electric machine
Trang 1Chapter 5 Synchronous Machines
Main features of synchronous machines:
A synchronous machine is an ac machine whose speed under steady-state conditions is proportional to the frequency of the current in its armature
The rotor, along with the magnetic field created by the dc field current on the rotor,
rotates at the same speed as, or in synchronism with, the rotating magnetic field produced
by the armature currents, and a steady torque results
Figure 4.12 Schematic views of three-phase generators: (a) two-pole, (b) four-pole, and
(c) Y connection of the windings
§5.1 Introduction to Polyphase Synchronous Machines
Synchronous machines:
Armature winding: on the stator, alternating current
Field winding: on the rotor, dc power supplied by the excitation system
Cylindrical rotor: for two- and four-pole turbine generators
Salient-pole rotor: for multipolar, slow-speed, hydroelectric generators and for most synchronous motors
Acting as a voltage source:
Frequency determined by the speed of its mechanical drive (or prime mover)
The amplitude of the generated voltage is proportional to the frequency and the field current
t N
k
t N
k
me p
ph w
m p
ph w a
ω
ωλ
cos
2
polescos
=
(4.45)
Trang 2m me
2poles ω
k t
dt
d N k dt
d
e a w ph p me me w ph p me
a = λ = Φ cosω −ω Φ sinω (4.47)
t N
k
e a =−ωme w phΦpsinωme (4.48)
p ph w me p
ph w me max = k N Φ =2 f k N Φ
E ω π (4.49)
p ph w me p
ph w me
It is often useful, when studying the behavior of an individual generator or group of generators, to represent the remainder of the system as a constant-frequency,
constant-voltage source, commonly referred to as an infinite bus
Analysis of a synchronous machine connected to an infinite bus
Torque equation:
RF f
R
2
sin2
δ = electric phase angle between magnetic axes of ΦR and Ff
The minus sign indicates that the electromechanical torque acts in the direction to bring the interacting fields into alignment
In a generator, the prime-mover torque acts in the direction of rotation of the rotor, and the electromechanical torque opposes rotation The rotor mmf wave leads the resultant air-gap flux
In a motor, the electromechanical torque is in the direction of rotation, in opposition
to the retarding torque of the mechanical load on the shaft
Torque-angle curve: Fig 5.1
Figure 5.1 Torque-angle characteristics
2
Trang 3An increase in prime-mover torque will result in a corresponding increase in the torque angle
: pull-out torque at Any further increase in prime-mover torque cannot be balanced by a corresponding increase in synchronous
electromechanical torque, with the result that synchronism will no longer be maintained and the rotor will speed up loss of synchronism, pulling out of step
max
T
⇒
§5.2 Synchronous-Machine Inductances; Equivalent Circuits
Figure 5.2 Schematic diagram of a two-pole,
three-phase cylindrical-rotor synchronous machine
§5.2.1 Rotor Self-Inductance
§5.2.2 Stator-to-Rotor Mutual Inductances
§5.2.3 Stator Inductances; Synchronous Inductance
§5.2.4 Equivalent Circuit
Equivalent circuit for the synchronous machine:
Single-phase, line-to-neutral equivalent circuits for a three-phase machine operating under balanced, three-phase conditions
s
L = effective inductance seen by phase a under steady-state, balanced three-phase
machine operating conditions
s e
a ˆ ˆ ˆ
ˆ R I jX I E
V = + + (5.23) Generator reference direction:
f a a s a a
ˆ R I jX I E
V =− − + (5.24)
Trang 4Figure 5.3 Synchronous-machine equivalent circuits:
(a) motor reference direction and (b) generator reference direction
ϕ
X X
E = air-gap voltage or the voltage behind leakage reactance
Figure 5.4 Synchronous-machine equivalent circuit showing air-gap and leakage components of synchronous reactance and air-gap voltage
4
Trang 5§5.4 Steady-State Power-Angle Characteristics
The maximum power a synchronous machine can deliver is determined by the maximum torque that can be applied without loss of synchronism with the external system to which it is connected
Both the external system and the machine itself can be represented as an impedance in series with a voltage source
Figure 5.11 (a) Impedance interconnecting two voltages; (b) phasor diagram
Trang 6Eˆ1 = 1 (5.36)
2 2
ˆ E
E = (5.37)
Z j
e Z X j R
Z = + = φ (5.38)
Z
j j
j
j j
e Z
E e
Z
E e
Z
E e E Ie
E
Icosφ = 1 cosδ −φ − 2 cos−φ ) (5.40)
2 1
2 cos
Z
R E Z
E E
P = δ −φZ − (5.41)
2 1
2 sin
Z
R E Z
E E
P = δ +αZ − (5.42) where
1 sin
Z
R E Z
E E
P = δ −φZ − (5.44) Frequently, R<< Z, Z ≈ X andαZ ≈0,
δsin
2 1 2 1
X
E E P
P = = (5.45)
Equation (5.45) is commonly referred to as the power-angle characteristic for a
synchronous machine
The angle δ is known as the power angle
Note that E1 and E2 are the line-to-neutral voltages
For three-phase systems, a factor “3” shall be placed in front of the equation
The maximum power transfer is
X
E E P
max , 2 max ,
1 = = (5.46) occurring when δ =±90o
If δ >0, Eˆ1 leadsEˆ2 and power flows from source Eˆ1 to Eˆ2
When δ <0, Eˆ1 lagsEˆ2 and power flows from source Eˆ2 to Eˆ1
Consider Fig 5.12 in which a synchronous machine with generated voltage
and synchronous is connected to a system whose Thevenin equivalent is a voltage source in series with a reactive impedance The power-angle characteristic can be written
EQ f a
X X
V E P
+
= (5.47)
6
Trang 7Figure 5.12 Equivalent-circuit representation of
a synchronous machine connected to an external system
Note that P∝E1E2, P ∝ X− 1, Pmax ∝E1E2, and Pmax ∝ X−1
In general, stability considerations dictate that a synchronous machine achieve steady-state operation for a power angle considerably less than 90o
Trang 8Figure 5.14 Equivalent circuits and phasor diagrams for Example 5.7
8
Trang 1010
Trang 11§5.3 Open- and Short-Circuit Characteristics
§5.3.1 Open-Circuit Saturation Characteristic and No-Load Rotational Losses
Figure 5.5 Open-circuit characteristic of a synchronous machine
§5.3.2 Short-Circuit Characteristic and Load Loss
Trang 12Figure 5.6 Typical form of an open-circuit core-loss curve
a f
Eˆ = ˆ + (5.26)
Figure 5.7 Open- and short-circuit characteristics of a synchronous machine
Figure 5.8 Phasor diagram for short-circuit conditions
ag a u s
I
V X
,
, , = (5.28)
a
rated a s
I
V X
′
= ,
(5.29)
12
Trang 13Figure 5.9 Open- and short-circuit characteristics showing equivalent magnetization line for saturated operating conditions
f O
f O
′′
′
=SCR (5.30)
AFSCAFNLSCR = (5.31)
Trang 14Figure 5.10 Typical form of short-circuit load loss and stray load-loss curves
t
T R
5.234
(5.32)
eff ,
ntaturecurrecircuitarm
short
lossloadcircuit short
Trang 15§5.5 Steady-State Operating Characteristics
Figure 5.15 Characteristic form of synchronous-generator compounding curves
Trang 16Figure 5.16 Capability curves of an 0.85 power factor, 0.80 short-circuit ratio,
hydrogen-cooled turbine generator Base MVA is rated MVA at 0.5 psig hydrogen
a
a I V Q
P + =
powerApparent (5.48)
Figure 5.17 Construction used for the derivation of a synchronous generator capability curve
a s
a jX I V
Q j
P− = ˆ + ˆ (5.49)
a s a f
Eˆ = ˆ + ˆ (5.50)
2 2
2 2
s
f a a s
a
X
E V X
V Q
P (5.51)
Figure 5.18 Typical form of synchronous-generator V curves
16
Trang 17Figure 5.19 Losses in a three-phase, 45-kVA, Y-connected, 220-V, 60-Hz, six-pole synchronous machine
Trang 18§5.6 Effects of Salient Poles; Introduction to Direct-And
Quadrature-Axis Theory
§5.6.1 Flux and MMF Waves
18
Trang 19Figure 5.20 Direct-axis air-gap fluxes in a salient-pole synchronous machine
3 ,
3 = 2V cos3ω t−120 +φ = 2V cos3ω t+φ
E c e o e (5.54)
Figure 5.21 Quadrature-axis air-gap fluxes in a salient-pole synchronous machine
Figure 5.22 Phasor diagram of a salient-pole synchronous generator
§5.3.2 Phasor Diagrams for Salient-Pole Machines
Trang 20Figure 5.23 Phasor diagram for a synchronous generator showing the relationship between the voltages and the currents
d l a
X = + ϕ (5.55)
q l a
q q
I X I I
X I
ˆˆ
ˆ
ˆoaba
aba
Eˆ = ˆ + ˆ + ˆ + ˆ (5.59)
20
Trang 21Figure 5.25 Generator phasor diagram for Example 5.9
Trang 2222