shall be demonstrated by reference to the characteristic curve shown in IEC 60269-3

The test method using fuses shall be the reference method in the case of dispute

Test specimen preparation

For testing, a cable sample must be at least 15.3 meters long for single-core cables or 5.1 meters long for multi-core cables The test specimen should consist of either a single piece of multi-core cable or three pieces of single-core cable, each no less than 1,700 mm in length, with approximately 100 mm of sheath or outer covering removed from both ends.

Each end of the test specimen must have conductors properly prepared for electrical connections After placing the conductors into the designated metal enclosure, the exposed conductors should be spread apart to prevent any contact between them, ensuring safety and reliability.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Test specimen mounting

The test specimen must be placed inside the suitable metal enclosure, ensuring it rests against the enclosure wall The enclosure size should be chosen based on the cable diameter, following the guidelines in Table 2 for multicore sheathed cables (including multipair and multi-triple cables) or Table 3 for single core sheathed or unsheathed cables.

Metal enclosure outer diameter mm

Table 3 – Single core unsheathed or sheathed cable

Metal enclosure outer diameter mm

The test specimen(s) shall be positioned in the metal enclosure such that it extends outside the enclosure by greater than 100 mm at each end

Test equipment and arrangement

The test procedure defined in Clause 7 shall be carried out using the apparatus detailed in

Draw the test specimen(s) into the metal enclosure and adjust the burner to the correct position relative to the enclosure in accordance with 5.6.

Electrical connections

At the transformer end of the test specimen, the neutral conductor and any protective conductors must be earthed, along with all metal screens, drain wires, or metallic layers, which should be interconnected and grounded The transformer(s) should be connected to the conductors, excluding those specifically designated as neutral or protective conductors, as illustrated in the circuit diagram in Figure 8 If a metallic sheath, armour, or screen functions as a neutral or protective conductor, it must be connected accordingly, following the same guidelines shown in Figure 8 Additionally, the metal enclosure must be properly earthed to ensure safety and compliance.

For single-, twin-, or three-phase conductor cables, each phase conductor must be connected to a separate phase of the transformer output, protected by a 2 A fuse or circuit breaker with equivalent characteristics In cases where the test specimen consists of three single-core cables, each single-core cable should be treated as an individual phase conductor This ensures proper phase separation and safety during testing.

For multicore cables with four or more conductors, excluding neutral or protective conductors, the conductors must be divided into three approximately equal groups It is essential to arrange the conductors so that adjacent ones are, as much as possible, placed in different groups to ensure proper organization and functionality.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

For multipair cables, conductors must be split into two equal groups, with the a-core of each pair connected to one phase and the b-core connected to another phase, such as L1 and L2 Additionally, quads should be treated as two separate pairs to ensure proper phase connection and functionality.

For multi-triple cables, conductors must be divided into three equal groups, with each a-core connected to one transformer phase, each b-core to a second phase, and each c-core to the third phase (L1, L2, and L3) This ensures proper phase distribution and optimal transformer performance.

Connect the conductors of each group in series and connect each group to a separate phase of the transformer output Ensure that each phase is protected with a 2 A fuse or a circuit breaker with equivalent characteristics to maintain safety and proper operation.

The test procedure typically involves connecting the neutral conductor to earth; however, this may not be suitable for cables designed for systems without an earthed neutral If specified by the cable standard, the neutral conductor can be tested as a phase conductor When a metallic sheath, armour, or screen serves as the neutral conductor, it must always be connected to earth Any deviations from the standard testing methodology should be clearly documented in the test report.

NOTE 2 For cable constructions not specifically identified above, the test voltage should be applied, as far as is practicable, to ensure that adjacent conductors are connected to different phases

When testing control cables with a three-phase transformer, it may not always be possible to apply the rated test voltage simultaneously between conductors and from conductor to earth In such cases, either the test voltage between conductors or the test voltage from conductor to earth must be equal to the rated voltage, ensuring that both test voltages are at least equal to or higher than the rated voltage.

At the end of the sample, remote from the transformer:

– connect each phase conductor, or group of conductors, to one terminal of the load and indicating device (as described in 5.7), the other terminal being earthed;

– connect the neutral conductor and any protective conductor to one terminal of the load and indicating device (as described in 5.7), the other terminal being connected to L1 (or L2 or

L3) at the transformer end (see Figure 8)

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

PE protective conductor (if present)

1 transformer 5 load and indicating device

3 L1 or L2 or L3 7 metal screen (if present)

Flame and shock application

Ignite the burner and adjust the propane and air flow rates to those obtained during the verification procedure (see Annex A)

Immediately after igniting the burner, activate the shock-producing device and start the test duration timer The device must impact the ladder at intervals of 5 minutes ± 10 seconds, beginning 5 minutes ± 10 seconds after activation After each impact, the impacting bar should be lifted from the ladder within 20 seconds.

