1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 01859 2009 + a1 2013

52 1 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Chimneys — Metal Chimneys — Test Methods
Trường học The British Standards Institution
Chuyên ngành Standards
Thể loại British Standard
Năm xuất bản 2009
Thành phố Brussels
Định dạng
Số trang 52
Dung lượng 1,67 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 4.1 Compressive strength (7)
    • 4.1.1 Sections and Fittings (7)
    • 4.1.2 Chimney support (8)
  • 4.2 Tensile strength (8)
    • 4.2.1 Test assembly (8)
    • 4.2.2 Test procedure and results (8)
  • 4.3 Lateral strength (8)
    • 4.3.1 Fittings in non-vertical orientation (8)
    • 4.3.2 Wind load (9)
  • 4.4 Gas tightness (9)
    • 4.4.1 Test assembly (9)
    • 4.4.2 Procedure and results (9)
  • 4.5 Thermal performance test (9)
    • 4.5.1 Apparatus (9)
    • 4.5.2 Test environment and conditioning (12)
    • 4.5.3 Test procedure (12)
    • 4.5.4 Results (13)
  • 4.6 Thermal resistance (15)
    • 4.6.1 Test assembly (15)
    • 4.6.2 Test procedure (15)
    • 4.6.3 Results (15)
  • 4.7 Water vapour diffusion resistance (16)
    • 4.7.1 Conditioning (16)
    • 4.7.2 Test assembly (16)
    • 4.7.3 Test procedure (16)
    • 4.7.4 Results (16)
  • 4.8 Condensate resistance test (16)
    • 4.8.1 Test apparatus (16)
    • 4.8.2 Test sample (16)
    • 4.8.3 Measuring parameters (16)
    • 4.8.4 Test procedure (16)
    • 4.8.5 Test results (17)
  • 4.9 Rainwater resistance (17)
    • 4.9.1 Chimney sections (17)
    • 4.9.2 Rainwater terminal (17)
  • 4.10 Terminal flow resistance (18)
    • 4.10.1 Conditioning (18)
    • 4.10.2 Test assembly (18)
    • 4.10.3 Procedure (18)
    • 4.10.4 Results (19)
  • 4.11 Aerodynamic behaviour of terminal under wind conditions (19)
    • 4.11.1 Conditioning (19)
    • 4.11.2 Test assembly (19)
    • 4.11.3 Procedure (19)
    • 4.11.4 Results (19)
  • 4.12 Flow resistance of fittings (19)
    • 4.12.1 Determination of flow conditions (19)
    • 4.12.2 Test assembly (20)
    • 4.12.3 Execution of the measurements (20)
    • 4.12.4 Calculation of the friction value (21)
  • E.1 Test structure, surface temperatures (40)
  • E.2 Test chimney, surface temperatures (40)
    • E.2.1 General (40)
    • E.2.2 Test chimney, freestanding (40)
    • E.2.3 Test chimney, corner installation (40)
    • E.2.4 Test chimney, corner installation, enclosed (41)
  • Annex I informative) Techniques for flue gas volume flow measurements (36)

Nội dung

4.1.1.2 Procedure and results Increase the test load on the components without shock up to 4 times the design load where the flue liner isload bearing or 3 times the design load where t

Trang 1

ICS 91.060.40

Chimneys —

Metal chimneys

— Test methods

Trang 2

Amendments/corrigenda issued since publication

30 April 2013 Implementation of CEN amendment A1:2013

This British Standard was

published under the authority

of the Standards Policy and

This British Standard is the UK implementation of EN 1859:2009+A1:2013

It supersedes BS EN 1859:2009 which is withdrawn

The start and finish of text introduced or altered by amendment is indicated

in the text by tags Tags indicating changes to CEN text carry the number of the CEN amendment For example, text altered by CEN amendment A1 is indicated by 

The UK participation in its preparation was entrusted by Technical Committee B/506, Chimneys to Subcommittee B/506/5, Chimneys and their components having inner linings of metal

A list of organizations represented on this subcommittee can be obtained on request to its secretary

The publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application

Compliance with a British Standard cannot confer immunity from legal obligations.

Trang 3

NORME EUROPÉENNE

English Version

Chimneys - Metal chimneys - Test methods

Conduits de fumée - Conduits de fumée métalliques -

Méthodes d'essai Abgasanlagen - Metall-Abgasanlagen - Prüfverfahren

This European Standard was approved by CEN on 1 May 2009 and includes Amendment 1 approved by CEN on 24 February 2013

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European

Standard the status of a national standard without any alteration Up-to-date lists and bibliographical references concerning such national

standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,

Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom

EUROPEAN COMMITTEE FOR STANDARDIZATION

C O M I T É E URO P É E N D E N O RM A LI S A T I O N

E URO P Ä I S C HE S K O M I T E E F ÜR N O RM UN G

Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2013 CEN All rights of exploitation in any form and by any means reserved worldwide

