1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 13063 2 2005 (2007)

42 3 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Chimneys — System Chimneys With Clay/Ceramic Flue Liners — Part 2: Requirements And Test Methods Under Wet Conditions
Trường học British Standards Institution
Chuyên ngành Standards
Thể loại standard
Năm xuất bản 2005
Thành phố Brussels
Định dạng
Số trang 42
Dung lượng 567,73 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

untitled BRITISH STANDARD BS EN 13063 2 2005 Incorporating amendment no 1 Chimneys — System chimneys with clay/ceramic flue liners — Part 2 Requirements and test methods under wet conditions The Europ[.]

Trang 1

Incorporating amendment no 1

Chimneys — System

chimneys with

clay/ceramic flue

liners —

Part 2: Requirements and test methods

under wet conditions

The European Standard EN 13063-2:2005, incorporating amendment

A1:2007, has the status of a British Standard

ICS 91.060.40

Trang 2

This British Standard was

published under the authority

of the Standards Policy and

A list of organizations represented on this subcommittee can be obtained on request to its secretary

This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application

Compliance with a British Standard cannot confer immunity from legal obligations.

Amendments issued since publication

17365 28 September 2007 Implementation of CEN amendment A1:2007

Trang 3

NORME EUROPÉENNE

ICS 91.060.40 Supersedes EN 13063-2:2005

English Version

Chimneys - System chimneys with clay/ceramic flue liners - Part

2: Requirements and test methods under wet conditions

Conduits de cheminées - Conduits de cheminées résistant

aux feux de cheminées à paroi intérieure en terre

cuite/céramique - Partie 2: Exigences et méthodes d'essai

en conditions humides

Abgasanlagen - System-Abgasanlagen mit Innenrohren - Teil 2: Anforderungen und Prüfungen für

Keramik-feuchte Betriebsweise

This European Standard was approved by CEN on 1 April 2005 and includes Amendment 1 approved by CEN on 14 June 2007

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom

EUROPEAN COMMITTEE FOR STANDARDIZATION

C O M I T É E U R O P É E N D E N O R M A L I S A T I O N

E U R O P Ä I S C H E S K O M I T E E FÜ R N O R M U N G

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2007 CEN All rights of exploitation in any form and by any means reserved

worldwide for CEN national Members

Ref No EN 13063-2:2005+A1:2007: E

Trang 4

Contents Page

Foreword 3

1 Scope 4

2 Normative references 5

3 Terms and definitions 5

4 Shapes, dimensions and tolerances 7

5 Material requirements 7

6 Replacement of single components of the system chimney 12

7 Designation 13

8 Product information 14

9 Marking and labelling 15

10 Evaluation of conformity 15

Annex A (normative) Test methods 18

Annex B (informative) Thermal resistance 27

Annex C (normative) Sampling procedures for an AQL of 10 % and inspection level S2 28

Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive 32

Bibliography 39

Trang 5

Foreword

This document (EN 13063-2:2005+A1:2007) has been prepared by Technical Committee CEN/TC 166

“Chimneys”, the secretariat of which is held by UNI

This document shall be given the status of a national standard, either by publication of an identical text or

by endorsement, at the latest by January 2008 and conflicting national standards shall be withdrawn at the latest by April 2009

This document includes Amendment 1 approved by CEN on 2007-06-14

This document supersedes EN 13063-2:2005

The start and finish of text introduced or altered by amendment is indicated in the text by tags ! " This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s)

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document This document is part 2 of a series of standards for system chimneys with clay/ceramic flue liners

Part 1 is for chimneys with sootfire resistance and part 3 is for system air flue chimneys

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom

Trang 6

1 Scope

This European Standard specifies the requirements and test methods for multiwall system chimneys working under wet conditions (in the following expressed as “wet chimney”) with pressure type N1, N2 or P1 according to EN 1443 and a working temperature below or equal T600 according

to !EN 13063-1:2005+A1", in which the products of combustion are conveyed to the atmosphere through clay/ceramic flue liners Marking and inspection are also covered by this document

This European Standard does not apply to structurally independent (free standing or self-supporting) system chimneys

The wet chimney may comprise the following appropriate components:

 clay/ceramic flue liners;

 insulation layer;

 outer walls;

 acid resistant mortar for jointing flue liners or elastomeric sealant;

 mortar for jointing outer walls;

Trang 7

2 Normative references

The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies

EN 998-2:2003,!Specification for mortar for masonry – Part 2: Masonry mortar"

EN 1366-8,!Fire resistance tests for service installations – Part 8: Smoke extraction ducts"

