If, however, these are given separately, they should be regarded I1 = load current at rated voltage I1r = main primary current at reduced voltage Io = no-load current at rated voltage Io
Trang 1Rotating electrical
machines —
Part 2: Methods for determining losses
and efficiency of rotating electrical
machinery from tests (excluding
machines for traction vehicles)
The European Standard EN 60034-2:1996 together with amendments A1:1996
and A2:1996 has the status of a British Standard
ICS 29.160.01
Trang 2This British Standard, having
been prepared under the
direction of the
Electrotechnical Sector
Board, was published
under the authority of the
Standards Board and
comes into effect on
Text introduced by amendments A1 and A2 is indicated by a sideline
The UK participation in its preparation was entrusted to Technical Committee PEL/2, Rotating electrical machinery, which has the responsibility to:
— aid enquirers to understand the text;
— present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed;
— monitor related international and European developments and promulgate them in the UK
A list of organizations represented on this committee can be obtained on request to its secretary
From 1 January 1997, all IEC publications have the number 60000 added to the old number For instance, IEC 27-1 has been renumbered as IEC 60027-1 For a period of time during the change over from one numbering system to the other, publications may contain identifiers from both systems
Cross-references
The British Standards which implement these international or European publications referred to in this document may be found in the BSI Standards Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Find” facility of the BSI Standards Electronic
Catalogue
A British Standard does not purport to include all the necessary provisions of
a contract Users of British Standards are responsible for their correct application
Compliance with a British Standard does not of itself confer immunity from legal obligations.
Amendments issued since publication
Amd No Date Comments
Trang 3Page
Trang 5November 1996
UDC 621.313.017.2/.6.017.8.083.001.4
ICS 29.160.00
Supersedes HD 53.2 S1:1974 Descriptors: Rotating electrical machines, power losses, efficiency, determination, tests, power measurements
Machines électriques tournantes
Partie 2: Méthodes pour la détermination des
pertes et du rendement des machines
électriques tournantes à partir d’essais
(à l’exclusion des machines pour véhicules de
traction)
(inclut les amendements A1:1996 et A2:1996)
(CEI 34-2:1972 + IEC 34-2A:1974 +
A1:1995 + A2:1996)
Drehende elektrische Maschinen Teil 2: Verfahren zur Bestimmung der Verluste und des Wirkungsgrades von drehenden elektrischen Maschinen aus Prüfungen (ausgenommen Maschinen für Schienen- und Straßenfahrzeuge) (enthält Änderungen A1:1996 und A2:1996) (IEC 34-2:1972 + IEC 34-2A:1974 + A1:1995 + A2:1996)
This European Standard was approved by CENELEC on 1996-07-02
CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration
Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any
CENELEC member
This European Standard exists in three official versions (English, French,
German) A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions
CENELEC members are the national electrotechnical committees of Austria,
Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,
Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and
United Kingdom
CENELEC
European Committee for Electrotechnical StandardizationComité Européen de Normalisation ElectrotechniqueEuropäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B-1050 Brussels
© 1996 Copyright reserved to CENELEC members
Ref No EN 60034-2:1996 + A1:1996 + A2:1996 E
标准分享网
www.bzfxw.com
Trang 6The text of the International Standard
IEC 34-2:1972 + IEC 34-2A:1974, prepared by
SC 2G, Test methods and procedures, of IEC TC 2,
Rotating machinery, was approved by CENELEC as
HD 53.2 S1 on 1974-12-11
This Harmonization Document was submitted to
the formal vote for conversion into a European
Standard and was approved by CENELEC as
EN 60034-2 on 1996-07-02
The following date was fixed:
Foreword to amendment A1
The text of amendment 1:1995 to the
International Standard IEC 34-2:1972, prepared by
SC 2G, Test methods and procedures, of IEC TC 2,
Rotating machinery, was submitted to the formal
vote and was approved by CENELEC as
amendment A1 to EN 60034-2 on 1996-07-02
without any modification
The following dates were fixed:
For products which have complied with
HD 53.2 S1:1974 (converted into EN 60034-2)
before 1997-06-01, as shown by the manufacturer or
by a certification body, this previous standard may
continue to apply for production until 2002-06-01
Foreword to amendment A2
The text of document 2/939/FDIS, prepared by
IEC TC 2, Rotating machinery, was submitted to
the formal vote and was approved by CENELEC as
amendment A2 to EN 60034-2 on 1996-07-02
The text of document 2G/73/FDIS, prepared by
SC 2G, Test methods and procedures, of IEC TC 2,
was submitted to the IEC-CENELEC parallel vote
and was approved by CENELEC for inclusion into
amendment A2 to EN 60034-2 on 1996-10-01
NOTE Amendment 2 to IEC 34-2, published in November 1996, contains both documents 2/939/FDIS and 2G/73/FDIS.
The following dates were fixed:
For products which have complied with
HD 53.2 S1:1974 (converted into EN 60034-2) before 1997-06-01, as shown by the manufacturer or
by a certification body, this previous standard may continue to apply for production until 2002-06-01
— latest date by which the EN
has to be implemented at
national level by publication
of an identical national
standard or by endorsement (dop) 1997-06-01
— latest date by which the
or by endorsement (dop) 1997-06-01
— latest date by which the national standards conflicting with the amendment have to be withdrawn (dow) 1997-06-01
标准分享网
www.bzfxw.com
Trang 74.4 Calibrated driving machine test 6
4.5 Mechanical back-to-back test 6
4.6 Electrical back-to-back test 6
4.10 Open-circuit test 6
4.11 Sustained short-circuit test 7
4.12 Zero power factor-test 7
7.2 Total loss measurement 10
7.3 Direct measurement of efficiency 10
Section 3 Polyphase induction machines
9.2 Total loss measurement 12
9.3 Direct measurement of efficiency 12
Section 4 Synchronous machines
11 Determination of efficiency 1311.1 Summation of losses 1311.2 Total loss measurement 1511.3 Direct measurement of efficiency 15Section 5 Methods of test
13 Calibrated machine test 16
14 Zero power factor test 16
vector of load current I1 at rated voltage 23Figure 4 — Method of the chord 23Figure 5 — Method of the limiting secant 24Figure A.1 — Maximum permissible
relative error (%P/Pin)max of input as well
as output measurement 25Figure A.2 — Schematic diagram of a
test set-up for the calorimetric calibration
by the calorimetric method 31
Section 1 General
2 Determination of losses P1 by measurement of the volume rate
of flow and rise in temperature of the cooling medium 32
3 Losses Pi measured electrically using the calorimetric calibration method 32
Trang 86 Losses external to the reference surface Pe 33
Section 2 Water as the cooling medium
7 Application and basic relationship 34
8 Measurement of water flow 34
9 Measurement of the temperature rise
10 Measuring accuracy 35
Section 3 Air as the cooling medium
11 Application and basic relationship 36
12 Determination of the mass rate of flow 36
13 Measurement of the temperature rise
14 Determination of the specific heat
capacity of the air 38
15 Measuring accuracy 38
Section 4 Practical considerations
16 Preparations for calorimetric
measurements with liquid coolants 39
17 Connections and equipment for
calorimetric measurements with
Figure 1 — Reference surface 41
Figure 2 — Parallel coolers 42
Figure 3 — Series coolers 42
Figure 4 — Characteristic values of pure
water as a function of temperature 43
Figure 5 — Position of thermometer
pockets in the water conduit 44
Figure 6 — Measuring throttles placed in
the cooling circuit on site 44
Figure 7 — Air density depending on
temperature and humidity 45
Figure 8 — Specific heat capacity cp of air for
different values of humidity and temperature 46
Trang 9Section 1 General
1 Scope
This Recommendation applies to d.c machines and
to a.c synchronous and induction machines of all
sizes within the scope of IEC Publication 34-1 The
principles can, however, be applied to other types of
machines such as rotary convertors, a.c
commutator motors and single- phase induction
motors for which other methods of determining
losses are generally use
2 Object
This Recommendation is intended to establish
methods of determining efficiencies from tests, and
also to specify methods of obtaining particular