for CEN national Members Ref No EN 1859:2009+A1:2013: E

Trang 4

Contents

Page

Foreword 4

1 Scope 5

2 Normative references 5

3 Definitions 5

4 Test methods for metal chimney products 5

4.1 Compressive strength 5

4.1.1 Sections and Fittings 5

4.1.2 Chimney support 6

4.2 Tensile strength 6

4.2.1 Test assembly 6

4.2.2 Test procedure and results 6

4.3 Lateral strength 6

4.3.1 Fittings in non-vertical orientation 6

4.3.2 Wind load 7

4.4 Gas tightness 7

4.4.1 Test assembly 7

4.4.2 Procedure and results 7

4.5 Thermal performance test 7

4.5.1 Apparatus 7

4.5.2 Test environment and conditioning 10

4.5.3 Test procedure 10

4.5.4 Results 11

4.6 Thermal resistance 13

4.6.1 Test assembly 13

4.6.2 Test procedure 13

4.6.3 Results 13

4.7 Water vapour diffusion resistance 14

4.7.1 Conditioning 14

4.7.2 Test assembly 14

4.7.3 Test procedure 14

4.7.4 Results 14

4.8 Condensate resistance test 14

4.8.1 Test apparatus 14

4.8.2 Test sample 14

4.8.3 Measuring parameters 14

4.8.4 Test procedure 14

4.8.5 Test results 15

4.9 Rainwater resistance 15

4.9.1 Chimney sections 15

4.9.2 Rainwater terminal 15

4.10 Terminal flow resistance 16

4.10.1 Conditioning 16

4.10.2 Test assembly 16

4.10.3 Procedure 16

4.10.4 Results 17

4.11 Aerodynamic behaviour of terminal under wind conditions 17

4.11.1 Conditioning 17

4.11.2 Test assembly 17

4.11.3 Procedure 17

4.11.4 Results 17

Trang 5

Contents

Page

Foreword 4

1 Scope 5

2 Normative references 5

3 Definitions 5

4 Test methods for metal chimney products 5

4.1 Compressive strength 5

4.1.1 Sections and Fittings 5

4.1.2 Chimney support 6

4.2 Tensile strength 6

4.2.1 Test assembly 6

4.2.2 Test procedure and results 6

4.3 Lateral strength 6

4.3.1 Fittings in non-vertical orientation 6

4.3.2 Wind load 7

4.4 Gas tightness 7

4.4.1 Test assembly 7

4.4.2 Procedure and results 7

4.5 Thermal performance test 7

4.5.1 Apparatus 7

4.5.2 Test environment and conditioning 10

4.5.3 Test procedure 10

4.5.4 Results 11

4.6 Thermal resistance 13

4.6.1 Test assembly 13

4.6.2 Test procedure 13

4.6.3 Results 13

4.7 Water vapour diffusion resistance 14

4.7.1 Conditioning 14

4.7.2 Test assembly 14

4.7.3 Test procedure 14

4.7.4 Results 14

4.8 Condensate resistance test 14

4.8.1 Test apparatus 14

4.8.2 Test sample 14

4.8.3 Measuring parameters 14

4.8.4 Test procedure 14

4.8.5 Test results 15

4.9 Rainwater resistance 15

4.9.1 Chimney sections 15

4.9.2 Rainwater terminal 15

4.10 Terminal flow resistance 16

4.10.1 Conditioning 16

4.10.2 Test assembly 16

4.10.3 Procedure 16

4.10.4 Results 17

4.11 Aerodynamic behaviour of terminal under wind conditions 17

4.11.1 Conditioning 17

4.11.2 Test assembly 17

4.11.3 Procedure 17

4.11.4 Results 17

4.12 Flow resistance of fittings 17

4.12.1 Determination of flow conditions 17

4.12.2 Test assembly 18

4.12.3 Execution of the measurements 18

4.12.4 Calculation of the friction value 19

5 Test report 19

Annex A (normative) Method for measuring ambient temperature 34

Annex B (normative) Method for hot gas temperature measurements 35

Annex C (informative) Method for metal surface temperature measurements 36

Annex D (normative) Method for combustible wood surface temperature measurements 37

Annex E (normative) Locations of thermocouples for surface temperature measurements 38

E.1 Test structure, surface temperatures 38

E.2 Test chimney, surface temperatures 38

E.2.1 General 38

E.2.2 Test chimney, freestanding 38

E.2.3 Test chimney, corner installation 38

E.2.4 Test chimney, corner installation, enclosed 39

Annex F (normative) Simplified calculation of thermal resistance for circular flues 43

Annex G (informative) Method for applying an evenly distributed load (horizontal) 45

Annex H (informative) Possible test sequence 46

Annex I (informative) Techniques for flue gas volume flow measurements 47

Bibliography 48

Trang 6

Foreword

This document (EN 1859:2009+A1:2013) has been prepared by Technical Committee CEN/TC 166

“Chimneys”, the secretariat of which is held by !ASI"

This European Standard shall be given the status of a national standard, either by publication of an identicaltext or by endorsement, at the latest by October 2013, and conflicting national standards shall be withdrawn atthe latest by October 2013

Attention is drawn to the possibility that some of the elements of this document may be the subject of patentrights CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights This document includes Amendment 1 approved by CEN on 24 February 2013

This document !supersedes EN 1859:2009"

The start and finish of text introduced or altered by amendment is indicated in the text by tags !"

According to the CEN/CENELEC Internal Regulations, the national standards organisations of the followingcountries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, CzechRepublic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom

Trang 7

Foreword

This document (EN 1859:2009+A1:2013) has been prepared by Technical Committee CEN/TC 166

“Chimneys”, the secretariat of which is held by !ASI"

This European Standard shall be given the status of a national standard, either by publication of an identical

text or by endorsement, at the latest by October 2013, and conflicting national standards shall be withdrawn at

the latest by October 2013

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent

rights CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights

This document includes Amendment 1 approved by CEN on 24 February 2013

This document !supersedes EN 1859:2009"

The start and finish of text introduced or altered by amendment is indicated in the text by tags !"

According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following

countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech

Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,

Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,

Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom

EN 1443:2003, Chimneys General requirements

EN 1856-1:2009, Chimneys Requirements for metal chimneys Part 1: System chimney products

EN 60068-2-59, Environmental testing Part 2: Test methods Test Fe: Vibration, Sine beat method (IEC 60068-2-59:1990)

EN 60529, Degrees of protection provided by enclosures (IP Code) (IEC 60529:1989) ISO 3966, Measurement of fluid flow in closed conduits Velocity area method using Pitot static tubes

3 Definitions

For the purposes of this standard, the definitions given in EN 1443:2003 and EN 1856-1:2009 apply

4 Test methods for metal chimney products 4.1 Compressive strength

4.1.1 Sections and Fittings 4.1.1.1 Test assembly

Assemble the fitting according to the manufacturer's installation instructions between two adaptors includingone chimney section (see Figure 1a) The adaptors shall be supplied by the chimney manufacturer and shalltransfer the test load in the usual way to the load bearing wall of the test components as it is done in theinstallation The test load shall be transferred to the test components by means of a pivoted plate

4.1.1.2 Procedure and results

Increase the test load on the components without shock up to 4 times the design load where the flue liner isload bearing or 3 times the design load where the flue liner is non load bearing The load shall be measured to

an accuracy of 2 % of the design load Record the result

Where the design load is unknown, increase the test load uniformly and record the results to allow the point offailure to be detected Failure is deemed to have occurred when the fitting cannot sustain a further increase inload

Use the minimum value from three failure loads to determine the design load

Trang 8

4.1.2 Chimney support

4.1.2.1 Test assembly

Install the chimney support according to the manufacturer's installation instructions Apply the test load to thechimney support through a chimney section and an adaptor (see Figure 1b) The adaptor shall be supplied bythe chimney manufacturer and shall transfer the test load in the usual way to the load bearing wall of thechimney sections The test load shall be transferred to the test component by means of a pivoted plate

4.1.2.2 Procedure and results

Increase the test load up to the design load without shock Record the maximum displacement of the chimney.Measure the displacement to an accuracy of 0,1 mm

