1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 50289 1 11 2016

42 0 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Communication Cables — Specifications For Test Methods Part 1-11: Electrical Test Methods — Characteristic Impedance, Input Impedance, Return Loss
Trường học British Standards Institution
Chuyên ngành Standards Publication
Thể loại Standard
Năm xuất bản 2016
Thành phố Brussels
Định dạng
Số trang 42
Dung lượng 2,76 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 4.1 Principle (12)
  • 4.2 Expression of test results (12)
  • 5.1 Method A: measurement of balanced cables using balun setup (12)
    • 5.1.1 Test Equipment (12)
    • 5.1.2 Test sample (13)
    • 5.1.3 Calibration procedure (13)
    • 5.1.4 Measuring procedure (14)
  • 5.2 Method B: measurement of balanced cables using balun-less setup (14)
    • 5.2.1 Test Equipment (14)
    • 5.2.2 Test sample (15)
    • 5.2.3 Calibration procedure (15)
    • 5.2.4 Measuring procedure (15)
  • 5.3 Method C: measurement of coaxial cables (16)
    • 5.3.1 Test Equipment (16)
    • 5.3.2 Test sample (16)
    • 5.3.3 Calibration procedure (16)
    • 5.3.4 Measuring procedure (17)
  • 5.4 Expression of test results (17)
  • A.1 General (20)
  • A.2 Polynomial function for function fitting of input impedance (20)
  • A.3 Fewer terms (21)
  • B.1 General (23)
  • B.2 Parasitic inductance corrected return loss (PRL) (23)
  • B.3 Gated return loss (GRL) (25)
  • B.4 Fitted return loss (FRL) (27)
  • B.5 Comparison of gated return loss (GRL) with fitted return loss (FRL) (33)
  • B.6 Influence of the correction technique on return loss peaks (34)
  • C.1 General (37)
  • C.2 Verification of termination loads (38)

Nội dung

β is phase constant rad/m; tanδ is loss factor; impedance measured at the near end input when the far end is terminated by a load resistance of value equal to the system nominal impedan

Trang 1

Communication cables — Specifications for test methods

Part 1-11: Electrical test methods — Characteristic impedance, input impedance, return loss

BSI Standards Publication

Trang 2

This British Standard is the UK implementation of EN 50289-1-11:2016 It supersedes BS EN 50289-1-11:2002 which is withdrawn.

The UK participation in its preparation was entrusted to Technical Committee EPL/46, Cables, wires and waveguides, radio frequency connectors and accessories for communication and signalling

A list of organizations represented on this committee can be obtained on request to its secretary

This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application

© The British Standards Institution 2017

Published by BSI Standards Limited 2017ISBN 978 0 580 93206 9

Amendments/corrigenda issued since publication

Trang 3

NORME EUROPÉENNE

English Version

Communication cables - Specifications for test methods - Part

1-11: Electrical test methods - Characteristic impedance, input

impedance, return loss

Câbles de communication - Spécifications des méthodes

d'essai - Partie 1-11: Méthodes d'essais électriques -

Impédance caractéristique, impédance d'entrée,

affaiblissement de réflexion

Kommunikationskabel - Spezifikationen für Prüfverfahren - Teil 1-11: Elektrische Prüfverfahren - Wellenwiderstand, Eingangsimpedanz, Rückflußdämpfung

This European Standard was approved by CENELEC on 2016-09-05 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any

