If additional cooling system such as fans or pumps… are used only for temporary overload conditions and not for continuous rating, then such overloading rating cannot be claimed to be as
Trang 1Medium power transformers
50 Hz, with highest voltage for equipment not exceeding 36 kV
Part 1: General requirements BSI Standards Publication
Trang 2NORME EUROPÉENNE
English VersionMedium power transformers 50 Hz, with highest voltage for equipment not exceeding 36 kV - Part 1: General requirements
Transformateurs 50 Hz de moyenne puissance, de tension
la plus élevée pour le matériel ne dépassant pas 36 kV
-Partie 1: Exigences générales
Mittelleistungstransformatoren 50 Hz, mit einer höchsten Spannung für Betriebsmittel nicht über 36 kV - Teil 1:
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
European Committee for Electrotechnical StandardizationComité Européen de Normalisation ElectrotechniqueEuropäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
National foreword
This British Standard is the UK implementation of EN50588-1:2015+A1:2016 It supersedes BS EN 50464-1:2007+A1:
2012 and BS EN 50541-1:2011 which arewithdrawn
BSI, as a member of CENELEC, is obliged to publish
EN 50588-1:2015+A1:2016 as a British Standard However, attention
is drawn to the fact that during the development of this EuropeanStandard the UK committee voted against its approval as a Europeanstandard The UK committee submitted a negative vote for thefollowing reasons:
a) This standard is not applicable to transformers for tram systems, whichhave the same, or similar, operating characteristics to railways The UKcommittee is of the opinion that the relevant exclusion in clause 1 shouldread ‘transformers and auto-transformers specifically designed for railwayand other traction feeding systems’
b) The UK committee advises that the de-energised tapping range forsingle-phase liquid immersed transformers with Sr ≤ 100 kVA should be ≤7,5 % as this is the limit for pad-mounted transformers in the
United Kingdom
The start and finish of text introduced or altered by amendment isindicated in the text by tags Tags indicating changes to CEN text carrythe number of the CEN amendment For example, text altered by CENamendment A1 is indicated by
The UK participation in its preparation was entrusted to TechnicalCommittee PEL/14, Power Transformers
A list of organizations represented on this committee can be obtained onrequest to its secretary
This publication does not purport to include all the necessary provisions of
a contract Users are responsible for its correct application
© The British Standards Institution 2017
Published by BSI Standards Limited 2017ISBN 978 0 580 97536 3
Amendments/corrigenda issued since publication
Trang 3NORME EUROPÉENNE
English Version Medium power transformers 50 Hz, with highest voltage for equipment not exceeding 36 kV - Part 1: General requirements
Transformateurs 50 Hz de moyenne puissance, de tension
la plus élevée pour le matériel ne dépassant pas 36 kV -
Partie 1: Exigences générales
Mittelleistungstransformatoren 50 Hz, mit einer höchsten Spannung für Betriebsmittel nicht über 36 kV - Teil 1:
Allgemeine Anforderungen
This European Standard was approved by CENELEC on 2015-06-25 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member
This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom
European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members
Ref No EN 50588-1:2015 E
June 2015
Trang 45�1 Highest voltages for equipment for winding with Um > 1,1 kV �������������������������������� 9
5�2 Rated voltage for winding with Um ≤ 1,1 kV ���������������������������������������������������������� 9 5�3 Tapping ��������������������������������������������������������������������������������������������������������������� 95�4 Connection designations for three phase transformers ����������������������������������������� 9
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance �������������������� 10 6�1 General ������������������������������������������������������������������������������������������������������������� 10
6�2 Transformers with rated power Sr ≤ 3 150 kVA ��������������������������������������������������� 116�2�1 General information ������������������������������������������������������������������������������� 11
6�2�2 One winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV ����������� 126�2�3 Load loss and no load loss in case of other insulation level �������������������� 146�2�4 Load loss and no load loss in case of dual voltage ��������������������������������� 146�2�5 Three winding transformers for PV applications �������������������������������������� 15
6.3 Transformers with rated power 3 150 kVA < Sr < 40 000 kVA ������������������������������ 156�4 Transformers with special requirements ������������������������������������������������������������� 176�4�1 Rated power not included in the list �������������������������������������������������������� 176�4�2 Transformers equipped with tapping connections suitable for
operation while transformer is energised or on load and rated
power Sr ≤ 3 150 kVA ����������������������������������������������������������������������������� 176�4�3 Liquid immersed pole mounted transformers ������������������������������������������ 186�4�4 PEI values for single-phase liquid immersed transformers with
Sr ≤ 100 kVA ������������������������������������������������������������������������������������������ 19
7 Tolerances ������������������������������������������������������������������������������������������������������������������ 197�1 Tolerances during factory acceptance tests �������������������������������������������������������� 19 7�1�1 General ������������������������������������������������������������������������������������������������� 19
7�1�2 Transformers subject to maximum losses ����������������������������������������������� 197�1�3 Transformers subject to minimum PEI ���������������������������������������������������� 197�2 Tolerances for Market surveillance ��������������������������������������������������������������������� 197.2.1 Acceptance criteria �������������������������������������������������������������������������������� 197�2�2 Transformers subjected to max losses ��������������������������������������������������� 207�2�3 Transformers subjected to PEI ��������������������������������������������������������������� 207�3 Uncertainties for market surveillance verification ������������������������������������������������ 20
8 Rating plate ���������������������������������������������������������������������������������������������������������������� 21
9 Tests �������������������������������������������������������������������������������������������������������������������������� 219�1 Routine tests ����������������������������������������������������������������������������������������������������� 219�2 Type tests ��������������������������������������������������������������������������������������������������������� 219�3 Special tests ������������������������������������������������������������������������������������������������������ 219�4 Special test for corrugated tank ������������������������������������������������������������������������� 219�4�1 General information ������������������������������������������������������������������������������� 219�4�2 Temperature variation ���������������������������������������������������������������������������� 22
Trang 59�4�3 Sealing temperature ������������������������������������������������������������������������������ 229�4�4 Calculation of the volume variation ��������������������������������������������������������� 229�4�5 Test procedure ��������������������������������������������������������������������������������������� 229.5 Other technologies with level of no load loss AAA0 ��������������������������������������������� 23
10 Design requirements ��������������������������������������������������������������������������������������������������� 2310�1 Liquid immersed transformers ���������������������������������������������������������������������������� 2310�1�1 Type of liquid preservation system and degree of sealing ����������������������� 2310�1�2 Terminal markings���������������������������������������������������������������������������������� 23 10�1�3 Terminations ������������������������������������������������������������������������������������������ 24