Further increase the load up to 3 times the design load Record the results

Measure the load to an accuracy of 2 % of the design load

Where the design load is unknown, increase the load uniformly and record the results to allow the point offailure to be detected Failure is deemed to have occurred when the support cannot sustain a further increase

4.2.2 Test procedure and results

Increase the test load on the components without shock up to 1,5 times the design load The load shall bemeasured to an accuracy of 2 % of the design load Record the result

Where the design load is unknown, increase the test load uniformly and record the results to allow the point offailure to be detected Failure is deemed to have occurred when the fitting cannot sustain a further increase inload

Use the minimum value from three failure loads to determine the design load

4.3.1.2 Procedure and results

Trang 9

4.1.2 Chimney support

4.1.2.1 Test assembly

Install the chimney support according to the manufacturer's installation instructions Apply the test load to the

chimney support through a chimney section and an adaptor (see Figure 1b) The adaptor shall be supplied by

the chimney manufacturer and shall transfer the test load in the usual way to the load bearing wall of the

chimney sections The test load shall be transferred to the test component by means of a pivoted plate

4.1.2.2 Procedure and results

Increase the test load up to the design load without shock Record the maximum displacement of the chimney

Measure the displacement to an accuracy of 0,1 mm

Further increase the load up to 3 times the design load Record the results

Measure the load to an accuracy of 2 % of the design load

Where the design load is unknown, increase the load uniformly and record the results to allow the point of

failure to be detected Failure is deemed to have occurred when the support cannot sustain a further increase

in load

Record the displacement during the load increase Use the minimum value from three failure loads to

determine the design load

4.2 Tensile strength

4.2.1 Test assembly

Install the chimney sections according to the manufacturer's installation instructions Apply the test load

through an adaptor (see Figure 1c) The adaptor shall be supplied by the chimney manufacturer and shall

transfer the test load in the usual way to the load bearing wall of the chimney sections

4.2.2 Test procedure and results

Increase the test load on the components without shock up to 1,5 times the design load The load shall be

measured to an accuracy of 2 % of the design load Record the result

Where the design load is unknown, increase the test load uniformly and record the results to allow the point of

failure to be detected Failure is deemed to have occurred when the fitting cannot sustain a further increase in

Install the chimney fittings and supports at the maximum angle from vertical according to the manufacturer's

installation instructions using additional vertical supports to install the sections without deflection

(see Figure 2)

4.3.1.2 Procedure and results

Remove the additional vertical supports Record the maximum deflection to an accuracy of 0,1 mm

4.3.2 Wind load 4.3.2.1 Test assembly

Install the chimney components according to the manufacturer's installation instructions Use the testassembly consisting of the manufacturer's declared freestanding components and further chimney sections up

to the manufacturer's maximum declared lateral support separation distance between the supports, and onceagain the same distance up to an anchor point (see Figure 3)

4.3.2.2 Procedure and results

Apply an evenly distributed test load increased uniformly up to 1,5 kN/m2 ± 2,5 %

NOTE A method for applying an evenly distributed load is described in informative Annex G Other methods using avertical assembly may also be used

Apply the test load to those components declared by the manufacturer for external use, except 50 % of thelast laterally supported section of the test assembly

Apply the test load by a number of individual evenly distributed loads equally spaced from the freestandingend at not more than (0,2 ± 0,01) m intervals The individual loads shall not vary by more than 1 % Recordthe results

4.4 Gas tightness

4.4.1 Test assembly

Construct the test assembly as described in 4.5 Seal the test assembly chimney flue outlet with an air tightseal Use adaptors supplied by the manufacturer in order to ensure that the chimney inlet and outlet areclosed in a typical manner Connect a positive pressure air supply and flow meter to the test chimney flue inletwith appropriate air tight seals Connect a manometer to the flue of the test assembly (see Figure 4)

4.4.2 Procedure and results

The test shall be carried out at ambient temperature

Deliver air from the air supply to the flue at a rate necessary to achieve and maintain the required testpressure given in Table 1 of EN 1856-1:2009

Measure the test pressure and the air flow rate, both to an accuracy of ± 5,0 %

Record the air flow rate

4.5 Thermal performance test

4.5.1 Apparatus

The test assembly shall comprise a test structure (see 4.5.1.2), a test chimney (see 4.5.1.3), a hot gasconnecting pipe (see 4.5.1.4), and measuring equipment (see 4.5.1.5)

4.5.1.1 Test assembly

Construct an open room outlet test assembly consisting of the test chimney in the test structure

The chimney shall be tested according to Figure 5

NOTE Figure 6 shows the arrangement for testing off-sets

Trang 10

4.5.1.2 Test structure

4.5.1.2.1 General

Construct a test structure consisting of two walls at right angles and two floors through which the test chimneypasses, of construction as described in 4.5.1.2.2 and 4.5.1.2.3 or of equivalent thermal characteristics anddimensions The floor opening and wall position shall enable the test chimney to be erected so that all parts ofthe test structure are at the manufacturer's specified clearance X mm from the chimney The area below thefirst floor referenced as Zone A, the area between the first floor and second floor as Zone B, and the areaabove the second floor as Zone C, as shown in Figure 5 The wall/floor interface shall be fitted with nominally

20 mm x 100 mm skirting board The vertical distance between the floor and ceiling in Zone B shall be(2 400 ± 25) mm The height of the chimney protruding into Zone C shall not be less than 900 mm Timbersshall have a dimensional tolerance of ± 1 mm

at 20 °C, with a minimum density of 70 kg/m3

4.5.1.3 Test chimney

Construct the test chimney using the components materials and construction representing the manufacturer'sproduct range, including a termination, and, at least 7 joints Assemble the chimney in accordance with themanufacturer's installation instructions, including firestops or firestops and spacers to a height of not less than4,5 m, including base support components, if used

Construct the test chimney according to Figure 5 for all sections, T pieces and inspection openings

Where a manufacturer’s product range includes bends, the test chimney shall include one offset(see Figure 6), with an offset angle of maximum 45° and an offset distance of 0.75 m ± 0.25 m

Any inspection opening shall be in Zone C

Include any finishing (e.g non-combustible enclosures or claddings) specified in the manufacturer'sinstructions

4.5.1.4 Hot gas connecting pipe

Construct a purpose-made insulated straight flue pipe having an internal diameter equal to that of the flue ofthe test chimney of a length of approximately seven diameters (7D) measured from the centre line of the fluegas generator to the entry to the test chimney, insulated to provide a thermal resistance value of not less thanthat equivalent to 50 mm thickness of material having a thermal conductivity of 0,125 W/m K ± 0,005 W/m K at750°C