losses when these are required for other purposes
3 General
Tests shall be conducted on a completely sound
machine with all covers fitted in the manner
required for normal service, with any devices for
automatic voltage regulation not a composite part of
the machine itself being made inoperative, unless
otherwise agreed
Unless otherwise agreed, measuring instruments
and their accessories, such as measuring
transformers, shunts and bridges used during the
test shall have an accuracy of 0,5 or better (IEC 51)
excluding three-phase wattmeters and wattmeters
for low power factor, for which an accuracy class
shall be 1,0 or better
Instruments shall be selected to give readings over
the effective range such that a fraction of a division
is a small percentage of the actual reading and can
be easily estimated
On machines with adjustable brushes, the brushes
shall be placed in the position corresponding to the
specified rating For measurements on no-load, the
brushes may be placed on the neutral axis
Speed of rotation may be measured by a stroboscopic
method, digital counter or tachometer When
measuring slip, the synchronous speed should be
determined from the supply frequency during the
test
When the over-all efficiency or the absorbed power
is measured for a group of machines comprising two
electrical machines, or a machine and a
transformer, or a generator and its driving machine,
or a motor and its driven machine, there is no need
to indicate the individual efficiencies If, however,
these are given separately, they should be regarded
I1 = load current at rated voltage
I1r = main primary current at reduced voltage
Io = no-load current at rated voltage
Ior = no-load current at reduced voltage
J = moment of inertia
n = speed of rotation in revolutions per minute
nN = rated speed
N = number of full revolutions of the shaft
P = losses which can be directly measured
P1 = power absorbed at rated voltage
P1r = power absorbed by main primary winding
at reduced voltage
PFe = iron losses defined in accordance
with 6.2 a), 8.1 a) and 10.1 a)
Pf = friction and windage losses (“mechanical
losses”) defined in accordance
with 6.2 b), 6.2 c), 8.1 b), 8.1 c), 10.1 b) and 10.1 c)
Pk = short-circuit losses representing the sum
of the I2R losses in operating windings on
load in accordance with 10.2 and
additional load losses in accordance
Ur = reduced voltage for load test
$ = per unit deviation of rotational speed from
rated speed: = load phase angle at rated voltage:r = load phase angle at reduced voltage:o = no-load phase angle at rated voltage:or = no-load phase angle at reduced voltage
标准分享网
www.bzfxw.com
Trang 104 Definitions
For definitions of general terms used in this
Recommendation, reference should be made to the
International Electrotechnical Vocabulary [IEC
Publication 50]
For the purpose of this Recommendation, the
following definitions apply:
4.1
efficiency
the ratio of output to input expressed in the same
units and usually given as a percentage
4.2
total loss
the difference between the input and the output
4.3 braking test
a test in which the mechanical power output of a machine acting as a motor is determined by the measurement of the shaft torque, by means of a brake or dynamometer, together with the rotational speed Alternatively, a test performed on a machine acting as a generator, by means of a dynamometer
to determine the mechanical power input
4.4 calibrated driving machine test
a test in which the mechanical input or output of an electrical machine is calculated from the electrical output or input of a calibrated machine
mechanically coupled to the machine on test
4.5 mechanical back-to-back test
a test in which two identical machines are mechanically coupled together, and the total losses
of both machines are calculated from the difference between the electrical input to one machine and the electrical output of the other machine
(see Figure 1, page 22)
4.6 electrical back-to-back test
a test in which two identical machines are mechanically coupled together, and they are both connected electrically to a power system The total losses of both machines are taken as the power input drawn from the system (see Figure 2, page 22)
4.7 retardation test
a test in which the losses in a machine are deduced from the rate of deceleration of the machine when only these losses are present
4.8 calorimetric test
a test in which the losses in a machine are deduced from the heat produced by them The losses are calculated from the product of the amount of coolant and its temperature rise, and the heat dissipated in the surrounding media
4.9 no-load test
a test in which the machine is run as a motor providing no useful mechanical output from the shaft
4.10 open-circuit test
a test in which a machine is run as a generator with its terminals open-circuited
Pi = losses inside reference surface
Pe = losses outside reference surface
P1 = losses which are dissipated by the cooling
circuits in the form of heat and which can be
measured calorimetrically
P2 = losses not transmitted to the cooling medium
but which are dissipated through the
reference surface by conduction, convection,
radiation, leakage, etc
cp = specific heat capacity of the cooling medium
Q = volume rate of flow of the cooling medium
Õ = density of the cooling medium
%t = rise in temperature of the cooling medium or
temperature difference between the machine
reference surface and the external ambient
temperature
É = exit velocity of cooling medium
! = discharge coefficient
e = error in measurement of losses, P1 and P2
h = coefficient of heat transfer
%p = difference between the static pressure in the
intake nozzle and ambient pressure
A = cross-sectional area of the intake nozzle
t = temperature
t1 = inlet temperature of the cooling medium
t2 = outlet temperature of the cooling medium
b = barometric pressure标准分享网
www.bzfxw.com
Trang 114.11
sustained short-circuit test
a test in which a machine is run as a generator with
its terminals short-circuited
4.12
zero power factor test
a no-load test on a synchronous machine which is
over-excited and operates at a power factor very
close to zero
5 Reference temperature
Unless otherwise specified, all I2R losses shall be
corrected to the temperatures given below:
If the rated temperature rise or the rated
temperature is specified as that of a lower thermal
class than that used in the construction, the
reference temperature shall be that of the lower
thermal class
Section 2 D.C Machines
6 Losses to be included
The total losses may be taken as the sum of the
following component losses:
6.1 Excitation circuit losses
a) I2R losses in shunt or separately excited
windings and in the excitation rheostats
b) Exciter losses
All the losses in an exciter mechanically driven from
the main shaft, which forms part of the complete
unit and is used solely for exciting the machine,
together with losses in the rheostat in the excitation
circuit of such an exciter, but with the exception of
friction and windage losses
In the case of a separate excitation supply such as
battery, rectifier or motor generator set, no
allowance is made for the losses in the excitation
source or in the connections between the source and
the brushes
NOTE When the losses in a separate excitation system are
require, these should be listed separately and can be taken as the
difference between the excitation power divided by the efficiency
of the excitation system and the excitation power.
NOTE When the losses in a separate lubricating system are required, these should be listed separately.
c) The total windage loss in the machine including power absorbed in integral fans and in auxiliary machines, if any, forming an integral part of the machine The losses in auxiliary machines such as external fans, water and oil pumps not forming an integral part of the machine, but provided exclusively for the machine in question, shall be included only by agreement
NOTE When the losses in a separate ventilating system are required, they should be listed separately as they are not part of the machine losses.
6.3 Load losses
a) I2R losses in armature, and windings carrying
armature current (e.g commutating, compensating, excitation and series connected windings)
b) Electrical losses in brushes
6.4 Additional load losses
a) Losses introduced by load in active iron, and other metal parts other than the conductors.b) Eddy current losses in armature conductors caused by current dependent flux pulsation and commutation
c) Losses in the brushes caused by commutation
NOTE These losses are sometimes called additional losses, but they do not include the additional no-load losses in
Sub-clause 6.2 a).