10�1�4 Distance between bushings ������������������������������������������������������������������� 24 10�1�5 Rollers ��������������������������������������������������������������������������������������������������� 2410�2 Dry-type transformers ���������������������������������������������������������������������������������������� 24 10�2�1 Terminals ����������������������������������������������������������������������������������������������� 24 10�2�2 Enclosure ���������������������������������������������������������������������������������������������� 24
11 Accessories ���������������������������������������������������������������������������������������������������������������� 2511�1 Liquid immersed transformers ���������������������������������������������������������������������������� 2511�2 Dry-type transformers ���������������������������������������������������������������������������������������� 25Annex A (informative) Calculation of PEI and kPEI �������������������������������������������������������������� 27A.1 Calculation of Peak Efficiency Index ������������������������������������������������������������������ 27A.2 Calculation of kPEI ��������������������������������������������������������������������������������������������� 27Ann ex ZZ (informative) Relationship between this European Standard and the
requirements of Commission Regulation (EC) No 548/2014 of 21 May 2014 on
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers ����������������������������������������� 29Bibliography ���������������������������������������������������������������������������������������������������������������������� 32
Trang 6Foreword
This document (EN 50588-1:2015) has been prepared by CLC/TC 14 "Power transformers"
The following dates are fixed:
- latest date by which this document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
(dop) 2016-06-25
- latest date by which the national
standards conflicting with this
document have to be withdrawn
(dow) 2018-06-25
This document supersedes EN 50464-1:2007 and EN 50541-1:2011
EN 50588-1:2015 includes the following significant technical changes with respect to
EN 50464-1:2007 and EN 50541-1:2011:
- both liquid filled and dry-type transformers are covered in the same document;
- the scope of applicability is extended in terms of rated power;
- new values of no load loss, load loss and sound power level for different values of rated
power are specified;
- for transformers having rated power above 3 150 kVA, the concept of Peak Efficiency Index
is introduced
Attention is drawn to the possibility that some of the elements of this document may be the subject
of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights
This document has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association, and supports requirements of Commission
Regulation (EC)
For the relationship with requirements of Commission Regulation (EC) see informative Annex ZZ,
which is an integral part of this document
5
1 Scope
This European Standard covers medium power transformers ‘Medium power transformer’ means apower transformer with a highest voltage for equipment higher than 1,1 kV, but not exceeding 36 kV and a rated power equal to or higher than 5 kVA but lower than 40 MVA
National practices may require the use of highest voltages for equipment up to (but not including)
52 kV, when the rated voltage is less than 36 kV (such as Um= 38,5 kV or Um= 40,5 kV) This isconsidered to be an unusual case of a large power transformer, where the requirements are those
for a medium power transformer with Um= 36 kV
NOTE 1 ‘Large power transformer’ means a power transformer with a highest voltage for equipmentexceeding 36 kV and a rated power equal or higher than 5 kVA, or a rated power equal to or higher than
40 MVA regardless of the highest voltage for equipment Large power transformers are in the scope of
The following transformers are excluded from this European Standard:
- instrument transformers, specifically designed to supply measuring instruments, meters,relays and other similar apparatus;
- transformers with low-voltage windings specifically designed for use with rectifiers to provide a DC supply;
- transformers specifically designed to be directly connected to a furnace;
- transformers specifically designed for offshore applications and floating offshore applications;
- transformers specially designed for emergency installations;
- transformers and auto-transformers specifically designed for railway feeding systems;
- earthing or grounding transformers, this is, three-phase transformers intended to provide aneutral point for system grounding purposes;
- traction transformers mounted on rolling stock, this is, transformers connected to an AC or
DC contact line, directly or through a converter, used in fixed installations of railwayapplications;
- starting transformers, specifically designed for starting three-phase induction motors so as
to eliminate supply voltage dips;
- testing transformers, specifically designed to be used in a circuit to produce a specificvoltage or current for the purpose of testing electrical equipment;
- welding transformers, specifically designed for use in arc welding equipment or resistance welding equipment;
- transformers specifically designed for explosion-proof and underground mining applications,
- transformers specifically designed for deep water (submerged) applications;
- medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5 MVA;
- large power transformers where it is demonstrated that for a particular application,technically feasible alternatives are not available to meet the minimum efficiencyrequirements set out by the commission regulation (EU) No 548/2014;
- large power transformers which are like for like replacements in the same physicallocation/installation for existing large power transformers, where this replacement cannot be achieved without entailing disproportionate costs associated to their transportation and/orinstallation
4
Foreword to amendment A1
This document (EN 50588-1:2015/A1:2016) has been prepared by CLC/TC 14 "Power transformers"
The following dates are fixed:
- latest date by which this document has to be
implemented at national level by publication of
an identical national standard or by
endorsement
(dop) 2017-05-23
- latest date by which the national standards
conflicting with this document have to
be withdrawn
(dow) 2019-05-23
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights
This document has been prepared under a mandate given to CENELEC by the European Commission and
the European Free Trade Association, and supports requirements of Commission Regulation (EU)
For the relationship with Commission Regulation (EU) see informative Annex ZZ, which is an integral part of
EN 50588-1:2015
Trang 74
Foreword
This document (EN 50588-1:2015) has been prepared by CLC/TC 14 "Power transformers"
The following dates are fixed:
- latest date by which this document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
(dop) 2016-06-25
- latest date by which the national
standards conflicting with this
document have to be withdrawn
(dow) 2018-06-25
This document supersedes EN 50464-1:2007 and EN 50541-1:2011
EN 50588-1:2015 includes the following significant technical changes with respect to
EN 50464-1:2007 and EN 50541-1:2011:
- both liquid filled and dry-type transformers are covered in the same document;
- the scope of applicability is extended in terms of rated power;
- new values of no load loss, load loss and sound power level for different values of rated
power are specified;
- for transformers having rated power above 3 150 kVA, the concept of Peak Efficiency Index
is introduced
Attention is drawn to the possibility that some of the elements of this document may be the subject
of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights
This document has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association, and supports requirements of Commission
Regulation (EC)
For the relationship with requirements of Commission Regulation (EC) see informative Annex ZZ,
which is an integral part of this document
5
1 Scope
This European Standard covers medium power transformers ‘Medium power transformer’ means a power transformer with a highest voltage for equipment higher than 1,1 kV, but not exceeding 36 kV and a rated power equal to or higher than 5 kVA but lower than 40 MVA