alteration

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation

under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the

same status as the official versions

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,

Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,

Turkey and the United Kingdom

European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members

Ref No EN 50289-1-11:2016 E

Trang 4

Contents Page

European foreword 4

1 Scope 5

2 Normative references 5

3 Terms and definitions 5

4 Test method for mean characteristic impedance (S 21 type measurement) 10

4.1 Principle 10

4.2 Expression of test results 10

5 Test method for input impedance and return loss (S 11 type measurement) 10

5.1 Method A: measurement of balanced cables using balun setup 10

5.1.1 Test Equipment 10

5.1.2 Test sample 11

5.1.3 Calibration procedure 11

5.1.4 Measuring procedure 12

5.2 Method B: measurement of balanced cables using balun-less setup 12

5.2.1 Test Equipment 12

5.2.2 Test sample 13

5.2.3 Calibration procedure 13

5.2.4 Measuring procedure 13

5.3 Method C: measurement of coaxial cables 14

5.3.1 Test Equipment 14

5.3.2 Test sample 14

5.3.3 Calibration procedure 14

5.3.4 Measuring procedure 15

5.4 Expression of test results 15

6 Test report 17

Annex A (normative) Function fitting of input impedance 18

A.1 General 18

A.2 Polynomial function for function fitting of input impedance 18

A.3 Fewer terms 19

Annex B (normative) Correction procedures for the measurement results of return loss and input impedance 21

B.1 General 21

B.2 Parasitic inductance corrected return loss (PRL) 21

B.3 Gated return loss (GRL) 23

B.4 Fitted return loss (FRL) 25

B.5 Comparison of gated return loss (GRL) with fitted return loss (FRL) 31

Trang 5

B.6 Influence of the correction technique on return loss peaks 32

Annex C (normative) Termination loads for termination of conductor pairs 35

C.1 General 35

C.2 Verification of termination loads 36

Bibliography 37

Trang 6

European foreword

This document [EN 50289-1-11:2016] has been prepared by CLC/TC 46X "Communication cables"

The following dates are fixed:

• latest date by which this document has to be

implemented at national level by publication of

an identical national standard or by

endorsement

(dop) 2017-09-05

• latest date by which the national standards

conflicting with this document have to

be withdrawn

(dow) 2019-09-05

This document supersedes EN 50289-1-11:2001

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights

Trang 7

EN 50289-1-1:2001, Communication cables - Specifications for test methods - Part 1-1: Electrical test methods - General requirements

EN 50289-1-5:2001, Communication cables - Specifications for test methods - Part 1-5: Electrical test methods - Capacitance

EN 50289-1-7:2001, Communication cables - Specifications for test methods - Part 1-7: Electrical test methods - Velocity of propagation

EN 50290-1-2, Communication cables - Part 1-2: Definitions

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 50290-1-2 and the following apply

uf,r is voltage wave propagating in forward respectively reverse direction;

if,r is current wave propagating in forward respectively reverse direction

Trang 8

3.2

mean characteristic impedance

in practice for real cables which always have structural variations the characteristic impedance is described

by the mean characteristic impedance which is derived from the measurement of the velocity of propagation (EN 50289-1-7) and the mutual capacitance (EN 50289-1-5) However, this method is only applicable for frequencies above 1 MHz and non-polar insulation materials (i.e materials having a dielectric permittivity which doesn’t change over frequency) The mean characteristic impedance approaches at sufficiently high

frequencies (≈100 MHz) an asymptotic value Z∞

The characteristic impedance may be expressed as the propagation coefficient divided by the shunt admittance This relationship holds at any frequency

β is phase constant (rad/m);

tanδ is loss factor;

impedance measured at the near end (input) when the far end is terminated by a load resistance of value

equal to the system nominal impedance ZR

Trang 9

where

Zos is input Impedance of the cable obtained from an open/short measurement;

Zopen is impedance with an open circuit at the far end of the cable;

Zshort is impedance with a short circuit at the far end of the cable

is only valid if the variations with frequency of the input impedance around its characteristic impedance are balanced

3.6

(operational) return loss

RL

(operational) return loss is measured at the near end (input) when the far end is terminated by a load

resistance of value equal to the system nominal impedance ZR It quantifies the reflected signal caused by impedance variations The (operational) return loss takes into account the structural variations along the cable length and the mismatch between the reference impedance and the (mean) characteristic impedance

of the cable (pair) If the (mean) characteristic impedance of the cable (pair) is different from the reference impedance, one gets, especially at lower frequencies (where the round trip attenuation is low), multiple

reflections that are overlaid to the structural and junction reflections Therefore, return loss RL is also

referenced as operational return loss

As an example, Figure 1, shows the operational return loss under different conditions The blue line shows the return loss of a pair having a characteristic impedance equal to the reference impedance but taking into account that the impedance is varying with frequency (see right-hand graph) The red line shows the return loss of a pair having a characteristic impedance that is different from the reference impedance (110 Ω vs 100 Ω) For both lines, periodic variations – that are caused by multiple reflections between the junctions at the near and far end – are observed The green line shows a simulation of a pair having a frequency independent characteristic impedance which is equal to the reference impedance