EN 1443:2003, Chimneys – General requirements

EN 1457:1999, Chimneys – Clay/ceramic flue liners – Requirements and test methods

EN 12446:2003, Chimneys – Components – Concrete outer wall elements

!EN 13063-1:2005+A1:2007", Chimneys – System chimneys with clay/ceramic flue liners – Part 1: Requirements and test methods for sootfire resistance

!EN 13069:2005", Chimneys – Clay/ceramic outer walls for system chimneys – Requirements and test methods

EN 13162:2001, Thermal insulation products for buildings – Factory made mineral wool (MW) products – Specification

EN 13216-1:2004, Chimneys - Test methods for system chimneys – Part 1: General test methods

EN 13384-1, Chimneys – Thermal and fluid dynamic calculation methods – Part 1: Chimneys serving one appliance

!EN 14241-1", Chimneys – Elastomeric seals and elastomeric sealants – Material requirements and test methods - Part 1: Seals in flue liners

EN 14297:2004, Chimneys – Freeze-thaw resistance test method for chimney products

!ISO 2859-1, Sampling procedures for inspection by attributes – Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-by-lot inspection"

3 Terms and definitions

For the purposes of this European Standard, the terms and definitions given in EN 1443:2003,

EN 13216-1:2004, !EN 13063-1:2005+A1:2007" and the following apply

3.1

system chimney under wet conditions

system chimney is a multiwall construction, consisting mainly of an outer wall, an insulation layer and the inner clay/ceramic flue liner that can work under wet conditions (see Figure 1)

Trang 8

5 cavities for structural reinforcement

6 non ventilated air gap

Figure 1 — Examples of construction of a chimney for wet conditions 3.2

wet operating conditions

conditions when the chimney is designed to operate normally with the temperature of the inner surface of the flue liner at and below the water dew point

prefabricated elastomeric seals

prefabricated element made of elastomeric material, which ensures a gastight seal in a joint

Trang 9

3.5.2

on site applied elastomeric sealant

sealing material which is applied on site to ensure the gas tightness

3.5.3

acid resistant mortar

jointing material made with acid resistant mortar

4 Shapes, dimensions and tolerances

4.1 Flue liners

4.1.1 General

Flue liners shall meet the requirements on size and tolerance of dimensions given in EN 1457:1999, 7.1, 7.2, 7.3, 7.4, 7.5, 7.6 and 7.7

4.1.2 External diameter of flue liner

When tested in accordance with A.2.6, the external diameter of circular flue liners measured on any diameter shall not deviate more than ± 3 % of the manufacturer’s stated nominal external diameter

4.2 Insulation

The insulation layer shall meet the requirements on tolerances of dimension given in EN 13162:2001, 4.2.2 (length and width) and 4.2.3 (thickness class T3)

4.3 Outer wall elements

Outer wall elements shall fulfil the requirements on shapes and tolerances on dimensions given in:

 concrete outer wall elements: EN 12446:2003, Clause 7;

 clay/ceramic outer walls: !EN 13069:2005", Clause 6;

 metal outer walls: !EN 13063-1:2005+A1:2007", Annex B

4.4 Cleaning and inspection doors

Dimensions and tolerances shall be declared by the manufacturers

!EN 13216-1:2004, 5.6, is passed according to the requirements in 5.3.2.1."

Trang 10

5.1.2 Maximum load for opening sections

When tested as described in A.2.3, components shall withstand a load (F) of at least five times the manufacturer's declared design load (H × G)

100

G H

where

F is the minimum load, expressed in kilonewton (kN);

χ is the safety factor equal to 5;

H is the height of the chimney, is expressed in meter (m);

G is expressed in kilogram per meter (kg/m)

NOTE The limiting factor of the maximum height of system chimneys is the compressive strength of the opening section

5.1.3 Jointing material for flue liners

5.1.3.1 Acid resistant mortar

When tested in accordance with A.2.2.5, the mass loss from any sample shall not exceed 2 %

5.1.3.2 Prefabricated elastomeric seals

The elastomeric seals shall comply with !EN 14241-1"

5.1.4 Insulation

5.1.4.1 General

The insulation shall be to the manufacturer’s specifications and shall be prefabricated and have an independent, permanent shape before and after being exposed to heat (e.g blocks or bonded loose material)

Trang 11

5.1.4.2 Durability under normal operating conditions

When tested in accordance with A.2.1 at test temperature related to the temperature class (see Table 1), the change in the outside surface temperature of the test sample after the fourth cycle of heating shall not exceed 10 % of the maximum outside surface temperature of the sample of the first cycle