National practices may require the use of highest voltages for equipment up to (but not including)
52 kV, when the rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV) This is considered to be an unusual case of a large power transformer, where the requirements are those
for a medium power transformer with Um = 36 kV
NOTE 1 ‘Large power transformer’ means a power transformer with a highest voltage for equipment exceeding 36 kV and a rated power equal or higher than 5 kVA, or a rated power equal to or higher than
40 MVA regardless of the highest voltage for equipment Large power transformers are in the scope of
The following transformers are excluded from this European Standard:
- instrument transformers, specifically designed to supply measuring instruments, meters, relays and other similar apparatus;
- transformers with low-voltage windings specifically designed for use with rectifiers to provide a DC supply;
- transformers specifically designed to be directly connected to a furnace;
- transformers specifically designed for offshore applications and floating offshore applications;
- transformers specially designed for emergency installations;
- transformers and auto-transformers specifically designed for railway feeding systems;
- earthing or grounding transformers, this is, three-phase transformers intended to provide a neutral point for system grounding purposes;
- traction transformers mounted on rolling stock, this is, transformers connected to an AC or
DC contact line, directly or through a converter, used in fixed installations of railway applications;
- starting transformers, specifically designed for starting three-phase induction motors so as
to eliminate supply voltage dips;
- testing transformers, specifically designed to be used in a circuit to produce a specific voltage or current for the purpose of testing electrical equipment;
- welding transformers, specifically designed for use in arc welding equipment or resistance welding equipment;
- transformers specifically designed for explosion-proof and underground mining applications,
- transformers specifically designed for deep water (submerged) applications;
- medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5 MVA;
- large power transformers where it is demonstrated that for a particular application, technically feasible alternatives are not available to meet the minimum efficiency requirements set out by the commission regulation (EU) No 548/2014;
- large power transformers which are like for like replacements in the same physical location/installation for existing large power transformers, where this replacement cannot be achieved without entailing disproportionate costs associated to their transportation and/or installation
5
In case one of the last two exclusions is claimed, this should be documented at the signature of the contract with a declaration made by the customer�
Trang 86
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies
EN 50180 Bushings above 1 kV up to 52 kV and from 250 A to 3,15 kA for liquid
filled transformers — Part 1: General requirements for bushings
EN 50181 Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA
for equipment other than liquid filled transformers
EN 50216 (all parts) Power transformer and reactor fittings
EN 50386 Bushings up to 1 kV and from 250 A to 5 kA, for liquid filled transformers
EN 50387 Busbar bushings up to 1 kV and from 1,25 kA to 5 kA, for liquid filled
transformers
EN 50464-4 Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to
2 500 kVA with highest voltage for equipment not exceeding 36 kV — Part 4: Requirements and tests concerning pressurised corrugated tanks
EN 60076 (all parts) Power transformers (IEC 60076, all parts)
EN 60076-19 Power transformers — Part 19: Rules for the determination of
uncertainties in the measurement of the losses on power transformers and reactors (IEC/TS 60076-19)
EN 60085 Electrical insulation — Thermal evaluation and designation
EN 60505 Evaluation and qualification of electrical insulation systems (IEC 60505)
EN 61100 Classification of insulating liquids according to fire point and net calorific
value (IEC 61100)
IEC/TR 60616 Terminal and tapping markings for power transformers
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 60076-1:2011 and the following apply
3.1 load factor
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application For dated references, only the edition cited applies For undated
references, the latest edition of the referenced document (including any amendments) applies
EN 50180 Bushings above 1 kV up to 52 kV and from 250 A to 3,15 kA for liquid
filled transformers — Part 1: General requirements for bushings
EN 50181 Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA
for equipment other than liquid filled transformers
EN 50216 (all parts) Power transformer and reactor fittings
EN 50386 Bushings up to 1 kV and from 250 A to 5 kA, for liquid filled transformers
EN 50387 Busbar bushings up to 1 kV and from 1,25 kA to 5 kA, for liquid filled
transformers
EN 50464-4 Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to
2 500 kVA with highest voltage for equipment not exceeding 36 kV — Part 4: Requirements and tests concerning pressurised corrugated tanks
EN 60076 (all parts) Power transformers (IEC 60076, all parts)
EN 60076-19 Power transformers — Part 19: Rules for the determination of
uncertainties in the measurement of the losses on power transformers and reactors (IEC/TS 60076-19)
EN 60085 Electrical insulation — Thermal evaluation and designation
EN 60505 Evaluation and qualification of electrical insulation systems (IEC 60505)
EN 61100 Classification of insulating liquids according to fire point and net calorific
value (IEC 61100)
IEC/TR 60616 Terminal and tapping markings for power transformers
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 60076-1:2011 and the
following apply
3.1
load factor
k
ratio of actual input current over the rated current of transformer where the actual current and rated
current are constant over time
Note 1 to entry: Normally 0 ≤ k ≤ 1
EI
ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted apparent power of the transformer
3.4 Peak Efficiency Index PEI
highest value of efficiency index that can be achieved at the optimum value of load factor Note 1 to entry: See Annex A for derivation
3.5 load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs Note 1 to entry: See Annex A for derivation
3.6 declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts Guaranteed values are related to contract, whereas declared values are related to compliance verifications with COMMISSION REGULATION (EU) No 548/2014
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages below 400 V and above 690 V
BS EN 50588-1:2015+A1:2016
EN 50588-1:2015+A1:2016
6
NOTE 3 This standard covers the transformers under the Commission Regulation (EU) No 548/2014 and
gives additional specific guidance for single phase transformers, multi winding transformers and for transformers
with OF or OD cooling systems, necessary for the correct application of energy efficiency requirements to these
categories of transformers�
Trang 96
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies
EN 50180 Bushings above 1 kV up to 52 kV and from 250 A to 3,15 kA for liquid
filled transformers — Part 1: General requirements for bushings
EN 50181 Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA
for equipment other than liquid filled transformers
EN 50216 (all parts) Power transformer and reactor fittings
EN 50386 Bushings up to 1 kV and from 250 A to 5 kA, for liquid filled transformers
EN 50387 Busbar bushings up to 1 kV and from 1,25 kA to 5 kA, for liquid filled
transformers
EN 50464-4 Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to
2 500 kVA with highest voltage for equipment not exceeding 36 kV — Part 4: Requirements and tests concerning pressurised corrugated tanks
EN 60076 (all parts) Power transformers (IEC 60076, all parts)
EN 60076-19 Power transformers — Part 19: Rules for the determination of
uncertainties in the measurement of the losses on power transformers and reactors (IEC/TS 60076-19)
EN 60085 Electrical insulation — Thermal evaluation and designation
EN 60505 Evaluation and qualification of electrical insulation systems (IEC 60505)