Electrification

Start the test duration timer and immediately switch on the electricity supply, adjusting the voltage to the sample's rated voltage, with a minimum of 100 V a.c Ensure that the test voltage between conductors matches the rated voltage between conductors, and the test voltage from conductor to earth equals the rated voltage from conductor to earth.

The test shall continue for the flame application time given in 8.1, after which the flame shall be extinguished

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Flame application time

The flame application time must adhere to the specifications outlined in the relevant cable standard If no such standard exists, a flame and impact application time of 30, 60, 90, or 120 minutes should be selected to ensure proper compliance and safety.

Acceptance criteria

With reference to the test procedure given in Clause 7, the cable possesses the characteristics for providing circuit integrity so long as during the course of the test

– the voltage is maintained, i.e no fuse fails or circuit-breaker is interrupted,

– a conductor does not rupture, i.e the lamp is not extinguished

In case of a failure according to the relevant standard's requirements, two additional test specimens from the same cable sample must be tested If both specimens meet the compliance criteria, the overall test will be considered successful.

The test report must include essential details such as the standard number, a comprehensive description of the cable tested, and the manufacturer's name It should specify the number of test pieces in the specimen, the dimensions of the metal enclosure, and the test voltage used Additionally, the report must reference the actual performance requirements applied, including the relevant clause or cable standard, and document the flame application time Any deviations from the specified test procedure should be noted, along with the chamber volume and temperature at the start of the test.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Verification procedure for the source of heat

The flame temperature shall be measured using two 1,5 mm mineral insulated, stainless steel sheathed thermocouples type K (see IEC 60584-1), mounted on the test wall as shown in

The thermocouple tips must be positioned precisely (20.0 ± 1.0) mm in front of the test wall, with their horizontal line located (100 ± 10) mm above the bottom of the wall The test wall should be constructed from a heat-resistant, non-combustible, and non-metallic board to ensure accurate and reliable temperature measurements.

(900 ± 100) mm long, (300 ± 50) mm high and (10 ± 2) mm thick

Position the burner 100 mm to 120 mm horizontally from the thermocouple (H) and 40 mm to

60 mm vertically below the centre line of the thermocouples (V) as shown in Figure A.1

H horizontal distance of thermocouple tip from burner face

V vertical distance of thermocouple tip from centre line of burner

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Ignite the burner and adjust the gas and air supplies to those given in 5.4.2

Monitor the temperature as recorded by the thermocouples over a period of 10 min to ensure conditions are stable

The verification procedure is deemed satisfactory if the mean of the averaged readings from each of the two thermocouples over a 10-minute period falls within the range of 830 ± 40 °C, and the difference between these averaged readings does not exceed 40 °C.

At least one measurement shall be made every 30 s in order to obtain the average

It is recommended to use a recorder with averaging capabilities to obtain the average thermocouple reading over a period, as this helps reduce variability caused by point measurements The exact method for calculating the average thermocouple reading is not specified, but employing averaging equipment ensures more accurate and stable temperature data.

If the verification is not successful, the flow rates shall be altered within the tolerances given in

5.4.2 and a further verification carried out

If the verification of Clause A.3 is not successful, the distances (H and V) between burner and thermocouples shall be altered (within the tolerance given in Clause A.1) and a further verification carried out

If the burner system fails to achieve successful verification within the specified tolerances, it will be deemed incapable of providing the required heat source according to the standard.

The positions established for successful verification (H and V) and flow rates used shall be recorded

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Guidance on the choice of recommended test apparatus

A commercially available burner face meeting the recommendations of this standard is the AGF burner insert 11-55, and a suitable 500 mm burner, including the specified burner face, is the

A recommended Venturi mixer is the AGF 14-18 1

The recommended burner and Venturi are available from:

USA www,amgasfur.com or www.pemfab.com

B.2 Influence of draughts in the test chamber

Experience demonstrates that flame geometry is affected by draughts within the test chamber, making it essential to shield the burner from such air currents To ensure accurate and consistent results, appropriate draught shields, like those specified in IEC 61034-1, should be used to protect the burner from any disturbances caused by airflow.