Table 1 — Test temperatures

Temperature class T 80 T 100 T 120 T 140 T 160 T 200 T 250 T 300 T 400 T 450 T 600 Test temperature (°C) 100 120 150 170 190 250 300 350 500 550 700

5.1.5 Outer wall elements

Outer wall elements shall fulfil EN 12446 for concrete outer wall elements, !EN 13069" for clay/ceramic outer wall or Annex B of !EN 13063-1:2005+A1:2007" for metal outer walls

5.1.6 Jointing material for outer wall elements

Jointing materials used for jointing outer walls according to EN 12446 for concrete outer wall elements and !EN 13069" for clay/ceramic outer walls, where supplied with the system chimney, shall comply with the system chimney manufacturer's declared specification and shall be at least M2,5 according to

EN 998-2:2003, 5.3.1, Table 1

5.1.7 Wind load

The freestanding part of the chimney above the last lateral support of the system chimney shall withstand

a wind load of 1,5 kN/m2 The maximum permissible height of a chimney outside the building of a system chimney shall be calculated according to calculation methods applicable in the place of use of the chimney, taking into account the tilt momentum of the outer wall element Alternatively the tilt momentum

of the complete construction can be taken into account A test method to evaluate the tilt momentum is given in A.2.4

5.2 Safety in use

5.2.1 Thermal shock resistance

The wet chimney shall be tested at the normal operating conditions in accordance with the heat stress test method described in !EN 13216-1:2004, 5.7", for the required temperature types according to Table 1

5.2.2 Distance to combustible materials

5.2.2.1 General

The distance to combustible materials shall be tested at the normal operating condition in accordance with !EN 13216-1:2004, 5.7", the test assembly shall be the corner installation The distance between the outer surface of the chimney and the adjacent combustible material shall be declared as O(xx), where (xx) is the minimum distance in mm

5.2.2.2 Normal operating conditions

The wet chimney shall be tested in accordance with the heat stress test method described in

!EN 13216-1:2004, 5.7" for the required temperature types according to Table 1 The maximum surface temperature of combustible materials adjacent to the test wet chimney shall not be greater than

85 °C, when related to an ambient temperature of 20 °C

Trang 12

NOTE 1 This requirement is declared fulfilled when chimneys, where combustibles are at least 50 mm from the outer walls and the space ventilated, are tested in a free standing open room test assembly at the test-temperatures

500 °C (for T400) or 700 °C (for T600) and the temperature of the outer wall does not exceed 100 °C at an ambient temperature of 20 °C For this case the distance is designated as O50

NOTE 2 If the wet chimney has already been tested according to !EN 13063-1:2005+A1:2007", 5.2.1.1, the results can be used

5.2.3 Relative movement between flue liner and outer wall

After thermal testing (normal operating conditions) in accordance with !EN 13216-1:2004, 5.7", the final position after cooling down to room temperature of the upper flue liner shall be ± 5 mm to the original position when tested according to !EN 13216-1:2004, 5.3"

5.2.4 Thermal resistance

The thermal resistance value of the system chimney declared by the manufacturer shall be verified by testing according to the test method of EN 13216-1:2004, 5.8 (as the reference test method) or calculation in accordance with Annex B, both with inner surface temperature of the flue liner at 200 °C The designation of the thermal resistance shall be given as Ryy, where yy is the value in square metres Kelvin per Watt multiplied by 100, rounded to the nearest integer (e.g.: R22 is R=0,22 m2K/W)

5.2.5 Resistance to fire external to external

!Until a European test method is available the resistance to fire, external to external, shall be evaluated and declared according to national regulations

Examples of European classification are given in Table 2."

!Table 2 — Examples of European fire resistance performance classes""

Trang 13

Table 3 — Leakage rate

5.3.2 Durability

5.3.2.1 Condensate resistance

Wet chimneys shall have either clay/ceramic flue liners which are designated W according

to !EN 1457:1999, Clause 13 and EN 1457:1999/A1:2002, Clause 13", or clay/ceramic flue liners which are designated D according to !EN 1457:1999 and EN 1457:1999/A1:2002" if the chimney, when tested according to !EN 13216-1:2004, 5.6", shows no water vapour saturation in any part of the system chimney

Prefabricated elastomeric seals and on site applied elastomeric sealant shall comply with !EN 1" condensate class W at the designated temperature class of the wet chimney

14241-5.3.2.2 Corrosion resistance of flue liners and jointing material

The mass loss of clay/ceramic flue liners shall not exceed 2 % when tested according to EN 1457:1999, 16.9 Prefabricated elastomeric seals and on site applied elastomeric sealant shall comply with !EN 14241-1" corrosion class 1 or 2 at the designated temperature class of the wet chimney

5.3.3 Flow resistance of flue liners and fittings

!The manufacturer shall declare either:

1) The flow resistance measured according to EN 13216-1:2004, 5.11; or

2) The friction coefficient ζ and the mean roughness r calculated according to EN 13216-1:2004, 5.11; or

3) The default roughness value for clay/ceramic inner liners of r = 0,0015 m and/or the default friction coefficient ζ for fittings taken from EN 13384-1."

