1. Trang chủ
  2. » Công Nghệ Thông Tin

Tài liệu HVAC Systems Design Handbook part 4 pdf

14 307 0
Tài liệu đã được kiểm tra trùng lặp

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Chapter 4 design procedures: part 2 general concepts for equipment selection
Thể loại Chapter
Năm xuất bản 2004
Định dạng
Số trang 14
Dung lượng 115,64 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

Design Procedures: Part 2 General Concepts for Equipment Selection 4.1 Introduction The purpose of this chapter is to outline the criteria used in the HVAC system and equipment selection

Trang 1

Design Procedures: Part 2

General Concepts for Equipment Selection

4.1 Introduction

The purpose of this chapter is to outline the criteria used in the HVAC system and equipment selection process, to describe some of the sys-tems and equipment available, and to develop some of the underlying philosophy and background related to system selection

Details of specific systems and items of equipment are discussed in later chapters

4.2 Criteria for System and

Equipment Selection

The problem-solving process requires some criteria that can be applied

in describing and evaluating alternatives In the selection of HVAC systems, the following criteria (Table 4.1) are used—consciously or unconsciously—because only rarely is the problem-solving process for-mally applied

1 Requirements of comfort or process. These requirements include temperature, always; humidity, ventilation, and pressurization, some-times; and zoning for better control, if needed In theory at least, the comfort requirement should have a high priority In practice, this cri-terion is sometimes subordinated to first cost or to the desires of some-one in authority This is happening less often as building occupants become more sophisticated in their expectations Process requirements are more difficult and require a thorough inquiry by the HVAC de-signer into the process and its needs Until the process is fully

Trang 2

under-TABLE 4.1 Criteria for HVAC System and

Equipment Selection

1 Demands of comfort or process

2 Energy conservation, code requirements

3 First cost versus life-cycle cost

4 Desires of owner, architect, and / or design office

5 Space limitations

6 Maintainability / reliability

7 Central plant versus distributed systems

8 Simplicity and controllability

stood, the designer cannot provide an adequate HVAC system Most often, different parts of the process have different temperature, hu-midity, pressure, and cleanliness requirements; the most extreme of these can penalize the entire HVAC system

2 Energy conservation. This is usually a code requirement and not optional State and local building codes almost invariably include

requirements constraining the use of new, nonrenewable energy

Non-renewable refers primarily to fossil-fuel sources Renewable sources

include solar power, wind, water, geothermal, waste processing, heat reclaim, and the like The strictest codes prohibit any form of reheat (except from reclaimed or renewable sources) unless humidity control

is essential This restriction eliminates such popular systems as ter-minal reheat, two-deck multizone, multizone, and constant volume dual-duct systems, although the two-fan dual-duct system is still pos-sible and the three-duct multizone system is acceptable (see Chap 11) Most HVAC systems for process environments have opportunities for heat reclaim and other ingenious ways of conserving energy Off-peak thermal storage systems are becoming popular for energy cost savings, although these systems may actually consume more energy than con-ventional systems.1Thermal storage is a variation on the age-old prac-tice of cutting and storing ice from the lake in winter, for later use in the summer

3 First cost and life-cycle cost. The first cost reflects only the ini-tial price, installed and ready to operate The first cost ignores such factors as expected life, ease of maintenance, and even, to some extent, efficiency, although most energy codes require some minimum effi-ciency rating The life-cycle cost includes all cost factors (first cost, operation, maintenance, replacement, and estimated energy use) and can be used to evaluate the total cost of the system over a period of years A common method of comparing the life-cycle costs of two or more systems is to convert all costs to present-worth values Typically, first cost governs in buildings being built for speculation or short-term investment Life-cycle costs are most often used by institutional

Trang 3

builders—schools, hospitals, government—and owners who expect to occupy the building for an indefinite extended period Life-cycle cost analysis requires the assumption of an interest, or discount, rate and may also include anticipated inflation

4 Desires of owner, architect, or design office. Very often, someone

in authority lays down guidelines which must be followed by the de-signer This is particularly true for institutional owners and major retailers Here the designer’s job is to follow the criteria of the em-ployer or the client unless it is obvious that some requirements are unsuitable in an unusual environment Examples of such environ-mental conditions are extremely high or low outside-air humidity, high altitude (which affects the AHU and air-cooled condenser capacity), and contaminated outside air (which may require special filtration and treatment)