Trang 10

0,8 0,84 0,88 0,92 0,96 1 1,04 1,08 1,12 1,16 1,2

MHz

frequency dependent factor of the characteristic impedance

Real Imag

Figure 1 — Return loss with and without junction reflections 3.7

open/short return loss

Another way (when long CUT length is not available) is to measure the characteristic impedance (open/short method) and to calculate the return loss As the characteristic impedance is obtained from the measurement

of the open and short circuit impedance, it is proposed to name such obtained return loss open/short return loss

This open/short return loss includes the effect of structural variations and the mismatch at the near end (including the effect due to a frequency-dependent characteristic impedance), but it does not take into account multiple reflections

Figure 2 shows the difference between operational return loss and open/short return loss The left-hand graph shows the results of a pair having a characteristic impedance which is different from the reference impedance (110 Ω vs 100 Ω) The right-hand graph shows the results of a pair having a characteristic impedance which is equal to the reference impedance (100 Ω) One may recognize that the open/short return loss does not take into account multiple reflections

RL OSRL

Figure 2 — Return loss and open/short return loss

Trang 11

Zfit is the (complex) characteristic impedance obtained from a curve fitting of the real and

imaginary part of ZOS

The left-hand graph of Figure 3 shows the operational return loss, open/short return loss and structural return loss of a CUT having a characteristic impedance of 110 Ω A difference between both is observable The operational return loss takes into account all effects (structural variations, mismatch effects at the input and output) The open/short return loss does not take into account mismatch effects at the output (i.e no multiple reflections) Whereas the structural return loss only takes into account structural variations along the cable The right-hand graph shows the real and imaginary part of the mean characteristic impedance (obtained from the measurement of the open and short circuit impedance) and it’s fitting

40 50 60 70 80 90 100 110 120 130 140

Trang 12

4 Test method for mean characteristic impedance (S

21

type measurement)

4.1 Principle

This method shall only be applied for cables having non-polar insulation materials (e.g PE, PTFE), i.e materials having a dielectric permittivity which doesn’t change over frequency Or in other words this method shall only be applied to cables having a mutual capacitance which doesn’t change over frequency

The mean characteristic impedance shall be derived from the measurement of the velocity of propagation, respectively phase delay, according to EN 50289-1-7 and the mutual capacitance according EN 50289-1-5 The measurement shall be carried out at frequencies above 100 MHz where the phase delay approaches an asymptotic value

4.2 Expression of test results

The mean characteristic impedance Zcm shall be derived from Formula (6):

Zcm is mean characteristic impedance (Ω);

v is velocity of propagation (m/s), measured according EN 50289-1-7;

τp is phase delay (s/m), measured according EN 50289-1-7;

C is mutual capacitance (F/m), measured according EN 50289-1-5

5 Test method for input impedance and return loss (S

11

type measurement)

5.1 Method A: measurement of balanced cables using balun setup

5.1.1 Test Equipment

The test equipment consists of a 2-port vector network analyser (VNA) with:

— S-parameter set-up;

Trang 13

— Balun to convert the unbalanced signal of the VNA to a balanced signal The balun shall have an impedance on the primary (unbalanced) side equal to the nominal impedance of the measuring devices (in general 50 Ω) and on the secondary (balanced) side equal to the nominal impedance of the CUT (e.g

100 Ω) (the balun shall fulfil the requirements of Class A baluns as described in EN 50289-1-1);

