IEC 60068-2-75:1997, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests IEC 60155, Glow-starters for fluorescent lamps IEC 60188, High-pressure mercury vapour lamps IEC 601

Trang 1

BRITISH STANDARD BS EN

61347-2-1:2001 +A1:2006

Incorporating corrigenda

Lamp controlgear —

Part 2-1: Particular requirements

for starting devices (other than

glow starters)

ICS 29.140.99

September 2003, January 2007 and December 2010

BS EN 61347-2-1:2001 +A2:2014

Incorporating corrigenda September 2003, January 2007 and December 2010

Trang 2

BS EN 61347-2-1:2001+A2:2014

ISBN 978 0 580 74466 2

Amendments/corrigenda issued since publication

29 January 2007 Change to EN foreword and Annex ZA

31 March 2011 Modification of CENELEC foreword

31 May 2014 Implementation of IEC amendment

2:2013 with CENELEC endorsement A2:2014 Annex ZA amended

This British Standard,

having been prepared

under the direction of the

Electrotechnical Sector

Committee, was published

under the authority of the

Standards Committee and

comes into effect on

This British Standard is the UK implementation of

EN 61347-2-1:2001+A2:2014, incorporating corrigenda July 2003, November 2006 and December 2010 It is identical to IEC 61347-2-1:2000, incorporating amendments 1:2005 and 2:2013 It supersedes

BS EN 61347-2-1:2001+A1:2006, which will be withdrawn on 30 October 2016.The start and finish of text introduced or altered by amendment is indicated in the text by tags Tags indicating changes to IEC text carry the number of the IEC amendment For example, text altered by IEC amendment 1 is indicated

by 

The UK participation in its preparation was entrusted by Technical Committee CPL/34, Lamps and Related Equipment, to Subcommittee CPL/34/3, Auxiliaries for lamps

A list of organizations represented on this subcommittee can be obtained on request to its secretary

This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application

Compliance with a British Standard cannot confer immunity from legal obligations.

Trang 3

(other than glow starters)

(IEC 61347-2-1:2000)

Appareillages de lampes —

Partie 2-1: Prescriptions particulières

pour les dispositifs d'amorçage

(autres que starters à lueur)

(CEI 61347-2-1:2000)

Geräte für Lampen — Teil 2-1: Besondere Anforderungen an Startgeräte (andere als Glimmstarter) (IEC 61347-2-1:2000)

Up-to-date lists and bibliographical references concerning such national standards may be obtained on

application to the Central Secretariat or to any CENELEC member

This European Standard exists in three official versions (English, French, German) A version in any other

language made by translation under the responsibility of a CENELEC member into its own language and

notified to the Central Secretariat has the same status as the official versions

eCntlar erceStirata: ure de tSrassat 53B , - rB 0501uesssl

EC 1002 ©ENLE- C All irhgts fo xelpiotatii non yna fomr dna yna yb mnaes ersew devrolrwdi f edoEC rENELm Cemrebs.

feR .oN EN :1-74316E 1002

silgnErev hsnoi

pmaL tnocrolgear — Patr :1 eGneral dna safety meriuqerents

appAralliegel ed sampes —

raPite 1rP :rcseipitong srénélae set

rprcseipited sno séruciét

(C316 IE-74:102)00

eGrärüf et Lampen Tiel 1: lAlgmeieen dnu iSrehciehstnarofredungen (ICE 316-74:102)00

hTsi uEpornae tSdnaraw das ppaordev by CENELEC no 2-000110-1 CENELEC members are dnuob

oitacilppaC eht ot ntairaterceS lartne yna ot ro CENECEL rebmem

Tsih European Standard xestsi aiciffo eerht nil vsilgnE( snoisreh, G ,hcnerFv A )namreyna ni noisre rehto

egaugnal amed yb noitalsnart nured nopser ehtlibisiyt C a foENECEL ti otni rebmemwo sdna egaugnal n

C eht ot deifitonterceS lartneeht sah taira emas a sutatss ffo ehtiv laic.snoisre

CENELEC members are the national electrotechnical committees irtsuA foC ,muigleB ,azR hceilbupec,

Switzerland and the United Kingdom

Spain, Sweden,

This European Standard was approved by CENELEC on 2002-11-01 CENELEC members are bound to

EN 61347-2-1:2001+A1

January 2001

I n c o r p o r a t i n g Corrigenda July 2003, November 2006 and December 2010.

Avenue Marnix 17, B-1000 Brussels

EN 61347-2-1:2001+A2

February 2014

Trang 4

The text of document 34C/498/FDIS, future edition 1 of IEC 61347-2-1, prepared by SC 34C, Auxiliaries

for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote

and was approved by CENELEC as EN 61347-2-1 on 2000-11-01

This European Standard, together with EN 61347-1, supersedes EN 60926:1996 + A1:1999

The following dates were fixed:

– latest date by which the EN has to be implemented

at national level by publication of an identical

national standard or by endorsement (dop) 2001-08-01

– latest date by which the national standards conflicting

This standard shall be used in conjunction with EN 61347-1

NOTE In this standard, the following print types are used:

- requirements: in roman type;

- test specifications: in italic type;

- notes: in smaller roman type.

Annexes designated "normative" are part of the body of the standard

In this standard, annexes A to J and ZA are normative

Annex ZA has been added by CENELEC

Endorsement notice

The text of the International Standard IEC 61347-2-1:2000 was approved by CENELEC as a European

Standard without any modification

Page 2

Foreword to amendment A1

The text of document 34C/697/FDIS, future amendment 1 to IEC 61347-2-1:2000, prepared by SC 34C,

Auxiliaries for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC

parallel vote and was approved by CENELEC as amendment A1 to EN 61347-2-1:2001 on 2006-02-01

The following dates were fixed:

– latest date by which the amendment has to be

implemented at national level by publication of

an identical national standard or by endorsement (dop) 2006-11-01

– latest date by which the national standards conflicting

with the amendment have to be withdrawn (dow) 2009-02-01

This European Standard makes reference to International Standards Where the International Standard

referred to has been endorsed as a European Standard or a home-grown European Standard exists, this