Trang 11

4.5.1.2 Test structure

4.5.1.2.1 General

Construct a test structure consisting of two walls at right angles and two floors through which the test chimney

passes, of construction as described in 4.5.1.2.2 and 4.5.1.2.3 or of equivalent thermal characteristics and

dimensions The floor opening and wall position shall enable the test chimney to be erected so that all parts of

the test structure are at the manufacturer's specified clearance X mm from the chimney The area below the

first floor referenced as Zone A, the area between the first floor and second floor as Zone B, and the area

above the second floor as Zone C, as shown in Figure 5 The wall/floor interface shall be fitted with nominally

20 mm x 100 mm skirting board The vertical distance between the floor and ceiling in Zone B shall be

(2 400 ± 25) mm The height of the chimney protruding into Zone C shall not be less than 900 mm Timbers

shall have a dimensional tolerance of ± 1 mm

4.5.1.2.2 Walls

Construct walls consisting of nominal dimension 38 mm x 89 mm thick timbers in a framework (see Figure 5)

faced on each side with one layer of nominally 12 mm thick plywood to give a total thickness of

113 mm ± 1 mm, insulated in the voids with mineral fibre insulant having a thermal conductivity of

0,035 W/m K ± 0,002 W/m K at 20 °C with a minimum density of 70 kg/m3 The walls shall extend at least

1 200 mm

4.5.1.2.3 Floors

Construct flooring framework of nominal dimension 50 mm x 200 mm timbers at the first floor level and

nominal dimension 50 mm x 100 mm timbers at the second floor level forming an opening that enables the

test chimney to be erected so that all parts of the test structure comply with the manufacturer's declared

minimum distance to combustible material from the chimney fittings (see Figure 5) and covered with one

thickness of nominal dimension 20 mm boarding for the floors and one thickness of nominal dimension 12 mm

plywood for the ceilings, except for the second floor ceiling (exposed top), and the spaces between the

timbers filled with 100 mm thick mineral wool slab with a thermal conductivity of 0,035 W/m K ± 0,002 W/m K

at 20 °C, with a minimum density of 70 kg/m3

4.5.1.3 Test chimney

Construct the test chimney using the components materials and construction representing the manufacturer's

product range, including a termination, and, at least 7 joints Assemble the chimney in accordance with the

manufacturer's installation instructions, including firestops or firestops and spacers to a height of not less than

4,5 m, including base support components, if used

Construct the test chimney according to Figure 5 for all sections, T pieces and inspection openings

Where a manufacturer’s product range includes bends, the test chimney shall include one offset

(see Figure 6), with an offset angle of maximum 45° and an offset distance of 0.75 m ± 0.25 m

Any inspection opening shall be in Zone C

Include any finishing (e.g non-combustible enclosures or claddings) specified in the manufacturer's

instructions

4.5.1.4 Hot gas connecting pipe

Construct a purpose-made insulated straight flue pipe having an internal diameter equal to that of the flue of

the test chimney of a length of approximately seven diameters (7D) measured from the centre line of the flue

gas generator to the entry to the test chimney, insulated to provide a thermal resistance value of not less than

that equivalent to 50 mm thickness of material having a thermal conductivity of 0,125 W/m K ± 0,005 W/m K at

750°C

NOTE This item should be supplied by the chimney manufacturer

4.5.1.5 Measuring equipment and its location 4.5.1.5.1 Ambient temperature

Measure ambient air temperature with an accuracy of ± 1,5°C, in Zone A at a position 300 mm ± 5 mm belowthe ceiling and in all other zones 300 mm ± 5 mm above the floor

When testing a non-enclosed chimney, place additional ambient measuring points at levels corresponding tothe outer surface temperature measurements

The method is described in normative Annex A

4.5.1.5.2 Hot gas temperature

Measure the hot gas temperature with an accuracy of ± 3 °C for hot gas temperatures less than or equal to

600 °C and ± 0,75 % for hot gas temperatures greater than 600 °C at a position 50 mm ± 2 mm before theinlet to the test chimney and at a point in the cross section coincident with the highest temperature position The method is described in normative Annex B

4.5.1.5.3 Metal surface temperature

Measure the surface temperature of metal components with an accuracy of ± 1,5 °C

A method is described in informative Annex C

4.5.1.5.4 Combustible/wood surface temperature

Measure the surface temperature of the adjacent wood/combustible parts of the test structure with anaccuracy of ± 1,5 °C

The method is described in normative Annex D

4.5.1.5.5 Locations for surface temperature measurements

Establish the maximum temperature of the surfaces of the test structure and the test chimney during thethermal cycle appropriate to the designation

Locations for thermocouples are described in normative Annex E

4.5.1.5.6 Chimney draught measurement

Measure the draught in the chimney with an accuracy of ± 2 %, through a 150 mm ± 2 mm length of stainlesssteel tubing, internal diameter

3mm

1

0 +mm

mm inserted through the flue pipe and flush with the flue surface and sealed by brazing, at a distance of 100 mm ± 2 mm from the entry to the test chimney

4.5.1.5.7 Hot gas volume flow

Measure the flue gas volume to an accuracy of + 10 %, - 5 %

Informative Annex I gives acceptable techniques

Trang 12

4.5.2 Test environment and conditioning

4.5.2.1 Test room

The test room shall consist of a ventilated space not subject to draughts greater than 0,5 m/s measured at theambient thermocouple positions (see 4.5.1.5) This requirement is deemed fulfilled in a closed test room Ambient temperature within the test building shall be maintained within the limit of 15 °C to 30 °C, measured

at the designated ambient temperature positions (see 4.5.1.5)

The humidity shall be controlled between 30 % - 70 % RH

Ambient air shall be able to circulate freely between all parts of the test room

The distance between the test assembly and other structures (e.g test room walls) shall be at least 1,0 m

Incorporate a drying phase into the thermal cycle if required by the manufacturer's instructions

Blow hot gases into the chimney in such a way that the hot gas temperature (see 4.5.1.5.2) rises to thenominated test temperature in 60 min ± 5 min, unless otherwise required

Seal only joints and openings between spacers or supports and the test structure and all joints in theenclosure casing

Install a chimney designated for use without an enclosure into the test structure, without enclosing the testchimney and without closing the floor penetrations (see Figure 7)

For a chimney designated for internal use and with non combustible enclosure, the sides of the enclosureshall be closed to the walls of the test assembly unless otherwise specified by the manufacturer, (seeFigure 8) Install the floor penetration assembly supplied by the manufacturer