— To perform a calibration of the test equipment (on the secondary side of the balun), a short circuit, an open circuit and a reference load are required The short circuit shall have negligible inductance and the open circuit shall have negligible capacitance The load resistor shall have a value close (within 1%) to the nominal impedance of the CUT (e.g 100 Ω) and with negligible inductance and capacitance;

— For the measurement of the input impedance and (operational) return loss a T-resistor network (see Figure 4) is required to terminate the common and differential mode impedance at the far end of the sample The differential mode termination resistors shall be matched in pairs, each half the value of the

differential mode reference impedance ZR (in general 100 Ω) If not specified otherwise, for example by particular cabling standards, the common mode termination resistors shall be:

— 0 Ω for individually screened pair cables;

— 25 Ω for overall screened cables;

— 45 Ω to 50 Ω for unscreened cables

Key

RtermDM differential mode termination resistor

RtermCM common mode termination resistor

Figure 4 — T-resistor network 5.1.2 Test sample

The CUT shall have or exceed the minimum length specified in the relevant sectional specification Both ends

of the CUT shall be prepared, such that when connected to the terminals of the test equipment the influence

to the test result is minimised The twisting of the pairs/quads shall be maintained

5.1.3 Calibration procedure

It is not the intent of the standard to detail the algorithms applied by a VNA to correct the measured results based on a calibration procedure but to detail the calibration procedure Further information may be obtained

in the manuals of the VNA supplier

The calibration shall be performed on the secondary side of the balun by applying consecutively an open, short and load standard (see Figure 5)

Trang 14

a) terminated input impedance (Zin) and (operational) return loss (RL)

Measure the scattering parameter Sxx – i.e the reflection coefficient Γ – of the CUT with the far end terminated by a load resistance as described in 4.1.1 Inactive pairs shall also be terminated by this T-resistor network

b) Open/short input impedance (ZOS) and open/short return loss (OSRL)

Measure consecutively the scattering parameter Sxx – i.e the reflection coefficient Γ – of the CUT with the far end in open and short circuit

5.2 Method B: measurement of balanced cables using balun-less setup

5.2.1 Test Equipment

Method B is the preferred one for balanced cables for frequencies above 1 000 MHz as it avoids the use of baluns which are often limited to 1 000 MHz With this configuration it is possible to measure impedance and return loss both of the differential and common mode

Multiport vector network analyser VNA (having at least 4 ports) with

— S-parameter set-up;

— A mathematical conversion from unbalanced to balanced, i.e the mixed mode set-up which is often referred to as an unbalanced, modal decomposition or balun-less setup This allows measurements of balanced devices without use of an RF balun in the signal path With such a test set-up, all balanced and unbalanced parameters can be measured over the full frequency range;

— Coaxial cables – where the characteristic impedance shall be the same as the nominal impedance of the VNA – are needed to interconnect the network analyser, switching matrix and the test fixture The screen

Trang 15

of the coaxial cables shall have a low transfer impedance, i.e double screen or more with a transfer impedance less than 100 mΩ/m at 100 MHz The screens of each cable shall be electrically bonded to a common ground plane, with the screens of the cable bonded to each other at multiple points along their length To optimize the dynamic range, the total interconnecting cable attenuation shall not exceed 3 dB

at 1 000 MHz;

— To perform a calibration at the end of the coaxial interconnection cable coaxial reference standards, so called calibration standards, i.e a short circuit, an open circuit and a reference load, are required An alternative to the before mentioned open, short and load references is the use of an electronic multiport calibration kit (E-cal module) which is supplied by the supplier of the VNA

— If the calibration is performed at the test interface calibration reference artefact, i.e a short circuit, an open circuit and a reference load, are required For further details refer to EN 50289-1-1

— Termination loads as described in Annex C

5.2.2 Test sample

The CUT shall have or exceed the minimum length specified in the relevant sectional specification Both ends

of the CUT shall be prepared, such that when connected to the terminals of the test equipment the influence

to the test result is minimised In case of balanced cables the twisting of the pairs/quads shall be maintained