European Standard shall be applied instead Pertinent information can be found on the CENELEC web

site

Endorsement notice

The text of amendment 1:2005 to the International Standard IEC 61347-2-1:2000 was approved by

CENELEC as an amendment to the European Standard without any modification

The following dates are fixed:

• latest date by which the document has

to be implemented at national level by publication of an identical national standard or by endorsement

(dop) 2014-07-30

• latest date by which the national standards conflicting with the document have to be withdrawn

(dow) 2016-10-30

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights

Endorsement notice

The text of the International Standard IEC 61347-2-1:2000/A2:2013 was approved by CENELEC as a European Standard without any modification

Trang 5

The following dates are fixed:

• latest date by which the document has

to be implemented at national level by

publication of an identical national

standard or by endorsement

(dop) 2014-07-30

• latest date by which the national

standards conflicting with the

document have to be withdrawn

(dow) 2016-10-30

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights

Endorsement notice

The text of the International Standard IEC 61347-2-1:2000/A2:2013 was approved by CENELEC as a European Standard without any modification

Foreword to amendment A2

Trang 6

 BSI 05-2001

CONTENTS

Page

INTRODUCTION 5

Clause 1 Scope 6

2 Normative references 6

3 Definitions 7

4 General requirements 7

5 General notes on tests 8

5.1 Starting devices for use with lamps having different electrical characteristics 8

5.2 Number of specimens 8

6 Classification 8

7 Marking 8

7.1 Mandatory markings 8

7.2 Information to be provided, if applicable 8

8 Protection against accidental contact with live parts 9

9 Terminals 9

10 Provisions for earthing 9

11 Moisture resistance and insulation 9

12 Electric strength 9

13 Thermal endurance test for windings 10

14 Fault conditions 10

15 Heating of independent starting devices 10

15.1 Normal operation 11

15.2 Abnormal operation 11

16 Pulse voltage of ignitors 12

17 Mechanical strength 12

18 Construction 12

19 Creepage distances and clearances 13

20 Screws, current-carrying parts and connections 13

21 Resistance to heat, fire and tracking 13

22 Resistance to corrosion 13

Annex A (normative) Test to establish whether a conductive part is a live part which may cause an electric shock 14

Annex B (normative) Particular requirements for thermally protected lamp controlgear 14

Annex C (normative) Particular requirements for electronic lamp controlgear with means of protection aginst overheating 14

Annex D (normative) Requirements for carrying out the heating tests of thermally protected lamp controlgear 14

Annex E (normative) Use of constant S other than 4 500 in tw tests 14

Annex G (informative) Explanation of the derivation of the values of pulse voltages 15

Page 3 Annex F (normative) Draught-proof enclosure 15

BS EN 61347-2-1:2001+A1:2006 EN 61347-2-1:2001+A1:2006 (E)  BSI 05-2001 CONTENTS Page INTRODUCTION 5

Clause 1 Scope 6

2 Normative references 6

3 Definitions 7

4 General requirements 7

5 General notes on tests 8

5.1 Starting devices for use with lamps having different electrical characteristics 8

5.2 Number of specimens 8

6 Classification 8

7 Marking 8

7.1 Mandatory markings 8

7.2 Information to be provided, if applicable 8

8 Protection against accidental contact with live parts 9

9 Terminals 9

10 Provisions for earthing 9

11 Moisture resistance and insulation 9

12 Electric strength 9

13 Thermal endurance test for windings 10

14 Fault conditions 10

15 Heating of independent starting devices 10

15.1 Normal operation 11

15.2 Abnormal operation 11

16 Pulse voltage of ignitors 12

17 Mechanical strength 12

18 Construction 12

19 Creepage distances and clearances 13

20 Screws, current-carrying parts and connections 13

21 Resistance to heat, fire and tracking 13

22 Resistance to corrosion 13

Annex A (normative) Test to establish whether a conductive part is a live part which may cause an electric shock 14

Annex B (normative) Particular requirements for thermally protected lamp controlgear 14

Annex C (normative) Particular requirements for electronic lamp controlgear with means of protection aginst overheating 14

Annex D (normative) Requirements for carrying out the heating tests of thermally protected lamp controlgear 14

Annex E (normative) Use of constant S other than 4 500 in tw tests 14

Annex G (informative) Explanation of the derivation of the values of pulse voltages 15

Page 3 Annex F (normative) Draught-proof enclosure 15

BS EN 61347-2-1:2001+A1:2006 EN 61347-2-1:2001+A1:2006 (E)  BSI 05-2001 CONTENTS Page INTRODUCTION 5

Clause 1 Scope 6

2 Normative references 6

3 Definitions 7

4 General requirements 7

5 General notes on tests 8

5.1 Starting devices for use with lamps having different electrical characteristics 8

5.2 Number of specimens 8

6 Classification 8

7 Marking 8

7.1 Mandatory markings 8

7.2 Information to be provided, if applicable 8

8 Protection against accidental contact with live parts 9

9 Terminals 9

10 Provisions for earthing 9

11 Moisture resistance and insulation 9

12 Electric strength 9

13 Thermal endurance test for windings 10

14 Fault conditions 10

15 Heating of independent starting devices 10

15.1 Normal operation 11

15.2 Abnormal operation 11

16 Pulse voltage of ignitors 12

17 Mechanical strength 12

18 Construction 12

19 Creepage distances and clearances 13

20 Screws, current-carrying parts and connections 13

21 Resistance to heat, fire and tracking 13

22 Resistance to corrosion 13

Annex A (normative) Test to establish whether a conductive part is a live part which may cause an electric shock 14

Annex B (normative) Particular requirements for thermally protected lamp controlgear 14

Annex C (normative) Particular requirements for electronic lamp controlgear with means of protection aginst overheating 14

Annex D (normative) Requirements for carrying out the heating tests of thermally protected lamp controlgear 14

Annex E (normative) Use of constant S other than 4 500 in tw tests 14

Annex G (informative) Explanation of the derivation of the values of pulse voltages 15