Maintain the test environment

Trang 13

4.5.2 Test environment and conditioning

4.5.2.1 Test room

The test room shall consist of a ventilated space not subject to draughts greater than 0,5 m/s measured at the

ambient thermocouple positions (see 4.5.1.5) This requirement is deemed fulfilled in a closed test room

Ambient temperature within the test building shall be maintained within the limit of 15 °C to 30 °C, measured

at the designated ambient temperature positions (see 4.5.1.5)

The humidity shall be controlled between 30 % - 70 % RH

Ambient air shall be able to circulate freely between all parts of the test room

The distance between the test assembly and other structures (e.g test room walls) shall be at least 1,0 m

4.5.2.2 Vibration conditioning

Vibration conditioning shall be undertaken using vibration equipment and measuring techniques complying

with EN 60068-2-59

4.5.2.2.1 Procedure

Place each fitting intended for inclusion in the thermal test onto the vibrating table in its vertical orientation

Subject each fitting to a sinusoidal excitation at an acceleration equal to 9,81 m/sec2, with a frequency of

10 Hz and an amplitude of 2,5 mm for 45 min

4.5.2.3 Drying/conditioning phase

Incorporate a drying phase into the thermal cycle if required by the manufacturer's instructions

Blow hot gases into the chimney in such a way that the hot gas temperature (see 4.5.1.5.2) rises to the

nominated test temperature in 60 min ± 5 min, unless otherwise required

4.5.3 Test procedure

Install the chimney components which have been subjected to the vibration conditioning criteria of 4.5.2.2 in

the test assembly which is appropriate to the manufacturer's declared product designation

Encase a chimney designated for internal use and with combustible enclosure in Zone B on the remaining two

sides with 12 mm nominal dimension plywood and positioned on the basis of the manufacturer's specified

clearance to the enclosure and walls, measured between the outer surface of the chimney sections and the

interior surface of the enclosing materials Such clearance is referenced by the dimension xx

(see Figures 5 and 6) Close the floor penetrations at each ceiling and floor level with a firestop or firestop and

spacer arrangement supplied by the manufacturer

Seal only joints and openings between spacers or supports and the test structure and all joints in the

enclosure casing

Install a chimney designated for use without an enclosure into the test structure, without enclosing the test

chimney and without closing the floor penetrations (see Figure 7)

For a chimney designated for internal use and with non combustible enclosure, the sides of the enclosure

shall be closed to the walls of the test assembly unless otherwise specified by the manufacturer, (see

Figure 8) Install the floor penetration assembly supplied by the manufacturer

Maintain the test environment

Generate hot gas with the velocity flow and test temperature specified in Table 1 appropriate to the productdesignation and diameter

Adjust the hot gas flow pattern so that the overall temperature distribution factor (OTDF) for the hot gas is notgreater than 1,05

Where

re gas temperatu hot

mean

re gas temperatu hot

peak

=

Ensure that the hot gas CO/CO2 ratio does not exceed 0,01

Maintain the ambient temperature of the test room so that it does not vary by more than 5 °C for the duration

of the test

4.5.3.1 Heat stress test

Generate hot gas with the volume flow at - % of the value and the test temperature at 0+5% of the values specified in Table 1 appropriate to the product designation and diameter Regulate the rate of rise of the hotgas temperature to achieve the specified gas temperature (Tt) in time T = (Tt x 60/50) s ± 30 s

Maintain the flue gas temperature at the specified test temperature at 0+5% until equilibrium is achieved.Equilibrium is deemed to exist when the average rate of rise of the temperature on the test chimney orstructure does not exceed 2 °C per 30 min

In addition, for positive pressure chimney systems and negative pressure chimneys which incorporate a seal

or sealant as part of the joint, introduce hot gas to achieve the hot gas velocity and test temperature specified

in Table 1 for the product designation and diameter Maintain this condition for 10 min, then shut off the hotgas generator and allow to cool for 10 min Repeat this cycle 11 times Measure, at ambient temperature, with

an accuracy of 0.001 m, the change in vertical position of the chimney wall(s) at the top of the test samplebefore and after subjecting the product to the cycles

Measure and record the gas tightness according to 4.4

4.5.3.2 Thermal shock test

With the test assembly temperatures within 10 °C of the test room ambient conditions generate hot gas withthe volume flow and test temperature specified in Table 1 appropriate to the diameter Regulate the rate ofrise of the hot gas temperature to achieve 1 000 °C in 10 min ± 1 min

Maintain the hot gas temperature at

1000

50

Measure and record flue regularity and measure gas tightness according to 4.4

Repeat the heat stress test

4.5.4 Results

Record all temperature values as specified in 4.5.1.5 Record any instance where the temperature exceedsthe allowed values

Trang 14

For the purposes of determining temperature rises on chimney accessory parts and on enclosures andstructures, such temperatures shall be related to the ambient air temperature as follows

The temperatures of joists shall be related to the average of the ambient temperatures above and below thejoist area

The temperatures of floor and roof material shall be related to the ambient temperatures above the floor orroof

The temperatures of ceiling material shall be related to the ambient temperature below the ceiling

The temperatures of chimney surfaces or accessories shall be related to the ambient temperature of the zone

in which the chimney surface or accessory temperature is measured

During the heat stress test the temperature rise shall be based on the ambient temperature recorded at theend of the relevant firing period

Table 1 — Hot gas velocity as a function of test temperature T and diameter of the test chimney

Hot gas velocity in m/s at test temperature Temperature class

T 080 T 100 T 120 T 140 T 160 T 200 T 250 T 300 T 400 T 450 T 600 Soot-fire Test temperature in °C

Trang 15

For the purposes of determining temperature rises on chimney accessory parts and on enclosures and

structures, such temperatures shall be related to the ambient air temperature as follows

The temperatures of joists shall be related to the average of the ambient temperatures above and below the

joist area

The temperatures of floor and roof material shall be related to the ambient temperatures above the floor or

roof

The temperatures of ceiling material shall be related to the ambient temperature below the ceiling

The temperatures of chimney surfaces or accessories shall be related to the ambient temperature of the zone

in which the chimney surface or accessory temperature is measured

During the heat stress test the temperature rise shall be based on the ambient temperature recorded at the

end of the relevant firing period

Table 1 — Hot gas velocity as a function of test temperature T and diameter of the test chimney

Hot gas velocity in m/s at test temperatureTemperature class

T 080 T 100 T 120 T 140 T 160 T 200 T 250 T 300 T 400 T 450 T 600 Soot-fire Test temperature in °C