EN 61100 Classification of insulating liquids according to fire point and net calorific
value (IEC 61100)
IEC/TR 60616 Terminal and tapping markings for power transformers
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 60076-1:2011 and the following apply
highest value of efficiency index that can be achieved at the optimum value of load factor
Note 1 to entry: See Annex A for derivation
3.5
load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs
Note 1 to entry: See Annex A for derivation
3.6
declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities
Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts Guaranteed values are related to contract, whereas declared values are related to compliance verifications with COMMISSION REGULATION (EU) No 548/2014
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages below 400 V and above 690 V
Note 2 to entry: The term “low-voltage winding” refers to the winding having the lowest rated voltage as per
EN 60076-1, whatever its voltage level�
Note 3 to entry: This definition does not include:
- transformers which are intended to provide AC from DC sources such as transformers for wind turbine and photo voltaic applications;
- transformers designed for DC transmission and distribution applications�
Trang 107
3.3 Efficiency Index
EI
ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted apparent power of the transformer
3.4 Peak Efficiency Index PEI
highest value of efficiency index that can be achieved at the optimum value of load factor Note 1 to entry: See Annex A for derivation
3.5 load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs Note 1 to entry: See Annex A for derivation
3.6 declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts Guaranteed values are related to contract, whereas declared values are related to compliance verifications with COMMISSION REGULATION (EU) No 548/2014
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages below 400 V and above 690 V
ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted
apparent power of the transformer
3.4
Peak Efficiency Index
PEI
highest value of efficiency index that can be achieved at the optimum value of load factor
Note 1 to entry: See Annex A for derivation
3.5
load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs
Note 1 to entry: See Annex A for derivation
3.6
declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities
Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts
Guaranteed values are related to contract, whereas declared values are related to compliance verifications with
COMMISSION REGULATION (EU) No 548/2014
4 Environmental classes
Classification of insulating liquids according to fire point and net calorific value is given in EN 61100
Climatic, environmental and fire behaviour classes for dry–type transformers are defined in
EN 60076-11
5 Electrical characteristics
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages
below 400 V and above 690 V
BS EN 50588-1:2015 EN 50588-1:2015 (E)
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand test between windings and earth need to be stated by the purchaser The most usual values are respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr ≤ 100kVA, for three phase transformers with a rated power Sr ≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr < 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
transformer to be installed on fixed or floating offshore platforms, offshore wind turbines or on board
of ships and all kind of vessels
3.7.4
transformers specially designed for emergency installations
transformer designed only to provide cover for a specific time limited situation when the normal power
supply is interrupted either due to an unplanned occurrence such as failure or a station refurbishment,
but not to permanently upgrade an existing substation
Note 1 to entry: Such transformer could have some specific features that make it suitable for emergency or
temporary use as opposed to normal use� Example of some specific features:
- multiple windings making it suitable for use at several locations;
- special low weight or dimensions for easy transport, or special capability to be disassembled into smaller units
for transport;
- increased overload capability achieved by the use of special materials;
- permanent mounting on a transporter arrangement�
3.7.5
transformers and auto-transformers specifically designed for railway feeding systems
transformer as defined in EN 50329
3.7.6
earthing or grounding transformers, this is, three-phase transformers intended to provide a
neutral point for system grounding purposes
transformer as defined in paragraph 3�1�10 of EN 60076-6:2008
3.7.7
traction transformer
transformer installed on board of rolling stock inserted in the traction and auxiliary circuits of rolling
stock and in the scope of EN 60310
3.7.8
starting transformers, specifically designed for starting three-phase induction motors so as
to eliminate supply voltage dips
transformer that is de energized during normal operation, used for the purpose of starting a rotating
machine
3.7.9
Medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5 MVA
transformer used in network voltage conversion program and placed at the junction between two
voltage levels of two MV networks and which needs to be able to cope with emergency overloads
Note 1 to entry: Such units may or maybe not part of a packaged compact substation including also MV
Reclosers and protection equipment�
Trang 117
3.3 Efficiency Index
EI
ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted apparent power of the transformer
3.4 Peak Efficiency Index PEI
highest value of efficiency index that can be achieved at the optimum value of load factor Note 1 to entry: See Annex A for derivation
3.5 load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs Note 1 to entry: See Annex A for derivation
3.6 declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts Guaranteed values are related to contract, whereas declared values are related to compliance verifications with COMMISSION REGULATION (EU) No 548/2014
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages below 400 V and above 690 V
ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted
apparent power of the transformer
3.4
Peak Efficiency Index
PEI
highest value of efficiency index that can be achieved at the optimum value of load factor
Note 1 to entry: See Annex A for derivation
3.5
load factor of Peak Efficiency Index
k PEI
load factor at which Peak Efficiency Index occurs
Note 1 to entry: See Annex A for derivation
3.6
declared value
regulatory value given in Clause 6 which is to be used for market surveillance activities
Note 1 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts
Guaranteed values are related to contract, whereas declared values are related to compliance verifications with
COMMISSION REGULATION (EU) No 548/2014
4 Environmental classes
Classification of insulating liquids according to fire point and net calorific value is given in EN 61100
Climatic, environmental and fire behaviour classes for dry–type transformers are defined in
EN 60076-11
5 Electrical characteristics
5.1 Highest voltages for equipment for winding with Um > 1,1 kV
Insulation levels and dielectric test shall be in accordance with the requirements of EN 60076-3
The values of the highest voltage Um for equipment are:
3,6 kV– 7,2 kV – 12 kV – 17,5 kV – 24 kV – 36 kV
NOTE National practices may require the use of highest voltages for equipment up to (but not including) 52 kV, when the
rated voltage is less than 36 kV (such as Um = 38,5 kV or Um = 40,5 kV)
5.2 Rated voltage for winding with Um ≤ 1,1 kV
For Um ≤ 1,1 kV the preferred rated voltage value shall be chosen in the hereunder list:
400 V – 410 V – 415 V – 420 V – 433 V – 690 V NOTE This document may be applied either as a whole or in part, to transformers with rated low voltages
below 400 V and above 690 V
BS EN 50588-1:2015 EN 50588-1:2015 (E)
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand test between windings and earth need to be stated by the purchaser The most usual values are respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr ≤ 100kVA, for three phase transformers with a rated power Sr ≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr < 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
BS EN 50588-1:2015+A1:2016
EN 50588-1:2015+A1:2016
9
Trang 12BS EN 50588-1:2015 EN 50588-1:2015 (E)
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand
test between windings and earth need to be stated by the purchaser The most usual values are
respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer
For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap
positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges
greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific
agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a
maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap
positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between
manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the
provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the
choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr≤ 100kVA, for three phase transformers with a rated power Sr≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr< 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
The names of the loss classes are the same for all of the highest voltage for equipment values (Um) whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular systemservice conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values Thesound power levels can be specified by the purchaser or by agreement between manufacturer and purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformersthe correct reference temperature shall be taken according to their insulation system temperature (see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformeraccording to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to referencetemperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand
test between windings and earth need to be stated by the purchaser The most usual values are
respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer
For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap
positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges
greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific
agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a
maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap
positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between
manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the
provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the
choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr ≤ 100kVA, for three phase transformers with a rated power Sr ≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr < 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
BS EN 50588-1:2015
EN 50588-1:2015 (E)
9
Several classes of losses are defined in this standard with a ranking of efficiency for no load loss
and for load loss The most efficient class for no load loss is class AAA0, then AA0, then A0 For load
loss the same logic is used with the most efficient class is Ak, then Bk, then Ck
The names of the loss classes are the same for all of the highest voltage for equipment values (Um)
whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system
service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The
sound power levels can be specified by the purchaser or by agreement between manufacturer and
purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and
short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers
the correct reference temperature shall be taken according to their insulation system temperature
(see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer
according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference
temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
BS EN 50588-1:2015
EN 50588-1:2015 (E)
9
Several classes of losses are defined in this standard with a ranking of efficiency for no load loss
and for load loss The most efficient class for no load loss is class AAA0, then AA0, then A0 For load
loss the same logic is used with the most efficient class is Ak, then Bk, then Ck
The names of the loss classes are the same for all of the highest voltage for equipment values (Um)
whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system
service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The
sound power levels can be specified by the purchaser or by agreement between manufacturer and
purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and
short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers
the correct reference temperature shall be taken according to their insulation system temperature
(see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer
according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference
temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
The names of the loss classes are the same for all of the highest voltage for equipment values (Um) whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular systemservice conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values Thesound power levels can be specified by the purchaser or by agreement between manufacturer and purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformersthe correct reference temperature shall be taken according to their insulation system temperature (see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformeraccording to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to referencetemperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
BS EN 50588-1:2015+A1:2016
EN 50588-1:2015+A1:2016
10
If different values of apparent power are assigned under different circumstances, for example, with
different methods of cooling (ONAN/ONAF, AN/AF, etc…), all values must be reported on the rating
plate and the highest of these values is the rated power� This applies also in case a provision for a
future value of apparent power is made (for example future ONAF, future AF, etc…)
Any evaluation of losses shall be done on continuous rated power as stated in EN 60076-1 If
additional cooling system such as fans or pumps… are used only for temporary overload conditions
and not for continuous rating, then such overloading rating cannot be claimed to be as rated power
and then not mentioned on the rating plate�
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3, 6�2�4 and 6�2�5�
The loss classes correspond to the values measured during the factory acceptance test without
any tolerances�
More specifically:
a) The reference temperature for liquid immersed transformers with rated average winding
temperature rise less than or equal to 65 K for OF or ON, or 70 K for OD is 75 °C;
b) For transformers with other rated average winding temperature rise, the reference temperature
is equal to the rated average winding temperature rise + 20 °C, or rated winding temperature
rise + yearly external cooling medium average temperature, whichever is higher�
Trang 13BS EN 50588-1:2015 EN 50588-1:2015 (E)
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand
test between windings and earth need to be stated by the purchaser The most usual values are
respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer
For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap
positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges
greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific
agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a
maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap
positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between
manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the
provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the
choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr ≤ 100kVA, for three phase transformers with a rated power Sr ≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr < 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
The names of the loss classes are the same for all of the highest voltage for equipment values (Um) whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The sound power levels can be specified by the purchaser or by agreement between manufacturer and purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers the correct reference temperature shall be taken according to their insulation system temperature (see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr ≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
8
The values for short duration power frequency withstand and/or for the lightning impulse withstand
test between windings and earth need to be stated by the purchaser The most usual values are
respectively 10 kV and 30 kV
5.3 Tapping
Taps can be provided with DETC or OLTC devices:
- DETC: De-energised tap changer
- OLTC: On load tap changer
For DETC the preferred tapping ranges are ± 2,5 % with 3 tap positions and ± 2 x 2,5 % with 5 tap
positions On special request ± 4 x 2,5 % with 9 tap positions can be provided Tapping ranges
greater than ± 10 % or with more than 9 tap positions are unusual and subject to specific
agreement
For transformer equipped with OLTC the tapping range shall be smaller than ± 15 % with a
maximum of 17 tap positions Tapping ranges greater than ± 15 % or with more than 17 tap
positions are unusual and subject to specific agreement
Tapping ranges outside the above definitions have to be specified by agreement between
manufacturer and purchaser
5.4 Connection designations for three phase transformers
Preferred connection designations, following IEV [421-10-09], shall be in accordance with the
provisions of Table 1
Table 1 — Connections
Sr ≤ 100 kVA 100 kVA < Sr < 5 000 kVA Sr ≥ 5 000 kVA Yzn or Dyn Dyn YNd or Dyn or YNyn
The clock hour figure should be 5 or 11 for Dyn or Yzn and 0 for Yy
Connections and clock hour figure shall be specified by the purchaser preferably amongst the
choice given above
6 Load loss, no load loss, PEI, sound power level, short-circuit impedance
6.1 General
The following tables give the maximum level of losses for single phase transformers with a rated
power Sr ≤ 100kVA, for three phase transformers with a rated power Sr ≤ 3 150 kVA and minimum
Peak Efficiency Index for three phase transformers with rated power Sr > 3 150 kVA and
Sr < 40 000 kVA
The losses and Peak Efficiency Index classes remain the same for all highest voltage for equipment
values (Um) regardless of the additional loss corrections specified in 6.2.3 and 6.2.4
Description and requirements for special cases are given in 6.4
BS EN 50588-1:2015
EN 50588-1:2015 (E)
9
Several classes of losses are defined in this standard with a ranking of efficiency for no load loss
and for load loss The most efficient class for no load loss is class AAA0, then AA0, then A0 For load
loss the same logic is used with the most efficient class is Ak, then Bk, then Ck
The names of the loss classes are the same for all of the highest voltage for equipment values (Um)
whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system
service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The
sound power levels can be specified by the purchaser or by agreement between manufacturer and
purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and
short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers
the correct reference temperature shall be taken according to their insulation system temperature
(see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer
according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference
temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr ≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
BS EN 50588-1:2015
EN 50588-1:2015 (E)
9
Several classes of losses are defined in this standard with a ranking of efficiency for no load loss
and for load loss The most efficient class for no load loss is class AAA0, then AA0, then A0 For load
loss the same logic is used with the most efficient class is Ak, then Bk, then Ck
The names of the loss classes are the same for all of the highest voltage for equipment values (Um)
whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system
service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The
sound power levels can be specified by the purchaser or by agreement between manufacturer and
purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and
short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers
the correct reference temperature shall be taken according to their insulation system temperature
(see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer
according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference
temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr ≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
The names of the loss classes are the same for all of the highest voltage for equipment values (Um) whatever the corrections done on the values described in the following clauses
Other values of short-circuit impedance can be specified by the purchaser for particular system service conditions, e.g in the case of parallel operations in all tables of this clause
The sound power levels, given in the tables in Clause 6 are preferred and maximum values The sound power levels can be specified by the purchaser or by agreement between manufacturer and purchaser for different values
For liquid immersed transformer and for dry-type transformer, load loss, Peak Efficiency Index and short circuit impedance shall be given at the reference temperature defined in EN 60076-1
To calculate and to compare the Peak Efficiency Index and the load loss of different transformers the correct reference temperature shall be taken according to their insulation system temperature (see EN 60076-1:2011, 11.1.1)
The insulation materials used in transformer shall have an insulation system temperature according
to EN 60085 and EN 60505 and in compliance with the temperature rise limits for the transformer according to EN 60076-2, EN 60076-11 and EN 60076-14
The symbols used are:
P0: no load loss at rated voltage and rated frequency, on the rated tap according to EN 60076-1;
Pk: load loss at rated current and rated frequency on the rated tap corrected to reference temperature according to EN 60076-1;
LWA: A weighted sound power level of transformers according to EN 60076-10
6.2 Transformers with rated power Sr ≤ 3 150 kVA
6.2.1 General information
Figure 1 indicates clauses to be chosen according to the highest voltage for equipment values Um
on the primary and on the secondary windings
Figure 1 — Choice of clauses according to the highest voltage for equipment values Um
Numbering into brackets are the references to the lines of Table 5
6.2.2 One winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
The following tables are defined for step down or step up transformer with one winding with
Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
Table 2 and Table 3 are for liquid immersed transformers and Table 4 for dry-type transformers
For the transformers AAA0 see special requirements in 9.5
Table 2 — No load loss (P 0 ) and sound power level for liquid immersed transformers
Rated power AAA 0 AA 0 LWA A 0 LWA
power 3 150 kVA < Sr < 40 000 kVA is given in paragraph 6.3.
If a purchaser needs to compare transformer with different insulation systems and different average winding temperature rises, the reference temperature should be according to b) above
Trang 146.2.2 One winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
The following tables are defined for step down or step up transformer with one winding with
Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
Table 2 and Table 3 are for liquid immersed transformers and Table 4 for dry-type transformers
For the transformers AAA0 see special requirements in 9.5
Table 2 — No load loss (P 0 ) and sound power level for liquid immersed transformers
Rated power AAA 0 AA 0 LWA A 0 LWA
Table 3 — Load loss (P k ) and short circuit impedance for liquid immersed transformers
Rated power Ak Bk Ck Short-circuit Impedance
Trang 156.2.2 One winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
The following tables are defined for step down or step up transformer with one winding with
Um ≤ 24 kV and the other one with Um ≤ 1,1 kV
Table 2 and Table 3 are for liquid immersed transformers and Table 4 for dry-type transformers
For the transformers AAA0 see special requirements in 9.5
Table 2 — No load loss (P 0 ) and sound power level for liquid immersed transformers
Rated power AAA 0 AA 0 LWA A 0 LWA
Table 3 — Load loss (P k ) and short circuit impedance for liquid immersed transformers
Rated power Ak Bk Ck Short-circuit Impedance
Trang 16BS EN 50588-1:2015 EN 50588-1:2015 (E)
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that the rated power is the same regardless of the combination of voltages
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that the rated power is the same regardless of the combination of voltages
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that the rated power is the same regardless of the combination of voltages
BS EN 50588-1:2015
EN 50588-1:2015 (E)
13
6.3 Transformers with rated power 3 150 kVA < Sr < 40 000 kVA
Peak efficiency Index (PEI) is the maximum value of the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer
The Peak Efficiency Index includes the losses associated with the cooling system (Pc0) that is in service in the no-load condition If additional cooling is required for the transformer to operate at
kPEI, then the additional cooling loss required for this cooling shall be added to Pc0 in the calculation
of PEI Any additional cooling and associated cooling loss in excess of that required at kPEI
necessary to achieve rated power is excluded
NOTE This applies to transformers equipped with heat-exchangers which need pumps and fans to provide heat dissipation (e.g ODAF, ODWF, OFWF, OFAF, OFAN, ONAF, KNAF)
The minimum PEI value, which shall be met in all cases, can be obtained with different combinations of no load and load losses This is equivalent to different load factors at which PEI occurs The ratio of the load and no load losses needs to be tailored to the application in order to obtain the best actual efficiency in service In order to achieve this, the following methods are available:
- Providing capitalization values for no load and load losses that reflect the anticipated loading (this is the recommended method);
- Prescribing maximum values for no load and load losses;
- Specifying minimum efficiency index at a specific load factor
Annex A includes the calculation method for the PEI Table 7 and Table 8 indicate the PEI for
transformers with rated power Sr > 3 150 kVA
Table 7— Minimum Peak Efficiency Index (PEI) for Liquid immersed transformers
RATED POWER (kVA) PEI (%)
Trang 1712
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that the rated power is the same regardless of the combination of voltages
BS EN 50588-1:2015 EN 50588-1:2015 (E)
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and
Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that
the rated power is the same regardless of the combination of voltages
BS EN 50588-1:2015 EN 50588-1:2015 (E)
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and
Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that
the rated power is the same regardless of the combination of voltages
BS EN 50588-1:2015 EN 50588-1:2015 (E)
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and
purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the
European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level
Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to
Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and
Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that
the rated power is the same regardless of the combination of voltages
12
Transformers can be requested and offered with sound power level LWA other than the listed values
The sound power level LWA for transformers AAA0 has to be agreed between manufacturer and purchaser
NOTE Some cells in Table 4 are empty because these combinations are not covered according the European Regulation No 548/2014 of May 21, 2014
6.2.3 Load loss and no load loss in case of other insulation level
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 5 below,
in order to take care of variations related to the highest voltage for equipment values
Table 5 — Correction of load loss and no load loss in case other insulation level Ref highest voltage for equipment
1,1 kV < Um≤ 24 kV and the
other with 1,1 kV < Um≤ 24 kV
The maximum levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 10 % for no load loss and
by 10 % for load loss
6.2.4 Load loss and no load loss in case of dual voltage
The level of losses given in 6.2.2 shall be weighted by the correction factors given in Table 6 below,
in order to take care of variations related to dual voltage windings
For transformer having insulation level according to Table 5 and having dual voltage according to Table 6 the loss level shall take into account both corrections
Table 6 — Correction of load loss and no load loss in case of dual voltage Ref Dual voltage Correction of load loss and no load loss
A One winding In case of transformers with one high-voltage winding and two voltages
available from tapped low-voltage winding, losses shall be calculated based
on the higher low-voltage and shall comply with the levels indicated in Table 2, Table 3 and Table 4
The maximum available power on the lower low-voltage on such transformers shall be no more than 0,85 times its rated power
In case of transformers with one high-voltage winding with two voltages available from a tap, the maximum available power on the lower high-voltage
on such transformer shall be limited to 0,85 of its nominal rated power
In the case where the full rated power is available regardless of the combination of voltages, the levels of losses indicated in Table 2, Table 3 and Table 4 can be increased by 15 % for no load loss and by 10 % for load loss
B Both windings The levels of losses indicated in Table 2, Table 3 and Table 4 shall be
increased by 20 % for no load loss and by 20 % for load loss in case of dual voltage on both windings These levels of losses are given on the basis that the rated power is the same regardless of the combination of voltages
BS EN 50588-1:2015
EN 50588-1:2015 (E)
13
6.3 Transformers with rated power 3 150 kVA < Sr < 40 000 kVA
Peak efficiency Index (PEI) is the maximum value of the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer
The Peak Efficiency Index includes the losses associated with the cooling system (Pc0) that is in service in the no-load condition If additional cooling is required for the transformer to operate at
kPEI, then the additional cooling loss required for this cooling shall be added to Pc0 in the calculation
of PEI Any additional cooling and associated cooling loss in excess of that required at kPEI
necessary to achieve rated power is excluded
NOTE This applies to transformers equipped with heat-exchangers which need pumps and fans to provide heat dissipation (e.g ODAF, ODWF, OFWF, OFAF, OFAN, ONAF, KNAF)
The minimum PEI value, which shall be met in all cases, can be obtained with different combinations of no load and load losses This is equivalent to different load factors at which PEI occurs The ratio of the load and no load losses needs to be tailored to the application in order to obtain the best actual efficiency in service In order to achieve this, the following methods are available:
- Providing capitalization values for no load and load losses that reflect the anticipated loading (this is the recommended method);
- Prescribing maximum values for no load and load losses;
- Specifying minimum efficiency index at a specific load factor
Annex A includes the calculation method for the PEI Table 7 and Table 8 indicate the PEI for
transformers with rated power Sr > 3 150 kVA
Table 7— Minimum Peak Efficiency Index (PEI) for Liquid immersed transformers
RATED POWER (kVA) PEI (%)
For transformers having dual voltage on both windings for which both voltages on one winding are fully rated in combination with one of the voltages on the other winding, the levels of losses shall be based on the highest power and the values indicated in Table 2, Table 3 and Table 4 can be increased
by 15 % for no load losses and by 10 % for load losses� The level of losses shall refer to the highest voltages of both windings� This remains valid even if further voltage combinations are available�
For transformer having insulation level according to Table 5 and having dual voltage according to Table 6 the loss level shall take into account both corrections�
6.2.5 Three winding transformers for PV applications
Dual voltage correction factors given in Table 6, Ref A, apply also to transformers for photovoltaic applications, which have two low voltage windings that each have half the rated power of the high voltage winding�
Trang 18BS EN 50588-1:2015 EN 50588-1:2015 (E)
14
Table 8 — Minimum Peak Efficiency Index (PEI) for dry-type transformers
RATED POWER (kVA) PEI (%)
The value of noise and short circuit impedance shall be defined during enquiry stage
6.4 Transformers with special requirements
6.4.1 Rated power not included in the list
For transformer having a rated power different from the values given in the tables, a linear interpolation shall be made based on the neighbouring values for losses and PEI