Page 3 Annex F (normative) Draught-proof enclosure 15

BS EN 61347-2-1:2001+A1:2006 EN 61347-2-1:2001+A1:2006 (E)  BSI 05-2001 CONTENTS Page INTRODUCTION 5

Clause 1 Scope 6

2 Normative references 6

3 Definitions 7

4 General requirements 7

5 General notes on tests 8

5.1 Starting devices for use with lamps having different electrical characteristics 8

5.2 Number of specimens 8

6 Classification 8

7 Marking 8

7.1 Mandatory markings 8

7.2 Information to be provided, if applicable 8

8 Protection against accidental contact with live parts 9

9 Terminals 9

10 Provisions for earthing 9

11 Moisture resistance and insulation 9

12 Electric strength 9

13 Thermal endurance test for windings 10

14 Fault conditions 10

15 Heating of independent starting devices 10

15.1 Normal operation 11

15.2 Abnormal operation 11

16 Pulse voltage of ignitors 12

17 Mechanical strength 12

18 Construction 12

19 Creepage distances and clearances 13

20 Screws, current-carrying parts and connections 13

21 Resistance to heat, fire and tracking 13

22 Resistance to corrosion 13

Annex A (normative) Test to establish whether a conductive part is a live part which may cause an electric shock 14

Annex B (normative) Particular requirements for thermally protected lamp controlgear 14

Annex C (normative) Particular requirements for electronic lamp controlgear with means of protection aginst overheating 14

Annex D (normative) Requirements for carrying out the heating tests of thermally protected lamp controlgear 14

Annex E (normative) Use of constant S other than 4 500 in tw tests 14

Annex G (informative) Explanation of the derivation of the values of pulse voltages 15

Page 3 Annex F (normative) Draught-proof enclosure 15

BS EN 61347-2-1:2001+A1:2006 EN 61347-2-1:2001+A1:2006 (E)  BSI 05-2001 CONTENTS Page INTRODUCTION 5

Clause 1 Scope 6

2 Normative references 6

3 Definitions 7

4 General requirements 7

5 General notes on tests 8

5.1 Starting devices for use with lamps having different electrical characteristics 8

5.2 Number of specimens 8

6 Classification 8

7 Marking 8

7.1 Mandatory markings 8

7.2 Information to be provided, if applicable 8

8 Protection against accidental contact with live parts 9

9 Terminals 9

10 Provisions for earthing 9

11 Moisture resistance and insulation 9

12 Electric strength 9

13 Thermal endurance test for windings 10

14 Fault conditions 10

15 Heating of independent starting devices 10

15.1 Normal operation 11

15.2 Abnormal operation 11

16 Pulse voltage of ignitors 12

17 Mechanical strength 12

18 Construction 12

19 Creepage distances and clearances 13

20 Screws, current-carrying parts and connections 13

21 Resistance to heat, fire and tracking 13

22 Resistance to corrosion 13

Annex A (normative) Test to establish whether a conductive part is a live part which may cause an electric shock 14

Annex B (normative) Particular requirements for thermally protected lamp controlgear 14

Annex C (normative) Particular requirements for electronic lamp controlgear with means of protection aginst overheating 14

Annex D (normative) Requirements for carrying out the heating tests of thermally protected lamp controlgear 14

Annex E (normative) Use of constant S other than 4 500 in tw tests 14

Annex G (informative) Explanation of the derivation of the values of pulse voltages 15

Page 3 Annex F (normative) Draught-proof enclosure 15

BS EN 61347-2-1:2001+A1:2006 EN 61347-2-1:2001+A1:2006 (E) Page 4 BS EN 61347-2-1:2001+A2:2014 EN 61347-2-1:2000+A2:2014 Heating of built-in and independent starting devices 15.1 General

15.2 Normal operation

15.3 Abnormal operation

6

7 7 8 9 9 9 9 9 9 9 10 10 10 10 10 10 11 11 11 11 12 13 15 15 16 16 16 17 17

18 18 18 18 18 19 19

Trang 7

 BSI 05-2001

Annex H (normative) 15

Annex I (normative) Mechanical strength testing 16

Annex ZA (normative) Normative references to international publications with their corresponding European publications 21

Bibliography 20

Figure 1 – Starting voltage measurement for ignitors 13

Figure I.1 – Tumbling barrel 17

Page 4 Annex J (normative) Precautions to be observed when measuring with sphere-gaps 18

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

Page 5

BS EN 61347-2-1:2001+A2:2014

EN 61347-2-1:2000+A2:2014

19 20 22 24 23 17 21

Trang 8

 BSI 05-2001

INTRODUCTION

This first edition of IEC 61347-2-1, published in conjunction with IEC 61347-1, represents an

editorial review of IEC 60926 The formatting into separately published parts provides for ease

of future amendments and revisions Additional requirements will be added as and when a

need for them is recognized

This standard, and the parts which make up IEC 61347-2, in referring to any of the clauses of

IEC 61347-1, specify the extent to which such a clause is applicable and the order in which the

tests are to be performed; they also include additional requirements, as necessary All parts

which make up IEC 61347-2 are self-contained and, therefore, do not include references to

each other

Where the requirements of any of the clauses of IEC 61347-1 are referred to in this standard

by the phrase ”The requirements of clause n of IEC 61347-1 apply”, this phrase is interpreted

as meaning that all requirements of the clause in question of part 1 apply, except any which are

clearly inapplicable to the specific type of lamp controlgear covered by this particular part of

Trang 9

LAMP CONTROLGEAR – Part 2-1: Particular requirements for starting devices

(other than glow starters)

1 Scope

This part of IEC 61347 specifies particular safety requirements for starting devices (starters

other than glow starters and ignitors) for fluorescent and other discharge lamps for use on a.c

supplies up to 1 000 V at 50 Hz or 60 Hz which produce starting pulses not greater than 100 kV

and which are used in combination with lamps and ballasts covered in IEC 60081, IEC 60188,

IEC 60192, IEC 60662, IEC 60901, IEC 61167, IEC 61195, IEC 61199, IEC 61347-2-8 and

IEC 61347-2-9

It does not apply to glow starters or starting devices which are incorporated in discharge lamps

or which are manually operated Preheat transformers for fluorescent lamps are covered by

IEC 61347-2-8

NOTE Glow starters are dealt with in IEC 60155.