5.2.3 Calibration procedure

It is not the intent of the standard to detail the algorithms applied by a VNA to correct the measured results based on a calibration procedure but to detail the calibration procedure Further information may be obtained

in the manuals of the VNA supplier

A full 4-port single ended (SE) calibration shall be performed The calibration shall be either performed at the ends of the coaxial interconnection cables or on the test interface

In the first case open, short and load measurements (using coaxial reference standards, so called calibration standards) shall be taken at the ends of the coaxial interconnection cables of each port concerned, and through and isolation measurements shall be taken on every pair combination of those ports One may also use an electronic multiport calibration kit (E-cal module) which reduces significantly the calibration time As the calibration plane is the end of the coaxial interconnection cables the effect of the test interface is not removed from the results which may have an influence in particular at high frequencies To remove the effect

of the test interface it may be de-embedded from the measurement or a correction procedure applied If the effect of the test fixture is removed by de-embedding techniques it shall incorporate a fully populated 16 port

S-matrix The de-embedded calibration shall not be performed by using only reflection terms (S11 , S22, S33, S44)

or only near-end terms (S11, S21, S12, S22)

When the calibration is performed at the test interface, open, short and load measurements (using calibration reference artefacts) shall be taken on each SE port concerned, and through and isolation measurements shall be taken on every pair combination of those ports

5.2.4 Measuring procedure

The test sample shall be connected to the terminals of test fixture The reflection coefficient Γ (in Formulae 9

to 13) – shall be measured over the whole specified frequency range and at the same frequency points as for the calibration procedure The values shall be measured as complex parameters All pairs/quads shall be measured from both ends unless otherwise specified The reflection coefficient Γ (in Formulae (9) to (13))

corresponds to the scattering parameter SDDxx when measuring the differential mode impedance and SCCxxwhen measuring the common mode impedance

Trang 16

a) terminated input impedance (Zin) and (operational) return loss (RL)

Measure the reflection coefficient Γ of the CUT with the far end terminated by termination loads as described in Annex C

b) Open/short input impedance (ZOS) and open/short return loss (OSRL)

Measure consecutively the reflection coefficient Γ of the CUT with the far end in open and short circuit The mixed-mode set-up allows to obtain all parameters in differential (denoted by the index DD) and common mode (denoted by the index CC) Common multi-port VNA have integrated mathematical functions to convert the single ended measurements to common mode or differential mode values (Formulae (7) and (8))

SDD11 is scattering parameter S11 in differential mode;

SCC11 is scattering parameter S11 in common mode;

Sxy is single ended scattering parameter

5.3 Method C: measurement of coaxial cables

The CUT shall have or exceed the minimum length specified in the relevant sectional specification Both ends

of the CUT shall be prepared, such that when connected to the terminals of the test equipment the influence

to the test result is minimised In case of balanced cables the twisting of the pairs/quads shall be maintained

5.3.3 Calibration procedure

It is not the intent of the standard to detail the algorithms applied by a VNA to correct the measured results based on a calibration procedure but to detail the calibration procedure Further information may be obtained

in the manuals of the VNA supplier

If the nominal impedance of the CUT is equal to the nominal impedance of the VNA the calibration shall be performed on the coaxial ports of the VNA, applying consecutively an open, short and load standard If the

Trang 17

nominal impedance of the CUT is different from the nominal impedance of the CUT the calibration shall be performed on the secondary side of the impedance matching adapter, by applying consecutively an open, short and load standard

5.3.4 Measuring procedure

The test sample shall be connected to the terminals of test fixture The scattering parameter Sxx – i.e the reflection coefficient Γ (in Formulae (9) to (13)) – shall be measured over the whole specified frequency range and at the same frequency points as for the calibration procedure The values shall be measured as complex parameters The cable shall be measured from both ends unless otherwise specified

a) terminated input impedance (Zin) and (operational) return loss (RL)

Measure the scattering parameter Sxx – i.e the reflection coefficient Γ – of the CUT with the far end

terminated by a load resistance of a value equal to the system nominal impedance ZR.