Thermal class of the
insulation system Reference temperature°C
Trang 127 Determination of efficiency
7.1 Summation of losses
The efficiency can be calculated from the total losses
which are assumed to be the summation of the
losses obtained in the following manner:
7.1.1 Excitation losses
These are:
7.1.1.1 Excitation winding I 2 R losses
These losses are calculated from the formula I2R,
where R is the resistance of the shunt excitation
winding (or separately excited winding), corrected
to the reference temperature, and I is the excitation
current Except for case c) below, the excitation
current shall be that corresponding to rated speed
under rated load conditions For case c) below, the
excitation current shall be that corresponding to
rated speed at no-load
If the excitation current cannot be measured during
a test on load, it should be taken as:
a) For shunt connected or separately excited
generators with or without commutation
poles; 110 % of the excitation current,
corresponding to no-load at a voltage equal to the
rated voltage plus ohmic drop in the armature
circuit (armature, brushes and commutating
windings if any, see also Sub-clause 7.1.3.2) at
rated load current
b) For compensated shunt or separately excited
generators: the excitation current corresponding
to no-load at a voltage equal to the rated voltage
plus the ohmic drop in the armature circuit
(armature, brushes, commutating windings and
compensating windings, see also
Sub-clause 7.1.3.2) at rated load current.
c) For level-compounded generators: the
excitation current for the rated no-load voltage
d) For over-compounded and under-compounded
generators, and special types of generator not
covered by items a) to c): as agreed between
manufacturer and purchaser
e) For shunt wound motors: equal to no-load
excitation current corresponding to the rated
voltage
7.1.1.2 Main rheostat losses
These losses are calculated from the formula I2R,
where R is the resistance of the part of the rheostat
in circuit for the rating considered, and I is the value
of the excitation current defined as in
Sub-clause 7.1.1.1 above They are also equal to the
product, IU, of the excitation current multiplied by
U, the excitation voltage which must be absorbed in
the rheostat
The sum of the losses, Sub-clauses 7.1.1.1
and 7.1.1.2, is also equal to the product IUe of the
excitation current I and the total excitation voltage Ue
NOTE Where a resistance is permanently connected in series in the excitation circuit it should be dealt with in the same way as the main rheostat.
7.1.1.3 Exciter losses
NOTE This applies only to the case where the exciter is mechanically driven from the main shaft and is used solely for exciting the main machine.
These losses include the difference between the power absorbed at the shaft by the exciter and the useful power which it provides at its terminals,1) as well as the excitation losses in the exciter if this is excited from a separate source
If the exciter can be uncoupled from the main machine and tested separately, the power which it absorbs may be measured by using the
calibrated-machine method
If the exciter cannot be uncoupled from the main machine, the power which it absorbs may be measured either by the method of working the main machine as a motor on no-load, or by the calibrated
machine method (Clause 13), or by the retardation method (Clause 15), applied to the whole unit In
these three methods, the power absorbed by the exciter is obtained as the difference between the total losses of the unit measured under identical conditions, first with the exciter on-load and secondly with the exciter non-excited, the excitation being supplied by an independent source
If none of these methods is applicable, the power absorbed by the exciter is obtained by adding to the power, measured at the terminals, the different
separate losses determined as under Clause 6
However, mechanical friction and windage losses which are measured at the same time as those of the main machine need not be taken into account
7.1.2 Constant losses 7.1.2.1 No-load test at rated voltage
The constant losses shall be determined by running the machine under no-load conditions as a motor with rated voltage applied and with rated speed achieved by adjustment of the excitation, which shall preferably be derived from a separate source
The total electric power absorbed, less the I2R losses
in the armature and in the excitation winding or, if necessary, less the power absorbed by the exciter, gives the sum of the constant losses
1) The useful power at the terminals of the exciter is equal to the sum of the losses, Sub-clauses 7.1.1.1 and 7.1.1.2, of the main
machine.
标准分享网
www.bzfxw.com
Trang 137.1.2.2 Open circuit test
The constant losses can be determined separately by
driving the machine at its rated speed by means of a
calibrated machine The machine on test is excited
(preferably from an independent source), so as to
work as a generator on no-load at a voltage equal to
its rated voltage, the power which it absorbs at its
shaft, and which can be obtained from the electric
power absorbed by the calibrated machine, giving
the sum of the constant losses By removing the
excitation, the sum of the friction and windage
losses is obtained in the same way The core losses
may be determined separately by subtracting the
losses during this test from those measured during
the previous no-load test By lifting the brushes the
brush friction loss may be determined separately by
subtracting the losses during this test from those
measured during the previous, unexcited test
7.1.2.3 Retardation test
In machines with large inertia, the total constant
losses, as well as the separate constant losses, can
be determined by the retardation method
7.1.3 Load losses
These are:
7.1.3.1 Armature circuit I 2 R losses
These losses are calculated from the current and the
measured resistance, corrected to the reference
temperature, except that where resistance
measurement is impracticable due to very low
resistances, calculation is permissible
NOTE Under this heading are included compensating
windings, commutating pole windings and diverters In the case
of diverters in parallel with a series winding, the I2R losses
should be determined using the total current and the resulting
resistance.
7.1.3.2 Electrical losses in brushes
The sum of these losses shall be taken as the
product of the armature current and a fixed voltage
drop
The voltage drop allowed for all brushes of each
polarity shall be 1.0 V for carbon or graphite
brushes and 0.3 V for metal-carbon brushes, i.e a
total drop of 2.0 V for carbon or graphite brushes,
and 0.6 V for metal-carbon brushes
7.1.4 Additional load losses
Unless otherwise specified, it is assumed that these
losses vary as the square of the current, and that
their total value at maximum rated current is, for:
Uncompensated machines
1 % of the rated input for motors;
1 % of the rated output for generators
Compensated machines
0.5 % of the rated input for motors;
0.5 % of the rated output for generators
For constant speed machines, the rated output or input as appropriate is taken as the output or input which would be obtained at maximum rated current and maximum rated voltage
For variable speed motors where the speed change
is obtained by applied voltage, the rated input is defined at each speed as being the input when the maximum rated current at any speed is associated with the applied voltage of the particular speed considered
For variable speed motors where the increase in speed is obtained by weakening the field, the rated input is defined as being the input when the rated voltage is associated with the maximum rated current For variable speed generators where the voltage is maintained constant by varying the field, the rated output is defined as being the output which is available at the terminals at rated voltage and maximum rated current The allowances for additional losses at the speed corresponding to the full field shall be as specified above The allowances for additional losses at other speeds shall be calculated using the appropriate multiplying factors given in Table I, 36
The speed ratio in the first column of Table I shall
be taken as the ratio of actual speed under consideration to the minimum rated speed for continuous running
For speed ratios other than those given in Table I the appropriate multiplying factors can be ascertained by interpolation
NOTE The additional load loss may be obtained from an input-output test or from a back-to-back test by subtracting from the total measured losses all other known losses.
7.1.4.1 Change in core loss due to load
In general, this variation is usually negligible By special agreement, for very low voltage machines,
the sum, Sub-clause 6.2 a) and 6.4 a), may be
measured as described for the constant losses in
active iron, Sub-clause 6.2 a) by one or other of the
two methods, by operating as a motor on no-load or
as a generator on no-load, but instead of making the test at the rated voltage, the test is made at the rated voltage increased or decreased by the voltage drop in the armature circuit for the current
considered, depending on whether the machine is a generator or a motor
Multiplying factors for different speed ratios
Trang 147.1.4.2 Additional load losses in d.c motors supplied
by static power converters
Whenever the current ripple factor
(see 2.29, IEC 34-1:1994) of the armature current
exceeds 0,1, the additional losses caused by the a.c
component of the armature current shall be
considered in addition to the losses specified
in 7.1.4.