5 Space limitations. Architects can influence the HVAC system selection by the space they make available in a new building In re-trofit situations, designers must work with existing space Sometimes

in existing buildings it is necessary to take additional space to provide

a suitable HVAC system For example, in adding air conditioning to a school, it is often necessary to convert a classroom to an equipment room Rooftop systems are another alternative where space is limited,

if the building structure will support such systems In new buildings,

if space is too restricted, it is desirable to discuss the implications of the space limitations in terms of equipment efficiency and maintain-ability with the architect There are ways of providing a functional HVAC system in very little space, such as individual room units and rooftop units, but these systems often have a high life-cycle cost

6 Maintainability. This criterion includes equipment quality (the mean time between failures is commonly used); ease of maintenance (are high-maintenance items readily accessible in the unit?); and ac-cessibility (Is the unit readily accessible? Is there adequate space around it for removing and replacing items?) Rooftop units may be readily accessible if an inside stair and a roof penthouse exist; but if

an outside ladder must be climbed, the adjective readily must be

de-leted Many equipment rooms are easy to get to but are too small for adequate access or maintenance This criterion is critical in the life-cycle cost analysis and in the long-term satisfaction of the building owner and occupants

7 Central plant versus distributed systems. Central plants may in-clude only a chilled water source, both heating and chilled water, an intermediate temperature water supply for individual room heat pumps, or even a large, central air-handling system Many buildings have no central plant This decision is, in part, influenced by previ-ously cited criteria and is itself a factor in the life-cycle cost analysis

Trang 4

In general, central plant equipment has a longer life than packaged equipment and can be operated more efficiently The disadvantages include the cost of pumping and piping or, for the central AHU, longer duct systems and more fan horsepower There is no simple answer to this choice Each building must be evaluated separately

8 Simplicity and controllability. Although listed last, this is the most important criterion in terms of how the system will really work There is an accepted truism that operators will soon reduce the HVAC system and controls to their level of understanding This is not to criticize the operator, who may have had little or no instruction about the system It is simply a fact of life The designer who wants or needs

to use a complex system must provide for adequate training—and retraining—for operators The best rule is: Never add an unnecessary complication to the system or its controls

4.3 Options in System and

Equipment Selection

Many of the various systems and equipment available are described

in later chapters They are briefly listed here to summarize the options available to the designer

4.3.1 Air-handling units

Air-handling units (AHUs) include factory-assembled package units and field-erected, built-up units (see Chap 11) The common compo-nents are a fan or fans, cooling and / or heating coils, and air filters Most units also include a mixing chamber with outside and return air connections with dampers The size range is from small fan-coil units with as little as 100 ft3/ min capacity to built-up systems handling over 100,000 ft3/ min When a package unit includes a cooling source, such

as a refrigeration compressor and condenser, or a heating source, such

as a gas-fired heater or electric heating coil, or both, then the unit is

said to be self-contained This classification includes heat pumps.

Many systems for rooftop mounting are self-contained, with capacities

as great as 100 tons or more of cooling and a comparable amount of heating Some room units for wall or window installation have capac-ities as small as 0.5 or 0.75 ton Split-system packages are also avail-able, with the heating and / or cooling source section matching the fan-coil section but installed outdoors The two sections are connected by piping Cooling coils may use chilled water, brine, or refrigerant (direct expansion) Heating coils may use steam or high- or low-temperature water; or ‘‘direct-fired’’ heating may be used, usually gas or electric resistance Heat reclaim systems of various types are employed Hu-midification equipment includes the steam grid, evaporative, and

Trang 5

slinger / atomizer types Dehumidification equipment includes the humidifying effect of most cooling coils as well as absorption-type de-humidifiers

Thus, the designer has a wide range of equipment to choose from Although generalizations are dangerous, some general rules may be applied, but the designer must also develop, through experience, an understanding of the best and worst choices There are some criteria which are useful:

1 Packaged equipment should be tested, rated, and certified in ac-cordance with standards of American Society of Heating, Refrigera-tion, and Air Conditioning Engineers (ASHRAE), Air Conditioning and Refrigeration Institute (ARI), Association of Home Appliance Manufacturers (AHAM), Air Movement and Control Association (AMCA), and / or others as applicable

2 Minimum unit efficiencies or effectiveness should be in accord-ance with codes or higher

3 In general, packaged equipment has a lower first cost and a shorter life than equipment used in built-up systems This is not al-ways true, and comparisons must be made for the specific application

4 In general, packaged equipment is designed to be as small as possible for a given capacity This may create problems of access for maintenance Also the supplier should show that capacity ratings were determined for the package as assembled and not just for the separate components See particularly the discussion on the effects of geometry on fan performance in Chap 5

5 In hotel guest rooms, motels and apartments, individual room units should be used to give occupants maximum control of their en-vironment Where many people share the same space, central systems are preferable, with controls which cannot be reset by occupants