Performance requirements are given in IEC 60927

2 Normative references

For the purpose of this part of IEC 61347, the normative references given in clause 2 of

IEC 61347-1 which are mentioned in this standard apply, together with the following normative

references

IEC 60068-2-75:1997, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests

IEC 60155, Glow-starters for fluorescent lamps

IEC 60188, High-pressure mercury vapour lamps

IEC 60192, Low-pressure sodium vapour lamps

IEC 60255-8:1990, Electrical relays – Part 8: Thermal electrical relays

IEC 60662, High-pressure sodium vapour lamps

IEC 61167, Metal halide lamps

IEC 61195, Double-capped fluorescent lamps – Safety specifications

IEC 61199, Single-capped fluorescent lamps – Safety specifications

IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements

ISO 3864, Safety colours and safety signs

3 Definitions

For the purpose of this part of IEC 61347, the definitions given in clause 3 of IEC 61347-1

apply, together with the following:

3.1

starting device/ignitor

apparatus which provides, by itself or in combination with other components in the circuit, the

appropriate electrical conditions needed to start a discharge type of lamp

3.2

starter

starting device, usually for fluorescent lamps, which provides for the necessary preheating of

the electrodes and may, in combination with the series impedance of the ballast, cause a surge

in the voltage applied to the lamp

NOTE The starter element that releases the starting voltage pulse may be either triggered, for example,

phase-angle synchronized, or non-triggered.

3.3

starting device with operating time limitation

starting device which prevents prolonged attempts to start lamps which refuse to start, for

example, lamps with deactivated electrodes

NOTE Prevention of starting attempts means that in the case of starters, the starting-current circuit is switched off

and/or the current in the starting circuit is limited to a value equal to or smaller than the rated lamp current.

In the case of ignitors, prevention of starting attempts means that pulse generation has ceased, or voltage pulses

are significantly reduced in amplitude.

spherical spark gap

two metal spheres of the same diameter arranged at a specified distance and used

under specified conditions for the measurement of peak voltages in excess of 15 kV

quotient of the square of the voltage produced at the output terminals of the voltage source,

open circuit condition, and its internal impedance, as seen from the output terminals

Trang 10

IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements

ISO 3864, Safety colours and safety signs

3 Definitions

For the purpose of this part of IEC 61347, the definitions given in clause 3 of IEC 61347-1

apply, together with the following:

3.1

starting device/ignitor

apparatus which provides, by itself or in combination with other components in the circuit, the

appropriate electrical conditions needed to start a discharge type of lamp

3.2

starter

starting device, usually for fluorescent lamps, which provides for the necessary preheating of

the electrodes and may, in combination with the series impedance of the ballast, cause a surge

in the voltage applied to the lamp

NOTE The starter element that releases the starting voltage pulse may be either triggered, for example,

phase-angle synchronized, or non-triggered.

3.3

starting device with operating time limitation

starting device which prevents prolonged attempts to start lamps which refuse to start, for

example, lamps with deactivated electrodes

NOTE Prevention of starting attempts means that in the case of starters, the starting-current circuit is switched off

and/or the current in the starting circuit is limited to a value equal to or smaller than the rated lamp current.

In the case of ignitors, prevention of starting attempts means that pulse generation has ceased, or voltage pulses

are significantly reduced in amplitude.

spherical spark gap

two metal spheres of the same diameter arranged at a specified distance and used

under specified conditions for the measurement of peak voltages in excess of 15 kV

quotient of the square of the voltage produced at the output terminals of the voltage source,

open circuit condition, and its internal impedance, as seen from the output terminals

IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements

ISO 3864, Safety colours and safety signs

3 Definitions

For the purpose of this part of IEC 61347, the definitions given in clause 3 of IEC 61347-1

apply, together with the following:

3.1

starting device/ignitor

apparatus which provides, by itself or in combination with other components in the circuit, the

appropriate electrical conditions needed to start a discharge type of lamp

3.2

starter

starting device, usually for fluorescent lamps, which provides for the necessary preheating of

the electrodes and may, in combination with the series impedance of the ballast, cause a surge

in the voltage applied to the lamp

NOTE The starter element that releases the starting voltage pulse may be either triggered, for example,

phase-angle synchronized, or non-triggered.

3.3

starting device with operating time limitation

starting device which prevents prolonged attempts to start lamps which refuse to start, for

example, lamps with deactivated electrodes

NOTE Prevention of starting attempts means that in the case of starters, the starting-current circuit is switched off

and/or the current in the starting circuit is limited to a value equal to or smaller than the rated lamp current.

In the case of ignitors, prevention of starting attempts means that pulse generation has ceased, or voltage pulses

are significantly reduced in amplitude.

spherical spark gap

two metal spheres of the same diameter arranged at a specified distance and used

under specified conditions for the measurement of peak voltages in excess of 15 kV

quotient of the square of the voltage produced at the output terminals of the voltage source,

open circuit condition, and its internal impedance, as seen from the output terminals

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additionalrequirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics aretested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall begiven on the starting device, or be made available in the manufacturer’s catalogue or similar:– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

Page 8

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

 BSI 05-2001

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additionalrequirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics aretested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall begiven on the starting device, or be made available in the manufacturer’s catalogue or similar:– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

This amendment has been prepared by subcommittee 34C: Auxiliaries for lamps, of IEC

technical committee 34: Lamps and related equipment

The text of this amendment is based on the following documents:

FDIS Report on voting 34C/1051/FDIS 34C/1067/RVD

Full information on the voting for the approval of this amendment can be found in the report

on voting indicated in the above table

The committee has decided that the contents of this amendment and the base publication will

remain unchanged until the stability date indicated on the IEC web site under

"http://webstore.iec.ch" in the data related to the specific publication At this date, the

Replace the titles of clause 15 and its subclauses by the following new titles:

15 Heating of built-in and independent starting devices

15.1 General

15.2 Normal operation

15.3 Abnormal operation

2 Normative references

Add the following new reference:

IEC 60598-1, Luminaires – Part 1: General requirements and tests

3 Definitions

Add, after 3.6, the following new entry 3.7:

3.7

maximum case temperature under abnormal conditions

maximum allowable case temperature of the starting devices and ignitors under abnormal

conditions with metal halide lamps

(tc + X)

NOTE The value of (tc + X) is declared by the manufacturer

[SOURCE: IEC 60927, 3.7, modified – The term "starting device" is added.]