4.6.2 Test procedure

Maintain the test environment specified in 4.5.2.1

Circulate hot gas around the test assembly The velocity of the hot air shall be of 4 m/s minimum and the hotgas temperature at the ends of the test sections shall not differ by more than 10 K For negative pressurechimneys maintain the pressure in the test chimney between 0 Pa and -10 Pa

Measure the internal and external surface temperature of the chimney sections as specified in 4.5.1.5.5 For chimneys designated suitable for dry operation, the hot gas shall have a heat content and temperature sothat the inner surface of the chimney sections under test reaches a temperature 20 % below the designatedtemperature (nominal working temperature), but not more than 200 °C

For chimneys designated suitable for wet applications, the hot gas shall be water vapour saturated and shallhave a heat content and temperature such that the inner surface reaches a temperature of 70 °C The gas isconsidered saturated if humidity is equal to or greater than 95 % measured at entry to the test sample

Adjust the temperature, heat content and humidity of the hot air until equilibrium conditions exist Equilibrium

is reached when the difference between the outer surface temperature of the chimney sections and theambient temperature does not change by more than 1 % in 60 min Record the heat input (Q1), in Watts, theflue gas temperature tg and the internal (tj) and external (t0) surface temperatures

Reassemble the test assembly without the test chimney sections or replace by the calibrated section Repeatthe test as described before until the hot gas temperature is the same as during the tests with the chimneysections in place, and until equilibrium condition exists Equilibrium is reached when the difference betweenthe hot gas temperature and the ambient temperature does not change by more than 1 % in 3 h

Record the heat input (Q2)

Q

1

is the total heat input in watts with the chimney section;

Q

2

is the total heat input in watts without the chimney sections;

t

j

is the inner surface temperature;

t

0

is the outer surface temperature;

Aj is the total inner surface area of the test chimney

Trang 16

4.7 Water vapour diffusion resistance

4.7.1 Conditioning

Condition the already thermally tested chimney sections and fittings used in the test for offsets, (see Figure 6),

or if no offset has been tested, see Figure 5, by standing in the test environment of 4.5.2 for at least 12 h

For negative pressure chimneys maintain the pressure in the test chimney between 0 Pa and -10 Pa

Determine the increase in the weight of the fittings to an accuracy of ± 0,5 g

4.7.4 Results

Record any evidence of moisture penetration Reweigh the test fittings and sections

Record the increase in weight of the sections and fittings

4.8 Condensate resistance test

Trang 17

4.7 Water vapour diffusion resistance

4.7.1 Conditioning

Condition the already thermally tested chimney sections and fittings used in the test for offsets, (see Figure 6),

or if no offset has been tested, see Figure 5, by standing in the test environment of 4.5.2 for at least 12 h

4.7.2 Test assembly

Install approximately 2 m of chimney fittings and sections including two joints into each arm of the test

assembly of 4.6.1

Alternatively the vapour generator is connected to the flue gas inlet or to the segment in zone B of the test

chimney according to Figure 6 (or Figure 5 if no offset has been tested thermally)

4.7.3 Test procedure

Pass water vapour saturated air at a temperature of 55 ºC ± 2 ºC through the fittings at 4 m/s ± 0,1 m/s for

24 h ± 15 min

For negative pressure chimneys maintain the pressure in the test chimney between 0 Pa and -10 Pa

Determine the increase in the weight of the fittings to an accuracy of ± 0,5 g

4.7.4 Results

Record any evidence of moisture penetration Reweigh the test fittings and sections

Record the increase in weight of the sections and fittings

4.8 Condensate resistance test

Precondition the test sample to the thermal designation parameters (thermal stress and thermal shock tests)

Spray coloured water with a temperature of 50 °C, a pressure of 3 bar and a volume related to the diameter

(e.g 0,020 m3/h for 150 mm diameter) maintained during 4 h or until the water appears on the outside of any

fitting

!Determine the increase in the weight of the fitting to an accuracy of ± 5 g."

4.8.5 Test results

Record the location of any appearance of water on the outside of any fitting

!Record the increase in weight of the sections and fittings."

4.9 Rainwater resistance

4.9.1 Chimney sections 4.9.1.1 Conditioning

Condition for at least 48 h in the test environment of 4.5.2.1, those chimney sections which have beensubjected to the thermal performance test of 4.5 (located in Zone C, including any inspection opening) Thereshall be at least one joint between the sections, and they shall be removed in their assembled state so thatany joint between the sections shall have been left undisturbed following the thermal performance test

4.9.1.2 Test assembly

The test structure shall consist of a rotating free draining plinth The spray tube shall be perforated to directjets of water towards the centre of the circle Install the sections onto the centre of the plinth of the teststructure so that the centre of the spray arc is approximately at the centre of the flue below or level with thejoint (see Figure 11) Seal the joint where the sections stand on the plinth to prevent ingress of water into openend of section

The spray tube shall be constructed and dimensioned to allow the flow conditions of EN 60529 to be achievedand maintained

Alternatively the test assembly of 4.9.2 may be used

4.9.1.3 Spray procedure

Determine the increase in the weight of the sections to an accuracy of ± 0,5 g

Spray water for 60 min ± 1 min while oscillating the spray arc through an angle of 120° ± 5° (60° either side ofthe vertical) and rotating the plinth The time for one complete traverse (two traverses of 120º) shall be

6 s ± 1 s and the time for one revolution of the plinth shall be 5 min ± 1 min Remove any surface moisturefrom the surfaces of the chimney sections and condition the sections for at least 12 h, and not more than 24 h,

in the test environment of 4.5.2 The sections may be separated to facilitate removal of surface moisture.Reweigh the test sections

4.9.1.4 Results

Record the increase in weight of the test sections

4.9.2 Rainwater terminal 4.9.2.1 Conditioning

Thermally condition the rainwater terminal to its test temperature either on the thermal test assembly, or in anoven for 4 h

4.9.2.2 Test assembly

A typical arrangement is shown in Figure 12

Trang 18

The rainmaking installation is made up of parallel pipes in a horizontal plane The tubes have small sprayholes (placed vertically downwards) These spray holes are evenly distributed across the area above the wiremesh The water from the spray holes shall be distributed through a web of fine 1,3 mm ± 0,1 mm wide wiremesh, after which the water will fall in the form of raindrops