6 Noise is a factor in almost any HVAC installation, yet noise is often neglected in equipment selection and installation Noise ratings are available for all types of HVAC equipment and should be used in design and specifications (see Chap 20)

4.3.2 Radiant and convective heating

and cooling

Convector radiators, using steam or hot water, are one of the oldest heating methods and are still in common use Modern systems are more compact than the old cast-iron radiators and depend more on natural convection than on radiation Rating methods are standard-ized by the Hydronics Institute

Radiant heating by means of floor, wall, or ceiling panels is common Hot-water piping or electric resistance heating tape is used Maximum

Trang 6

temperatures of the surface must be limited, and there are some con-trol problems, particularly in floor panels, due to the mass of the panel

Radiant cooling by means of wall or ceiling panels may also be used Surface temperatures must be kept above the dew point; therefore, any dehumidification required must be accomplished by other means

In modern practice, radiant and / or convective heating or cooling is usually a supplement to the air system and is used primarily to offset exterior wall, roof, and radiant floor heat gains or losses

4.3.3 Refrigeration equipment

Source cooling equipment includes refrigeration compressors of re-ciprocating, centrifugal, and screw types; absorption chillers using steam, hot water, or direct fuel firing; water chiller heat exchangers; condensers cooled by air, water, and evaporation; cooling towers; and evaporative coolers, including spray, slinger, and drip types (see Chap 9)

Self-contained package AHUs typically use direct-expansion cooling with reciprocating or rotary compressors Other AHUs may use direct expansion, chilled water, or brine cooling, with the cooling medium provided by a separate, centralized, refrigeration system (see Chap 6) Evaporative cooling is used primarily in climates with low design ambient wet-bulb temperatures, although it may be used in almost any climate to achieve some cooling Evaporative cooler efficiencies are highest for the spray type and lowest for the drip type Centrifugal and screw-type compressors and absorption refrigeration are used al-most entirely in large central-station water or brine chillers Absorp-tion refrigeraAbsorp-tion may be uneconomical unless there is an adequate source of waste heat or solar energy Air-cooled condensers are less costly to purchase and maintain than cooling towers or evaporative condensers, but they result in higher peak condensing temperatures

at design conditions and may result in lower overall efficiency in the cooling system

The selection of the source cooling equipment is influenced primarily

by the selection of the AHU equipment and systems Often both are selected at the same time The use of individual room units does not preclude the use of central-station chillers; this combination may be preferable in many situations For off-peak cooling with storage, a cen-tral chilling plant is an essential item

4.3.4 Heating equipment

Source heating equipment includes central plant boilers for steam and high-, medium-, and low-temperature hot water; heat pumps, both

Trang 7

Figure 4.1 Single-zone draw-through air-handling unit.

central and unitary; direct-fired heaters; solar equipment, including solar-assisted heat pumps; and geothermal and heat reclaim Fuels include coal, oil, natural and manufactured gas, and peat Waste

prod-ucts such as refuse-derived fuel (RDF) and sawdust are also being used

in limited ways Electricity for resistance heating is not a fuel in the combustion sense but is a heat source Heat reclaim takes many forms, some of which are discussed in Chap 10

Self-contained package AHUs use direct-fired heaters—usually gas

or electric—or heat pumps For other systems, some kind of central plant equipment is needed The type of equipment and fuel used is determined on the basis of the owner’s criteria, local availability and comparative cost of fuels, and, to some extent, the expertise of the designer Large central plants for pressure steam or high-temperature hot water, may present safety problems, are regulated by codes and require special expertise on the part of the designer, con-tractor, and operator New buildings connected to existing central plants will require the use of heat exchangers, secondary pumping or condensate return pumping, and an understanding of limitations im-posed by the existing plant, such as limitations on the pressure and temperature of returned water or condensate

4.4 The Psychrometric Chart

When the system type has been selected and a summary completed, showing design CFM, temperature difference (TD), and latent load, it

is time to complete the psychrometric chart For a detailed discussion

of psychrometrics, see Chap 19 Consider a single-zone, draw-through air-handling system, as in Fig 4.1 In summer the return air is mixed with some minimum amount of outside air; is pulled through the filter, the coils, and the fan; and is supplied to the space Cooling is provided

by the cooling coil through the use of chilled water (as in this example)

Trang 8

Figure 4.2 Psychrometric chart, cooling cycle example.

or by direct refrigerant expansion On the psychrometric chart (Fig 4.2), the designer first plots the inside and outside design conditions—say 75⬚F and 50 percent RH inside and 95⬚F dry bulb (db),

75⬚F wet bulb (wb) outside The return air to the system will usually

be at a higher temperature than the space due to heat gains in return-air plenums (This does not hold for direct-return units.) This heat gain can be estimated or calculated from the geometry of the building, the wattage of recessed lighting, etc For this example, assume a 3⬚F rise Then the return air is at 78⬚F with the same humidity ratio w

as the space A straight line between this point and the outside air state point represents the mixing process The mixed-air state point lies on this line at a distance from the return-air point equal to the design minimum percentage of outside air—for this example, 20 per-cent Then the mixed-air condition is 81.4⬚F db and 66.2⬚F wb, with

an enthalpy (h) of 30.8 (Btu / lb) The design condition of the supply

air is calculated as described in Chap 3 and for this example is as-sumed to be 56⬚F db with a humidity ratio (w) equal to 0.0086 lbw/

lba Because this is a draw-through system, there is some heating ef-fect due to fan work If the fan horsepower and efficiency are known, this can be calculated For preliminary purposes, a temperature rise

of 0.5⬚F per inch of pressure rise across the fan can be assumed—for this example, 3-in static pressure or 1.5⬚F Then the air must leave the coil at 54.5⬚F db, with w equal to 0.0086 as above The resulting point has an h value of 22.5 Now the cooling (coil) process can be

represented by a straight line from the mixed-air point through the

‘‘leaving coil’’ point and can be extended to the saturation curve The

intersection with the saturation curve is called the apparatus dew

Trang 9

Figure 4.3 Psychrometric chart, heating cycle example.

point (ADP) and is the coil surface temperature required to obtain the

design process (here about 53⬚F) The total cooling load in Btu/h is

determined from the difference in h values multiplied by the total

CFM, 60 min / h, and the air density in pounds per cubic foot (0.075 for standard air) Thus

q c ⫽ CFM ⫻ (h ⫺ h ) ⫻ 60 ⫻ 0.075 m c (4.1)

where q c⫽ total cooling, Btu/h

h m⫽ enthalpy of mixed air entering cooling coil, Btu/lb

h c⫽ enthalpy of air leaving the cooling coil, Btu/lb

The cooling load thus calculated includes the sensible and latent space load plus the load due to outside air, fan work, and any return-air

‘‘pickup.’’

The cycle at winter design conditions can also be plotted, as shown

in Fig 4.3 The mixed air is controlled at the low-limit condition, say

60⬚F, although this may be reset upward as the outside temperature decreases for energy conservation Return air will be about 3⬚F above the 72⬚F space temperature, or 75⬚F For this example, the outside design temperature is assumed to be 32⬚F and 50 percent RH Heating will be provided as required to maintain the space conditions (some design heating temperature difference will be calculated) If space hu-midity is uncontrolled, the cycle will automatically fall into a position such that the humidity ratio difference between supply air and space will be the same as that for cooling This will typically result in a lower space humidity in winter

Most designers use the psychrometric chart only for the design cool-ing cycle, or for both heatcool-ing and coolcool-ing if humidity control is pro-vided It is sometimes useful to look at intermediate conditions such

Trang 10

Figure 4.4 Psychrometric chart, intermediate cycle example.

as in Fig 4.4 Here an outside temperature of 60⬚F is assumed, and

100 percent outside air is used by the economy cycle The inside hu-midity will depend on the outside huhu-midity, as discussed before No mechanical cooling and little or no heating should be needed Other intermediate conditions can be examined in similar ways

4.5 Effects of Altitude and Temperature

Air density varies directly and linearly with temperature, and inverse / exponentially with altitude See Fig 4.5 Standard conditions are defined as 0.075 lb / ft3 at 59⬚F All HVAC airside calculations are recognized as being inexact, where seasonal ambient temperatures may vary from 0 to 100⬚F (a 10 percent effect), and local barometric pressures may fluctuate plus or minus 2 percent, depending on weather But changes in density related to altitude or related to heat-ing or coolheat-ing processes may compound all other effects and should not be taken lightly

4.5.1 Changes due to altitude

Atmospheric pressure and related air density decreases as altitude or elevation above sea level increases Inversely, atmospheric pressure increases for those elevations below sea level or some other reference point At elevations up to 6000 ft where the altitude / density variation

is nearly linear, the rate of density change is approximately 3 to 4 percent per 1000 ft of elevation change This corresponds to furnace manufacturer’s counsel to derate natural draft burner equipment at 4 percent per 1000 ft elevation Altitude effects are often ignored below

Ngày đăng: 26/01/2014, 14:20

TỪ KHÓA LIÊN QUAN