Trang 11

IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements ISO 3864, Safety colours and safety signs

3 Definitions

For the purpose of this part of IEC 61347, the definitions given in clause 3 of IEC 61347-1apply, together with the following:

3.1 starting device/ignitor

apparatus which provides, by itself or in combination with other components in the circuit, theappropriate electrical conditions needed to start a discharge type of lamp

3.2 starter

starting device, usually for fluorescent lamps, which provides for the necessary preheating ofthe electrodes and may, in combination with the series impedance of the ballast, cause a surge

in the voltage applied to the lamp

NOTE The starter element that releases the starting voltage pulse may be either triggered, for example, angle synchronized, or non-triggered.

phase-3.3 starting device with operating time limitation

starting device which prevents prolonged attempts to start lamps which refuse to start, forexample, lamps with deactivated electrodes

NOTE Prevention of starting attempts means that in the case of starters, the starting-current circuit is switched off and/or the current in the starting circuit is limited to a value equal to or smaller than the rated lamp current.

In the case of ignitors, prevention of starting attempts means that pulse generation has ceased, or voltage pulses are significantly reduced in amplitude.

3.4 peak voltage

Up

highest value of the voltage pulses generated by an ignitor at the output terminals

3.5 short-circuit power (of a voltage source)

3.6 spherical spark gap

two metal spheres of the same diameter arranged at a specified distance and usedunder specified conditions for the measurement of peak voltages in excess of 15 kV

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additionalrequirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics aretested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall begiven on the starting device, or be made available in the manufacturer’s catalogue or similar:

– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

Page 8

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

 BSI 05-2001

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additionalrequirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics aretested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall begiven on the starting device, or be made available in the manufacturer’s catalogue or similar:

– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

This amendment has been prepared by subcommittee 34C: Auxiliaries for lamps, of IEC

technical committee 34: Lamps and related equipment

The text of this amendment is based on the following documents:

FDIS Report on voting 34C/1051/FDIS 34C/1067/RVD

Full information on the voting for the approval of this amendment can be found in the report

on voting indicated in the above table

The committee has decided that the contents of this amendment and the base publication will

remain unchanged until the stability date indicated on the IEC web site under

"http://webstore.iec.ch" in the data related to the specific publication At this date, the

Replace the titles of clause 15 and its subclauses by the following new titles:

15 Heating of built-in and independent starting devices

15.1 General

15.2 Normal operation

15.3 Abnormal operation

2 Normative references

Add the following new reference:

IEC 60598-1, Luminaires – Part 1: General requirements and tests

3 Definitions

Add, after 3.6, the following new entry 3.7:

3.7

maximum case temperature under abnormal conditions

maximum allowable case temperature of the starting devices and ignitors under abnormal

conditions with metal halide lamps

(tc + X)

NOTE The value of (tc + X) is declared by the manufacturer

[SOURCE: IEC 60927, 3.7, modified – The term "starting device" is added.]

61347-2-1 Amend.2 © IEC:2013 – 3 –

7.1 Mandatory markings

Add, at the end of the list, a new dashed item as follows:

– The manufacturer shall declare the allowable maximum case temperature under normal condition (A) and, for ignitors which are intended to be connected in series with discharge lamps which could, according to the lamp specification cause rectification, the maximum case temperature under abnormal condition (B) The marking shall be “tc A/B” (example

tc 60/90 = maximum temperature 60 °C for the normal and maximum temperature 90 °C for the abnormal conditions)

14 Fault conditions

Replace the first sentence of 14.2 in Amendment 1 by the following sentence:

Independent starting devices shall not exceed the temperature values for abnormal operation given in 15.3.3

15 Heating of independent starting devices

Replace the title and text of clause 15 and the changes made to it by Amendment 1 with the following:

15 Heating of built-in and independent starting devices

15.1 General

Built-in and independent starting devices shall not exceed the temperature limits during

normal operation (tc) and abnormal operation (tc + X)

In addition to the requirements of this clause of IEC 61347-2-1 for built-in starting devices the normal and the abnormal operating condition are checked together with the luminaire in accordance with IEC 60598-1

15.2 Normal operation 15.2.1 General

Normal conditions are working conditions in which one or more of the following situations apply:

a) lamps are operating normally;

b) rated current flows through the starting device;

c) the starting device has been connected to a voltage source, for example, the mains voltage or the lamp voltage arising during normal operation;

d) combination of b) and c)

15.2.2 Normal operation of built-in starting devices

Compliance of built-in starting device in normal operation is checked by the following procedure

The starting devices are connected as for normal use with appropriate lamps

The built-in starting device shall be placed in a test enclosure as detailed in annex D of IEC 61347-1, the starting device being supported by two wooden blocks as shown in figure H.1 of IEC 61347-1

Trang 12

 BSI 05-2001

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additional

requirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics are

tested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7 Marking

7.1 Mandatory markings

In accordance with the requirements of 7.2 of IEC 61347-1, starting devices shall be clearly

and durably marked with the following markings:

– items a), b), c) and f) of 7.1 of IEC 61347-1, together with

– a marking to show the peak value of the voltage produced if the peak value exceeds

1 500 V Connections having this voltage shall be marked; for ignitors with a pulse voltage

over 5 kV, this marking shall be a flash symbol (broken arrow) (see ISO 3864)

The marking of the earthing terminal is not required for ignitors over 5 kV because these are

mandatorily provided with a time limitation

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall be

given on the starting device, or be made available in the manufacturer’s catalogue or similar:

– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

Page 8

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

 BSI 05-2001

– an indication of the time limitation, if this is provided by the starting device;