The rain intensity shall be (1,6 ± 0,2) mm/min Establish by calibration where, with and without wind, the rainintensity is (1,6 ± 0,2) mm/min over an area that is at least 5 times the nominal diameter of the test sample For this calibration, 5 buckets of a diameter of 150 mm, one on each corner of a rectangular area and one inthe middle, shall be positioned at a level corresponding to the centre of the test sample Make sure that thenominal diameter of the test sample is less than 20 % of the area within the line circumscribing the buckets.Start the calibration test during 10 min without wind and determine that the rain intensity is1,6 mm/min ± 0,2 mm/min by weighing the 5 buckets Repeat the calibration test with a horizontal airflow of

12 m/s

The wind generator shall supply a horizontal airflow at a velocity of 12 m/s ± 0,5 m/s, measured in the place ofthe test sample with a minimum wind front of 5 times the projected cross section of the terminal to be tested.The outlet of the wind generator should be square or circular

4.9.2.3 Procedure

Install the rainwater terminal fitted to some chimney sections according to the manufacturer's instructions.Adjust the position so that the centre of the rainwater terminal is in the centre line of the wind generator(see Figure 12)

Expose the test sample to the rain with a horizontal airflow from the wind generator of 12 m/s ± 0,5 m/s for atleast 20 min

Collect and weigh any moisture entering the flue

4.9.2.4 Results

Record the weight of water collected inside the flue

4.10 Terminal flow resistance

4.10.1 Conditioning

Condition the flue terminal thermally to the test temperature corresponding to its designation either during thethermal performance test 4.5, or in an oven for 4 h

4.10.2 Test assembly

The test assembly comprises a fan capable of delivering a flue flow between and including 15 m3/h and

120 m3/h, measured to an accuracy of ± 5 % A suitable means of measurement is by an appropriate orificeplate arrangement

4.10.3 Procedure

Connect the flue terminal to a flue duct with the same nominal diameter The flue duct shall have a straightlength of at least 6 times the nominal diameter Place pressure measurement points in the flue duct at adistance of approximately 3 times the nominal diameter from the terminal For this purpose, at least

3 openings, with a 1 mm diameter, shall be distributed evenly around the circumference of the duct, in a planeperpendicular to the duct axis The openings shall be free of burrs on the inside of the duct These openingsshall be used to determine the average static pressure within the duct

Deliver air by means of a fan at a nominal velocity in the flue of 2 m/s ± 2,5 % Measure the pressure

Trang 19

The rainmaking installation is made up of parallel pipes in a horizontal plane The tubes have small spray

holes (placed vertically downwards) These spray holes are evenly distributed across the area above the wire

mesh The water from the spray holes shall be distributed through a web of fine 1,3 mm ± 0,1 mm wide wire

mesh, after which the water will fall in the form of raindrops

The rain intensity shall be (1,6 ± 0,2) mm/min Establish by calibration where, with and without wind, the rain

intensity is (1,6 ± 0,2) mm/min over an area that is at least 5 times the nominal diameter of the test sample

For this calibration, 5 buckets of a diameter of 150 mm, one on each corner of a rectangular area and one in

the middle, shall be positioned at a level corresponding to the centre of the test sample Make sure that the

nominal diameter of the test sample is less than 20 % of the area within the line circumscribing the buckets

Start the calibration test during 10 min without wind and determine that the rain intensity is

1,6 mm/min ± 0,2 mm/min by weighing the 5 buckets Repeat the calibration test with a horizontal airflow of

12 m/s

The wind generator shall supply a horizontal airflow at a velocity of 12 m/s ± 0,5 m/s, measured in the place of

the test sample with a minimum wind front of 5 times the projected cross section of the terminal to be tested

The outlet of the wind generator should be square or circular

4.9.2.3 Procedure

Install the rainwater terminal fitted to some chimney sections according to the manufacturer's instructions

Adjust the position so that the centre of the rainwater terminal is in the centre line of the wind generator

Record the weight of water collected inside the flue

4.10 Terminal flow resistance

4.10.1 Conditioning

Condition the flue terminal thermally to the test temperature corresponding to its designation either during the

thermal performance test 4.5, or in an oven for 4 h

4.10.2 Test assembly

The test assembly comprises a fan capable of delivering a flue flow between and including 15 m3/h and

120 m3/h, measured to an accuracy of ± 5 % A suitable means of measurement is by an appropriate orifice

plate arrangement

4.10.3 Procedure

Connect the flue terminal to a flue duct with the same nominal diameter The flue duct shall have a straight

length of at least 6 times the nominal diameter Place pressure measurement points in the flue duct at a

distance of approximately 3 times the nominal diameter from the terminal For this purpose, at least

3 openings, with a 1 mm diameter, shall be distributed evenly around the circumference of the duct, in a plane

perpendicular to the duct axis The openings shall be free of burrs on the inside of the duct These openings

shall be used to determine the average static pressure within the duct

Deliver air by means of a fan at a nominal velocity in the flue of 2 m/s ± 2,5 % Measure the pressure

difference between static pressure in the flue duct and the pressure in the test room The pressure difference

is measured with an accuracy of ± 0,2 Pa

in the wind front at velocities up to 10 m/s at the terminal test position

b) A fan capable of delivering a flue flow between and including 15 m3/h and 120 m3/h, measured to anaccuracy of ± 5 % A suitable means of measurement is by an appropriate orifice plate arrangement

4.11.3 Procedure

Connect the flue terminal to a flue duct with the same nominal diameter The flue duct shall have a straightlength of at least 6 times the nominal diameter Place pressure measurement points in the flue duct at adistance of approximately 3 times the nominal diameter from the terminal For this purpose, at least

3 openings, with a 1 mm diameter, shall be distributed evenly around the circumference of the duct, in a planeperpendicular to the duct axis The openings shall be free of burrs on the inside of the duct These openingsshall be used to determine the average static pressure within the duct

Deliver air by means of a fan at a nominal velocity in the flue of 1 m/s ± 2,5 % for terminals for negativepressure chimneys and 2 m/s ± 2,5 % for terminals for positive pressure chimneys Measure the pressuredifference between static pressure in the flue duct and the pressure in the test room The pressure difference

is measured with an accuracy of ± 0,2 Pa

Rotate the flue terminal in front of the wind system in such a way that wind pressure angles relative to the flueterminal range from downward wind (+ 90°) to an upward wind (-45°) in maximum steps of 7,5°

Determine the pressure characteristics through wind influences of the flue terminal under the followingconditions:

a) a nominal velocity of 2 m/s in the flue duct

b) wind speeds of 3, 6, 9, 12 m/s in combination with wind direction angles ranging from -45° to + 90°