6.4.2 Transformers equipped with tapping connections suitable for operation while
transformer is energised or on load and rated power Sr ≤ 3 150 kVA
When transformers are equipped with tapping connections suitable for operation while transformer
is energised or on load for voltage adaptation purposes, the level of load loss and no load loss of the list of this standard shall be increased as per COMMISSION REGULATION (EU) No 548/2014
of 21 May 2014:
- From 01/07/2015 the maximum allowable levels of losses set out in Table 2, Table 3 and Table 4 for the cases detailed in Table ZZ.1 shall be increased by 20 % for no load losses and 5 % for load losses
- From 01/07/2021 the maximum allowable levels of losses set out in Table 2, Table 3 and Table 4 for the cases detailed in Table ZZ.1 shall be increased by 10 % for no load losses and 0 % for load losses
Such corrections are applicable irrespectively of the technology used to perform the voltage adaptation
The losses of the transformers counted, shall be the overall losses whatever the kind of transformers, included all devices to manage the AVR inside the transformers
For transformer having insulation level according to Table 5 and having tapping connections suitable for operation while transformer is energised or on load for voltage adaptation purposes both corrections shall be taken into account
NOTE AVR: Automatic Voltage Regulation: to automatically control the input or output voltage of the transformer for on-load voltage regulation purposes
13
6.3 Transformers with rated power 3 150 kVA < Sr < 40 000 kVA
Peak efficiency Index (PEI) is the maximum value of the ratio of the transmitted apparent power of a
transformer minus the electrical losses to the transmitted apparent power of the transformer
The Peak Efficiency Index includes the losses associated with the cooling system (Pc0) that is in
service in the no-load condition If additional cooling is required for the transformer to operate at
kPEI, then the additional cooling loss required for this cooling shall be added to Pc0 in the calculation
of PEI Any additional cooling and associated cooling loss in excess of that required at kPEI
necessary to achieve rated power is excluded
NOTE This applies to transformers equipped with heat-exchangers which need pumps and fans to
provide heat dissipation (e.g ODAF, ODWF, OFWF, OFAF, OFAN, ONAF, KNAF)
The minimum PEI value, which shall be met in all cases, can be obtained with different
combinations of no load and load losses This is equivalent to different load factors at which PEI
occurs The ratio of the load and no load losses needs to be tailored to the application in order to
obtain the best actual efficiency in service In order to achieve this, the following methods are
available:
- Providing capitalization values for no load and load losses that reflect the anticipated
loading (this is the recommended method);
- Prescribing maximum values for no load and load losses;
- Specifying minimum efficiency index at a specific load factor
Annex A includes the calculation method for the PEI Table 7 and Table 8 indicate the PEI for
transformers with rated power Sr > 3 150 kVA
Table 7— Minimum Peak Efficiency Index (PEI) for Liquid immersed transformers
RATED POWER (kVA) AA PEI (%) A
Table 8 — Minimum Peak Efficiency Index (PEI) for dry-type transformers
RATED POWER (kVA) PEI (%)
The value of noise and short circuit impedance shall be defined during enquiry stage
6.4 Transformers with special requirements
6.4.1 Rated power not included in the list
For transformer having a rated power different from the values given in the tables, a linear
interpolation shall be made based on the neighbouring values for losses and PEI
6.4.2 Transformers equipped with tapping connections suitable for operation while
transformer is energised or on load and rated power Sr ≤ 3 150 kVA
When transformers are equipped with tapping connections suitable for operation while transformer
is energised or on load for voltage adaptation purposes, the level of load loss and no load loss of
the list of this standard shall be increased as per COMMISSION REGULATION (EU) No 548/2014
of 21 May 2014:
- From 01/07/2015 the maximum allowable levels of losses set out in Table 2, Table 3 and
Table 4 for the cases detailed in Table ZZ.1 shall be increased by 20 % for no load losses and 5 % for load losses
- From 01/07/2021 the maximum allowable levels of losses set out in Table 2, Table 3 and
Table 4 for the cases detailed in Table ZZ.1 shall be increased by 10 % for no load losses and 0 % for load losses
Such corrections are applicable irrespectively of the technology used to perform the voltage
adaptation
The losses of the transformers counted, shall be the overall losses whatever the kind of
transformers, included all devices to manage the AVR inside the transformers
For transformer having insulation level according to Table 5 and having tapping connections
suitable for operation while transformer is energised or on load for voltage adaptation purposes both
corrections shall be taken into account
NOTE AVR: Automatic Voltage Regulation: to automatically control the input or output voltage of the
transformer for on-load voltage regulation purposes
BS EN 50588-1:2015+A1:2016
EN 50588-1:2015+A1:2016
16
The PEI requirements in Table 7 and Table 8 apply to autotransformers and separate winding
transformers having three windings as follows Assuming that ratings are x/y/z, then:
– if x and y are equal and z is lower or equal than one third of x or y, the PEI shall be the one
corresponding to x or y rating and the losses of winding z shall not be considered for PEI
calculation;
– if x is equal to the sum of y and z, the PEI shall be the one corresponding to x rating and the three
winding losses shall be considered for PEI calculation;
– in all other cases, the PEI shall be the one corresponding to maximum of the three ratings� Load
loss must be measured for each winding pairs and the load combination to be used for PEI
calculation is:
EN 50588-1:2015/A1:2016 (E)
7
For transformer having insulation level according to Table 5 and having dual voltage according to Table 6 the
loss level shall take into account both corrections.”
After 6.2.4, add the following new subclause:
“6.2.5 Three winding transformers for PV applications
Dual voltage correction factors given in Table 6, Ref A, apply also to transformers for photovoltaic
applications, which have two low voltage windings that each have half the rated power of the high voltage
winding.”
5 Modification to 6.3, Transformers with rated power 3 150 kVA < Sr < 40 000 kVA
At the end of 6.3, after “The value of noise and short circuit impedance shall be defined during enquiry stage.",
add the following new paragraphs:
"The PEI requirements in Table 7 and Table 8 apply to autotransformers and separate winding transformers
having three windings as follows Assuming that ratings are x/y/z, then:
- if x and y are equal and z is lower or equal than one third of x or y, the PEI shall be the one corresponding
to x or y rating and the losses of winding z shall not be considered for PEI calculation;
- if x is equal to the sum of y and z, the PEI shall be the one corresponding to x rating and the three winding
losses shall be considered for PEI calculation;
- in all other cases, the PEI shall be the one corresponding to maximum of the three ratings Load loss must
be measured for each winding pairs and the load combination to be used for PEI calculation is:
z y
x z z y
x y x
+ +
NOTE 1 In general, transformers of similar design criteria, but with more than two windings, have higher total losses
and lower PEI values This formula also allows for the verification of PEI requirements in transformers other than two
winding transformers, such as three winding transformers and autotransformers For the computation of the load loss for
each winding, the criteria given in IEC 60076-8 can be taken as reference
NOTE 2 For example, for a 6 000/6 000/3 000 kVA, the PEI limit shall be that of 6 000 kVA and the load combination for
load loss calculation shall be:
2000 / 4000 / 6000 3000
6000
6000 3000
3000 6000
6000 6000
+ +
The approach used for three winding transformers can be applied in principle to transformers with more than
three windings
For transformers with re-connectable windings PEI calculation shall be made based on loss measurements
taken at the highest rated voltage(s)."