b) Open/short input impedance (ZOS) and open/short return loss (OSRL)

Measure consecutively the scattering parameter Sxx – i.e the reflection coefficient Γ – of the CUT with the far end in open and short circuit

5.4 Expression of test results

All indicated parameters are complex parameters with magnitude and phase Therefore all evaluations are complex evaluations

Trang 18

If the specified reference impedance of the common or differential mode is different from the conventional reference impedance of the VNA the return loss shall be corrected In general a VNA has an integrated function to change the reference impedance Otherwise the return loss shall be corrected as follows

Zin is terminated input impedance in Ω when the far end is terminated by a load resistance

of value equal to the system nominal impedance ZR;

ZOS is open/short input impedance in Ω;

ZR is (conventional) reference impedance in Ω;

ZR* is specified reference impedance if different from the conventional reference

impedance;

Zopen is input impedance with an open circuit at the far end in Ω;

Zshort is input impedance with a short circuit at the far end in Ω;

Zfit is fitted input impedance in Ω obtained from data fitting (see Annex A) of Zin;

ΓR is reflection coefficient measured with the far end terminated by a load resistance of

value equal to the reference impedance ZR;

Γopen is reflection coefficient with an open circuit at the far end;

Γshort is reflection coefficient with an short circuit at the far end;

RL is (operational) return loss in dB for conventional reference impedance of the VNA;

RL* is (operational) return loss in dB for specified reference impedance if different from the

conventional reference impedance of the VNA;

SRL is structural return loss in dB;

OSRL is open/short return loss in dB;

OSRL* is open/short return loss in dB for specified reference impedance if different from the

conventional reference impedance of the VNA;

f is frequency in Hz;

Kx is fitting coefficients, see Annex A

Trang 20

In general the measurement data may be fitted by a polynomial function:

)()

()

()

(x =k1⋅f1 x +k2⋅f2 x +k3⋅f3 x +

To obtain the fitting coefficients kn a matrix is build in the form:

K A

)(

)(

3 2 1

x f x f x f x f x f x f

x f x f x f x f x f x f

x f x f x

f x f x

f x f

x f y

x f y

x f y

where

y(x) is polynomial function which fits the measurement data;

kn is fitting coefficients;

N is number of data points

A.2 Polynomial function for function fitting of input impedance

Function fitting can be applied to the magnitude, real and imaginary components or phase of the input

impedance The fitting shall be applied to open/short input impedance data (ZOS) It works best with logarithmic spaced frequency data (most VNA offer this type of sweep) in that it results in appropriate weighting of the lower and upper ends of a multi-decade frequency sweep

The magnitude of the open/short input impedance it fitted by following polynomial:

Trang 21

IZfitI is fitting of the magnitude of the open/short input impedance;

Re(Zfit) is fitting of the real part of the open/short input impedance;

Im(Zfit) is fitting of the imaginary of the open/short input impedance;

(Zfit) is fitting of the angle of the open/short input impedance

A.3 Fewer terms

Depending on the measurement frequency range and the amount of structural variation, usage of one or more of the higher order terms may not be justifiable The contributions from the higher order terms are intended to be second order

Where the data spans one decade or less, only the first two terms (or perhaps only the constant term) may

be justified The resultant function fit is considered valid if it has a negative slope at low frequencies, is asymptotic at higher frequencies and is free of oscillation with frequency Two or three terms may be sufficient when the data spans only one or two decades of frequency If the capacitance is changing with frequency as it does when polar dielectric material is present, more terms are generally justified

Four criteria indicate use of fewer terms – check or have the computer program determine if the fitted meets the following set of four criteria

a) The fitted function, except when it is only a constant, has negative slope for frequencies below 3 MHz b) The 10 MHz fitted value is within the impedance range of +5 to –2 of the high frequency asymptote (fitted constant value)

c) The area under the fitted function supplied by the frequency dependent terms on a log frequency basis, exclusive of the constant area, is positive (constant component is not above the data)

Ngày đăng: 14/04/2023, 08:35

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN