Using knowledge of the controlled variable to motivate changes to the manipulated variable is a fundamental control structure, known as feedback control.. We might moderate these swings
Trang 11.0 context and direction
Process control is an application area of chemical engineering - an
identifiable specialty for the ChE It combines chemical process
knowledge (how physics, chemistry, and biology work in operating
equipment) and an understanding of dynamic systems, a topic important to
many fields of engineering Thus study of process control allows
chemical engineers to span their own field, as well as form a useful
acquaintance with allied fields Practitioners of process control find their
skills useful in design, operation, and troubleshooting - major categories of
chemical engineering practice
Process control, like any coherent topic, is an integrated body of
knowledge - it hangs together on a multidimensional framework, and
practitioners draw from many parts of the framework in doing their work
Yet in learning, we must receive information in sequence - following a
path through multidimensional space It is like entering a large building
with unlighted rooms, holding a dim flashlight and clutching a vague map
that omits some of the stairways and passages How best to learn one’s
way around?
In these lessons we will attempt to move through a significant portion of
the structure - say, half a textbook - in about two weeks Then we will
repeat the journey several times, each time inspecting the rooms more
thoroughly By this means we hope to gain, from the start, a sense of
doing an entire process control job, as well as approach each new topic in
the context of a familiar path
1.1 the job we will do, over and over
We encounter a process, learn how it behaves, specify how we wish to
control it, choose appropriate equipment, and then explore the behavior
under control to see if we have improved things
1.2 introducing a simple process
A large tank must be filled with liquid from a supply line One operator
stands at ground level to operate the feed valve Another stands on the
tank, gauging its level with a dipstick When the tank is near full, the stick
operator will instruct the other to start closing the valve Overfilling can
cause spills, but underfilling will cause later process problems
Trang 2To learn how the process works, we write an overall material balance on
the tank
i
FV
The tank volume V can be expressed in terms of the liquid level h The
inlet volumetric flow rate Fi may vary with time due to supply pressure
fluctuations and valve manipulations by the operator The liquid density
depends on the temperature, but will usually not vary significantly with
time during the course of filling Thus (1.2-1) becomes
)t(Fdt
1)0(
h
1.3 planning a control scheme
Clearly the liquid level h is important, and we will call it the controlled
variable Our control objective is to bring h quickly to its target value hr
and not exceed it (To be realistic, we would specify allowable limits ± δh
on hr.) We will call the volumetric flow Fi the manipulated variable,
because we adjust it to achieve our objective for the controlled variable
The existing control scheme is to measure the controlled variable via
dipstick, decide when the controlled variable is near target, and instruct
Trang 3the valve operator to change the manipulated variable The scheme suffers
from
• delay in measurement Overfilling can occur if the stick operator
cannot complete the measurement in time
• performance variations Both stick and valve operators may vary in
attentiveness and speed of execution
• resources required There are better uses for operating personnel
• unsafe conditions There is too much potential for chemical exposure
A new scheme is proposed: put a timer on the valve Calculate the time
required for filling from (1.2-3) Close the valve when time has expired
The timing scheme would no longer require an operator to be on the tank
top, and with a motor-driven valve actuator the entire operation could be
directed from a control room These are indeed improvements However,
the timing scheme abandons a crucial virtue of the existing scheme: by
measuring the controlled variable, the operators can react to unexpected
disturbances, such as changes in the filling rate Using knowledge of the
controlled variable to motivate changes to the manipulated variable is a
fundamental control structure, known as feedback control The proposed
timing scheme has no feedback mechanism, and thus cannot accommodate
changes to h(0) and Fi(t) in (1.2-3)
An alternative is to build on the feedback already inherent in the
two-operator scheme, but to improve its operation We propose an automatic
controller that behaves according to the following controller algorithm:
near i max
r near i max
Algorithm (1.3-1) is an idealization of what the operators are already
doing: filling occurs at maximum flow until the level reaches a value hnear
Beyond this point, the flow decreases linearly, reaching zero when h
reaches the target hr The setting of hnear may be adjusted to tune the
control performance
1.4 choosing equipment
We need a sensor to replace the dipstick, a valve actuator to replace the
valve operator, and a controller mechanism to replace the stick operator
We imagine a buoyant object floating on the liquid surface The float is
linked to a lever that drives the valve stem When the liquid level is low,
the float rests above it on a structure so that the valve is fully open
Trang 41.5 process behavior under automatic control
Typically these things work quite well We predict its performance by
combining our process model (1.2-2) with the controller algorithm (1.3-1),
which eliminates the manipulated variable between the equations We
take the simple case in which Fmax does not vary during filling due to
pressure fluctuations, etc For h less than hnear,
tA
F)0(
h
h
known)
0(hF
Equation (1.5-1) can be used to calculate tnear, the time at which h reaches
hnear For h greater than hnear,
Content removed due to copyright restrictions
(To see a cut-away diagram of a toilet, go to
http://www.toiletology.com/lg-views.shtml#cutaway2x)
Trang 5where the parameter tfill is the time required for the level to reach hr at
flow Fmax, starting from an empty tank
r fill
The plot shows the filling profile from h(0) = 0.10hr with several values of
hnear/hr Certainly the filling goes faster if the flow can go instantaneously
from Fmax to zero at hr; however this will not be practical, so that hnear will
1.6 defining ‘system’
In Section 1.2, we introduced a process - a tank with feed piping - whose
inventory varied in time We thought of the process as a collection of
equipment and other material, marked off by a boundary in space,
communicating with its environment by energy and material streams
'Process' is a good notion, important to chemical engineers Another
useful notion is that of 'system' A system is some collection of equipment
and operations, usually with a boundary, communicating with its
environment by a set of input and output signals By these definitions, a
process is a type of system, but system is more abstract and general For
example, the system boundary is often tenuous: suppose that our system
comprises the equipment in the plant and the controller in the central
control room, with radio communication between the two A physical
boundary would be in two pieces, at least; perhaps we should regard this
Trang 6system boundary as partly physical (around the chemical process) and
partly conceptual (around the controller)
Furthermore, the inputs and outputs of a system need not be material and
energy streams, as they are for a process System inputs are "things that
cause" or “stimuli”; outputs are "things that are affected" or “responses”
systeminputs
(causes)
outputs(responses)
To approach the problem of controlling our filling process in Section 1.3,
we thought of it in system terms: the primary output was the liquid level h
not a stream, certainly, but an important response variable of the system
and inlet stream Fi was an input And peculiar as it first seems, if the
tank had an outlet flow Fo, it would also be an input signal, because it
influences the liquid level, just as does Fi
The point of all this is to look at a single schematic and know how to view
it as a process, and as a system View it as a process (Fo as an outlet
stream) to write the material balance and make fluid mechanics
calculations View it as a system (Fo as an input) to analyze the dynamic
behavior implied by that material balance and make control calculations
System dynamics is an engineering science useful to mechanical,
electrical, and chemical engineers, as well as others This is because
transient behavior, for all the variety of systems in nature and technology,
can be described by a very few elements To do our job well, we must
understand more about system dynamics how systems behave in time
That is, we must be able to describe how important output variables react
to arbitrary disturbances
1.7 systems within systems
We call something a system and identify its inputs and outputs as a first
step toward understanding, predicting, and influencing its behavior In
some cases it may help to determine some of the structure within the
system boundaries; that is, if we identify some component systems Each
of these, of course, would have inputs and outputs, too
system
2
Trang 7Considering the relationship of these component systems, we recognize
the existence of intermediate variables within a system Neither inputs
nor outputs of the main system, they connect the component systems
Intermediate variables may be useful in understanding and influencing
overall system behavior
1.8 the system of single-loop feedback control
When we add a controller to a process, we create a single time-varying
system; however, it is useful to keep process and controller conceptually
distinct as component systems This is because a repertoire of relatively
few control schemes (relationships between process and controller)
suffices for myriad process applications Using the terms we defined in
Section 1.3, we represent a control scheme called single-loop feedback
control in this fashion:
outputs
controlled variable
outputs
controlled variable system
Figure 1.8-1 The single-loop feedback control system and its
subsystems
We will see this structure repeatedly Inside the block called "process" is
the physical process, whatever it might be, and the block is the boundary
we would draw if we were doing an overall material or energy balance
HOWEVER, we remember that the inputs and outputs are NOT
necessarily the same as the material and energy streams that cross the
process boundary From among the outputs, we may select a controlled
variable (often a pressure, temperature, flow rate, liquid level, or
composition) and provide a suitable sensor to measure it From the inputs,
we choose a manipulated variable (often a flow rate) and install an
appropriate final control element (often a valve) The measurement is fed
to the controller, which decides how to adjust the manipulated variable to
keep the controlled variable at the desired condition: the set point The
Trang 8other inputs are potential disturbances that affect the controlled variable,
and so require action by the controller
1.9 conclusion
Think of a chemical process as a dynamic system that responds in
particular ways to its inputs We attach other dynamic systems (sensor,
controller, etc.) to that process in a single-loop feedback structure and
arrive at a new dynamic system that responds in different ways to the
inputs If we do our job well, it responds in better ways, so to justify all
the trouble
Trang 92.0 context and direction
Imagine a system that varies in time; we might plot its output vs time A
plot might imply an equation, and the equation is usually an ODE
(ordinary differential equation) Therefore, we will review the math of the
first-order ODE while emphasizing how it can represent a dynamic
system We examine how the system is affected by its initial condition
and by disturbances, where the disturbances may be non-smooth, multiple,
or delayed
2.1 first-order, linear, variable-coefficient ODE
The dependent variable y(t) depends on its first derivative and forcing
function x(t) When the independent variable t is t0, y is y0
0
0) yt(y)t(Kx)t(ydt
In writing (2.1-1) we have arranged a coefficient of +1 for y Therefore
a(t) must have dimensions of independent variable t, and K has
dimensions of y/x We solve (2.1-1) by defining the integrating factor p(t)
∫
=
)(exp)
(
t a
dt t
Notice that p(t) is dimensionless, as is the quotient under the integral The
solution
∫+
t
0 0
0
dt)t(a
)t(x)t(p)t(p
K)
t(p
)t(y)t(p)
t
(
comprises contributions from the initial condition y(t0) and the forcing
function Kx(t) These are known as the homogeneous (as if the right-hand
side were zero) and particular (depends on the right-hand side) solutions
In the language of dynamic systems, we can think of y(t) as the response
of the system to input disturbances Kx(t) and y(t0)
2.2 first-order ODE, special case for process control applications
The independent variable t will represent time For many process control
applications, a(t) in (2.1-1) will be a positive constant; we call it the time
constant τ
0
0) yt(y)t(Kx)t(ydt
The integrating factor (2.1-2) is
Trang 10=τ
Ke
y)
t 0
0
0
∫ τ τ
− τ
−
−
τ+
The initial condition affects the system response from the beginning, but
its effect decays to zero according to the magnitude of the time constant -
larger time constants represent slower decay If not further disturbed by
some x(t), the first order system reaches equilibrium at zero
However, most practical systems are disturbed K is a property of the
system, called the gain By its magnitude and sign, the gain influences
how strongly y responds to x The form of the response depends on the
nature of the disturbance
Example: suppose x is a unit step function at time t1 Before we proceed
formally, let us think intuitively From (2.2-3) we expect the response y to
decay toward zero from IC y0 At time t1, the system will respond to being
hit with a step disturbance After a long time, there will be no memory of
the initial condition, and the system will respond only to the disturbance
input Because this is constant after the step, we guess that the response
will also become constant
Now the math: from (2.2-3)
=
−τ
−
−
τ τ
− τ
−
−
∫
1 0
0 0
t t 1
t t 0
t
t
1 t
t t
t 0
e1)tt(KUe
y
dt)tt(Uee
Ke
y)
t
(
y
(2.2-4)
Figure 2.2-1 shows the solution Notice that the particular solution makes
no contribution before time t1 The initial condition decays, and with no
disturbance would continue to zero At t1, however, the system responds
to the step disturbance, approaching constant value K as time becomes
large This immediate response, followed by asymptotic approach to the
new steady state, is characteristic of first-order systems Because the
response does not track the step input faithfully, the response is said to lag
behind the input; the first-order system is sometimes called a first-order
lag
Trang 112.3 piecewise integration of non-smooth disturbances
The solution (2.2-3) is applied over succeeding time intervals, each
featuring an initial condition (from the preceding interval) and disturbance
<
<
τ+
∫
τ τ
− τ
−
−
τ τ
− τ
−
−
.etc
tttdt)t(xee
Ke
)t(y
tttdt)t(xee
Ke
)t(y)
t 1
1 0
t
t
t t t
t 0
1 1
0 0
(2.3-1)
Example: suppose
Trang 122t11t2
1t00
x
0)0(yxy
dt
dy
(2.3-2)
In this problem, variables t, x, and y should be presumed to have
appropriate, if unstated, units; in these units, both gain and time constant
are of magnitude 1 From (2.3-1),
e2
2t1e
2t2
1t00
1
With a zero initial condition and no disturbance, the system remains at
equilibrium until the ramp disturbance begins at t = 1 Then the output
immediately rises in response, lagging behind the linear ramp At t = 2,
the disturbance ceases, and the output decays back toward equilibrium
Trang 132.4 multiple disturbances and superimposition
Systems can have more than one input Consider a first-order system with
two disturbance functions
0 0 2
2 1
1x (t) K x (t) y(t ) yK
)t(ydt
Applying (2.2-3) and distributing the integral across the disturbances, we
find that the effects of the disturbances on y are additive
dt)t(xee
Kdt)t(xee
Ke
y)
t
t
t t 1 t
t 0
0 0
−
−
τ
+τ
+
This additive behavior is a happy characteristic of linear systems Thus
another way to view problem (2.4-1) is to decompose it into component
problems That is, define
2 1
H y y
y
Trang 14and write (2.4-1) in three equations We put the initial condition with no
disturbances, and each disturbance with a zero initial condition
0)t(y)t(xK)t(ydt
dy
0)t(y)t(xK)t(ydt
dy
y)t(y0
)t(ydt
dy
0 2 2
2 2
2
0 1 1
1 1
1
0 0 H H
H
=
=+
τ
=
=+
τ
=
=+
τ
(2.4-4)
Equations and initial conditions (2.4-4) can be summed to recover the
original problem specification (2.4-1) The solutions are
dt)t(xee
K)
t
(
y
dt)t(xee
K)
t
(
y
ey)
t
(
y
2 t
t
t t 2 2
1 t
t
t t 1 1
t t 0 H
0 0 0
∫
∫
τ τ
−
τ τ
and of course these solutions can be added to recover original solution
(2.4-2) Thus we can view the problem of multiple disturbances as a
system responding to the sum of the disturbances, or as the sum of
responses from several identical systems, each responding to a single
disturbance
Example: consider
2)0(y)3t(U)1t(U4
3y4
1dt
Equation (2.4-7) shows us that the time constant is 1, and that the system
responds to the first disturbance with a gain of 3, and to the second with a
gain of -4 The solution is
t 3U(t 1)1 e 4U(t 3)1 ee
2
Trang 15In Figure 2.4-1, the individual solution components are plotted as solid
traces; their sum, which is the system response, is a dashed trace Notice
how the first-order lag responds to each new disturbance as it occurs
Figure 2.4-1 first-order response to multiple disturbances
Writing the step functions explicitly in solution (2.4-8) emphasizes that
particular disturbances do not influence the solution until the time of their
occurrence For example, if they were omitted, some deceptively correct
but inappropriate rearrangement would lead to errors
) 3 t ) 1 t t
) 3 t )
1 t t
) 3 t )
1 t t
e4e
3e21
e44e
33e
2
e14e
13e
=
−
−
−+
=
(do not do this!) (2.4-9)
This notation at least implies that two of the exponential functions have
delayed onsets However, further correct-but-inappropriate rearrangement
makes things even worse
Trang 16( 1 3) t
t 3 t 1 t
) 3 t ) 1 t t
ee4e321
ee4ee3e21
e4e
3e21
−
=
+
−+
−
=
+
−+
−
=
(do not do this!) (2.4-10)
The incorrect solutions are plotted with (2.4-8) in Figure 2.4-2 Equation
(2.4-9) has become discontinuous - the response takes non-physical leaps
at the onset of each new disturbance Equation (2.4-10) has lost all
dependence on the disturbances and decays from a non-physical initial
condition Even with the mistakes, both incorrect solutions lead to the
correct long-term condition
Figure 2.4-2 comparison of correct and incorrect solutions
2.5 delayed response to disturbances
Consider a system that reacts to a disturbance, but only after some
intervening time interval θ has passed That is
0
0) yt(y)t(Kx)t(ydt
Equation (2.5-1) shows the dependence of y, at any time t, on the value of
x at earlier time t - θ The solution is written directly from (2.2-3)
dt)t(xee
Ke
y)
t 0
0
0
θ
−τ
+
We must integrate the disturbance considering the time delay Take as an
example a disturbance x(t) occurring at time t1 The plot shows the
Trang 17disturbance, as well as the disturbance as the system experiences it, which
begins at time t1 + θ We could express this disturbance-as-experienced as
some new function x1(t), occurring at time t1 + θ
=
=θ
θ
− τ θ + ξ τ
τx(t )dt e x (t)dt e x( )d
e
0 0
1 t
t
t t
t
t
(2.5-4) Therefore, solution (2.5-2) becomes
ξξτ
+
θ
− τ ξ τ τ
− τ
−
−
d)(xeee
Ke
y)
t
Example: consider a step disturbance at time t = 2 that affects the system
3 time units later
)2t(U)
t
(
x
0)0(y)3t(xy
(2.5-6)
Using (2.5-5)
Trang 18[ ]
3 t 2 3 t 3 t
2 3 t 3 t 2 3
t
2
2
3 0
3 t
3 0
3 t
e1)5t(U
ee
)5t(U
eeee)23t(U
e)2(Uee
d)2(Ued)2(Ueee
d)2(Ueee
−
ξ ξ
ξ
−ξ
=
ξ
−ξ
Figure 2.5-1 shows that a typical first-order lag step response occurs 3
time units after being disturbed at t = 2
Figure 2.5-1 step response of first order system with dead time
The time delay in responding to a disturbance is often called dead time
Dead time is different from lag Lag occurs because of the combination of
y and its derivative on the left-hand side of the equation Dead time
Trang 19occurs because of a time delay in processing a disturbance on the
right-hand side
2.6 conclusion
Please become comfortable with handling ODEs View them as systems;
identify their inputs and outputs, their gains and time parameters
Trang 203.0 context and direction
A particularly simple process is a tank used for blending Just as promised
in Section 1.1, we will first represent the process as a dynamic system and
explore its response to disturbances Then we will pose a feedback control
scheme We will briefly consider the equipment required to realize this
control Finally we will explore its behavior under control
DYNAMIC SYSTEM BEHAVIOR
3.1 math model of a simple continuous holding tank
Imagine a process stream comprising an important chemical species A in
dilute liquid solution It might be the effluent of some process, and we
might wish to use it to feed another process Suppose that the solution
composition varies unacceptably with time We might moderate these
swings by holding up a volume in a stirred tank: intuitively we expect the
changes in the outlet composition to be more moderate than those of the
Our concern is the time-varying behavior of the process, so we should
treat our process as a dynamic system To describe the system, we begin
by writing a component material balance over the solute
Ao Ai
Ao FC FCVC
dt
In writing (3.1-1) we have recognized that the tank operates in overflow:
the volume is constant, so that changes in the inlet flow are quickly
duplicated in the outlet flow Hence both streams are written in terms of a
single volumetric flow F Furthermore, for now we will regard the flow as
constant in time
Balance (3.1-1) also represents the concentration of the outlet stream, CAo,
as the same as the average concentration in the tank That is, the tank is a
perfect mixer: the inlet stream is quickly dispersed throughout the tank
volume Putting (3.1-1) into standard form,
Trang 21Ai Ao
we identify a first-order dynamic system describing the response of the
outlet concentration CAo to disturbances in the inlet concentration CAi
The speed of response depends on the time constant, which is equal to the
ratio of tank volume and volumetric flow Although both of these
quantities influence the dynamic behavior of the system, they do so as a
ratio Hence a small tank and large tank may respond at the same rate, if
their flow rates are suitably scaled
System (3.1-2) has a gain equal to 1 This means that a sustained
disturbance in the inlet concentration is ultimately communicated fully to
the outlet
Before solving (3.1-2) we specify a reference condition: we prefer that CAo
be at a particular value CAo,r For steady operation in the desired state,
there is no accumulation of solute in the tank
r , Ao r , Ai r
Thus, as expected, steady outlet conditions require a steady inlet at the
same concentration; call it CA,r Let us take this reference condition as an
initial condition in solving (3.1-2) The solution is
dt)t(Ce
eeC)
− τ
−
τ+
Equation (3.1-4) describes how outlet concentration CAo varies as CAi
changes in time In the next few sections we explore the transient
behavior predicted by (3.1-4)
3.2 response of system to steady input
Suppose inlet concentration remains steady at CA,r Then from (3.1-4)
Trang 22r , A t
t r , A
t r , A
t
0
t r , A
t t r , A Ao
C1eeCe
C
eC
eeCC
+
=
τ τ
− τ
−
τ τ
− τ
−
(3.2-1)