They shall be calculated as the eddy current losses
caused by the fundamental component of the
above-mentioned a.c component
The method of calculation used shall be the subject
of agreement between manufacturer and purchaser
7.2 Total loss measurement
7.2.1 Electrical back-to-back tests
(see clause 16)
When identical machines are run at essentially the
same rated conditions, the losses supplied from the
electrical system are assumed to be equally
distributed and the efficiency is calculated as 7.3.3.
The test shall be made as nearly as possible at the
temperature attained in operation at the end of the
time specified in the rating No winding
temperature correction shall be made
7.3 Direct measurement of efficiency
7.3.1 Braking test
When the machine is run at rated conditions of
speed, voltage and current, the efficiency is then
taken as the ratio of output to input The test shall
be made as nearly as possible at the temperature
attained in operation at the end of the time specified
in the rating No winding temperature correction
shall be made
7.3.2 Calibrated machine test (see clause 13)
When the machine is run at rated conditions of
speed, voltage and current, the efficiency is taken as
the ratio of output to input
The test shall be made as nearly as possible at the
temperature attained in operation at the end of the
time specified in the rating No winding
temperature correction shall be made
7.3.3 Mechanical back-to-back test
When identical machines are run at essentially the
same rated conditions, the losses are assumed to be
equally distributed, and the efficiency is calculated
from half the total losses and the electrical input (in
the case of a motor) or electrical output (in the case
of a generator)
The test shall be made as nearly as possible at the
temperature attained in operation at the end of the
time specified in the rating No winding
temperature correction shall be made
Section 3 Polyphase induction machines
NOTE When the losses in a separate lubricating system are required these should be listed separately.
c) The total windage loss in the machine, including power absorbed in integral fans, and in auxiliary machines, if any, forming an integral part of the machine The losses in auxiliary machines such as external fans, water and oil pumps not forming an integral part of the machine, but provided exclusively for the machine in question, shall be included only by agreement
NOTE When the losses in a separate lubricating system are required they should be listed separately.
8.2 Load losses
a) I2R losses in primary windings.
b) I2R losses in secondary windings.
c) Electrical losses in brushes (if any)
8.3 Additional load losses
a) Losses introduced by load in active iron and other metal parts other than the conductors.b) Eddy current losses in primary or secondary winding conductors caused by current dependent flux pulsation
NOTE 1 Losses, Sub-clause 8.3 a) and b), are sometimes called
additional losses, but they do not include the additional no-load
losses in Sub-clause 8.1 a).
NOTE 2 In the case of auxiliary machines such as phase advancers driven mechanically from the main shaft, the losses should be included in the same way as the exciter losses are included for synchronous machines Losses in separately driven phase advancers or regulating equipment should be given separately for rated operating conditions of the main machine These losses should be determined by the standard method for the types of apparatus involved.
标准分享网
www.bzfxw.com
Trang 159 Determination of efficiency
9.1 Summation of losses
The efficiency can be calculated from the total losses
which are assumed to be the summation of the
losses obtained in the following manner:
9.1.1 Constant losses
9.1.1.1 No-load test at rated voltage
The sum of the constant losses, Sub-clause 8.1 a), b)
and c), is determined by running the machine as a
motor on no-load The machine is fed at its rated
voltage and frequency The power absorbed,
decreased by the I2R losses in the primary winding,
gives the total of the constant losses The I2R losses
in the secondary winding may be neglected
9.1.1.2 Calibrated machine test (see Clause 13)
The constant losses may be determined separately
by driving the machine, disconnected from the
network, at its rated speed by means of a calibrated
motor (see Sub-clause 9.2.2) With the brushes, if
any, in place, the power absorbed at the shaft of the
machine, which may be deduced from the electrical
power absorbed by the calibrated motor, gives the
sum of the losses in Sub-clause 8.1 b) and 8.1 c)
With the brushes, if any, lifted the sum of the
bearing friction losses and the total windage losses
is obtained in the same manner The losses
described in Sub-clause 8.1 a) may be obtained from
the test described in Sub-clause 9.1.1.1 by
subtraction
9.1.1.3 No-load test at variable voltage
The losses described in Sub-clause 8.1 a) and the
sum of the losses described in Sub-clause 8.1 b)
and c) may alternatively be separated by running
the machine as a motor at rated frequency but at
different voltages The power absorbed, less the I2R
losses in the primary winding, is plotted against the
square of the voltage This, at low values of
saturation, will give a straight line which can be
extrapolated to zero voltage to give the sum of the
losses, Sub-clause 8.1 b) and c).
It should be borne in mind that at very low voltages,
losses plotted on the diagram may be high because
of the increased secondary winding losses with
increased slip When plotting the straight line,
those values should not be taken into account
If the motor is started with a short-circuited
secondary winding and the brushes are lifted (which
is possible if the supply generator is started at the
same time as the motor) the bearing friction and
total windage losses are obtained at zero voltage by
extrapolation as above
NOTE For wound rotor motors a synchronous no-load test can
be carried out as for synchronous machines with d.c excitation in
two rotor phases (or three if desired).
9.1.2 Load losses 9.1.2.1 Load test
The losses described in Sub-clause 8.2 a) are
calculated from the resistance of the primary windings measured using direct current and corrected to the reference temperature, and from the current corresponding to the load at which the losses are being calculated
To determine the losses in Sub-clause 8.2 b) when
an on-load test is made the secondary winding losses are taken to be equal to the product of the slip and the total power transmitted to the secondary winding, i.e the power absorbed, decreased by the
core losses in Sub-clause 8.1 a) and the I2R losses in
the primary winding in Sub-clause 8.2 a) This
method gives directly the sum of the losses in
Sub-clauses 8.2 b) and 8.2 c) for wound rotor machines, and the losses in Sub-clause 8.2 b) for
cage machines For this latter type of machine, this
is the only applicable method as it is not possible to measure the resistance and current of the secondary winding directly When use is made of this method, the slip may be measured by a stroboscopic method
or by counting the beats of a permanent-magnet millivoltmeter connected between two rings (for motors with wound secondary windings) or the terminals of an auxiliary coil (for motors with short-circuited secondary windings) or between the ends of the shaft
9.1.2.2 Calculated values
For wound rotor motors, the losses in
Sub-clause 8.2 b) may be calculated from the
resistance measured by direct current and corrected
to the reference temperature, and from the secondary current calculated from a circle diagram
or equivalent circuit, account being taken of the true transformation ratio of the machine The type of circle diagram to be used should be agreed between manufacturer and purchaser
To make an on-load test, the losses in
Sub-clause 8.2 c) in the brushes cannot be measured
directly and these losses shall be taken as the product of the current flowing in the brushes and a fixed voltage drop The voltage drop in all brushes of the same phase shall be taken as 1.0 V for carbon or graphite brushes, and 0.3 V for metal-carbon brushes
9.1.2.3 Load test at reduced voltage
This method is also applicable to cage rotor machines
标准分享网
www.bzfxw.com
Trang 16When the voltage is reduced, while keeping the
rotational speed of the machine constant, the
currents diminish approximately in proportion to
the voltage, and the power approximately in
proportion to the square of the voltage When the
voltage is down to half its rated value, the currents
will then be reduced to about one half, and the
power to about one quarter, of their values at the
rated voltage
When a load is applied to an induction motor at a
reduced voltage Ur, the power absorbed P1r, the
main primary current I1r and the slip s are
measured, as well as the no-load current Ior at the
same reduced voltage Ur, and the no-load current Io
at the rated voltage Un
The current vector It of the load at rated voltage is
obtained by constructing a vector diagram
(Figure 3, page 23) in the following manner:
To the current vector I1r, multiplied by the ratio
add the vector:
The resultant vector represents the current which
would flow at the rated voltage Un for the following
absorbed power:
By means of the values I1, P1, thus determined, and
with the slip s measured at reduced voltage, it is
then possible to calculate the on-load losses, as
indicated in Sub-clause 9.1.2.1.