5.4 Cleaning and inspection doors

The increase of the surface temperature of the outer surface of the cleaning and inspection doors shall not exceed 140 K during thermal testing, the test shall be carried out in accordance with !EN 13216-1:2004, 5.7"

NOTE It is recommended that the distance to combustible materials should not be less than 400 mm from cleaning and inspection doors

When tested in accordance with !EN 13216-1:2004, 5.4", the complete system with cleaning and inspection doors shall not have a leakage rate greater than the values given in Table 3

The inspection opening shall not hinder the relative movement of the flue liner and no water shall occur

at the outside of the cleaning and inspection doors

Trang 14

5.5 Cladding and accessory exposed to freeze/thaw

!For particular climatic conditions and where subject to national regulations, the freeze/thaw resistance

of the flue liner and/or the outer wall of the system chimney shall be tested according to EN 14297 The product shall not present any damage of type 7, 8, 9 and 10 in accordance with EN 14297:2004, Table 1."

6 Replacement of single components of the system chimney

6.1 General

If the manufacturer changes a part of the system, it is possible to replace single components as described below If the manufacturing process or material of a single component changes, it shall also be tested like a replacement

6.2 Change of flue liner

To change the type of flue liner, the new values of each characteristic shall be compared to the original flue liner and shall not deviate more than the values given in Table 4

Table 4 — Requirements of flue liners for exchange

Characteristic of flue liner Requirement compared to originally used flue liner Test method for comparison

EN 1457:1999

Tolerances on dimensions Equal or tighter Clause 7

Density Equal or denser Clause 11

Temperature Equal or higher 16.8 Compressive strength Equal or higher 8.1

Acid resistance (mass loss) Equal or less Clause 10

Condensate resistance Equal or tighter 13.1

6.3 Change of opening sections

The opening sections shall be tested as described in A.2.3 The minimum load shall be equal or more than the original value

6.4 Change of insulation

To change the type of insulation, the new values of each characteristic shall be compared to the original flue liner and shall not deviate more than the values given in Table 5

Table 5 — Requirements of insulation for exchange

Characteristic of insulation originally used insulation flue liner Requirement compared to Test method for comparison

Thermal conductivity Equal or lower EN 13162:2001, 4.2.1

Layer thickness Equal or greater EN 13162 :2001, 4.2.3

Durability At least equal A.2.1

Trang 15

6.5 Change of jointing materials for flue liners

To change the jointing materials for flue liners, the new values of each characteristic shall be compared

to the original flue liner and shall not deviate more than the values given in Table 6

Table 6 — Requirements of jointing materials for flue liners for exchange

Characteristic of jointing materials originally used jointing materials Requirement compared to Test method for comparison

Compressive strength of mortar Equal or higher A.2.2.3

Water resistance of mortar (mass

loss) Equal or less A.2.2.4

Acid resistance of mortar (mass loss) Equal or less A.2.2.5

Prefabricated elastomeric seals Equal or higher !EN 14241-1"

Elastomeric sealant applied on site Equal or higher !EN 14241-1"

6.6 Change of outer wall elements

If concrete outer wall elements have to be changed they shall be according to EN 12446 and the flue liner shall be designated W Otherwise the system test for system chimneys under wet conditions according to !EN 13216-1:2004, 5.6", shall be applied

6.7 Change of cleaning and inspection doors

If a cleaning and inspection door shall be tested separately from the initial type test of the system chimney (e.g for exchange of component or use in more than one system), the doors shall be tested according to A.2.5

The increase of surface temperature before and after thermal testing shall be !less than 140 K" The gas tightness before and after thermal testing shall be within the leakage rate given in Table 3 The door shall not hinder the movement of the flue liner No condensate shall occur at the outside of the door when tested

 temperature class (see Table 1);

 resistance to condensate class (see 5.3.2.1);

 corrosion condensate class (see 5.3.2.2);

 soot fire resistance class followed by the distance to combustible materials (see 5.2.2);