Equation (3.2-1) merely confirms that the system remains steady if not
disturbed
3.3 leaning on the system - response to step disturbance
Step functions typify disturbances in which an input variable moves
relatively rapidly to some new value and remains there Suppose that
input CAi is initially at the reference value CA,r and changes at time t1 to
value CA1 Until t1 the outlet concentration is given by (3.2-1) From the
step at t1, the outlet concentration begins to respond
=
τ
−
− τ
−
−
τ τ τ
− τ
−
−
τ τ
− τ
−
−
) t 1
A
) t r A
t t t 1 A
) t r A
1 t
t
t 1 A
t ) t r A Ao
1 1
1 1
1 1
e1Ce
C
eeeCe
C
tte
C
ee
CC
(3.3-1)
In Figure 3.3-1, CA,r = 1 and CA1 = 0.8 in arbitrary units; t1 has been set
equal to τ At sufficiently long time, the initial condition has no influence
and the outlet concentration becomes equal to the new inlet concentration
After time equal to three time constants has elapsed, the response is about
95% complete – this is typical of first-order systems
In Section 3.1, we suggested that the tank would mitigate the effect of
changes in the inlet composition Here we see that the tank will not
eliminate a step disturbance, but it does soften its arrival
Trang 23Figure 3.3-1 first-order response to step disturbance
3.4 kicking the system - response to pulse disturbance
Pulse functions typify disturbances in which an input variable moves
relatively rapidly to some new value and subsequently returns to normal
Suppose that CAi changes to CA1 at time t1 and returns to CA,r at t2 Then,
−
− τ
−
− τ
−
−
tte
1Ce
e1Ce
C
ttte
1Ce
C
tt0C
C
2
) t t r
A
) t ) t 1
A
) t r A
2 1
) t 1
A
) t r A
1 r
A
Ao
2 2
1 2 1
2
1 1
(3.4-1)
In Figure 3.4-1, CA,r = 0.6 and CA1 = 1 in arbitrary units; t1 has been set
equal to τ and t2 to 2.5τ We see that the tank has softened the pulse and
reduced its peak value A pulse is a sequence of two counteracting step
changes If the pulse duration is long (compared to the time constant τ),
Trang 24the system can complete the first step response before being disturbed by
Figure 3.4-1 first-order response to pulse disturbance
3.5 shaking the system - response to sine disturbance
Sine functions typify disturbances that oscillate Suppose the inlet
concentration varies around the reference value with amplitude A and
frequency ω, which has dimensions of radians per time
( )tsinAC
+τ
ω+
ωτ
−
2 2
t 2 2 r
, A
1
Ae
1
AC
Trang 25Solution (3.5-2) comprises the mean value CA,r, a term that decays with
time, and a continuing oscillation term Thus, the long-term system
response to the sine input is to oscillate at the same frequency ω Notice,
however, that the amplitude of the output oscillation is diminished by the
square-root term in the denominator Notice further that the outlet
oscillation lags the input by a phase angle tan-1(-ωτ)
In Figure 3.5-1, CA,r = 0.8 and A = 0.5 in arbitrary units; ωτ has been set
equal to 2.5 radians, and τ to 1 in arbitrary units The decaying portion of
the solution makes a negligible contribution after the first cycle The
phase lag and reduced amplitude of the solution are evident; our tank has
mitigated the inlet disturbance
Figure 3.5-1 first-order response to sine disturbance
3.6 frequency response and the Bode plot
The long-term response to a sine input is the most important part of the
solution; we call it the frequency response of the system We will
examine the frequency response for an abstract first order system
(Because we wish to focus on the oscillatory response, we will write
(3.6-1) so that x and y vary about zero The effect of a non-zero bias term can
be seen in (3.5-1) and (3.5-2).)
Trang 262 2
fr A
1
2 2 fr
fr fr
1
Kx
yR:ratioamplitude
)(tan:
anglephase
1
KAy
:amplitude
)tsin(
yy:resp
freq
)tsin(
Ax:
input
Kxydt
dyτ:system
τω+
τω+
=
φ+ω
=
ω
=
=+
−
(3.6-1)
The frequency response is a sine function, characterized by an amplitude,
frequency, and phase angle The amplitude and phase angle depend on
system properties (τ and K) and characteristics of the disturbance input (ω
and A) It is convenient to show the frequency dependence on a Bode
plot, Figure 3.6-1
The Bode plot abscissa is ω in radians per time unit; the scale is
logarithmic The frequency may be normalized by multiplying by the
system time constant Thus plotting ω is good for a particular system;
plotting ωτ is good for systems in general
The upper ordinate is the amplitude ratio, also on logarithmic scale RA is
often normalized by dividing by the system gain K The lower ordinate is
the phase angle, in degrees on a linear scale
In Figure 3.6-1, the coordinates have been normalized to depict first-order
systems in general; the particular point represents conditions in the
example of Section 3.5
For a first order system, the normalized amplitude ratio decreases from 1
to 0 as frequency increases Similarly, the phase lag decreases from 0 to
-90º Both these measures indicate that the system can follow slow inputs
faithfully, but cannot keep up at high frequencies
Another way to think about it is to view the system as a low-pass filter:
variations in the input signal are softened in the output, particularly for
high frequencies
The slope of the amplitude ratio plot approaches zero at low frequency;
the high frequency slope approaches -1 These two asymptotes intersect at
the corner frequency, the reciprocal of the system time constant At the
corner frequency, the phase lag is -45º
Trang 27If we disturb our system, will it return to good operation, or will it get out
of hand? This is asking whether the system is stable We define stability
as "bounded output for a bounded input" That means that
• a ramp disturbance is not fair – even stable systems can get into
trouble if the input keeps rising
• a stable system should handle a step change in input, ultimately
coming to some new steady state (We must be realistic, however
If the system is so sensitive that a small input step leads to an
unacceptably high, though steady, output, we might declare it
unstable for practical purposes.)
Trang 28• it should also handle a sine input; here the result is in general not
steady state, because the output may oscillate (Thus we
distinguish between 'steady state' and 'long-term stability'.)
The solutions for the typical bounded step, pulse, and sine disturbances,
given in Sections 3.3 through 3.5, show no terms that grow with time, so
long as the time constant τ is a positive value For these categories of
bounded input, at least, a first-order system appears to be stable We will
need to examine stability again when we introduce automatic control to
our process
3.8 concentration control in a blending tank
In Section 3.1 we described how variations in stream composition could
be moderated by passing the stream through a larger volume - a holding
tank Let us be more ambitious and seek to control the outlet composition:
we add a small inlet stream Fc of concentrated solution to the tank This
will allow us to adjust the composition in response to disturbances
Ao FC FC F F CVC
Ac
Ai c Ao
Ao c
FF
F1F
CCF
F1
1C
dtdCF
=
+
Notice that our equation coefficients each contain the input variable Fc
Notice, as well, that for dilute CAo and concentrated CAc stream Fc
Trang 29(however it may vary) will not be very large in comparison to the main
flow F If this is the case, we may be justified in making an engineering
approximation: neglecting the ratio Fc/F in comparison to 1 Thus
c
Ac Ai Ao
F
CCCdt
dC
F
Now we have a linear first-order system Comparison with (3.1-2) shows
the same time constant V/F and the same unity gain for inlet concentration
disturbances There is a new input Fc, whose influence on CAo (i.e., gain)
increases with high concentration CAc and decreases with large
throughflow F
3.9 use of deviation variables in solving equations
In process control applications, we usually have some desired operating
condition We now write system model (3.8-3) at the target steady state
All variables are at reference values, denoted by subscript r
r c
Ac r Ai r
F
CC
We recognize that deviations from these reference conditions represent
errors to be corrected Hence we recast our system description (3.8-3) in
terms of deviation variables; we do this by subtracting (3.9-1) from
(3.8-3)
' c Ac '
Ai
' Ao
'
Ao
r , c c
Ac r , Ai Ai r
, Ao Ao r
, Ao Ao
FF
CCCdt
dC
F
V
FFF
CC
CC
Cdt
CC
−+
−
=
−+
−
(3.9-2)
where we indicate a deviation variable by a prime superscript The target
condition of a deviation variable is zero, indicating that the process is
operating at desired conditions Using deviation variables
• makes conceptual sense for process control because they indicate
deviations from desired states
• makes the mathematical descriptions simpler
Thus we shall use deviation variables for derivations and modeling For
doing process control (computing valve positions, e.g.) we will return to
the physical variables We can recover the physical variable by adding its
deviation variable to its reference value For example,
)t(CC)
t
(
Ao r , Ao
Trang 30where we emphasize the variables that are time-varying
3.10 integration from zero initial conditions
As a rule, we will presume that our systems are initially at the reference
condition That is, the initial conditions for our differential equations are
zero Integrating (3.9-2) we find
dt)t(FeF
Cedt)t(Ce
e
c t
0
t Ac
t '
Ai t
0
t t '
− τ
τ
−
τ
+τ
Equation (3.10-1) shows how the outlet composition deviates from its
desired value CAo,r under disturbances to inlet composition CAi and the
flow rate of the concentrated makeup stream Fc, where both of these are
also expressed as deviations from reference values Equation (3.10-1) is
analogous to (3.1-4) for the simpler holding tank
3.11 response to step changes
Proceeding as in Section 3.3, we presume a step in inlet composition of
ΔCAi at time t1 and of ΔFc in makeup flow at time t2
−+
−
=
Δ
−τ
+Δ
−τ
=
τ
−
− τ
−
−
τ τ
− τ τ
−
∫
∫
) t t Ac
c 2
) t Ai
1
t
t
t Ac c 2
t t
t
t Ai 1
t '
Ao
2 1
2 1
e1F
CF)tt(Ue
1C)tt(U
dteF
CF)tt(U
edteC)tt(U
eC
(3.11-1)
CAo′ exhibits a first-order response to each of these step inputs
Example: try these numbers:
3 m
3 3
)0001.0(m
kg)400(m
kg)8(m
kg
)
10
Trang 31(Notice that the exact steady-state balance, derived from (3.8-2), is
satisfied to within 1%, so that our approximation in deriving (3.8-3)
appears to be reasonable.) The time constant for our process is
s300
m)02.0(
)6(F
V
s
3 m
300 t 3
300 ) 120 t 5
3 300
) 0 t 3
'
Ao
e1m
kg)1)(
120t(Ue
1m
kg)1(
e1)02.0(
)105(m
kg)400)(
120t(Ue
1m
kg)1)(
0t(UC
(3.11-4)
where t must be computed with units of seconds In Figure 3.11-1, we can
see that the reduction in make-up flow at 120 s compensates for the earlier
increase in inlet composition Now we are ready to consider control
CONTROL SCHEME
3.12 developing a control scheme for the blending tank
A control scheme is the plan by which we intend to control a process A
control scheme requires:
1) specifying control objectives, consistent with the overall objectives
of safety for people and equipment, environmental protection,
product quality, and economy
2) specifying the control architecture, in which various of the system
variables are assigned to roles of controlled, disturbance, and
manipulated variables, and their relationships specified
3) choosing a controller algorithm
4) specifying set points and limits
3.13 step 1 - specify a control objective for the process
Our control objective is to maintain the outlet composition at a constant
value Insofar as the process has been described, this seems consistent
with the overall objectives
3.14 step 2 - assign variables in the dynamic system
The controlled variable is clearly the outlet composition The inlet
composition is a disturbance variable: we have no influence over it, but
must react to its effects on the controlled variable We do have available a
variable that we can manipulate: the make-up flow rate
Trang 32We specify feedback control as our control architecture: departure of the
controlled variable from the set point will trigger corrective action in the
manipulated variable Said another way, we manipulate make-up flow to
control outlet composition
Figure 3.11-1 outlet composition response to opposing step inputs
3.15 step 3 - introduce proportional control for our process
The controller algorithm dictates how the manipulated variable is to be
adjusted in response to deviations between the controlled variable and the
set point We will introduce a simple and plausible algorithm, called
Trang 33proportional control This algorithm specifies that the magnitude of the
manipulation is directly proportional to the magnitude of the deviation
( Ao , setpt Ao)
gain bias
In algorithm (3.15-1) the controlled variable CAo is subtracted from the set
point (Subtracting from the set point, rather than the reverse, is a
convention.) Any non-zero result is an error The error is multiplied by
the controller gain Kgain Their product determines the degree to which
manipulated variable Fc differs from Fbias, its value when there is no error
The gain may be adjusted in magnitude to vary the aggressiveness of the
controller Large errors and high gain lead to large changes in Fc
We must consider the direction of the controller, as well as its strength:
should the outlet composition exceed the set point, the make-up flow must
be reduced Algorithm (3.15-1) satisfies this requirement if controller gain
Kc is positive
3.16 step 4 - choose set points and limits
The set point is the target operating value For many continuous processes
this target rarely varies In our blending tank example, we may always
desire a particular outlet concentration In other cases, such as a process
that makes several grades of product, the set point might be varied from
time to time In batch processes, moreover, the set point can show
frequent variation because it provides the desired trajectory for the
time-varying process conditions
Several sorts of limits must be considered in control engineering:
safety limits: if a variable exceeds these limits, a hazard exists Examples
are explosive composition limits on mixtures, bursting pressure in a
vessel, temperatures that trigger runaway reactions
These limits are determined by the process, and the control scheme must
be designed to abide by them
expected variation: it is necessary to estimate how much variation might
be expected in a disturbance variable This estimate is the basis for
specifying the strength of the manipulated variable response In Section
3.11, our system model (based on the material balance) showed us how
much variation in make-up flow, at specified make-up composition, was
required to compensate for a particular change in the inlet composition
These limits are determined by the process and its environment No
amount of controller design can compensate for a manipulated variable
that is unequal to the disturbance task
Trang 34tolerable variation: ideally the controlled variable would never deviate
from the set point This, of course, is unrealistic; in practice some
variation must be tolerated, because
• obtaining enough information on the process and disturbance is
usually impossible, and in any case too expensive
• exerting sufficient manipulative strength to suppress variation in the
control variable might be expected to require large variations in the
manipulated variable, which can cause problems elsewhere in the
process
Tolerable limits are determined by the safety limits, above, and then an
economic analysis that considers the cost of variation and the cost of
control We do not expect to achieve perfect control, but good control is
usually worth spending some money
For the blending tank example, then, we select:
• set point: CAo,setpt = 10 kg m-3 This would be determined by the user
of the stream
• safety limits: none apparent from problem statement
• expected variation: ±1 kg m-3; such a specification might come from
historical data or engineering calculations The steady-state material
balance (e.g., (3.11-1) applied at long times) shows that the make-up
flow must vary at least ±5×10-5 m3 s-1 to compensate such
disturbances However, might we need more capability during the
course of a transient??
• tolerable variation: ±0.1 kg m-3 This specification depends on the
user of the stream
EQUIPMENT
3.17 type of equipment needed for process control
Figure 3.17-1 shows our process and control scheme as two
communicating systems The system representing the process has two
inputs and one output Of these only one is a material stream; however,
we recall that systems communicate with their environment (and other
systems) through signals, and in the blending process the outlet
composition responds to the inlet composition and make-up flow rate
The system representing feedback control describes the needed operations,
but we have not described the nature of the equipment – could there be a
single device that takes in a composition measurement and puts out a
flow? Can we find a vendor to make such a device to execute controller
algorithm (3.15-1)? Can we have the gain knob calibrated in units
consistent with those we want to use for flow and composition?
Trang 35-tank to hold liquid -agitator to mix contents -inlet and outlet piping
multiply gain and add bias
subtract from set point
measure signal
set point
adjust make-up flow
system representing process
system representing controller and other equipment
make-up flow
-tank to hold liquid -agitator to mix contents -inlet and outlet piping
multiply gain and add bias
subtract from set point
measure signal
set point
adjust make-up flow
system representing process
system representing controller and other equipment make-up flow
Figure 3.17-1: Closed loop feedback control of process
We will address these questions in later lessons For now, we assume that
there will be several distinct pieces of equipment involved, and that they
work together so that
( Ao , setpt Ao)
c bias
where we use the conventional symbol Kc for controller gain In the case
of (3.17-1), we notice that the dimensions of Kc are volume2 mass-1 time-1
In good time we will improve our description of both equipment and
controller algorithms When we do, however, we will find that the overall
concept of feedback control is the same as presented in Figure 3.17-1: the
controlled variable is measured, decisions are made, and the manipulated
variable is adjusted to improve the controlled variable
CLOSED LOOP BEHAVIOR
3.18 closing the loop - feedback control of the blending process
Our next task will be to combine our controller algorithm with our system
model to describe how the process behaves under control We begin by
expressing algorithm (3.17-1) in deviation variables At the reference
condition, all variables are at steady values, indicated by subscript r
( Ao,setptr Aor)
c bias r
Trang 36Presumably the reference condition has no error, so that the set point is
simply the target outlet composition CAo,r Thus we learn that Fbias, the
zero-error manipulated variable value, is simply Fc,r Subtracting (3.18-1)
'
c
r Ao Ao r setpt , Ao setpt , Ao c bias bias r c
c
CC
K
F
CCC
CKFFF
We replace the manipulated variable in system model (3.9-2) with
controller algorithm (3.18-2) to find
Ao
' setpt , Ao c Ac '
Ai
' Ao
'
F
CCC
t
On expressing (3.18-3) in standard form, we arrive at a first-order
dynamic system model representing the process under proportional-mode
feedback control, as shown in Figure 3.17-1
' setpt , Ao c Ac
c Ac '
Ai c Ac
' Ao
' Ao c Ac
CF
KC1F
KCC
F
KC1
1C
dtdCF
KC
++
=
++
τ
(3.18-4)
Equation (3.18-4) describes a dynamic system (process and controller in
closed loop) in which the outlet composition varies with two inputs: the
inlet composition and the set point Figure 3.18-1 compares (3.18-4) with
the process model (3.9-2) alone; we see that
• the closed loop responds more quickly because the closed loop time
constant is less than process time constant τ
• the closed loop has a smaller dependence on disturbance C′Ai because
the gain is less than unity Both time constant and gain are reduced by
increasing the controller gain Kc
3.19 integration from zero initial conditions
In Section 3.10, we integrated our open-loop system model to find how
C′Ao responded to inputs C′Ai and F′c Now we integrate closed-loop
system model (3.18-4) in a similar manner
dtC
eK
edtCeK
e
setpt , Ao t
0
t SP CL
t '
Ai t
0
t CL CL
t '
CL CL
CL
∫
− τ
τ
−
τ
+τ
Trang 37where
F
KC1F
KCK
F
KC1
1K
F
KC
c Ac
SP c
Ac
CL c
Ac CL
+
=+
=+
τ
=
' c Ac '
Ai
' Ao
'
F
CC
Cdt
τ
' setpt , Ao c Ac
c Ac '
Ai c Ac
' Ao
' Ao c Ac
CF
KC1F
KCC
F
KC1
1C
dtdCF
KC
(the process under control)
variable gain
other input
' c Ac '
Ai
' Ao
'
F
CC
Cdt
τ
' setpt , Ao c Ac
c Ac '
Ai c Ac
' Ao
' Ao c Ac
CF
KC1F
KCC
F
KC1
1C
dtdCF
KC
(the process under control)
variable gain
other input
Figure 3.18-1: Comparing open- and closed-loop system descriptions
3.20 closed-loop response to pulse disturbance
We test our controlled process by a pulse ΔC in the inlet composition that
begins at time t1 and ends at t2 We find
e1KC
ttte
1KC
tt00
C
2
) t t )
t CL
Ai
2 1
) t CL
1 2
CL 1
(3.20-1)
Figure 3.20-1 shows both uncontrolled (open-loop) and controlled
(closed-loop) process responses for the same operating conditions used in Section
3.11 We see the faster response and smaller error that we expected when
we examined (3.18-4) in Section 3.18 These characteristics improve as
gain increases Increasing gain also elicits stronger manipulated variable
action Thus automatic control appears to have improved matters
Trang 38Kc= 0 m 6 kg -1 s -1
Figure 3.20-1: Response to pulse input under proportional control
3.21 closed-loop response to step disturbance - the offset phenomenon
Integrating (3.19-1) for a step of ΔC, we obtain
Trang 39Figure 3.21-1 shows open- and closed-loop step responses Notice that for
no case does the controlled variable return to the set point! This is the
phenomenon of offset, which is a characteristic of the proportional control
algorithm responding to step inputs
CL
' Ao
setpt , Ao Ao
KC
)(C
C)(C
pointset -responselongterm
Recalling (3.19-2), increasing the controller gain decreases the closed-loop
disturbance gain KCL, and thus decreases the offset
We find that offset is implicit in the proportional control definition
(3.15-1) An off-normal disturbance variable requires the manipulated
variable to change to compensate For the manipulated variable to differ
from its bias value, (3.15-1) shows that the error must be non-zero Hence
some error must persist so that the manipulated variable can persist in
compensating for a persistent disturbance
3.22 response to set point changes
We apply (3.19-1) to a change in set point
SP setpt , Ao
'
We recall from (3.19-2) that KSP is less than 1 Thus, the outlet
composition follows the change, but cannot reach the new set point This
is again offset due to proportional-mode control Increasing controller
gain increases KSP and reduces the offset
3.23 tuning the controller
Choosing values of the adjustable controller parameters, such as gain, for
good control is called tuning the controller So far, our experience has
been that increasing the gain decreases offset - then should we not set the
gain as high as possible?
We should not jump to that conclusion In general, tuning positions the
closed-loop response between two extremes At one extreme is no control
at all, gain set at zero (open-loop) At the other is too much attempted
control, driving the system to instability In the former case, the
controlled variable wanders where it will; in the latter case,
over-aggressive manipulation produces severe variations in the controlled
variable, worse than no control at all Tuning seeks a middle ground in
Trang 40which control reduces variability in the controlled variable This means
both rejection of disturbances and fidelity to set point changes