9.1.3 Additional load losses
Unless otherwise specified, it is assumed that the
losses specified in Sub-clauses 8.3 a) and 8.3 b) vary
as the square of the primary current and that their
total value at full load is equal to 0.5 % of the rated
input for motors and 0.5 % of the rated output for
generators
NOTE For some designs of small machines these losses might
be higher than 0.5 % of the rated input If, for a particular case,
the value is of importance, the loss should be determined by the
direct method of efficiency measurement.
9.2 Total loss measurement
9.2.1 Electrical back-to-back test (see clause 16)
When Identical machines are run at essentially the same rated conditions, the losses supplied from the electrical system are assumed to be equally
distributed and the efficiency is calculated from half the total losses and the electrical input to one machine
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
NOTE Where a gear box is required, as in the case of induction motors, it is necessary for the loss in this to be deducted from the electrical input before determining the losses in the electrical machine.
9.3 Direct measurement of efficiency
9.3.1 Braking test
When the machine is run at rated conditions of speed, voltage and current, the efficiency is taken as the ratio of output to input
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
9.3.2 Calibrated machine test (see clause 13)
When the machine is running in accordance with
clause 13 at rated conditions of speed, voltage and
current, the efficiency is then taken as the ratio of output to input
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
9.3.3 Mechanical back-to-back test
When identical machines are run at essentially the same rated conditions, the losses are assumed to be equally distributed, and the efficiency shall be calculated from half the total loss and the electrical input The driven machine operates as an induction generator if a source of reactive power is provided, and a suitable load is connected to its terminals.The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
Trang 17Section 4 Synchronous machines
10 Losses to be included
The total losses may be taken as the sum of the
following component losses:
10.1 Constant losses
a) Losses in active iron, and additional no-load
losses in other metal parts
b) Losses due to friction (bearings and brushes),
not including any losses in a separate lubricating
system Losses in common bearings shall be
stated separately whether or not such bearings
are supplied with the machine For water-driven
generators and synchronous motors for pump
storage schemes, the losses in thrust bearings,
and if the thrust bearings are associated with
guide bearings the total losses in those bearings
shall be stated separately The thrust-load,
temperature of the bearings, and type of oil and
oil temperature at which the loss values are valid
shall also be given
NOTE When the losses in a separate lubricating system are
required these should be listed separately.
c) The total windage loss in the machine
including power absorbed in integral fans, and in
auxiliary machines, if any, forming an integral
part of the machine The losses in auxiliary
machines such as external fans, water and oil
pumps not forming an integral part of the
machine, but provided exclusively for the
machine in question, shall be included only by
agreement
NOTE 1 When the losses in a separate ventilating system are
required they should be listed separately.
NOTE 2 For machines indirectly cooled or directly cooled by
hydrogen, see 11.5 of IEC 34-1.
10.2 Load losses
a) I2R losses in primary windings.
b) I2R losses in starting or damping windings.
NOTE These are significant only for single-phase machines.
10.3 Excitation circuit losses
a) I2R losses in the excitation windings and in the
excitation rheostats
b) All the losses in an exciter mechanically driven
from the main shaft which forms part of the
complete unit, and is used solely for exciting the
machine, together with losses in the rheostat in
the excitation circuit of such an exciter, but with
the exception of friction and windage losses
Losses in rotary rectifiers and in a gear, rope or
belt, or similar drive between shaft and exciter
should be included
All the losses in any apparatus for self-excitation and regulation receiving its input from the a.c supply connected to the terminals of the synchronous machine
In the case of a separate excitation supply such
as a battery, rectifier or motor generator set, no allowance is made for the losses in the excitation source or in the connections between the source and the brushes
c) The electrical losses in brushes
10.4 Additional load losses
a) Losses introduced by load in active iron and other metal parts other than the conductors.b) Eddy current losses in primary winding conductors
11 Determination of efficiency
11.1 Summation of losses
The efficiency can be calculated from the total losses which are assumed to be the summation of the losses obtained in the following manner:
11.1.1 Excitation circuit losses 11.1.1.1 Excitation winding I 2 R losses
These losses are calculated from the formula I2R,
taking for R the resistance of the excitation winding corrected to the reference temperature, and for I the
value of the exciting current for the particular rating of the machine, measured directly during the on-load test or calculated when this test is not possible Where such a calculation is made, the method to be used is for agreement between manufacturer and purchaser
11.1.1.2 Main rheostat losses
These losses are calculated from the formula I2R,
where R is the resistance of the part of the rheostat
in circuit for the rating considered, and I is the value
of the exciting current for the rating considered
defined as in Sub-clause 11.1.1.1 They are also
equal to the product IU of the excitation current at the particular rating, and the voltage U at the
terminals of the rheostat
NOTE Where a resistance is permanently connected in series in the excitation circuit it should be dealt with in the same way as the main rheostat.
11.1.1.3 Electrical losses in brushes
The sum of these losses shall be taken as the product of the excitation current at the rating considered and a fixed voltage drop The voltage drop allowed for all brushes of each polarity shall
be 1.0 V for carbon, or graphite brushes, and 0.3 V for metal-carbon brushes, i.e a total drop of 2.0 V for carbon or graphite brushes, and 0.6 V for metal-carbon brushes
Trang 18The sum of the losses according to
Sub-clauses 11.1.1.1, 11.1.1.2 and 11.1.1.3, is also
equal to the product IUe of the exciting current I and
the total excitation voltage Ue
11.1.1.4 Exciter losses
NOTE This applies only to the case where the exciter is
mechanically driven from the main shaft and is used solely for
exciting the synchronous machine.
These losses include the difference between the
power absorbed at the shaft of the exciter and the
useful power which it provides at the terminals of
the exciter2), and the excitation losses of the exciter
if this machine itself is excited by a separate source
If the exciter can be uncoupled from the main
machine and tested separately, the power which it
absorbs may be measured by the calibrated machine
method
If the exciter cannot be uncoupled from the main
machine, the power which it absorbs may be
measured either by the calibrated machine method
or by the retardation method applied to the whole
unit In these two methods, the power absorbed by
the exciter is obtained as the difference between the
total losses of the unit measured under identical
conditions, first with the exciter on-load and
secondly with the exciter not excited, the excitation
being furnished by an independent source
If none of these methods is applicable, the separate
losses should be determined as described under
Clause 6 for d.c machines (see Sub-clause 7.1.1.3,
last paragraph)
NOTE The manufacturer and purchaser should agree on the
method of determining the losses in apparatus for self-excitation
and regulation receiving their input from the a.c lines connected
to the terminals of the machine.
11.1.2 Constant losses
11.1.2.1 Unity power factor test at rated voltage and
frequency
The sum of the constant losses is generally
determined by the method of running the machine
as a motor on no-load The synchronous machine is
fed at its rated voltage and rated frequency, so as to
work as a motor on no-load The excitation is
adjusted so that the machine absorbs the minimum
a.c current The electrical power absorbed,
decreased by the I2R loss in the primary windings,
and, if appropriate, by the power absorbed by the
exciter, gives the sum of the constant losses
NOTE This latter correction may be avoided by the use of a
separate source of excitation power.
11.1.2.2 Open circuit test
The sum of the constant losses,
Sub-clauses 10.1 a), 10.1 b) and 10.1 c), the losses Sub-clause 10.1 a), and the sum of the losses, Sub-clauses 10.1 b) and 10.1 c), may also be
determined by driving the machine at its rated speed by means of a calibrated machine The machine is excited by an independent source so as to work as a generator with open circuit at a voltage equal to its rated voltage The power which it absorbs at its shaft, and which may be calculated from the power absorbed from the calibrated motor, gives the sum of the constant losses
Sub-clauses 10.1 a), 10.1 b) and 10.1 c) By
removing the excitation, the sum of the losses,
Sub-clauses 10.1 b) and 10.1 c) is obtained in the same manner The core losses Sub-clause 10.1 a)
are obtained by subtraction Given the small number of brushes used on synchronous machines,
it is generally not possible to separate the brush friction losses from the sum of the other constant losses by means of a test with the brushes lifted
11.1.2.3 Retardation test (see Clause 15)
The sum of the constant losses
Sub-clauses 10.1 a), 10.1 b) and 10.1 c), the losses Sub-clause 10.1 a) and the sum of the losses, Sub-clauses 10.1 b) and 10.1 c) may be determined
by using the retardation method
11.1.2.4 Unity power factor test at variable voltage
The losses Sub-clause 10.1 a), 10.1 b) and 10.1 c)
may be separated by running the machine as a motor at rated frequency, but at different voltages
as described in Sub-clause 9.1.1.3 of Section 3.
The power factor shall be maintained at unity by adjusting the excitation current during the test
11.1.2.5 Variable cooling gas density test
For machines cooled by a gas at variable pressure, the total windage loss may be separated from the friction losses by tests at different densities of cooling gas
NOTE Tests at different speeds are under consideration.
11.1.2.6 Calorimetric test (see Clause 17)
The bearing losses may be separately determined when possible by using the calorimetric method
NOTE The determination of losses in thrust bearings, possibly combined with guide bearings, in vertical shaft machines, should only be made by agreement.
2) The useful power at the terminals of the exciter is equal to the sum of the losses according to Sub-clauses 11.1.1.1, 11.1.1.2 and 11.1.1.3, of the main machine.
Trang 1911.1.3 Load losses
These consist of I2R losses in primary windings The
I2R losses in the primary winding are normally
measured during the short-circuit test described
in 11.1.4.
When they are to be given separately, the losses are
calculated from the rated current and the resistance
of the windings corrected to the reference
temperature
11.1.4 Additional load losses
Unless otherwise specified, the sum of the losses,
Sub-clauses 10.4 a) and 10.4 b) is measured by
means of the short-circuit test method
The machine to be tested, with its primary winding
short-circuited, is driven at its rated speed and so
excited that the current in the short-circuited
primary winding is equal to the rated current The
power absorbed at the shaft, decreased by the
mechanical losses, Sub-clauses 10.1 b) and 10.1 c),
and the power absorbed by the exciter, if
appropriate, presents the sum of the load losses and
the additional losses, Sub-clauses 10.2 and 10.4 If
the leakage reactance is abnormally high, as for a
machine for high frequency, a correction shall also
be made for core losses The load losses vary in
different senses as a function of the temperature
The sum of the load losses and additional losses is
assumed to be independent of the temperature and
no correction is made to a reference temperature
Unless otherwise specified, it is assumed that the
additional load losses vary as the square of the
armature current
NOTE It is recognized that the sum of the additional losses,
Sub-clauses 10.4 a) and 10.4 b), thus determined, is generally a
little higher than the losses which actually exist at rated load.
The power absorbed at the shaft of the machine
during the short-circuit test may be measured by
the calibrated machine method (Clause 13), or by
the retardation method (Clause 15).
11.2 Total loss measurement
11.2.1 Electrical back-to-back test
(see clause 16)
When identical machines are run at essentially the
same rated conditions, the losses are assumed to be
equally distributed and the efficiency shall be
calculated as in 11.3.3.
The test shall be made as nearly as possible at the
temperature attained in operation at the end of the
time specified in the rating No winding
temperature correction shall be made
11.2.2 Zero power factor test (see clause 14)
When the machine is run at rated conditions of speed, voltage and current, the total losses are equivalent to the absorbed power during the test, corrected for the difference between actual and the full-load exciting current losses
11.3 Direct measurement of efficiency
11.3.1 Braking test
When the machine is run at rated conditions of speed, voltage and current, the efficiency is taken as the ratio of output to input
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
11.3.2 Calibrated machine test (see clause 13)
When the machine is run at rated conditions of speed, voltage and current, the efficiency is taken as the ratio of output to input
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
11.3.3 Mechanical back-to-back test
When identical machines are run at essentially the same rated conditions, the losses are assumed to be equally distributed, and the efficiency shall be calculated from half the total losses and the electrical input
The test shall be made as nearly as possible at the temperature attained in operation at the end of the time specified in the rating No winding
temperature correction shall be made
Section 5 Methods of test
c) Measurement of the actual loss in a machine under a particular condition
Trang 20This is not usually the total loss, but comprises
certain component losses The method may,
however, be used to calculate the total loss or to
calculate a component loss
The choice of test to be made depends on the
information required, the accuracy required, and
the type and size of the machine involved Where
alternative methods are available for a particular
type of machine, the preferred method is indicated
(see Clause 18).
A distinction is made between direct and indirect
efficiency determination
The direct determination of efficiency is made by
measuring directly the power supplied by the
machine and the power absorbed by it
The indirect determination of efficiency is made by
measuring the losses of the machine Those losses
are added to the power supplied by the machine,
thus giving the absorbed power
The indirect determination may be carried out by
the following methods:
i) determination of separate losses for
summation;
ii) determination of total losses
NOTE The methods for determining the efficiency of machines
are based on a number of assumptions; it is therefore not possible
to make a comparison between the losses obtained by the direct
method of measurement and those obtained by the measurement
of the separate losses.
Unless otherwise specified, the guaranteed
efficiency of a machine is that which is based on the
determination of separate losses, but when there is
a choice of method, the evaluation of efficiency
should be base on the accuracy obtainable from the
method, the efficiency and the type of machine
involved.3)
When the efficiency or total loss is derived from the
measured input and output power, any inaccuracy
in these measurements appears as a direct error in
the efficiency (e.g with an accuracy of power
measurement not better than 1 %, the efficiency can
be 2 % in error or the total losses can be in error
by 2 % of the total input power) On small machines
or machines with relatively low efficiencies (say
below 90 %),3) this method may be quite acceptable
and gives a convenient form of test for such
machines On these and other machines efficiency
can be obtained with high accuracy by the
calculation of losses from direct measurements
13 Calibrated machine test
The machine of which the losses are to be measurement is separated from the network, uncoupled from its driving motor if necessary, and driven at its rated speed by a calibrated motor, that
is by an electric motor of which the losses have been previously determined with great accuracy, such that it is possible to determine the mechanical power which it furnishes at its shaft, knowing the electric power which it absorbs and its speed of rotation The mechanical power transmitted by the calibrated motor to the shaft of the machine under test is a measure of the losses of this latter machine for the working conditions under which the test is made In this method, the machine tested may be on no-load, excited or not excited, with or without brushes or short-circuit which enables categories of losses to be separated
As an alternative, the calibrated motor may be replaced by a dynamometer or by any other motor driving the machine under test through an appropriate torsionmeter, which enables the torque transmitted to the machine under test to be known, and hence the mechanical power absorbed by this latter machine
When use is made of this alternative, the speed of rotation, which comes directly into the calculation of the power, must be measured with extreme care
14 Zero power factor test
The machine operates as a motor at no-load and at rated speed, with a power factor in the
neighbourhood of zero, while the excitation current
is adjusted so that the machine carries its rated primary current
The supply voltage is such that the magnetic losses have the same value as in no-load operation at rated voltage The supply voltage is usually equal to the rated voltage unless this would give an active iron loss appreciably greater than that at full load In principle, the reactive power should be positive, i.e over-excited, but when this is impossible because the exciter voltage is not sufficient, the test can be made with absorption of the reactive power (i.e under-excited)
NOTE The accuracy of this method is dependent upon the accuracy at low power factor of the wattmeters used.
3) NOTE In some countries 90 % efficiency is accepted as a basis for using the indirect method whereas some other countries prefer a lower value, e.g 70 %.
Trang 2115 Retardation method
A retardation method can be used for determining
the separate losses of rotating electrical machines
The methods of determination of losses covered by
this clause are basically intended for large
synchronous machines, but the principles used can
also be applied to other machines (a.c induction and
d.c machines, exhibiting mainly an appreciable
rotational inertia) using the appropriate losses for
such machines
15.1 General
The retardation method is used to determine:
— sum of the friction loss and windage loss
(“mechanical losses”) in machines of all types;
— sum of losses in active iron and additional
open-circuit losses in d.c and synchronous
machines;
— sum of I2R losses in an operating winding and
additional load losses (“short-circuit losses”) in
synchronous machines
15.1.1 Fundamentals
The total of the loss Pt which retard the machine is
proportional to the product of the speed to which
these losses correspond and the deceleration at this
speed:
When n is expressed in rev/min and Pt is given in
kW, then the retardation constant C is:
where J is given in kg/m2
The deceleration dn/dt can be obtained either
directly, using an accelerometer, or indirectly, by
one of the methods given in 15.1.2, 15.1.3
and 15.1.4 below.
15.1.2 Method of the chord
This requires the measurement of the time interval
t2 – t1 during which the speed of the tested machine
changes from nN (1 + $) to nN (1 – $), see Figure 4
The ratio of speed interval 2 $ nN to time interval
t2– t1 is approximately the deceleration at rated
speed:
The value of deviation $ shall not be greater than 0,1 and may have to be less than this depending on the characteristics of the machine
15.1.3 Method of the limiting secant
This is a variant of the method of the chord and is intended to be applied in cases when the speed of rotation cannot be increased above the rated value The instant of time when the speed of rotation is of
the rated value nN is marked as t1, and the time instants at which the speed of rotation acquires the
values of (1 – $) nN are marked as t2 The deviation $ is successively decreased, and the time derivative of the speed of rotation is the limit of the tangent of the angle made by the line passing
through the points t1 and t2 with the time axis, as $ approaches zero, see Figure 5
15.1.4 Method of the average speed of rotation
If t1, t2 and t3 represent the successively recorded
time readings, the shaft making N complete
revolutions within the time interval between any two subsequent readings, then the average values of speed during the time intervals shall be:
and the deceleration of the shaft at an intermediate
moment of time t2
Calculated values of deceleration are plotted against the average values of speed of rotation The value of deceleration at the rated speed of rotation is determined from the curve
15.2 Composition of retardation tests
15.2.1 Composition of tests with known moment
of inertia
When the moment of inertia of a machine rotating part is known by measurement or by design, then for a d.c machine two basic retardation tests are sufficient: the machine running unexcited and the machine running open-circuited, excited at rated voltage at rated speed For a synchronous machine
a third retardation test should be made with the armature winding being short-circuited and the excitation set to give the rated armature current
Trang 22The first test gives the mechanical losses of the
tested machine from the formula:
The second test gives the total of mechanical losses
and iron losses from the formula:
The third test gives the sum of mechanical losses
and short-circuit losses from the formula:
In the above equations
are the values of speed derivative in time in the
first, second and third tests respectively
The iron losses are determined as the difference of
the losses measured in the second and first tests
The sum of the I2R losses and the additional losses
in the armature circuit are determined as the
difference of losses measured in the third and first
tests Separation of this sum into components If
required, is done by subtracting from it the I2R
losses in the armature circuit calculated from the
armature circuit resistance corresponding to the
test temperature For this purpose the winding
temperature shall be deduced by the appropriate
method of temperature measurement directly after
each retardation test with the armature circuit
being short-circuited
15.2.2 Composition of test with unknown
moment of inertia
When the moment of inertia of a machine rotating
part is not known, or the machine is coupled
mechanically to other rotating parts, e.g a turbine,
whose inertia is not known, some additional tests
shall be carried out to determine the retardation
constant C.
In the instance where there is a possibility to run the tested machine as an unloaded motor from a power supply of the proper voltage, number of phases and frequency (in the case of a.c machines), and the power supplied to the tested machine can be measured, (equal to the sum of the mechanical
losses and iron losses as the armature circuit I2R are
usually ignored), then the retardation constant C is
determined from the formula:
If the measurement of power is difficult because of frequency oscillations of the power supply, then as
an alternative the energy supplied to the tested machine may be measured with an integrating meter For this purpose it is necessary to run the machine as a motor for some time at constant supply conditions
In the instance where there is no possibility of running the tested machine as an unloaded motor, then, in addition to the three retardation test
considered in 15.2.1, one more retardation test shall
be conducted The tested machine in this case is
slowed down by any losses P which can be measured and are of the same order as the expected losses PFeand Pk For this purpose the open-circuit or short-circuit losses of a connected transformer can
be used, which are separately measured
Alternatively, if an exciter or auxiliary generator mounted on the tested machine shaft is available, its load with a ballast resistance may be used
If the tested machine is slowed down by the transformer open-circuit losses, and the short-circuit losses according to the transformer open-circuit current are ignored, then
hence
Trang 23When the tested machine is slowed down by the
transformer short-circuit losses, usually the iron
losses corresponding to magnetic flux in the
short-circuited transformer are ignored Hence
and
When the tested machine is slowed down by an
exciter or auxiliary generator loaded with a ballast
resistance, the retardation losses consist only of the
tested machine mechanical losses Pf and the
measured load P (with allowance for efficiency of the
load machine that can be determined by
calculations) Hence:
so that
15.3 Retardation test procedure
15.3.1 State of a tested machine during
retardation tests
A tested machine shall be completely assembled as
for normal operation The bearings shall be “run in”
prior to the test The air temperature shall be
adjusted wherever possible to the normal
temperature at which the windage loss
measurement is required by throttling the air
coolant flow The bearing temperatures shall be
adjusted to the normal temperature at which the
bearings operate with rated load, by adjusting the
of the runner in the air produces windage losses which can be stated experimentally or from calculation by agreement between manufacturer and purchaser
15.3.3 Rotation of a tested machine
In some cases the tested machine can be driven by its normal prime mover, e.g by Pelton turbine where the water supply to the runner can be cut off instantly However, the tested machine is usually running as a motor on no-load, fed from a separate source with a wide range of variable speed In all cases the excitation shall be obtained from a separate source with a rapid and precise voltage control The excitation from the inherent
mechanically-coupled exciter is not recommended in principle, but may be permitted in those when the value of the deviation of speed $ is relatively small, e.g it does not exceed 0,05 In all these cases the losses in exciters coupled to the shaft of the tested machine shall be taken into account
15.3.4 Procedure performed prior to starting
the tests
Each test begins with the tested machine being
rapidly accelerated to a speed above (1 + $) nN so that during deceleration to this speed the machine can be placed in the required condition, namely:
— the machine is disconnected from a supply source;
— in the case of retardation by only mechanical losses, the machine field is suppressed;
— in the case of retardation by the sum of the mechanical loss and short-circuit loss, the machine field is suppressed, the armature terminals are short-circuited and the machine is reexcited to the preset short-circuit current;
— in the case of retardation by the transformer losses after field suppression, the tested machine
is connected to the transformer previously set to
a certain state (at no-load or short-circuit) and excited to the preset values of current or open-circuit voltage;
Trang 24— in the case of retardation by the exciter load
losses or auxiliary generator mounted on the
machine shaft, the tested machine field is