4.11.4 Results

Record the pressure characteristics

4.12 Flow resistance of fittings

4.12.1 Determination of flow conditions

The air velocity in the components tested shall be set in such a way that the air flow rate equals the nominalflow rate, depending on the actual inside diameter of the fittings

The nominal flow rate is a function of the nominal diameter and the nominal velocity, where:

Trang 20

3600 4

=

2nom nom

where

V

nom is the nominal air flow rate in square metres per hour;

D

nom is the nominal diameter in metres;

w

nom is the nominal velocity in metres per second

4.12.2 Test assembly

A fitting is connected on both sides to a measuring duct through which test air is supplied and discharged.These measuring ducts shall have a straight length of at least 2000 mm and, except for testing adaptors, thesame diameter

Pressure measuring points are placed in the measuring ducts For this purpose, at least 3 openings with a

1 mm diameter are distributed evenly across the circumference of each duct, in a plane in line with the centralline These openings shall be free of burrs on the inside of the duct The average static pressure in the duct ismeasured via these openings

The length of the measuring ducts, the position of the pressure measuring points in the measuring ducts andthe position of the pressure measuring points relative to the connected pipe or fitting to be tested and theposition of the pressure measuring points relative to the other supply and flue ducts to which the measuringducts are, in turn, connected shall be such as to permit an undisturbed flow at all times, over a distance of

15 dmeasuring duct on each side of the pressure measuring points

For testing adaptors, measuring ducts of varying diameter are available

These measuring ducts of varying diameter, reducing or enlarging, are made of stainless steel with thesmoothest possible finish and have a transition angle α = 10° (2 x 5°)

The air transport through the ducts is set to an accuracy of ± 2,5 % The pressure differential between thesupply and flue duct is measured to an accuracy of ± 0,2 Pa

All tests are carried out with air at a temperature of the test environment

4.12.3 Execution of the measurements

The friction of a section or fitting is determined as the difference between the static pressures in the twomeasuring ducts

Testing takes place at a nominal flow rate equivalent to a nominal velocity of 6 m/s in the pipe section or fitting

to be tested

First determine the friction of the measuring duct between the pressure measuring points without the pipesection or fitting to be tested There are two possible situations:

a) There are two measuring ducts of the same diameter

b) There are two measuring ducts of different diameter because a reducing or enlarging adaptor should betested

In the latter case, a reducing or enlarging measuring duct (see 4.12.2) should be placed between the twomeasuring ducts referred to above

Trang 21

3600 4

=

2nom nom

where

V

nom is the nominal air flow rate in square metres per hour;

D

nom is the nominal diameter in metres;

w

nom is the nominal velocity in metres per second

4.12.2 Test assembly

A fitting is connected on both sides to a measuring duct through which test air is supplied and discharged

These measuring ducts shall have a straight length of at least 2000 mm and, except for testing adaptors, the

same diameter

Pressure measuring points are placed in the measuring ducts For this purpose, at least 3 openings with a

1 mm diameter are distributed evenly across the circumference of each duct, in a plane in line with the central

line These openings shall be free of burrs on the inside of the duct The average static pressure in the duct is

measured via these openings

The length of the measuring ducts, the position of the pressure measuring points in the measuring ducts and

the position of the pressure measuring points relative to the connected pipe or fitting to be tested and the

position of the pressure measuring points relative to the other supply and flue ducts to which the measuring

ducts are, in turn, connected shall be such as to permit an undisturbed flow at all times, over a distance of

15 dmeasuring duct on each side of the pressure measuring points

For testing adaptors, measuring ducts of varying diameter are available

These measuring ducts of varying diameter, reducing or enlarging, are made of stainless steel with the

smoothest possible finish and have a transition angle α = 10° (2 x 5°)

The air transport through the ducts is set to an accuracy of ± 2,5 % The pressure differential between the

supply and flue duct is measured to an accuracy of ± 0,2 Pa

All tests are carried out with air at a temperature of the test environment

4.12.3 Execution of the measurements

The friction of a section or fitting is determined as the difference between the static pressures in the two

measuring ducts

Testing takes place at a nominal flow rate equivalent to a nominal velocity of 6 m/s in the pipe section or fitting

to be tested

First determine the friction of the measuring duct between the pressure measuring points without the pipe

section or fitting to be tested There are two possible situations:

a) There are two measuring ducts of the same diameter

b) There are two measuring ducts of different diameter because a reducing or enlarging adaptor should be

tested

In the latter case, a reducing or enlarging measuring duct (see 4.12.2) should be placed between the two

measuring ducts referred to above

Mount the section or fitting to be tested in the rig (after removing the reducing or enlarging measuring duct iffitted) Determine the friction of the measuring ducts between the pressure measuring points again Thefriction of the section or fitting is then given by the difference between the two test results

NOTE The friction of the reducing or enlarging measuring ducts is thus ignored

4.12.4 Calculation of the friction value

The friction value may be calculated from the friction measured according to 4.12.3 by means of the equation:

w

p

=

2 nomρ

ζ

21

where

ζ

is the zeta = friction factor;

p

is the measured friction in Pascals;

ρ = rho

is the density of air = 1,202 kg/m3;

w

nom is the nominal velocity in metres per second

NOTE In the case of adaptors, wnom is related to the smaller diameter

In carrying out the friction measurement as described under 4.12.3, i.e with:

w

nom=6 m/s, the equation, therefore, becomes:

ρ

5 Test report

The test report should include the following:

a) number and year of publication of this European Standard, i.e EN 1859:2009!+A1:2013";

b) description of the product or assembly tested;

c) test applied and results obtained

Trang 22

(a) Compressive strength on

fitting ref, see 4.1.1.1

(b) Compressive strength on chimney support, see 4.1.2.1 (c) Tensile strength on chimney section, see 4.2.1

Key

1 Adaptor

2 Direction of flue gas

Figure 1  Structural test configurations

Trang 23

(a) Compressive strength on

fitting ref, see 4.1.1.1

(b) Compressive strength onchimney support, see 4.1.2.1 (c) Tensile strength on chimneysection, see 4.2.1

Key

1 Adaptor

2 Direction of flue gas

Figure 1  Structural test configurations

Key

lmax = maximum declared length between supports

Figure 2  Structural strength - Fittings in non-vertical orientation

Trang 24

D distance over which the load is distributed = A + C + C/2

Figure 3  Wind load test assembly

Trang 25

D distance over which the load is distributed = A + C + C/2

Figure 3  Wind load test assembly

Trang 26

All dimensions in millimetres

Tolerance as stated

Key

Figure 5  Test rig structure in a corner fully enclosed test assembly

Ngày đăng: 13/04/2023, 22:06