– the catalogue reference of the ballast which may be associated with the starting device, if

the ballast design governs the magnitude of the pulse voltage;

special conditions relating to the use of the starting device

8 Protection against accidental contact with live parts

The requirements of clause 10 of IEC 61347-1 apply

9 Terminals

The requirements of clause 8 of IEC 61347-1 apply

10 Provisions for earthing

The requirements of clause 9 of IEC 61347-1 apply

11 Moisture resistance and insulation

The requirements of clause 11 of IEC 61347-1 apply together with the following:

Electric components, enclosures and other parts which can be removed without the aid of a

tool are removed and subjected, if necessary, to the humidity treatment with the main part

In order to achieve the specified conditions within the cabinet, it is necessary to ensure

constant circulation of the air within and, in general, to use a cabinet which is thermally

insulated

With double or reinforced insulation, the resistance shall be not less than 7 M

Care should be taken to avoid the moisture content of the devices at the end of the moisture

treatment changing appreciably before the measurement of the insulation resistance

To achieve this, it is recommended that the insulation resistance be measured while the

devices are still kept in the humidity cabinet or in an adjacent room protected against draught

and having similar conditions to those in the humidity cabinet

12 Electric strength

The requirements of clause 12 of IEC 61347-1 apply, together with the following additional

requirement:

Pulsing test

For starting devices which incorporate a high-voltage winding, compliance is checked by the

following pulsing test The starting device is operated at 110 % rated supply voltage without a

lamp load until 50 pulses have occurred, switching the supply on and off if necessary.

NOTE High-voltage winding denotes a winding incorporated in the starting device which produces the necessary

voltage to start the lamp.

Add, at the end of the list, a new dashed item as follows:

– The manufacturer shall declare the allowable maximum case temperature under normal condition (A) and, for ignitors which are intended to be connected in series with discharge lamps which could, according to the lamp specification cause rectification, the maximum case temperature under abnormal condition (B) The marking shall be “tc A/B” (example

tc 60/90 = maximum temperature 60 °C for the normal and maximum temperature 90 °C for the abnormal conditions)

14 Fault conditions

Replace the first sentence of 14.2 in Amendment 1 by the following sentence:

Independent starting devices shall not exceed the temperature values for abnormal operation given in 15.3.3

15 Heating of independent starting devices

Replace the title and text of clause 15 and the changes made to it by Amendment 1 with the following:

15 Heating of built-in and independent starting devices

15.1 General

Built-in and independent starting devices shall not exceed the temperature limits during

normal operation (tc) and abnormal operation (tc + X)

In addition to the requirements of this clause of IEC 61347-2-1 for built-in starting devices the normal and the abnormal operating condition are checked together with the luminaire in accordance with IEC 60598-1

15.2 Normal operation 15.2.1 General

Normal conditions are working conditions in which one or more of the following situations apply:

a) lamps are operating normally;

b) rated current flows through the starting device;

c) the starting device has been connected to a voltage source, for example, the mains voltage or the lamp voltage arising during normal operation;

d) combination of b) and c)

15.2.2 Normal operation of built-in starting devices

Compliance of built-in starting device in normal operation is checked by the following procedure

The starting devices are connected as for normal use with appropriate lamps

The built-in starting device shall be placed in a test enclosure as detailed in annex D of IEC 61347-1, the starting device being supported by two wooden blocks as shown in figure H.1 of IEC 61347-1

Trang 13

 BSI 05-2001

– an indication of the time limitation, if this is provided by the starting device;

– the catalogue reference of the ballast which may be associated with the starting device, ifthe ballast design governs the magnitude of the pulse voltage;

special conditions relating to the use of the starting device

8 Protection against accidental contact with live parts

The requirements of clause 10 of IEC 61347-1 apply

9 Terminals

The requirements of clause 8 of IEC 61347-1 apply

10 Provisions for earthing

The requirements of clause 9 of IEC 61347-1 apply

11 Moisture resistance and insulation

The requirements of clause 11 of IEC 61347-1 apply together with the following:

Electric components, enclosures and other parts which can be removed without the aid of atool are removed and subjected, if necessary, to the humidity treatment with the main part

In order to achieve the specified conditions within the cabinet, it is necessary to ensureconstant circulation of the air within and, in general, to use a cabinet which is thermallyinsulated

With double or reinforced insulation, the resistance shall be not less than 7 M

Care should be taken to avoid the moisture content of the devices at the end of the moisturetreatment changing appreciably before the measurement of the insulation resistance

To achieve this, it is recommended that the insulation resistance be measured while thedevices are still kept in the humidity cabinet or in an adjacent room protected against draughtand having similar conditions to those in the humidity cabinet

NOTE High-voltage winding denotes a winding incorporated in the starting device which produces the necessary voltage to start the lamp.

Page 9

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

 BSI 05-2001

5 General notes on tests

The requirements of clause 5 of IEC 61347-1 apply, together with the following additional

requirements:

5.1 Starting devices for use with lamps having different electrical characteristics

Starting devices intended for use with lamps having different electrical characteristics are

tested with the lamp which gives the most unfavourable conditions

5.2 Number of specimens

The following number of specimens shall be submitted for testing:

– one unit for the tests of clauses 6 to 12 and 15 to 22;

– one unit for the tests of clause 14 (additional units or components, where necessary, may

be required in consultation with the manufacturer)

– greater than 5 kV, and up to and including 10 kV;

– greater than 10 kV, and up to and including 100 kV

7 Marking

7.1 Mandatory markings

In accordance with the requirements of 7.2 of IEC 61347-1, starting devices shall be clearly

and durably marked with the following markings:

– items a), b), c) and f) of 7.1 of IEC 61347-1, together with

– a marking to show the peak value of the voltage produced if the peak value exceeds

1 500 V Connections having this voltage shall be marked; for ignitors with a pulse voltage

over 5 kV, this marking shall be a flash symbol (broken arrow) (see ISO 3864)

The marking of the earthing terminal is not required for ignitors over 5 kV because these are

mandatorily provided with a time limitation

7.2 Information to be provided, if applicable

In addition to the above mandatory markings, the following information, if applicable, shall be

given on the starting device, or be made available in the manufacturer’s catalogue or similar:

– items d), e), h), i), j), k) and l) of 7.1 of IEC 61347-1, together with

Page 8

BS EN 61347-2-1:2001+A1:2006

EN 61347-2-1:2001+A1:2006 (E)

 BSI 05-2001

– an indication of the time limitation, if this is provided by the starting device;

– the catalogue reference of the ballast which may be associated with the starting device, if

the ballast design governs the magnitude of the pulse voltage;

special conditions relating to the use of the starting device

8 Protection against accidental contact with live parts

The requirements of clause 10 of IEC 61347-1 apply

9 Terminals

The requirements of clause 8 of IEC 61347-1 apply

10 Provisions for earthing

The requirements of clause 9 of IEC 61347-1 apply

11 Moisture resistance and insulation

The requirements of clause 11 of IEC 61347-1 apply together with the following:

Electric components, enclosures and other parts which can be removed without the aid of a

tool are removed and subjected, if necessary, to the humidity treatment with the main part

In order to achieve the specified conditions within the cabinet, it is necessary to ensure

constant circulation of the air within and, in general, to use a cabinet which is thermally

insulated

With double or reinforced insulation, the resistance shall be not less than 7 M

Care should be taken to avoid the moisture content of the devices at the end of the moisture

treatment changing appreciably before the measurement of the insulation resistance

To achieve this, it is recommended that the insulation resistance be measured while the

devices are still kept in the humidity cabinet or in an adjacent room protected against draught

and having similar conditions to those in the humidity cabinet

12 Electric strength

The requirements of clause 12 of IEC 61347-1 apply, together with the following additional

requirement:

Pulsing test

For starting devices which incorporate a high-voltage winding, compliance is checked by the

following pulsing test The starting device is operated at 110 % rated supply voltage without a

lamp load until 50 pulses have occurred, switching the supply on and off if necessary.

NOTE High-voltage winding denotes a winding incorporated in the starting device which produces the necessary

voltage to start the lamp.

b) no sparkover or flashover;

c) no collapse or reduction of the front or the tail of the impulse voltage waveshape when observed on an oscilloscope.

13 Thermal endurance test for windings

The requirements of clause 13 of IEC 61347-1 are not applicable and a separate test is underconsideration

14 Fault conditions

The requirements of clause 14 of IEC 61347-1 apply, together with the following additionalrequirements:

14.1 The current in the lamp circuit shall not be increased by a fault in the starting device to

such an extent that the ballast becomes overheated, i.e the winding temperature exceeds the

tw-value at abnormal conditions For starters having external dimensions as specified inIEC 60155, this requirement is met if the current in the lamp circuit does not exceed themaximum pre-heat current value as specified in IEC 60081 and IEC 60901 for a period longerthan 5 min

15 Heating of independent starting devices

Independent starting devices shall not reach excessive temperatures during normal operationand abnormal operation

NOTE Built-in starting devices are checked together with the luminaire in accordance with IEC 60598-1.

Compliance is checked by the following tests:

Normal conditions are working conditions in which one or more of the following situations apply:

a) lamps are operating normally;

b) rated current flows through the starting device;

14.2 Independent starting devices shall not exceed the temperature values for abnormal

operation given in 15.2 This requirement is regarded as complied with when, for preheated lamp electrodes, the preheating current does not increase above its rated value by more than

5 % when the starting device is short-circuited

!

"

c) the starting device has been connected to a voltage source, for example, the mains voltage

or the lamp voltage arising during normal operation;

operation given in 15.3.3. This requirement is regarded as complied with when, for preheated lamp electrodes, the preheating current does not increase above its rated value by more than 5 % when the starting device is short-circuited.

61347-2-1 Amend.2 © IEC:2013 – 3 –

7.1 Mandatory markings

Add, at the end of the list, a new dashed item as follows:

– The manufacturer shall declare the allowable maximum case temperature under normal condition (A) and, for ignitors which are intended to be connected in series with discharge lamps which could, according to the lamp specification cause rectification, the maximum case temperature under abnormal condition (B) The marking shall be “tc A/B” (example

tc 60/90 = maximum temperature 60 °C for the normal and maximum temperature 90 °C for the abnormal conditions)

14 Fault conditions

Replace the first sentence of 14.2 in Amendment 1 by the following sentence:

Independent starting devices shall not exceed the temperature values for abnormal operation given in 15.3.3

15 Heating of independent starting devices

Replace the title and text of clause 15 and the changes made to it by Amendment 1 with the following:

15 Heating of built-in and independent starting devices

15.1 General

Built-in and independent starting devices shall not exceed the temperature limits during

normal operation (tc) and abnormal operation (tc + X)

In addition to the requirements of this clause of IEC 61347-2-1 for built-in starting devices the normal and the abnormal operating condition are checked together with the luminaire in accordance with IEC 60598-1

15.2 Normal operation 15.2.1 General

Normal conditions are working conditions in which one or more of the following situations apply:

a) lamps are operating normally;

b) rated current flows through the starting device;

c) the starting device has been connected to a voltage source, for example, the mains voltage or the lamp voltage arising during normal operation;

d) combination of b) and c)

15.2.2 Normal operation of built-in starting devices

Compliance of built-in starting device in normal operation is checked by the following procedure

The starting devices are connected as for normal use with appropriate lamps

The built-in starting device shall be placed in a test enclosure as detailed in annex D of IEC 61347-1, the starting device being supported by two wooden blocks as shown in figure H.1 of IEC 61347-1

Trang 14

The controlgear employed for the components shall meet the requirements of the relevant IEC standard and be compatible with the lamp type to be started by the starting device

The whole test circuit (controlgear, built-in starting device and the lamp(s)) is connected to the supply voltage When the lamp is in stable operation, the lamp current is set for rated value by modifying the voltage applied The ambient temperature of the test enclosure is adjusted to reach tc on the starting device In this condition, the starting devices and lamp are operated until they reach steady temperature