B.3 Guidance on provision of a suitable test chamber

The chamber used for testing must have a sufficient volume to ensure that fire effluents released during combustion do not affect the test conditions A chamber similar in size to the "3 m cube" specified in IEC 61034-1 is considered suitable, although other chambers with appropriate volume can also be used To observe the cable's behavior during the test, windows may be installed in the chamber walls Additionally, fume exhaust should be managed through a chimney positioned at a safe distance to maintain proper ventilation.

1 m from the burner A damper may be used for adjustment of ventilation conditions

Air inlets to the chamber must be positioned through orifices near the base to ensure proper airflow Additionally, the placement of air inlets and the exhaust chimney should maintain burner flame stability throughout the verification procedure and testing process.

This information is provided for the convenience of users of this International Standard and does not imply IEC endorsement of the named product Equivalent products may be used if they demonstrate the same results.

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

IEC 60331-11:1999, Tests for electric cables under fire conditions – Circuit integrity – Part 11:

Apparatus – Fire alone at a flame temperature of at least 750 °C

IEC 61034-1, Measurement of smoke density of cables burning under defined conditions –

IEC 61386-1, Conduit systems for cable management – Part 1: General requirements

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

4 Conditions d’essai – Environnement de l'essai 32

5.3 Échelle d'essai et son montage 37

5.5 Dispositif de production de chocs 40

5.6 Positionnement de la source de chaleur 41

5.7 Dispositif de contrôle de la continuité 41

7.3 Application de la flamme et des chocs 44

8.1 Durée d’application de la flamme 45

Annexe A (normative) Procédure de vérification de la source de chaleur 46

Annexe B (informative) Guide pour le choix d’appareillage recommandé 48

Figure 1 – Schéma de configuration de l’essai 33

Figure 2 – Méthode de montage recommandée du conduit métallique sur l’échelle d’essai 34

Figure 3 – Vue en plan de l’équipement d’essai au feu 35

Figure 4 – Vue en élévation de l’équipement d’essai (non à l’échelle) 36

Figure 5 – Manchon amortisseur type en caoutchouc pour supporter l’échelle d’essai 38

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

Figure 7 – Schéma d’un exemple de montage du système de contrôle du brûleur utilisant des débitmètres à flotteur 40

Figure 8 – Schéma de base du circuit électrique 44

Figure A.1 – Dispositif du système de mesure de la température 46

Tableau 3 – Monoconducteur non gainé ou câble gainé 42

LICENSED TO MECON Limited - RANCHI/BANGALORE FOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

ESSAIS POUR CÂBLES ÉLECTRIQUES SOUMIS AU FEU –

Partie 3: Méthode d’essai au feu pour les câbles de tension assignée au plus égale à 0,6/1,0 kV, essayés sous conduit métallique avec chocs, à une température d’au moins 830 °C

The International Electrotechnical Commission (IEC) is a global standardization organization composed of national electrotechnical committees Its mission is to promote international cooperation on standardization in the fields of electricity and electronics To achieve this, the IEC publishes International Standards, Technical Specifications, Technical Reports, Publicly Available Specifications (PAS), and Guides These publications are developed by study committees, with participation from any interested national committee Additionally, international governmental and non-governmental organizations collaborate with the IEC in its work The IEC works closely with the International Organization for Standardization (ISO) under agreements established between the two entities.

Official decisions or agreements by the IEC on technical matters represent, whenever possible, an international consensus on the topics studied, as the relevant IEC National Committees are represented in each study committee.

IEC publications are issued as international recommendations and are approved by the IEC National Committees Every reasonable effort is made to ensure the technical accuracy of IEC publications; however, the IEC cannot be held responsible for any misuse or misinterpretation by end users.

To promote international uniformity, IEC National Committees commit to transparently applying IEC Publications in their national and regional publications whenever possible Any discrepancies between IEC Publications and corresponding national or regional documents must be clearly stated in the latter.

5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa responsabilité pour les équipements déclarés conformes à une de ses Publications

6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication

No liability shall be attributed to the IEC, its directors, employees, auxiliaries, or agents, including its experts and members of its study committees and National Committees, for any harm caused by bodily injury, material damage, or any other type of direct or indirect damage This also includes any costs (such as legal fees) and expenses arising from the publication or use of this IEC Publication or any other IEC Publication, or from the credit given to it.

8) L'attention est attirée sur les références normatives citées dans cette publication L'utilisation de publications référencées est obligatoire pour une application correcte de la présente publication

Ngày đăng: 17/04/2023, 10:35

w