3.2 About the Control Panel
3.2.1 Names and functions of the control panel (FR-PA02- 02 )
Hz A PU
RUN MON EXT
Display LED 4 digits
Mode key MODE SET REV
STOP RESET FWD
Setting key
STOP RESET RUN
Hz A PU
RUN MON EXT
STOP/RESET key RUN key
Cover opened
Unit indication Operation status indication
STOP/RESET key Up/down keys Forward key
Reverse key
z Key indication
Key Description
RUN key Used to give a start rotation command.
MODE key You can select the operation mode or setting mode.
SET key You can determine the frequency and parameter setting.
/ key
z Used to increase or decrease the running frequency
consecutively. Hold down this key to change the frequency.
z Press this key in the setting mode to change the parameter setting consecutively.
FWD key Used to give a forward rotation command.
REV key Used to give a reverse rotation command.
STOP RESET key
z Used to stop operation.
z Used to reset the inverter when its output is stopped by the activated protective function.
z Unit indications, operating status indications
Indication Description
Hz Lit to indicate the frequency.
A Lit to indicate the current.
RUN Lit while the inverter is operating. Lit to indicate forward rotation, and flickers to indicate reverse rotation.
MON Lit in the monitor display mode.
PU Lit in the PU operation mode.
EXT Lit in the external operation mode.
3
zMonitoring mode zFrequency setting mode (Note)
zParameter setting mode
MODE SET REV STOP RESET FWD
Hz
PU MON
EXT PU
Hz
PU
MODE SET REV STOP RESET FWD
MODE SET REV STOP RESET FWD
zOperating mode
PU
MODE SET REV STOP RESET FWD
zHelp mode
PU EXT
MODE SET REV STOP RESET FWD
MODE MODE
MODE
MODE
MODE
(Note) The frequency setting mode is displayed only in the PU operation mode.
3.2.3 Monitoring
y Operation command indications given while a monitor display is being provided EXT is lit to indicate external operation.
PU is lit to indicate PU operation.
Both EXT and PU are lit to indicate combined operation.
y The monitor display can also be changed during operation.
zFrequency monitor
zAlarm monitor
Alarm absent
SET SET
*2
To 3.2.4 Frequency setting mode (Note3)
SET MODE
*1
SET Hz
MON EXT PU
MODE SET REV STOP RESET FWD
Alarm present
SET
zVoltage monitor
*1
SET PU
MON EXT zCurrent monitor
*1
SET PU
MON EXT A
SET
Note: 1. Hold down the SET key marked *1 for more than 1.5 seconds to change the
In the PU operation mode, set the frequency value used for operation performed under the operation command given by the RUN key ( FWD or REV key).
This mode is displayed only in PU operation.
To 3.2.5 Parameter setting mode
MODE
Hz PU
MODE SET REV STOP RESET FWD
zFrequency setting mode zSet frequency changing
SET
To frequency monitoring
MODE
Hz
PU zSet frequency write
Flicker
Hz
PU Hz
PU
Change the set frequency with
3.2.5 Parameter setting method
With the exception of some parameters, parameter setting can be made only when the PU operation mode is selected by the Pr. 79 setting.
y A parameter value may either be set by updating its parameter number or setting the value digit-by-digit using the / key.
y To write the setting, change it and press the SET key for about 1.5 seconds.
Note: If parameter write cannot be performed, refer to page 174. 3
from "2" (external operation mode) to "1" (PU operation mode)
(For details of Pr. 79, refer to page 109.)
SET
zCurrent setting zSetting change
Press for 1.5 sec.
SET
Middle digit flickers Most significant
digit flickers
SET
Least significant digit flickers
0 to 9
PU
MODE SET REV STOP RESET FWD
SET
zParameter setting mode
zSetting write
Flicker
MODE
To 3.2.6 Operation mode
0 to 9 Press the key, to choose the MODE
parameter setting mode.
When appears
1) If the RUN indication is lit or flickering, stop operation by pressing the key or turning off the forward rotation (STF) or reverse rotation (STR) signal connected to the control terminal.
2) You cannot set any value that is outside the parameter setting range. Write a value within the setting range.
RUN STOP
RESET SET
×7 times or
×3 times
×9 times or
×1 times
"1" (PU operation mode) has been set in Pr. 79.
If the value and do not flicker but appears, you did not press the keySET
The operation mode change method which is shown below is only allowed when Pr. 79
"operation mode selection" is "0".
zPU operation
To 3.2.7 Help mode
MODE MODE MODE
PU
MODE SET REV STOP RESET FWD
zPU jog operation zExternal operation
PU EXT
Note: If the operation mode cannot be changed, refer to page 174.
3.2.7 Help mode
PU
To 3.2.3 Monitoring mode
zAlarm history
zAlarm history
clear zParameter clear
zAll clear
zSoftware version read
MODE MODE SET REV
STOP RESET FWD
EXT
3
Four past alarms can be displayed with the / key.
("." is appended to the most recent alarm.) When no alarm exists, E._ _0 is displayed.
SET
SET
When alarm occurs
zMost recent alarm
PU Hz
EXT PU EXT
A
PU EXT
Voltage
PU EXT
Energization time
Frequency Current
(2) Alarm history clear Clears all alarm history.
Cancel
SET
SET
Flicker
SET
1.5sec
Initializes the parameter values to the factory settings. The calibration values are not initialized.
(Parameter values are not cleared by setting "1" in Pr. 77 "parameter write disable selection")
Cancel
SET
SET
Flicker
SET
1.5sec
Note: 1. In the FR-E520-0.1K to 7.5K-NA and FR-E510W-0.1K to 0.75K-NA, Pr. 122
"communication check time interval" setting is "0". (Factory setting: 9999) 2. The Pr. 75 "reset selection/PU disconnection detection/PU stop selection"
value is not initialized.
(4) All clear
Initializes the parameter values and calibration values to the factory settings.
Cancel
SET
SET
Flicker
SET
1.5sec
Note: 1. In the FR-E520-0.1K to 7.5K-NA and FR-E510W-0.1K to 0.75K-NA, Pr. 122
"communication check time interval" setting is "0". (Factory setting: 9999) 2. The Pr. 75 "reset selection/PU disconnection detection/PU stop selection"
value is not initialized.
3