Unidrive M400 UG Issue 3 book User Guide Unidrive M400 Model size 1 to 8 Variable Speed AC drive for induction motors Part Number 0478 0044 04 Issue 4 www controltechniques com Original Instructions F[.]
Warnings, Cautions and Notes
A Note contains information which helps to ensure correct operation of the product.
Electrical safety - general warning
error code: 502
Specific warnings are given at the relevant places in this User Guide.
System design and safety of personnel
The drive is intended as a component for professional incorporation into complete equipment or a system If installed incorrectly, the drive may present a safety hazard.
The drive uses high voltages and currents, carries a high level of stored electrical energy, and is used to control equipment which can cause injury.
error code: 502
error code: 502
error code: 502
error code: 502
error code: 502
Environmental limits
error code: 502
Access
Drive access must be restricted to authorized personnel only Safety regulations which apply at the place of use must be complied with.
Fire protection
The drive enclosure is not classified as a fire enclosure A separate fire enclosure must be provided For further information, refer to section 3.2.5Fire protectionon page 22.
Compliance with regulations
error code: 502
Within the European Union, all machinery in which this product is used must comply with the following directives:
Motor
Ensure the motor is installed in accordance with the manufacturer’s recommendations Ensure the motor shaft is not exposed.
error code: 502
error code: 502
It is essential that the correct value is entered in Pr 00.006 motor rated current This affects the thermal protection of the motor.
Mechanical brake control
error code: 502
Adjusting parameters
error code: 502
A Warning contains information which is essential for avoiding a safety hazard
A Caution contains information which is necessary for avoiding a risk of damage to the product or other equipment.
Electrical installation
The voltages present in the following locations can cause severe electric shock and may be lethal:
AC supply cables and connections
Many internal parts of the drive, and external option units
Unless otherwise indicated, control terminals are single insulated and must not be touched.
error code: 502
Hazard
The drive presents a falling or toppling hazard This can still cause injury to personnel and therefore should be handled with care.
Model number
The way in which the model numbers for the Unidrive M range are formed is illustrated below:
Identification Label Derivative Electrical Specifications
Ratings
The size 1 to 4 drive is Heavy Duty rated only.
The size 5 to 8 drive is dual rated.
The setting of the motor rated current determines which rating applies -
Heavy Duty or Normal Duty
The two ratings are compatible with motors designed to IEC60034.
The graph aside illustrates the difference between Normal Duty and
Heavy Duty with respect to continuous current rating and short term overload limits.
Normal Duty Heavy Duty (default)
For applications which use Self ventilated (TENV/TEFC) induction motors and require a low overload capability, and full torque at low speeds is not required (e.g fans, pumps).
error code: 502
The speed at which the low speed protection takes effect can be changed by the setting of Low Speed Thermal Protection Mode
(04.025) The protection starts when the motor speed is below 15 % of base speed when Pr 04.025 = 0 (default) and below 50 % when
For constant torque applications or applications which require a high overload capability, or full torque is required at low speeds (e.g winders, hoists).
The thermal protection is set to protect force ventilated induction motors by default.
error code: 502
Motor I 2 t protection is fixed as shown below and is compatible with:
• Self ventilated (TENV/TEFC) induction motors
Motor I 2 t protection defaults to be compatible with:
Available output current Overload limit -
Maximum continuous current (above 50% base speed) -
Motor rated current set in the drive Heavy Duty - with high overload capability Normal Duty
Motor total current (Pr 04.001) as a percentage of motor rated current
Motor speed as a percentage of base speed
I t protection operates in this region 2
Motor total current (Pr 04.001) as a percentage of motor rated current
Motor speed as a percentage of base speed
I t protection operates in this region 2
Open loop peak current RFC peak current Nominal power at
2.2.1 Typical short term overload limits
error code: 502
Typical values are shown in the table below for RFC-A and open loop (OL) modes:
Generally the drive rated current is higher than the matching motor rated current allowing a higher level of overload than the default setting.
The time allowed in the overload region is proportionally reduced at very low output frequency on some drive ratings.
The maximum overload level which can be attained is independent of the speed
Operating mode RFC From cold RFC From 100 % Open loop from cold Open loop from 100 %
Normal Duty overload with motor rated current = drive rated current 110 % for 165 s 110 % for 9 s 110 % for 165 s 110 % for 9 s
Heavy Duty overload with motor rated current = drive rated current 180 % for 3 s 180 % for 3 s 150 % for 60 s 150 % for 8 s
Operating modes
The drive is designed to operate in any of the following modes:
error code: 502
error code: 502
Typically 100 % torque is available down to 1 Hz for a 50 Hz motor.
error code: 502
Typically 100 % torque is available down to 4 Hz for a 50 Hz motor.
error code: 502
Rotor Flux Control for Asynchronous (induction) motors (RFC-A) encompasses closed loop vector control without a position feedback device
error code: 502
Drive features
Figure 2-2 Features of the drive (size 1 to 4)
1 Rating label (On side of drive) 5 Control connections 9 DC bus - 13 SAFE TORQUE OFF connections
2 Identification label 6 Braking terminal 10 Motor connections 14 Keypad connection
3 Option module connection 7 Internal EMC filter screw 11 AC supply connections
4 Relay connections 8 DC bus + 12 Ground connections
Figure 2-3 Features of the drive (size 5 to 8)
Keypad and display
error code: 502
(1) The Enter button is used to enter parameter view or edit mode, or to accept a parameter edit
error code: 502
(3) The Start key is used to start the drive in keypad mode.
(4) The Stop / Reset key is used to stop and reset the drive in keypad mode It can also be used to reset the drive in terminal mode.
(5) The Escape key is used to exit from the parameter edit / view mode or disregard a parameter edit.
The keypad is not supplied with the drive.
Nameplate description
See Figure 2-2 for location of rating labels.
Figure 2-5 Typical drive rating labels size 2
Refer to Figure 2-1Model numberon page 10 for further information relating to the labels.
Patents: www.ctpatents.info Manuals: www.ctmanuals.info
Refer to User Guide Date code
Options
Figure 2-6 Options available with the drive
Table 2-7 System Integration (SI) option module identification
Table 2-8 Adaptor Interface (AI) option module identification
Type Option module Color Name Further details
Purple SI-PROFIBUS Profibus option
PROFIBUS adaptor for communications with the drive
Medium Grey SI-DeviceNet DeviceNet option
DeviceNet adaptor for communications with the drive
Light Grey SI-CANopen CANopen option
CANopen adaptor for communications with the drive
Increases the I/O capability by adding the following combinations:
• Analog Inputs (differential or single ended)
Type Option module Name Further details
Provides a 485 serial communications interface via an RJ45 connector or alternative screw terminals.
Backup AI-Backup adaptor +24 V Backup and SD card interface
Items supplied with the drive
error code: 502
Table 2-9 Parts supplied with the drive
Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6 Size 7 Size 8
This chapter describes how to use all mechanical details to install the drive The drive is intended to be installed in an enclosure Key features of this chapter include:
• High IP as standard or Through-panel mounting
• Terminal location and torque settings
Planning the installation
The following considerations must be made when planning the installation:
Access must be restricted to authorized personnel only Safety regulations which apply at the place of use must be complied with.
The IP (Ingress Protection) rating of the drive is installation dependent
For further information, refer to section 3.9Enclosing size 5 to 8 drive for high environmental protectionon page 44.
The drive must be protected from:
• Moisture, including dripping water or spraying water and condensation An anti-condensation heater may be required, which must be switched off when the drive is running.
• Contamination with electrically conductive material
• Contamination with any form of dust which may restrict the fan, or impair airflow over various components
• Temperature beyond the specified operating and storage ranges
During installation it is recommended that the vents on the drive are covered to prevent debris (e.g wire off-cuts) from entering the drive
error code: 502
For further information, refer to section 3.5.3Mounting bracketson page 40
The installation must be safe under normal and fault conditions Electrical installation instructions are given in Chapter 4Electrical installation on page 53.
The drive enclosure is not classified as a fire enclosure A separate fire enclosure must be provided.
For installation in the USA, a NEMA 12 enclosure is suitable.
For installation outside the USA, the following (based on IEC 62109-1, standard for PV inverters) is recommended.
error code: 502
Air filter assemblies to be at least class V-2.
error code: 502
Figure 3-1 Fire enclosure bottom layout
error code: 502
Figure 3-2 Fire enclosure baffle construction
error code: 502
error code: 502
The drive is intended to be mounted in an enclosure which prevents access except by trained and authorized personnel, and which prevents the ingress of contamination
It is designed for use in an environment classified as pollution degree 2 in accordance with IEC 60664-1 This means that only dry, non-conducting contamination is acceptable.
Not less than 2 times ‘X’ Baffle plates (may be above or below bottom of enclosure)
Variable speed drives are powerful electronic circuits which can cause electromagnetic interference if not installed correctly with careful attention to the layout of the wiring.
Some simple routine precautions can prevent disturbance to typical industrial control equipment.
error code: 502
The drive must not be located in a classified hazardous area unless it is installed in an approved enclosure and the installation is certified.
Terminal cover removal
Figure 3-3 Location and identification of terminal covers (size 1 to 4)
error code: 502
error code: 502
Figure 3-4 Location and Identification of terminal covers (size 5 to 8)
DC / Braking terminal cover left
AC / Motor terminal cover Motor / Braking terminal cover Motor / Braking terminal cover
Control terminal cover Control terminal cover Control terminal cover Control terminal cover
Figure 3-5 Removing the terminal cover (size 1 to 4)
1 Using a flat bladed screwdriver, turn the terminal cover locking clip anti-clockwise by approximately 30°
2 Slide the terminal cover down
3 Remove terminal cover in direction shown.
Figure 3-6 Removing the size 5 terminal covers
Figure 3-7 Removing the size 6 terminal covers
When replacing the terminal covers, the screws should be tightened to a maximum torque of 1 N m (0.7 lb ft).
Figure 3-8 Removing the size 7 to 8 terminal covers (size 7 shown)
When replacing the terminal covers, the screws should be tightened to a maximum torque of 1 N m (0.7 lb ft).
3.3.2 Removing the finger-guard and DC terminal cover break-outs
Figure 3-9 Removing the finger-guard break-outs
error code: 502
Remove any flash / sharp edges once the break-outs are removed.
Grommet kits are available for size 7 to 8 finger guards For size 8, two versions are available allowing for either single or double cable entries.
Drive size Part number Picture
Size 7 - Kit of 8 x single entry grommets 3470-0086-00
Size 8 - Kit of 8 x single entry grommets 3470-0089-00
Size 8 - Kit of 8 x double entry grommets 3470-0090-00
Installing / removing options and keypad
Figure 3-10 Installation of an SI option module (size 2 to 4)
• With the option module tilted slightly backwards, align and locate the two holes in the rear of the option module onto the two tabs (1) on the drive.
• Press the option module onto the drive as shown in (2) until the connector mates with the drive, ensuring that the tab (3) retains the option module in place.
error code: 502
Figure 3-11 Removal of an SI option module (size 2 to 4)
• Press down on the tab (1) to release the option module from the drive housing as shown.
• Tilt the option module slightly towards you and pull away from the drive housing (2).
Power down the drive before installing / removing the SI option module Failure to do so may result in damage to the product.
Figure 3-12 Installation of an SI option module (size 5 to 8)
• Move the option module in the direction shown (1).
• Align and insert the option module tab into the slot provided This is shown in the detailed view (A).
• Press down on the option module until it locks into place.
Figure 3-13 Removal of an SI option module (size 5 to 8)
• To release the option module from the drive housing, press down on the tab (1) as shown in detailed view (A).
• Tilt the option module towards you as shown in (2).
• Remove the option module by lifting away from the drive as shown in (3).
Figure 3-14 Installing the AI-485 adaptor to the drive
error code: 502
2 Hold the adaptor firmly and push the spring loaded protective cover towards the back of the drive to expose the connector block (2) below.
3 Press the adaptor downwards (3) until the adaptor connector locates into the drive connection below.
Figure 3-15 Removal of the AI-485 adaptor
* To remove the AI-485 adaptor, pull it up and away from the drive in the direction shown (1)
Figure 3-16 Installing the AI-Backup adaptor
error code: 502
2 Hold the adaptor firmly and push the spring loaded protective cover towards the back of the drive to expose the connector block (2) below.
3 Press the adaptor downwards (3) until the adaptor connector locates into the drive connection below.
Figure 3-17 Removal of the AI-Backup adaptor
Figure 3-18 Installing the CI-Keypad on the drive
To remove the CI-Keypad, reverse the installation procedure shown in Figure 3-18.
The keypad can be installed / removed while the drive is powered up and running motor, providing that the drive is not operating in keypad mode.
Figure 3-19 Installing the CI-485 Adaptor
To remove the CI-485 Adaptor, reverse the process shown in Figure 3-19.
The CI-485 Adaptor can be installed / removed while the drive is powered up and running a motor, providing that the drive is not operating in keypad mode.
Dimensions and mounting methods
error code: 502
The Through-panel mounting kit is not supplied with the drive and can be purchased separately, below are the relevant part numbers:
Table 3-2 Through-panel mounting kit part numbers for size 3 to 8
Figure 3-20 Surface mounting the size 1 drive
error code: 502
Many of the drives in this product range weigh in excess of 15 kg (33 lb) Use appropriate safeguards when lifting these models.
A full list of drive weights can be found in section 12.1.19Weightson page 195.
Figure 3-21 Surface mounting the size 2 drive
Figure 3-22 Surface mounting the size 3 drive
Figure 3-23 Surface mounting the size 4 drive
Figure 3-24 Surface mounting the size 5 drive
Figure 3-25 Surface mounting the size 6 drive
Figure 3-26 Surface mounting the size 7 drive
9.5 mm (0.37 in) ặ 9.0 mm (0.35 in) 220.0 mm
Figure 3-27 Surface mounting the size 8 drive
Figure 3-28 Through-panel mounting the size 5 drive
393 mm (15.47 in) ặ5.0 mm (0.20 in) (x 4 holes)
Figure 3-29 Through-panel mounting the size 6 drive
The outer holes plus the hole located in the center of the bracket are to be used for through panel mounting.
Figure 3-30 Through-panel mounting the size 7 drive
399 m m (15.71) 264 m m (10.39 in) 21 mm (0.83 in) 167 mm (6.58 in) ặ 5.0 mm (0.20 in)
538 mm (21.18 in) 488 mm (19.21 in) 278 mm (10.95 in) ặ 9mm (0.35 in)
Figure 3-31 Through-panel mounting the size 8 drive
784 mm (30.87 in) 730 mm (28.74 in) 730 mm (28.74 in)
161 mm (6.34 in) 240 mm (9.45 in) 240 mm (9.45 in)
Table 3-3 Mounting brackets (size 5 to 8)
Frame size Surface Qty Through-panel Qty
Hole size: 6.5 mm (0.26 in) Hole size: 6.5 mm (0.26 in)
Hole size: 6.5 mm (0.26 in) Hole size: 6.5 mm (0.26 in)
Hole size: 9 mm (0.35 in) Hole size: 9 mm (0.35 in)
Hole size: 9 mm (0.35 in) Hole size: 9 mm (0.35 in)
Enclosure for standard drives
3.6.1 Recommended spacing between the drives
Figure 3-32 Recommended spacing between the drives
Table 3-4 Spacing required between the drives (without high IP bung)
* 50 °C derating applies, refer to Table 12-5Maximum permissible continuous output current @ 50 °C (122 °F) (size 5 to 8)on page 187.
When through-panel mounted, ideally drives should be spaced 30 mm
(1.18 in) to maximize panel stiffness.
Please observe the clearances in the diagram below taking into account any appropriate notes for other devices / auxiliary equipment when planning the installation.
Table 3-5 Spacing required between drive / enclosure and drive / EMC filter
AC supply contactor and fuses or MCB
Signal cables Plan for all signal cables to be routed at least
300 mm (12 in) from the drive and any power cable
Ensure minimum clearances are maintained for the drive and external EMC filter Forced or convection air-flow must not be restricted by any object or cabling ³100 mm
Optional braking resistor and overload
Locate optional braking resistor external to cubicle (preferably near to or on top of the cubicle).
Locate the overload protection device as required
The external EMC filter can be bookcase mounted (next to the drive) or footprint mounted (with the drive mounted onto the filter).
1) When using an external EMC filter, one filter is required for each drive
2) Power cabling must be at least 100 mm (4 in) from the drive in all directions
1 Add the dissipation figures from section 12.1.2Power dissipationon page 188 for each drive that is to be installed in the enclosure
error code: 502
3 If the braking resistor is to be mounted inside the enclosure, add the average power figures from for each braking resistor that is to be installed in the enclosure
4 Calculate the total heat dissipation (in Watts) of any other equipment to be installed in the enclosure.
5 Add the heat dissipation figures obtained above This gives a figure in Watts for the total heat that will be dissipated inside the enclosure
Calculating the size of a sealed enclosure
error code: 502
Calculate the minimum required unobstructed surface area A e for the enclosure from:
A e Unobstructed surface area in m 2 (1 m 2 = 10.9 ft 2 )
T ext Maximum expected temperature in o C outside the enclosure
T int Maximum permissible temperature in o C inside the enclosure
P Power in Watts dissipated by all heat sources in the enclosure k Heat transmission coefficient of the enclosure material in W/m 2 / o C
To calculate the size of an enclosure for the following:
• Two drives operating at the Normal Duty rating
• External EMC filter for each drive
• Braking resistors are to be mounted outside the enclosure
• Maximum ambient temperature inside the enclosure: 40°C
• Maximum ambient temperature outside the enclosure: 30°C
For example, if the power dissipation from each drive is 187 W and the power dissipation from each external EMC filter is 9.2 W.
Power dissipation for the drives and the external EMC filters can be obtained from Chapter 12Technical dataon page 183.
error code: 502
error code: 502
Figure 3-34 Enclosure having front, sides and top panels free to dissipate heat
The minimum required heat conducting area is then:
= 7.135 m 2 (77.8 ft 2 ) (1 m 2 = 10.9 ft 2 ) Estimate two of the enclosure dimensions - the height (H) and depth (D), for instance Calculate the width (W) from:
Inserting H = 2m and D = 0.6 m, obtain the minimum width:
If the enclosure is too large for the space available, it can be made smaller only by attending to one or all of the following:
• Using a lower PWM switching frequency to reduce the dissipation in the drives
• Reducing the ambient temperature outside the enclosure, and/or applying forced-air cooling to the outside of the enclosure
• Reducing the number of drives in the enclosure
• Removing other heat-generating equipment
Calculating the air-flow in a ventilated enclosure
The dimensions of the enclosure are required only for accommodating the equipment The equipment is cooled by the forced air flow.
Calculate the minimum required volume of ventilating air from:
V Air-flow in m 3 per hour (1 m 3 /hr = 0.59 ft 3 /min)
T ext Maximum expected temperature in°C outside the enclosure
T int Maximum permissible temperature in °C inside the enclosure
P Power in Watts dissipated by all heat sources in the enclosure
To calculate the size of an enclosure for the following:
• Three drives operating at the Normal Duty rating
• External EMC filter for each drive
• Braking resistors are to be mounted outside the enclosure
• Maximum ambient temperature inside the enclosure: 40 °C
• Maximum ambient temperature outside the enclosure: 30 °C
For example, dissipation of each drive: 101 W and dissipation of each external EMC filter: 6.9 W (max).
= 126.2 m 3 /hr (74.5 ft 3 /min) (1 m 3 / hr = 0.59 ft 3 /min)
Enclosure design and drive ambient
Drive derating is required for operation in high ambient temperatures
Totally enclosing or through panel mounting the drive in either a sealed cabinet (no airflow) or in a well ventilated cabinet makes a significant difference on drive cooling.
The chosen method affects the ambient temperature value (T rate ) which should be used for any necessary derating to ensure sufficient cooling for the whole of the drive
The ambient temperature for the four different combinations is defined below:
1 Totally enclosed with no air flow (2 m/s) over the drive
3 Through panel mounted with no airflow (2 m/s) over the drive
T rate = the greater of T ext or T int
T ext = Temperature outside the cabinet
T int = Temperature inside the cabinet
T rate = Temperature used to select current rating from tables in
Heatsink fan operation
The drive is ventilated by an internal heatsink fan The fan channels air through the heatsink chamber
Ensure the minimum clearances around the drive are maintained to allow air to flow freely.
error code: 502
Enclosing size 5 to 8 drive for high
An explanation of the environmental protection rating is provided in section 12.1.9IP / UL Ratingon page 193.
error code: 502
Refer to Table 12-3 on page 185.
error code: 502
This relies on a good seal being made between the heatsink and the rear of the enclosure using the gaskets provided.
Figure 3-35 Example of IP65 through-panel layout
The main gasket should be installed as shown in Figure 3-36.
error code: 502
Table 3-6 Through-panel mounting kit part numbers
Drive with high IP insert installed
error code: 502
Figure 3-37 Through-panel mounting detail
Figure 3-38 Installation of high IP insert for size 5
• To install the high IP insert, firstly place a flat head screwdriver into the slot highlighted (1).
• Pull the hinged baffle up to expose the ventilation holes, install the high IP inserts into the ventilation holes in the heatsink (2).
• Ensure the high IP inserts are securely installed by firmly pressing them into place (3).
• Close the hinged baffle as shown (1).
To remove the high IP inserts, reverse the above instructions.
The guidelines in Table 3-7 should be followed.
error code: 502
Environment High IP insert Comments
Dry, dusty (non-conductive) Installed
Table 3-8 Power losses from the front of the drive when through-panel mounted
External EMC filter
The external EMC filter details for each drive rating are provided in the table below.
Mount the external EMC filter following the guidelines in section 4.8.5Compliance with generic emission standardson page 78
Model CT part number Weight kg Ib
Figure 3-39 Footprint mounting the EMC filter Figure 3-40 Bookcase mounting the EMC filter
Figure 3-41 Size 1 to 8 external EMC filter
Table 3-9 Size 1 external EMC filter dimensions
Table 3-10 Size 2 external EMC filter dimensions
Table 3-11 Size 3 external EMC filter dimensions
Table 3-12 Size 4 external EMC filter dimensions
Table 3-13 Size 5 external EMC filter dimensions
V: Ground stud X: Threaded holes for footprint mounting of the drive Y: Footprint mounting hole diameter Z: Bookcase mounting slot diameter CS: Cable size
U1 V 1 W1 Netz /L ine Last /Loa d PE U2 V2 W 2
Table 3-14 Size 6 external EMC filter dimensions
Table 3-15 Size 7 external EMC filter dimensions
Table 3-16 Size 8 external EMC filter dimensions
Electrical terminals
3.11.1 Location of the power and ground terminals
Figure 3-42 Location of the power and ground terminals (size 1 to 4)
1 Control terminals 4 AC power terminals 7 DC bus +
2 Relay terminals 5 Motor terminals 8 Brake terminal
Figure 3-43 Location of the power and ground connection terminals (size 5 to 8)
3.11.2 Terminal sizes and torque settings
Table 3-17 Drive control terminal data
Table 3-18 Drive relay terminal data
Table 3-19 Drive power terminal data
Table 3-20 Terminal block maximum cable sizes
Table 3-21 External EMC filter terminal data
To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified tightening torques for the power and ground terminals Refer to the following tables.
Model Connection type Torque setting
All Screw terminals 0.2 N m (0.15 lb ft)
Model Connection type Torque setting
All Screw terminals 0.5 N m (0.4 lb ft)
AC and motor terminals DC and braking Ground terminal
Recommended Maximum Recommended Maximum Recommended Maximum
5 Plug-in terminal block M4 Nut (7 mm AF) M5 Nut (8 mm AF)
1.5 N m (1.1 lb ft) 1.8 N m (1.3 lb ft) 1.5 N m (1.1 lb ft) 2.5 N m (1.8 lb ft) 2.0 N m (1.4 lb ft) 5.0 N m (3.7 lb ft)
6 M6 Nut (10 mm AF) M6 Nut (10 mm AF) M6 Nut (10 mm AF)
6.0 N m (4.4 lb ft) 8.0 N m (6.0 lb ft) 6.0 N m (4.4 lb ft) 8.0 N m (6.0 lb ft) 6.0 N m (4.4 lb ft) 8.0 N m (6.0 lb ft)
7 M8 Nut (13 mm AF) M8 Nut (13 mm AF) M8 Nut (13 mm AF)
12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft) 12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft) 12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft)
8 M10 Nut (17 mm AF) M10 Nut (17 mm AF) M10 Nut (17 mm AF)
15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft) 15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft) 15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft)
Model size Terminal block description Max cable size
All Control connector 1.5 mm 2 (16 AWG)
All 2-way relay connector 2.5 mm 2 (12 AWG)
AC input power connector 6 mm 2 (10 AWG)
AC output power connector 2.5 mm 2 (12 AWG) 5
3-way AC power connector 3-way motor connector 8 mm 2 (8 AWG)
5 to 8 STO connector 2.5 mm 2 (12 AWG)
Max cable size Max torque Ground stud size Max torque
Routine maintenance
The drive should be installed in a cool, clean, well ventilated location Contact with moisture and/or dust with the drive should be avoided.
Regular checks of the following should be carried out to ensure drive / installation reliability are maximized:
Figure 3-44 Removal of the size 5 heatsink fan
• Ensure the fan cable is disconnected from the drive prior to attempting fan removal.
• Press the two outer tabs (1) inwards to release the fan from the drive frame.
• Using the central fan tab (2), withdraw the fan assembly from the drive housing.
Replace the fan by reversing the above instructions.
If the drive is surface mounted using the outer holes on the mounting bracket, then the heatsink fan can be replaced without removing the drive from the backplate.
Ambient temperature Ensure the enclosure temperature remains at or below maximum specified
Dust Ensure the drive remains dust free – check that the heatsink and drive fan are not gathering dust
The lifetime of the fan is reduced in dusty environments.
Moisture Ensure the drive enclosure shows no signs of condensation
Enclosure door filters Ensure filters are not blocked and that air is free to flow
Screw connections Ensure all screw terminals remain tight
Crimp terminals Ensure all crimp terminals remains tight – check for any discoloration which could indicate overheating
Cables Check all cables for signs of damage
Figure 3-45 Removal of the size 6 heatsink fan
A: Press the tabs (1) inwards to release the fan assembly from the underside of the drive.
B: Use the tabs (1) to withdraw the fan by pulling it away from the drive.
C: Depress and hold the locking release on the fan cable lead as shown (2)
D: With the locking release depressed (2), take hold of the fan supply cable and carefully pull to separate the connectors.
Many cable management features have been incorporated into the product and accessories, this chapter shows how to optimize them Key features include:
• EMC compliance with shielding / grounding accessories
• Product rating, fusing and cabling information
• Brake resistor details (selection / ratings)
Power connections
See Figure 4-8Size 1 to 4 ground connections (size 2 shown)on page 56 for further information on ground connections.
The voltages present in the following locations can cause severe electric shock and may be lethal:
• AC supply cables and connections
• DC and brake cables, and connections
• Many internal parts of the drive, and external option units
Unless otherwise indicated, control terminals are single insulated and must not be touched.
error code: 502
The STOP function does not remove dangerous voltages from the drive, the motor or any external option units.
The SAFE TORQUE OFF function does not remove dangerous voltages from the drive, the motor or any external option units.
error code: 502
error code: 502
Techniques or their authorized distributor.
Equipment supplied by plug and socket
error code: 502
See Figure 4-8Size 1 to 4 ground connections (size 2 shown)on page 56 for further information on ground connections.
On the size 2 110 V drives, the supply should be connected to L1 and
L3 Also the -DC bus (-) terminal has no internal connection.
See Figure 4-8Size 1 to 4 ground connections (size 2 shown)on page 56 for further information on ground connections.
See Figure 4-8Size 1 to 4 ground connections (size 2 shown)on page 56 for further information on ground connections.
The upper terminal block (1) is used for AC supply connection.
The lower terminal block (2) is used for Motor connection.
See Figure 4-9Size 5 ground connectionson page 56 for further information on ground connections.
See Figure 4-10Size 6 ground connectionson page 57 for further information on ground connections.
Figure 4-7 Size 7 and 8 power connections (size 7 shown)
See Figure 4-11Size 7 and 8 ground connections (size 7 shown)on page 57 for further information on ground connections.
On sizes 1 to 4, the supply and motor ground connections are made using the ground busbar located at the bottom of the drive as shown in Figure 4-8.
Figure 4-8 Size 1 to 4 ground connections (size 2 shown)
1: 4 x M4 threaded holes for the ground connection busbar Size 5
On size 5, the supply and motor ground connections are made using the M5 studs located near the plug -in power connector.
Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against corrosion i.e as could be caused by condensation.
On a size 6, the supply and motor ground connections are made using the M6 studs located above the supply and motor terminals Refer to
On size 7, the supply and motor ground connections are made using the
M8 studs located by the supply and motor connection terminals
On size 8, the supply and motor ground connections are made using the
M10 studs located by the supply and motor connection terminals
Figure 4-11 Size 7 and 8 ground connections (size 7 shown)
Table 4-1 Protective ground cable ratings
AC supply requirements
690 V drive: 500 V to 690 V ±10 % Number of phases: 3
Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance between phases).
Frequency range: 48 to 62 Hz For UL compliance only, the maximum supply symmetrical fault current must be limited to 100 kA
All drives are suitable for use on any supply type i.e TN-S, TN-C-S, TT and IT.
• Supplies with voltage up to 600 V may have grounding at any potential, i.e neutral, centre or corner (“grounded delta”)
error code: 502
A ground fault in the supply has no effect in any case If the motor must
The ground loop impedance must conform to the requirements of local safety regulations
The drive must be grounded by a connection capable of carrying the prospective fault current until the protective device (fuse, etc.) disconnects the AC supply
The ground connections must be inspected and tested at appropriate intervals.
Input phase conductor size Minimum ground conductor size
≤ 10 mm 2 Either 10 mm 2 or two conductors of the same cross-sectional area as the input phase conductor.
> 10 mm 2 and ≤ 16 mm 2 The same cross-sectional area as the first input phase conductor.
> 35 mm 2 Half of the cross-sectional area of the input phase conductor.
Operation with IT (ungrounded) supplies:
error code: 502
Input line reactors reduce the risk of damage to the drive resulting from poor phase balance or severe disturbances on the supply network.
Where line reactors are to be used, reactance values of approximately 2
% are recommended Higher values may be used if necessary, but may result in a loss of drive output (reduced torque at high speed) because of the voltage drop.
For all drive ratings, 2 % line reactors permit drives to be used with a supply unbalance of up to 3.5 % negative phase sequence (equivalent to
Severe disturbances may be caused by the following factors, for example:
• Power factor correction equipment connected close to the drive.
• Large DC drives having no or inadequate line reactors connected to the supply.
• Across the line (DOL) started motor(s) connected to the supply such that when any of these motors are started, the voltage dip exceeds
error code: 502
Drives of low power rating may also be susceptible to disturbance when connected to supplies with a high rated capacity.
Line reactors are particularly recommended for use with the following drive models when one of the above factors exists, or when the supply capacity exceeds 175 kVA: Size 1 to 3
Model sizes 04200133 to 07600540 have an internal DC choke and
082001160 to 08600860 have internal AC line chokes so they do not require AC line reactors except for cases of excessive phase unbalance or extreme supply conditions.
When required, each drive must have its own reactor(s) Three individual reactors or a single three-phase reactor should be used.
The current rating of the line reactors should be as follows:
Not less than the continuous input current rating of the drive
Not less than twice the continuous input current rating of the drive
To calculate the inductance required (at Y%), use the following equation:
4.2.4 Input line reactor specification for size 1 to 7
Table 4-2 AC line reactor values
**These input reactors are not stocked by Control Techniques Contact your local Drive Centre.
The AC line reactors for the 110 V and other size drives should be sourced locally.
The reactance values will be higher than 2 % with some of these drives,
Figure 4-12 Input line reactor 4402-0224, 4402-0225 and 4402-0226
Part No Dimensions Ground terminal
4402-0224 90 mm (3.54 in) 72 mm (2.84 in) 44.5 mm (1.75in) 35 mm (1.38 in) 65 mm (2.56 in)
82 mm (3.23 in) 54 mm (2.13in) 40 mm (1.58 in) 75 mm (2.95 in)
4402-0226 105 mm (4.13 in) 53 mm (2.09 in) 90 mm (3.54 in)
Part No Dimensions Ground terminal
150 mm (5.91in) 150 mm (5.91in) 120 mm (4.72 in) 47 mm (1.85 in) 90mm (3.54in) 17 mm x 7 mm
The 24 Vdc supply connected to the +24 V supply terminals on the AI-
Backup adaptor provides the following functions:
error code: 502
error code: 502
However, the drive will be in the Under Voltage state unless the line power supply is enabled, therefore diagnostics may not be possible
(Power down save parameters are not saved when using the 24 V back-up power supply input).
The working voltage range of the 24 V back-up power supply is as follows:
Minimum and maximum voltage values include ripple and noise Ripple and noise values must not exceed 5 %.
Figure 4-14 Location of the 24 Vdc power supply connection on the AI-Backup adaptor
Minimum power supply requirement at 24 V 20 W
Ratings
The input current is affected by the supply voltage and impedance.
The values of typical input current are given to aid calculations for power flow and power loss.
The values of typical input current are stated for a balanced supply.
error code: 502
error code: 502
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence imbalance and rated at the supply fault current given in Table 4-5.
Table 4-5 Supply fault current used to calculate maximum input currents
Table 4-6 AC Input current and fuse ratings (100 V)
Table 4-7 AC Input current and fuse ratings (200 V)
Model Symmetrical fault level (kA)
error code: 502
IEC gG Class CC or Class J
Table 4-8 AC Input current and fuse ratings (400 V)
Table 4-9 AC Input current and fuse ratings (575 V)
Table 4-10 AC Input current and fuse ratings (690 V)
Ensure cables used suit local wiring regulations.
error code: 502
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
PVC insulated cable should be used.
Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction factor for 40°C ambient of 0.87 (from table A52.14) for cable installation method B2 (multicore cable in conduit).
C - Multicore cable in free air.
Cable size may be reduced if a different installation method is used, or if the ambient temperature is lower.
error code: 502
A fuse or other protection must be included in all live connections to the
The fuse voltage rating must be suitable for the drive supply voltage.
Do not use an MCB instead of the recommended fuses.
The drive must be connected to the system ground of the AC supply
The ground wiring must conform to local regulations and codes of practice.
For information on ground cable sizes, refer to Table 4-1Protective ground cable ratingson page 57.
The recommended AC supply contactor type for size 1 to 8 is AC1.