suppressed and the specified load is set
simultaneously
In all cases described above a sufficient time delay
shall separate the switching off of the supply and
starting the measurements to allow electromagnetic
transients to decay
In the case of retardation by the sum of mechanical
and iron losses or by the open-circuit losses of a
supply transformer, no procedures are required
after the machine is disconnected from the supply if
the tested machine excitation corresponds to the
preset open-circuit voltage, in the case of a
synchronous machine, at rated speed and unity
power factor
15.3.5 Procedures during retardation
The readings of all instruments used for each test
(field current ammeter, open-circuit voltage
voltmeter, short-circuit current ammeter) and of all
instruments required to measure the power in
additional retardation tests when the moment of
inertia J is not known shall be taken at the instant
when the tested machine passes through rated
speed; no readings at this instant are required in the
case of an unexcited retardation test
The measured values of open-circuit voltage or
short-circuit current shall not differ from the preset
values by more than ± 2 % The calculated final
value of the speed derivative in time for each of the
tests shall be adjusted proportionally by the ratio of
the square of the preset value to the measured
value
15.3.6 Programme of retardation tests
The retardation tests shall be conducted as a series
without interruption, whenever possible It is
recommended that the series start and finish with
some retardation tests of an unexcited machine If
for any reason the test series is not conducted in a
continuous manner then it is recommended that
each subsequent series of tests start and finish with
some unexcited retardation tests
Tests may be either repeated several times at the
same preset values of open-circuit voltage or
short-circuit current, e.g at rated values, or at
various values within limits of the order
of 95 %–105 % of the rated values In the first case
the arithmetic mean values obtained from all
measurements are assumed to be the real measured
value of each type of loss In the second case the
values are plotted on a curve as a function of voltage
or current Real measured values are assumed to be
those occurring at the points of intersection of the
preset values of voltage or current as read from the
curves
Additional retardation tests, when the moment of inertia of the tested machine is not known, shall be conducted at the same values of voltage or current
as those obtained with the winding open or short-circuited If this is not possible the respective values shall be determined from curves as indicated above
15.4 Taking of measurements
15.4.1 Methods of measurements
The measurements taken during retardation tests are aimed at obtaining the required value of the speed derivative in time and may be performed by one of the three methods:
a) accelerometric — direct measurement of deceleration with time:
b) tachometric — by determining the dependence
of speed with time:
n = f (t);
c) chronographic — by determining the dependence of angular displacement of the tested machine shaft with time:
S = f (t).
For all cases recording measuring instruments may
be used both with continuous and with discrete recording of measured values and time
15.4.2 Accelerometric method
The dependence of speed on time for large machines having a complex ventilation route may not be regular As a consequence of this the instantaneous values of deceleration during retardation at the moment of passing through rated speed may be random Therefore, true values of the speed derivative may be determined by plotting measured decelerations versus time or speed and using a suitable curve fitting or correlation technique
15.4.3 Tachometric method
A plot of speed versus time is obtained from the results of measurements On this plot the time instants are defined at which the speed acquired the values indicated for the chord or limiting secant method The differences between the times at the lower and upper limits of speed are used to calculate the decelerations
If there is in exciter or any other electrical machine
on the tested machine shaft, it can be used as a tachogenerator, provided that the voltage signal does not pulsate with the speed of rotation of the tested machine The excitation shall be supplied from a stable d.c source, such as a separate storage battery
Trang 25If the voltage signal does pulsate with the speed of
rotation or when there is no such tachogenerator on
the tested machine, a coupled d.c machine may be
used It can be driven from the shaft of the tested
machine by a seamless belt or by other means to
provide smooth rotation
Readings of the speed may be made either in the
exact time intervals, specified by the respective
method, in which case there is no need for special
recording of time or of signals from the tested
machine shaft; in this case, the readings of time
shall be taken concurrently with readings of speed
There is no need to take readings with each turn of
the shaft; usually 30 to 40 readings during the
whole test are quite sufficient
With the availability of high-accuracy measuring
instruments, the measurement of speed of rotation
may be substituted by measurement of the
instantaneous values of speed or of the period of the
voltage of the tested machine or of any other a.c
machine situated on its shaft; it is not necessary
that the number of pole pairs of both machines is
equal
15.4.4 Chronographic method
The time-counters used may be either visual
indicators with continuous (non-stepwise) motion of
the pointer, or digital indicators with printers
(electrical or mechanical)
Time readings shall be taken according to the
signals obtained from the tested machine shaft,
either with each complete revolution of the shaft or
for a known number of revolution
NOTE If when using the tachometric method the speed of
rotation is determined by signals from the tested machine shaft,
then the time readings may be used both for tachometric and
chronographic methods, thus providing a mutual check.
In some cases, when the unit has smooth
deceleration characteristics, sufficient accuracy can
be obtained by measuring the time for retardation
between two speeds with the same difference to the
rated speed
The stator voltage frequency provides the best
means of determining the speed of a synchronous
machine
15.4.5 Measurement of losses in bearings
The losses in bearings and thrust bearings can be subtracted from the total sum of the mechanical losses, if required These may be determined by the calorimetric method in with IEC 34-2A If the tested machine uses direct-flow cooling of the bearings, these losses are distributed between the tested machine and any other coupled to it mechanically, such as turbine, in proportion to the masses of their rotating parts If there is no direct-flow cooling, the distribution of bearing losses shall be determined from empirical formulae by agreement between manufacturer and purchaser
16 Electrical back-to-back test
This method is applicable when two identical machines are available The machines are coupled mechanically and electrically so as to operate at rated speed, one as a motor and the other as a generator The actual temperature at which the measurements are carried out should be as close as possible to the working temperature and no further correction should be made The losses of the assembled machines are supplied either by a network to which they are connected, or by a calibrated driving motor, or by a booster, or else by
a combination of these various means
The average value of the armature currents is adjusted to the rated value, the average of the voltage of the two armatures is above or below the rated voltage by an amount equal to the voltage drop, depending on whether the d.c machines are intended to be used respectively as generators or as motors
Where two induction machines are electrically connected, they should be mechanically coupled with a speed adjusting device, such as a gear box, to ensure the correct circulation of power The
magnitude of power circulated depends upon the difference in speed The electrical system supplying the losses to the two machines will be required to provide magnetizing kvar to both machines
When two synchronous machines are electrically connected, they should be mechanically coupled with a correct angular phase relationship The magnitude of the power circulated depends upon the difference in phase angle between them
Trang 2617 Calorimetric test
Measurement of losses by calorimetric methods
shall be performed in accordance with IEC 34-2A
(given in Annex B)
18 Schedule of preferred tests
18.1 D.C machines
The preferred test for d.c machines is in accordance
with Sub-clause 7.1 and the preferred method of
calculating the efficiency is in accordance with
Sub-clause 7.1.2.
18.2 Polyphase induction machines
The preferred test for polyphase induction machines
is in accordance with Sub-clause 9.1 and the
preferred method of determining the constant losses
is in accordance with Sub-clause 9.1.1.1.
18.3 Synchronous machines
The preferred test for synchronous machines is in
accordance with Sub-clause 11.1 and the preferred
method of determining the constant losses is in
accordance with Sub-clause 11.1.2.1.
Figure 1 — Mechanical back-to-back test
Figure 2 — Electrical back-to-back test