NOTE The CE marking the distance to combustible material should not be indicated

 pressure class (see 5.3.1)

Trang 16

Typical example

System chimney EN 13063 –2 T400 N1 W 2 O50

Soot fire resistance

class followed by the

 product designation with explanation;

 installation drawing typical of the application;

 method of jointing the components;

 method of installing sections or fittings and accessories;

 minimum distance to combustibles;

 limitations of height and location of exposed section of the chimney;

 location of the inspection doors;

 resistance to fire external to external;

 values for performance calculation according to EN 13384-1:

 nominal temperature of the chimney;

Trang 17

 internal size of the flue liner (diameter or length and width);

 external size of the chimney (length and width or diameter);

 thermal resistance of the chimney;

 roughness of the flue liner;

 coefficient of flow resistance due to a directional change in the flue

9 Marking and labelling

The manufacturer shall make available a chimney plate made of a durable material that shall include the following information:

a) name or trademark of the manufacturer, engraved or indelibly marked;

 initial type testing;

 factory production control by the manufacturer, including product assessment

For the purposes of testing, the system chimneys working under wet conditions may be grouped into families, where it is considered that the selected property/properties is/are common to all the system chimneys working under wet conditions within that family

 clay/ceramic outer wall elements !EN 13069";

 concrete outer wall elements EN 12446;

 metal outer wall elements Annex B

Trang 18

10.3 Initial type testing

Type tests for the required characteristics given in Table 7 shall be performed initially together with

factory production control tests

The test sequence according to A.1 shall be carried out on one size of flue liner for each geometrical

configuration (e.g circular, square, rectangular) For circular flue liners the size to be tested shall be

(200 ± 50) mm internal diameter For other geometrical configurations the flue liner shall have an

equivalent cross-sectional area range

All other tests of Table 7, which are not included in the test sequence of A.1, are carried out separately

10.4 Exchange of components

A new component in the system chimney shall comply with the relevant requirement clauses given in

Table 7

Table 7 — Factory production control and type tests

Relevant requirement clauses

Exchange of components 10.4

Wind load 5.1.7 Thermal shock

Thermal

Gas tightness 5.3.1 Flow resistance

of inner liners and fittings

5.3.3 Wet chimney

13063-B.2

!EN 1:2005+A1:2007",

13063-B.3

not possible cleaning and inspection doors 4.4 5.4 6.7

10.5 Factory production control

To achieve compliance with this document the manufacturer shall establish and maintain an effective

documented quality system

Trang 19

Factory production control tests are carried out by the manufacturer to monitor the quality of product (see Table 7)

Sampling and testing of any batch shall be completed prior to removal from the works and shall be in accordance with ISO 2859-1 at an AQL of 10 % and inspection level S2 Isolated batches of units shall

be assessed in accordance with tightened inspection procedures, with a maximum batch size of

1 200 (see Annex C)

Batches rejected under the factory production control procedure may be resubmitted once, after removal

of units with previously undetected visible defects, under the tightened inspection procedures, in respect only of the defect that caused initial rejection

NOTE A FPC system conforming with the above requirements of the relevant part(s) of EN ISO 9001 and made specific to the requirements of this document, is considered to satisfy the above requirements

Trang 20

Annex A

(normative)

A.1 Test sequence for wet chimneys

The testing of wet chimneys in accordance with EN 13216-1 shall be carried out with the following test sequence:

A.2 Additional test methods

A.2.1 Heat resistant test method for insulation (durability)

The test sample of insulation shall be placed in the test frame (0,4 x 0,4) m so that it will remain stable during the test The test frame shall be fitted into the opening on one side of a box furnace which is capable of being heated so that the temperature on the inside surface of the inside face of the test sample follows the heating curve shown in Figure A.1 until it reaches the test temperature according to Table 1

Trang 21

Key

X time in min

Y temperature in K

Figure A.1 — Heating curve

Thermocouples shall be placed at the centre of the inside and outside surface of the test sample Both temperatures shall be measured and recorded

After reaching the required test temperature the furnace is allowed to cool for one hour The heating and cooling cycle is repeated four times

A.2.2 Test for acid resistant mortar

A.2.2.1 Preparation of specimens

Specimens shall be prepared as cylinders and shall be preconditioned at ambient temperature and at a relative humidity of 65 % for 7 d or as manufacturer declared They shall have a minimum diameter of 26

mm and their height shall be between 1 and 1,5 times the diameter They shall have flat top and bottom faces which are to be in contact with the platens of the testing machine

Ngày đăng: 14/04/2023, 00:55

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN