CAU TION ; Never connect the AC motor drive output terminals U/T1, V/T2 and W/T3 directly to the AC mains circuit power supply.. When wiring the AC motor drive, please make sure that the
Trang 1RIILFLDOUHOHDVHGGRFXPHQW&(
Trang 2manufactured with high-quality components and materials and incorporate the latest
microprocessor technology available
This manual is to be used for the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drive To guarantee safe operation of the equipment, read the following safety guidelines before connecting power to the AC motor drive Keep this operating manual at hand and distribute to all users for reference
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor drive are to do installation, start-up and maintenance Always read this manual thoroughly before using VFD-C200 series AC Motor Drive, especially the DANGER and CAUTION notes Failure to comply may result in personal injury and equipment damage If you have any questions, please contact your dealer
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY
DANGER
; AC input power must be disconnected before any wiring to the AC motor drive is made
; Even if the power has been turned off, a charge may still remain in the DC-link capacitors with hazardous voltages before the POWER LED is OFF Please do not touch the internal circuit and components
; There are highly sensitive MOS components on the printed circuit boards These components are especially sensitive to static electricity Please do not touch these components or the circuit boards before taking anti-static measures Never reassemble internal components or wiring
; Ground the AC motor drive using the ground terminal The grounding method must comply with the laws of the country where the AC motor drive is to be installed
; DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight and inflammables
CAU TION
; Never connect the AC motor drive output terminals U/T1, V/T2 and W/T3 directly to the
AC mains circuit power supply
; Only qualified persons are allowed to install, wire and maintain the AC motor drives
; Even if the 3-phase AC motor is stop, a charge may still remain in the main circuit terminals of the AC motor drive with hazardous voltages
; If the AC motor drive is stored in no charge condition for more than 3 months, the ambient temperature should not be higher than 30 °C Storage longer than one year is not recommended, it could result in the degradation of the electrolytic capacitors
NOTE
The content of this manual may be revised without prior notice Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation
Trang 3CHAPTER 1 INTRODUCTION 1-1 CHAPTER 2 INSTALLATION 2-1 CHAPTER 3 HOW TO SELECT THE RIGHT AC MOTOR DIRVE 3-1 CHAPTER 4 WIRING 4-1 CHAPTER 5 MAIN CIRCUIT TERMINALS .5-1 CHPATER 6 CONTROL TERMINALS 6-1 CHAPTER 7 OPTIONAL ACCESSORIES 7-1 CHAPTER 8 SPECIFICATION 8-1 CHAPTER 9 DIGITAL KEYPAD 9-1 CHAPTER 10 SUMMARPY OF PARAMETERS 10-1 CHAPTER 11 DESCRIPTION OF PARAMETER SETTINGS 11-1 CHPAPTER 12 WARNING CODES 12-1 CHAPTER 13 CANOPEN OVERVIEW 13-1 CHAPTER 14 PLC FUNCTION 14-1 CHAPTER 15 SUGGESTIONS AND ERROR CORRECTIONS FOR STANDARD AC MOTOR DRIVES 15-1
Trang 4Chapter 1 Introduction
Receiving and Inspection
After receiving the AC motor drive, please check for the following:
1 Please inspect the unit after unpacking to assure it was not damaged during shipment Make sure that the part number printed on the package corresponds with the part number indicated on the nameplate
2 Make sure that the voltage for the wiring lie within the range as indicated on the nameplate Please install the AC motor drive according to this manual
3 Before applying the power, please make sure that all the devices, including power, motor, control board and digital keypad, are connected correctly
4 When wiring the AC motor drive, please make sure that the wiring of input terminals “R/L1, S/L2, T/L3” and output terminals”U/T1, V/T2, W/T3” are correct to prevent drive damage
5 When power is applied, select the language and set parameter groups via the digital keypad
(KPE-LE02) When executes trial run, please begin with a low speed and then gradually increases the speed untill the desired speed is reached
Nameplate Information
INPUT : Normal Duty: 3PH 380-480V 50/60Hz 4.3A Heavy Duty: 3PH 380-480V 50/60Hz 4.1A OUTPUT :
Normal Duty: 3PH 380-480V 3A 2.4KVA 1HP Heavy Duty: 3PH 380-480V 2.9A 2.3KVA 1HP FREQUENCY RANGE :
Normal Duty: 0-600Hz Heavy Duty: 0-600Hz Version:VX.XX
F req ue ncy Ra ng e
F irmware Version
Ce rtification s
S eria l Numbe r
Trang 5Model Name
VFD 007 CB 43 A - 21 M
Series name (Variable Frequency Drive)
004:0.5HP(0.375kW)~ 075:10HP(7.5kW)
Installation method Wall mounting:
Blank: standard modelM: Enhanced case model
Serial Number
007 CB EA I T 1 08 0001
EA 460V 3 PHASE
BA 230V 1-PHASEDA: 230V 3-PHASE
: :
-1HP(0.75kW)
Model number
T:TaoyuanW: WujianS: Shanghai
CB: C200CM: C200 standard enhanced case protection model
I IP20/UL Open TypeJ: IP20/NEMA1:
Prcoduction numberPrcoduction weekPrcoduction year (2011)Prcoduction factory
Product series:
Trang 6RFI Jumper
RFI Jumper: The AC motor drive may emit the electrical noise The RFI jumper is used to suppress the interference (Radio Frequency Interference) on the power line
Frame A0~A Screw Torque: 8~10kg-cm(6.9-8.7 lb -in.)
Loosen the screws and remove the MOV-PLATE Fasten the screws back to the original position after MOV-PLATE is removed
Frame A0
Frame A
Main power isolated from earth:
If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage
(according to IEC 61800-3) and reduce earth leakage current
CAUTION!
Trang 73 The gap discharge may occur when the transient voltage is higher than 1,000V Besides,
electro-magnetic compatibility of the AC motor drives will be lower after cutting the RFI jumper
4 Do NOT cut the RFI jumper when main power is connected to earth
5 The RFI jumper cannot be cut when Hi-pot tests are performed The mains power and motor must be separated if high voltage test is performed and the leakage currents are too high
6 To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC motor drive is installed on an ungrounded power system or a high resistance-grounded (over 30 ohms) power system or a corner grounded TN system
Trang 14Frame A
VFD040CB43A-20; VFD055CB43A-20; VFD075CB43A-20;
VFD040CB43A-21; VFD055CB43A-21; VFD075CB43A-21
Unit: mm [inch]
130.0
[5.12] 250.0 [9.84] 179.0 [7.05] [4.57] 116.0 236.0 [9.29] 170.0 [6.69] [0.24] 6.2 [0.87] 22.2 [1.34] 34.0 [1.10] 28.0
Trang 15116.0 [4.57]
236.0 [9.29]
170.0 [6.69]
6.2 [0.24]
22.2 [0.87]
34.0 [1.34]
28.0 [1.10]
Trang 17prevent the risk of fire accident
; Install the AC motor drive in Pollution Degree 2 environments only: normallyl only
nonconductive pollution occurs and temporary conductivity caused by condensation is
expected
The appearances shown in the following figures are for reference only
Airflow direction: (Blue arrow) inflow (Red arrow) outflow
Single drive installation Side-by-side installation
Multiple drives, side-by-side installation
Trang 18Multiple drives side-by-side installation and in rows
When installing one AC motor drive below another one (top-bottom installation), use a metal separation between the drives to prevent mutual heating The temperature measured at the fan’s inflow side must be lower than the temperature measured at the operation side If the fan’s inflow temperature is higher, use
a thicker or larger size of metal seperature Operation temperature is the temperature measured at 50mm away from the fan’s inflow side (As shown in the figure below)
Minimum mounting clearance
Frame A0 VFD004CB21A-20/-21/-21M; VFD007CB21A-20/-21/-21M; VFD004CB23A-20/-21/-21M;
VFD007CB23A-20/-21/-21M; VFD015CB23A-20/-21/-21M; VFD007CB43A-20/-21/-21M; VFD015CB43A-20/-21/-21M; VFD015CB21A-20/-21/-21M; VFD022CB21A-20/-21/-21M; VFD022CB23A-20/-21/-21M; VFD037CB23A-20/-21/-21M; VFD022CB43A-20/-21/-21M; VFD037CB43A-20/-21/-21M;
Frame A VFD040CB43A-20/-21/-21M; VFD055CB43A-20/-21/-21M; VFD075CB43A-20/-21/-21M;
NOTE
1 The minimum mounting clearances stated in the table above applies to AC motor drives frame A to D A drive fails to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problem
Trang 19NO T E
※ The mounting clearances stated in the figure is for installing the drive in an open area To install the drive in a confined space (such as cabinet or electric box), please follow the following three rules: (1) Keep the minimummounting clearances (2) Install a ventilation equipment or an air
conditioner to keep surrounding temperature lower than operation temperature (3) Refer to parameter setting and set up Pr 00-16, Pr.00-17, and Pr 06-55
※ The following table shows the heat dissipation and the required air volume when installing a single drive in a confined space When installing multiple drives, the required air volume shall be multiplied
by the number the drives
※ Refer to the chart (Air flow rate for cooling) for ventilation equipment design and selection
※ Refer to the chart (Power dissipation) for air conditioner design and selection
Air flow rate for cooling Power dissipation of AC motor drive
Power Dissipation
(cfm)
Flow Rate(m3/hr) Loss External
※ The required airflow shown in chart is for installing
single drive in a confined space
※ When installing the multiple drives, the required air
volume should be the required air volume for single
drive X the number of the drives
※ The heat dissipation shown in the chart is for installing single drive in a confined space
※ When installing the multiple drives, volume of heat dissipation should be the heat dissipated for single drive X the number of the drives
※ Heat dissipation for each model is calculated by rated voltage, current and default carrier
Trang 20Derating Curve Diagram of Normal Duty (Pr.00-16=0)
460V
100 110
90 80 70 60
4 5 6 7 8 9 10 11 12 13 14 15
Fc(kHz)
230V
100 110
90 80 70
50
2 5 6 7 8 9 10 11 12 13 14 15
Fc(kHz)
60
40 4 3
Trang 21Derating Curve Diagram of Heavy Duty (Pr.00-16=1)
460V
100 110
90 80 70
50
2 5 6 7 8 9 10 11 12 13 14 15
Fc(kHz)
230V
100 110
90 80 70
50
2 5 6 7 8 9 10 11 12 13 14 15
Fc(kHz)
60
40 4 3
Trang 22Chapter 3 How to Select the Right AC
Motor Drive
The choice of the right AC motor drive for the application is very important and has great influence on its lifetime If the capacity of AC motor drive is too large, it cannot offer complete protection to the motor and motor maybe damaged If the capacity of AC motor drive is too small, it cannot offer the required
performance and the AC motor drive maybe damaged due to overloading
But by simply selecting the AC motor drive of the same capacity as the motor, user application
requirements cannot be met completely Therefore, a designer should consider all the conditions,
including load type, load speed, load characteristic, operation method, rated output, rated speed, power and the change of load capacity The following table lists the factors you need to consider, depending on your requirements
Related Specification
torque characteristics
Time ratings Overload
capacity
Starting torque
Load type
Friction load and weight load Liquid (viscous) load
Inertia load Load with power transmission
Load speed and
torque characteristics
Constant torque Constant output Decreasing torque Decreasing output
Load characteristics
Constant load Shock load Repetitive load High starting torque Low starting torque
Continuous operation, Short-time operation
Maximum output current (instantaneous)
Power supply transformer capacity or percentage
impedance
Voltage fluctuations and unbalance
Number of phases, single phase protection
Frequency
Trang 233-1 Capacity Formulas
1 When one AC motor drive operates one motor
The starting capacity should be less than 1.5x rated capacity of AC motor drive
The starting capacity=
(kVA) otor_drive ty_of_AC_m
the_capaci 1.5
t
N 375
GD T cos η
×
×
×
ϕ
2 When one AC motor drive operates more than one motor
2.1 The starting capacity should be less than the rated capacity of AC motor drive
Acceleration time ≦60 seconds
The starting capacity=
( )
cos 1 1 n k 1 the capacity of AC motor drive kVA
n P k
n n N k
s C
s s
Acceleration time ≧60 seconds
The starting capacity=
( )
n P k n n N k
s C
s s
T s
2.2 The current should be less than the rated current of AC motor drive(A)
Acceleration time ≦60 seconds
)(
_
_5.11
1 n n k the rated current of AC motor drive A I
T S
_ _ _
_ 1
1 n n k the rated current of AC motor drive A I
T S
2.3 When it is running continuously
The requirement of load capacity should be less than the capacity of AC motor drive(kVA)
The requirement of load capacity=
)(
_
cos the capacity of AC motor drive kVA
_ _ _
10
kVA drive motor
AC of capacity the
I V
k × × M× M× − ≤
The current should be less than the rated current of AC motor drive(A)
) ( _ _
_ _ _
_ rated current of AC motor drive A the
I
k × M ≤
Trang 24Symbol explanation
M
P : Motor shaft output for load (kW)
η : Motor efficiency (normally, approx 0.85)
I : Motor rated current(A), for commercial power
k : Correction factor calculated from current distortion factor (1.05-1.1, depending on PWM
method) 1
Trang 253-2 General Precaution
Selection Note
1 When the AC Motor Drive is connected directly to a large-capacity power transformer (600kVA or above) or when a phase lead capacitor is switched, excess peak currents may occur in the power input circuit and the converter section may be damaged To avoid this, use an AC input reactor (optional) before AC Motor Drive mains input to reduce the current and improve the input power efficiency
2 When a special motor is used or more than one motor is driven in parallel with a single AC Motor Drive, select the AC Motor Drive current ≥1.25x(Sum of the motor rated currents)
3 The starting and accel./decel characteristics of a motor are limited by the rated current and the overload protection of the AC Motor Drive Compared to running the motor D.O.L (Direct On-Line),
a lower starting torque output with AC Motor Drive can be expected If higher starting torque is required (such as for elevators, mixers, tooling machines, etc.) use an AC Motor Drive of higher capacity or increase the capacities for both the motor and the AC Motor Drive
4 When an error occurs on the drive, a protective circuit will be activated and the AC Motor Drive output is turned off Then the motor will coast to stop For an emergency stop, an external
mechanical brake is needed to quickly stop the motor
Parameter Settings Note
1 The AC Motor Drive can be driven at an output frequency up to 400Hz (less for some models) with the digital keypad Setting errors may create a dangerous situation For safety, the use of the upper limit frequency function is strongly recommended
2 High DC brake operating voltages and long operation time (at low frequencies) may cause
overheating of the motor In that case, forced external motor cooling is recommended
3 Motor accel./decel time is determined by motor rated torque, load torque, and load inertia
4 If the stall prevention function is activated, the accel./decel time is automatically extended to a length that the AC Motor Drive can handle If the motor needs to decelerate within a certain time with high load inertia that can’t be handled by the AC Motor Drive in the required time, either use
an external brake resistor and/or brake unit, depending on the model, (to shorten deceleration time only) or increase the capacity for both the motor and the AC Motor Drive
Trang 263-3 How to Choose a Suitable Motor
Standard motor
When using the AC Motor Drive to operate a standard 3-phase induction motor, take the following precautions:
1 The energy loss is greater than for an inverter duty motor
2 Avoid running motor at low speed for a long time Under this condition, the motor temperature may rise above the motor rating due to limited airflow produced by the motor’s fan Consider external forced motor cooling
3 When the standard motor operates at low speed for long time, the output load must be decreased
4 The load tolerance of a standard motor is as follows:
3 6 20 60
100 82 70 60 50
8 Because of the high carrier frequency PWM control of the VFD series, pay attention to the
following motor vibration problems:
Resonant mechanical vibration: anti-vibration (damping) rubbers should be used to mount
equipment that runs at varying speed
Motor imbalance: special care is required for operation at 50 or 60 Hz and higher frequency
To avoid resonances, use the Skip frequencies
9 The motor fan will be very noisy when the motor speed exceeds 50 or 60Hz
Special motors:
1 Pole-changing (Dahlander) motor:
The rated current is differs from that of a standard motor Please check before operation and select the capacity of the AC motor drive carefully When changing the pole number the motor needs to be stopped first If over current occurs during operation or regenerative voltage is too high, please let the motor free run to stop (coast)
2 Submersible motor:
The rated current is higher than that of a standard motor Please check before operation and choose the capacity of the AC motor drive carefully With long motor cable between AC motor drive and motor, available motor torque is reduced
3 Explosion-proof (Ex) motor:
Needs to be installed in a safe place and the wiring should comply with the (Ex) requirements Delta AC Motor Drives are not suitable for (Ex) areas with special precautions
Gear reduction motor:
Trang 27different and depending on brand The lubricating function for operating long time at low speed and for high-speed operation needs to be considered carefully
5 Synchronous motor:
The rated current and starting current are higher than for standard motors Please check before operation and choose the capacity of the AC motor drive carefully When the AC motor drive operates more than one motor, please pay attention to starting and changing the motor
Power Transmission Mechanism
Pay attention to reduced lubrication when operating gear reduction motors, gearboxes, belts and chains, etc over longer periods at low speeds At high speeds of 50/60Hz and above, lifetime reducing noises and vibrations may occur
Motor torque
The torque characteristics of a motor operated by an AC motor drive and commercial mains power
are different
Below you’ll find the torque-speed characteristics of a standard motor (4-pole, 15kW):
180 155 140 100 80 55 38
60 seconds
Base freq.: 60Hz V/F for 220V/60Hz
180 155
100
55 38
130 140 100 85
45 35
180 150
100
45 35
3 20 Base freq.: 50Hz
V/F for 220V/50Hz
Base freq.: 50Hz V/F for 220V/50Hz
Trang 28Chapter 4 Wiring
After removing the front cover, examine if the power and control terminals are clearly noted Please read following precautions before wiring
; Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals Failure to comply may result
in damage to the equipments The voltage and current should lie within the range as indicated on the nameplate (Chapter 1-1)
; All the units must be grounded directly to a common ground terminal to prevent lightning strike or electric shock
; Please make sure to fasten the screw of the main circuit terminals to prevent sparks which is made
by the loose screws due to vibration
DANGER
; It is crucial to turn off the AC motor drive power before any wiring installation are made A charge may still remain in the DC bus capacitors with hazardous voltages even if the power has been turned off therefore it is suggested for users to measure the remaining voltage before wiring For your personnel saftery, please do not perform any wiring before the voltage drops to a safe level < 25 Vdc Wiring installation with remaninig voltage condition may caus sparks and short circuit
; Only qualified personnel familiar with AC motor drives is allowed to perform installation, wiring and commissioning Make sure the power is turned off before wiring to prevent electric shock
; When wiring, please choose the wires with specification that complys with local regulation for your personnel safety
; Check following items after finishing the wiring:
1 Are all connections correct?
2 Any loosen wires?
3 Any short-circuits between the terminals or to ground?
Trang 29Wiring Diagram
* It provides 1-phase/3-phase power
R(L1) S(L2) T(L3)
R(L1)
S(L2)
T(L3)
U(T1) V(T2) W(T3)
IM3~
When fault occurs, the
contact will switch ON to shut
the power and protect the power system.
250Vac/5A (N.O.) 250Vac/3A (N.C.)
NOTE
AFM1 ACM
RA1 RB1 RC1
FWD REV MI1
MI3 MI4 MI5 MI6 MI7 DCM
MI2
MI8 COM
AFM2
RA2 RB2 RC2
+24V
30Vdc/5A (N.O.) 30Vdc/3A (N.C.)
250Vac/1.2A (N.C.) Estimate at COS (0.4)
250Vac/2A (N.O.) Estimate at COS (0.4)
Analog Signal common
Analog Signal Common
* Do NOT apply the mains voltage directly
to above terminals.
* MI7, MI8 can input 33kHz pulses Digital Signal Common
Factory setting: NPN (SINK) Mode
Please refer to Figure 1 for wiring
of NPN mode and
PNP mode.
Factory setting
Analog Multi-function Output Terminal 0~10VDC
Analog Multi-function Output Terminal 0~20mA/4-20mA
Multi-function output terminals
FWD/STOP REV/STOP Multi-step 1 Multi-step 2 Multi-step 3 Multi-step 4
N/A
N/A N/A N/A
Multi-function output frequency terminals 30V30mA 33kHz
Main circuit (power) terminals Control terminals
Shielded leads & Cable
OPEN
120Ω 485
J5
PIN 1: CAN H PIN 2: CAN L PIN 3, 7:GND PIN 6: Reserved PIN 8: EV CANopen
A CI
A UI
0 /4~2 0 mA /0~1 0V -10 ~+1 0 V
Trang 30MI2
MI8~
COM
with internal pow er (+24VDC) with internal power (+24VDC )
internal c irc ui t internal c irc ui t
Trang 31Chapter 5 Main Circuit Terminals
Main Circuit Diagram
* Provide 1-phase/3-phase input power
Fuse/NFB(No Fuse Brea ke r)
R(L1)S(L2)T(L3)
IM 3~
DC+
Bra ke resistor (optio nal)
B1 B2DC-
For frame A0
R/L1, S/L2, T/L3 AC line input terminals 3-phase;
AC line input terminals 1-phase (R/L1, S/L2);
U/T1, V/T2, W/T3 AC drive output terminals for connecting 3-phase induction motor
DC+, DC- Connections for brake unit (VFDB series)
B1, B2 Connections for brake resistor (optional)
Earth connection, please comply with local regulations
* Provide 3-phase input power
Fuse/NFB(No Fu se Bre aker)
R(L1)S(L2)T(L3)
IM 3~
For frame A
J u m p e r
Brake resistor (optional)
DC choke (o ption al)
+2 +1/DC+ DC- B1 B2
R/L1, S/L2, T/L3 AC line input terminals 3-phase
U/T1, V/T2, W/T3 AC drive output terminals for connecting 3-phase induction motor
+1, +2 Connections for DC reactor to improve the power factor It needs to remove the
jumper for installation
+1/DC+, -/DC- Connections for brake unit (VFDB series)
B1, B2 Connections for brake resistor (built-in)
Earth connection, please comply with local regulations
Trang 32Main power terminals
; Do not connect 3-phase model to one-phase power R/L1, S/L2 and T/L3 has no phase-sequence requirement, it can be used upon random selection
; It is recommend to add a magnetic contactor (MC) to the power input wiring to cut off power quickly and reduce malfunction when activating the protection function of the AC motor drive Both ends of the MC should have an R-C surge absorber
; Fasten the screws in the main circuit terminal to prevent sparks condition made by the loose screws due to vibration
; Please use voltage and current within the specification
; When using a general GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of 200mA or above and not less than 0.1-second operation time to avoid nuisance tripping
; Please use the shield wire or tube for the power wiring and ground the two ends of the shield wire or tube
; Do NOT run/stop AC motor drives by turning the power ON/OFF
Run/stop AC motor drives by RUN/STOP command via control terminals
or keypad If you still need to run/stop AC motor drives by turning power ON/OFF, it is recommended to do so only ONCE per hour
Output terminals for main circuit
; When it needs to install the filter at the output side of terminals U/T1, V/T2, W/T3 on the AC motor drive Please use inductance filter Do not use phase-compensation capacitors or L-C (Inductance-Capacitance) or R-C (Resistance-Capacitance), unless approved by Delta
; DO NOT connect phase-compensation capacitors or surge absorbers at the output terminals of AC motor drives
; Use well-insulated motor, suitable for inverter operation
Terminals for connecting DC reactor, external brake resistor, external brake resistor and DC circuit
; This is the terminals used to connect the DC reactor to improve the power factor For the factory setting, it connects the short-circuit object Please remove this short-circuit object before connecting to the DC reactor
+1/DC+ +2
DC reactor (optional)
; When the AC Motor Drive is connected directly to a large-capacity power transformer (600kVA or above) or when a phase lead capacitor is
Trang 33avoid this, it is recommend to use a serial connected AC input reactor(6%) at the AC Motor Drive mains input side to reduce the current and improve the input power efficiency
; Connect a brake resistor or brake unit in applications with frequent deceleration ramps, short deceleration time, too low brake torque or requiring increased brake torque
Brake resistor (optional)
; The external brake resistor should connect to the terminals (B1, B2) of
AC motor drives
; For those models without built-in brake resistor, please connect external brake unit and brake resistor (both of them are optional) to increase brake torque
; DC+ and DC- are connected by common DC bus, please refer to Chapter 5-1(Main Circuit Terminal) for the wiring terminal specification and the wire gauge information
; Please refer to the VFDB manual for more information on wire gauge when installing the brake unit
Trang 345-1 Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , DC+, DC-, B1, B2
Gauge Min Wire Gauge
Torque (±10%)
10 AWG (5.3mm2)
M4 20kg-cm (17.4 lb-in.) (1.96Nm)
UL installations must use 600V, 75℃ or 90℃ wire Use copper wire only
NOTE
Figure 1 shows the terminal specification
Figure 2 shows the specification of insulated heat shrink tubing that comply with UL
(600V, YDPU2)
Figure 1 Figure 2
Trang 35Frame A Main circuit terminals :
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , DC+(+2,+1), DC-, B1, B2
Gauge Min Wire Gauge
Torque (±10%)
VFD075CB43A-20/-21/-21M
8 AWG (8.4mm2)
8 AWG (8.4mm2)
M4 20kg-cm (17.4 lb-in.) (1.96Nm)
UL installations must use 600V, 75℃ or 90℃ wire Use copper wire only
NOTE
Figure 1 shows the terminal specification
Figure 2 shows the specification of insulated heat shrink tubing that comply with
UL (600V, YDPU2)
Figure 1 Figure 2
Trang 36Chapter 6 Control Terminals
Please remove the top cover before wiring the multi-function input and output terminals,
The drive appearances shown in the figures are for reference only, a real drive may look different
Remove the cover for wiring
Frame A0 Remove theConduit-Box
1 Remove the cover, and then loosen the screws
of wiring guard Keep those screws for future
use
2 Use spare screws to fasten the Conduit box Screw torque: 8-10Kg-cm(6.9-8.7lb-in.)
Trang 373 Put back the cover then fasten tightly the screw Screw torque (M3): 6-8Kg-cm(5.2-6.9lb-in.)
Control Terminal the sketch map
MI1 +24V COM FWD MI3 MI5 ACI
SG-SG+
RA2 RC2 RB1 RC1 RA1
B
485 120Ω OPEN
AVI DFM1
Frame A0
ACIAVI
0-10V 0/4-20mA setting of terminal resistor
MI1 +24V COM FWD MI3 MI5 ACI
SG-SG+
RA2 RC2 RB1 RC1 RA1
A
B
485 120Ω OPEN
0-20mA 4-20mA 0-10V
setting of terminal resistor
Specifications of Control Terminal
Wire Gauge: 26~16AWG(0.1281-1.318mm2),
Torque: (A) 5kg-cm [4.31Ib-in.] (0.49Nm) (As shown in figure above)
(B) 8kg-cm [6.94Ib-in.] (0.78Nm) (As shown in figure above)
Trang 38Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a slotted screwdriver If the wire is stripped, sort the wire before install into the terminal
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit The factory setting for +24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more detail
Terminals Terminal Function Factory Setting (NPN mode)
+24V Digital control signal common
ONÎ forward running
OFFÎ deceleration to stop
REV Reverse-Stop command
REV-DCM:
ONÎ reverse running OFFÎ deceleration to stop MI1
RA1 Multi-function relay output 1 (N.O.) a
RB1 Multi-function relay output 1 (N.C.) b
RC1 Multi-function relay common 1
RA2 Multi-function relay output 2 (N.O.) a
RC2 Multi-function relay common 2
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC 5A(N.O.)/3A(N.C.) 30VDC Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC 2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive
is in operation, frequency attained or overload indication
DFM1
Digital frequency meter 1
(when Pr.02-21=0, DFM1 is the setting of Pr.02-16)
(When Pr.02-21≧1, DM1 is the pulse output.)
DFM2
Digital frequency meter 2
(When Pr.02-55 = 0, DFM2 is the setting value
of Pr.02-17.) (When Pr.02-55≧1, DFM2 is the pulse output)
DCM Digital frequency signal common
The AC motor drive releases various monitor signals, such as drive in operation, frequency attained and overload indication, via transistor (open collector) Regard the pulse voltage as the output monitor signalDuty-cycle: 50%
Min load impedance: 1kΩ/100pf Max current: 30mA
Max voltage: 30Vdc
DFM1
30V/30mA 33kHz
DFM2 DCM
Multi-function output frequency terminals
SG+ Modbus RS-485
PIN4、PIN5 equals to the PIN4, PIN5 of the RJ45 internet cable connector
Trang 39Terminals Terminal Function Factory Setting (NPN mode)
+10V Potentiometer power supply Analog frequency setting: +10Vdc 20mA
AVI
Analog voltage input
ACM AVI +10V AVI circuit
internal circuit
Impedance: 20kΩ Range: 0~10V/0~20mA/ 4~20mA(Pr.03-38)
=0~Max Output Frequency (Pr.01-00) AVI switch, factory setting is 0~10V
=0~Max Output Frequency (Pr.01-00) ACI Switch, factory setting is 4~20mA
ACI
1
ON 2
0-20mA 4-20mA 0-10V
AUI
Auxiliary analog voltage input
ACM AUI +10 AUI circuit
internal circuit
Impedance: 20kΩ Range: -10~+10VDC=0 ~ Max Output
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm2) with shielded wire
Analog input terminals (AVI, ACI, AUI, ACM)
; Analog input signals are easily affected by external noise Use shielded wiring and keep it as short as possible (<20m) with proper grounding If the noise is inductive, connecting the shield to terminal ACM can bring improvement
; If the analog input signals are affected by noise from the AC motor drive, please connect a capacitor and ferrite core as indicated in the following diagram
Trang 40AVI/ACI/AUI ACM
ferrite core
Wind each wires 3 times or more around the core
Digital inputs (FWD, REV, MI1~MI8, COM)
; When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce
Transistor outputs (MO1, MO2, MCM)
; Make sure to connect the digital outputs to the right polarity
; When connecting a relay to the digital outputs, connect a surge absorber across the coil and check the polarity
3 For External terminal MI7~MI8, their the minimum working voltage is 21Vdc, maximum
input/output frequency is 33kHz Refer to the formula below:
Maximum output rotation speed (rpm) /60*PG ≤33.000Hz Maximum output rotation speed (rpm)=(120*frequency/motor pole number)
For example: Set up PG function to be 600pulse, pole number to be 4 and the maximum rotation frequency is 60Hz
The maximum rotation speed(rpm)=( 120*60)/4=1800rpm
1800/60*600=18000Hz
4 Set up Pr10-01~ 10-04 before using PG function Its wiring diagram is shown as below:
Sink Mode Internal Power Supply(+24Vdc)
DCM
+24VCOMVcc