Compliance is checked by the temperature measurement The measured value shall not exceed limits specified in tables 12.1 and 12.2 of IEC 60598-1

15.2.3 Normal operation of independent starting devices

Compliance of independent starting device in normal operation is checked by the following procedure

Independent starting devices are connected as for normal use with appropriate lamps

Independent starting devices are mounted in a test corner consisting of three dull black painted laminated wood boards 15 mm to 25 mm thick and arranged so as to resemble two walls and the ceiling of a room The starting device is secured to the ceiling as close as possible to the walls, the ceiling extending at least 250 mm beyond the other sides of the starting device This assembly is positioned as far as possible from the five internal surfaces

of the enclosure

The tests are carried out in a draught-proof room or enclosure as specified in annex F The ambient temperature within the draught-proof enclosure shall be within 5 °C of the ta rating and should preferably be the same as the t a rating

The controlgear employed for the components shall meet the requirements of the relevant IEC standard and be compatible with the lamp type to be started by the starting device

The whole test circuit (controlgear, independent starting device and the lamp(s)) is connected

to the supply voltage When the lamp is in stable operation, the lamp current is set for the rated value by modifying the voltage applied In this condition, the starting device and lamps are operated until they reach steady temperature

Compliance is checked by the temperature measurement The measured value shall not exceed limits specified in tables 12.1 and 12.2 of IEC 60598-1

15.3 Abnormal operation 15.3.1 Abnormal operation of built-in ignitors

Compliance of built-in starting device in abnormal operation is checked by the following test procedure:

The test is required for built-in starting devices (built-in ignitors) intended to be connected in series with discharge lamps which could, according to the lamp specification cause rectification and are tested additionally with rectifying test circuit in accordance with 12.5 and annex C of IEC 60598-1

61347-2-1 Amend.2 © IEC:2013 – 3 –

7.1 Mandatory markings

Add, at the end of the list, a new dashed item as follows:

– The manufacturer shall declare the allowable maximum case temperature under normal

condition (A) and, for ignitors which are intended to be connected in series with discharge

lamps which could, according to the lamp specification cause rectification, the maximum

case temperature under abnormal condition (B) The marking shall be “tc A/B” (example

tc 60/90 = maximum temperature 60 °C for the normal and maximum temperature 90 °C

for the abnormal conditions)

14 Fault conditions

Replace the first sentence of 14.2 in Amendment 1 by the following sentence:

Independent starting devices shall not exceed the temperature values for abnormal operation

given in 15.3.3

15 Heating of independent starting devices

Replace the title and text of clause 15 and the changes made to it by Amendment 1 with the

following:

15 Heating of built-in and independent starting devices

15.1 General

Built-in and independent starting devices shall not exceed the temperature limits during

normal operation (tc) and abnormal operation (tc + X)

In addition to the requirements of this clause of IEC 61347-2-1 for built-in starting devices the

normal and the abnormal operating condition are checked together with the luminaire in

accordance with IEC 60598-1

15.2 Normal operation

15.2.1 General

Normal conditions are working conditions in which one or more of the following situations

apply:

a) lamps are operating normally;

b) rated current flows through the starting device;

c) the starting device has been connected to a voltage source, for example, the mains

voltage or the lamp voltage arising during normal operation;

d) combination of b) and c)

15.2.2 Normal operation of built-in starting devices

Compliance of built-in starting device in normal operation is checked by the following

procedure

The starting devices are connected as for normal use with appropriate lamps

The built-in starting device shall be placed in a test enclosure as detailed in annex D of

IEC 61347-1, the starting device being supported by two wooden blocks as shown in

figure H.1 of IEC 61347-1 – 4 – 61347-2-1 Amend.2 © IEC:2013

The wooden blocks shall be 75 mm high, 10 mm thick and of a width equal to, or greater than,

the width of the starting device Furthermore, the blocks shall be positioned with the extreme

end of the starting device aligned with the outer vertical sides of the block

The controlgear employed for the components shall meet the requirements of the relevant IEC

standard and be compatible with the lamp type to be started by the starting device

The whole test circuit (controlgear, built-in starting device and the lamp(s)) is connected to

the supply voltage When the lamp is in stable operation, the lamp current is set for rated

value by modifying the voltage applied The ambient temperature of the test enclosure is

adjusted to reach tc on the starting device In this condition, the starting devices and lamp are

operated until they reach steady temperature

Compliance is checked by the temperature measurement The measured value shall not

exceed limits specified in tables 12.1 and 12.2 of IEC 60598-1

15.2.3 Normal operation of independent starting devices

Compliance of independent starting device in normal operation is checked by the following

procedure

Independent starting devices are connected as for normal use with appropriate lamps

Independent starting devices are mounted in a test corner consisting of three dull black

painted laminated wood boards 15 mm to 25 mm thick and arranged so as to resemble two

walls and the ceiling of a room The starting device is secured to the ceiling as close as

possible to the walls, the ceiling extending at least 250 mm beyond the other sides of the

starting device This assembly is positioned as far as possible from the five internal surfaces

of the enclosure

The tests are carried out in a draught-proof room or enclosure as specified in annex F The

ambient temperature within the draught-proof enclosure shall be within 5 °C of the ta rating

and should preferably be the same as the t a rating

The controlgear employed for the components shall meet the requirements of the relevant IEC

standard and be compatible with the lamp type to be started by the starting device

The whole test circuit (controlgear, independent starting device and the lamp(s)) is connected

to the supply voltage When the lamp is in stable operation, the lamp current is set for the

rated value by modifying the voltage applied In this condition, the starting device and lamps

are operated until they reach steady temperature

Compliance is checked by the temperature measurement The measured value shall not

exceed limits specified in tables 12.1 and 12.2 of IEC 60598-1

15.3 Abnormal operation

15.3.1 Abnormal operation of built-in ignitors

Compliance of built-in starting device in abnormal operation is checked by the following test

procedure:

The test is required for built-in starting devices (built-in ignitors) intended to be connected in

series with discharge lamps which could, according to the lamp specification cause

rectification and are tested additionally with rectifying test circuit in accordance with 12.5 and

annex C of IEC 60598-1