3.2 About the Control Panel

3.2.1 Names and functions of the control panel (FR-PA02- 02 )

Hz A PU

RUN MON EXT

Display LED 4 digits

Mode key MODE SET REV

STOP RESET FWD

Setting key

STOP RESET RUN

Hz A PU

RUN MON EXT

STOP/RESET key RUN key

Cover opened

Unit indication Operation status indication

STOP/RESET key Up/down keys Forward key

Reverse key

z Key indication

Key Description

RUN key Used to give a start rotation command.

MODE key You can select the operation mode or setting mode.

SET key You can determine the frequency and parameter setting.

/ key

z Used to increase or decrease the running frequency

consecutively. Hold down this key to change the frequency.

z Press this key in the setting mode to change the parameter setting consecutively.

FWD key Used to give a forward rotation command.

REV key Used to give a reverse rotation command.

STOP RESET key

z Used to stop operation.

z Used to reset the inverter when its output is stopped by the activated protective function.

z Unit indications, operating status indications

Indication Description

Hz Lit to indicate the frequency.

A Lit to indicate the current.

RUN Lit while the inverter is operating. Lit to indicate forward rotation, and flickers to indicate reverse rotation.

MON Lit in the monitor display mode.

PU Lit in the PU operation mode.

EXT Lit in the external operation mode.

3

zMonitoring mode zFrequency setting mode (Note)

zParameter setting mode

MODE SET REV STOP RESET FWD

Hz

PU MON

EXT PU

Hz

PU

MODE SET REV STOP RESET FWD

MODE SET REV STOP RESET FWD

zOperating mode

PU

MODE SET REV STOP RESET FWD

zHelp mode

PU EXT

MODE SET REV STOP RESET FWD

MODE MODE

MODE

MODE

MODE

(Note) The frequency setting mode is displayed only in the PU operation mode.

3.2.3 Monitoring

y Operation command indications given while a monitor display is being provided EXT is lit to indicate external operation.

PU is lit to indicate PU operation.

Both EXT and PU are lit to indicate combined operation.

y The monitor display can also be changed during operation.

zFrequency monitor

zAlarm monitor

Alarm absent

SET SET

*2

To 3.2.4 Frequency setting mode (Note3)

SET MODE

*1

SET Hz

MON EXT PU

MODE SET REV STOP RESET FWD

Alarm present

SET

zVoltage monitor

*1

SET PU

MON EXT zCurrent monitor

*1

SET PU

MON EXT A

SET

Note: 1. Hold down the SET key marked *1 for more than 1.5 seconds to change the

In the PU operation mode, set the frequency value used for operation performed under the operation command given by the RUN key ( FWD or REV key).

This mode is displayed only in PU operation.

To 3.2.5 Parameter setting mode

MODE

Hz PU

MODE SET REV STOP RESET FWD

zFrequency setting mode zSet frequency changing

SET

To frequency monitoring

MODE

Hz

PU zSet frequency write

Flicker

Hz

PU Hz

PU

Change the set frequency with

3.2.5 Parameter setting method

With the exception of some parameters, parameter setting can be made only when the PU operation mode is selected by the Pr. 79 setting.

y A parameter value may either be set by updating its parameter number or setting the value digit-by-digit using the / key.

y To write the setting, change it and press the SET key for about 1.5 seconds.

Note: If parameter write cannot be performed, refer to page 174. 3

from "2" (external operation mode) to "1" (PU operation mode)

(For details of Pr. 79, refer to page 109.)

SET

zCurrent setting zSetting change

Press for 1.5 sec.

SET

Middle digit flickers Most significant

digit flickers

SET

Least significant digit flickers

0 to 9

PU

MODE SET REV STOP RESET FWD

SET

zParameter setting mode

zSetting write

Flicker

MODE

To 3.2.6 Operation mode

0 to 9 Press the key, to choose the MODE

parameter setting mode.

When appears

1) If the RUN indication is lit or flickering, stop operation by pressing the key or turning off the forward rotation (STF) or reverse rotation (STR) signal connected to the control terminal.

2) You cannot set any value that is outside the parameter setting range. Write a value within the setting range.

RUN STOP

RESET SET

×7 times or

×3 times

×9 times or

×1 times

"1" (PU operation mode) has been set in Pr. 79.

If the value and do not flicker but appears, you did not press the keySET

The operation mode change method which is shown below is only allowed when Pr. 79

"operation mode selection" is "0".

zPU operation

To 3.2.7 Help mode

MODE MODE MODE

PU

MODE SET REV STOP RESET FWD

zPU jog operation zExternal operation

PU EXT

Note: If the operation mode cannot be changed, refer to page 174.

3.2.7 Help mode

PU

To 3.2.3 Monitoring mode

zAlarm history

zAlarm history

clear zParameter clear

zAll clear

zSoftware version read

MODE MODE SET REV

STOP RESET FWD

EXT

3

Four past alarms can be displayed with the / key.

("." is appended to the most recent alarm.) When no alarm exists, E._ _0 is displayed.

SET

SET

When alarm occurs

zMost recent alarm

PU Hz

EXT PU EXT

A

PU EXT

Voltage

PU EXT

Energization time

Frequency Current

(2) Alarm history clear Clears all alarm history.

Cancel

SET

SET

Flicker

SET

1.5sec

Initializes the parameter values to the factory settings. The calibration values are not initialized.

(Parameter values are not cleared by setting "1" in Pr. 77 "parameter write disable selection")

Cancel

SET

SET

Flicker

SET

1.5sec

Note: 1. In the FR-E520-0.1K to 7.5K-NA and FR-E510W-0.1K to 0.75K-NA, Pr. 122

"communication check time interval" setting is "0". (Factory setting: 9999) 2. The Pr. 75 "reset selection/PU disconnection detection/PU stop selection"

value is not initialized.

(4) All clear

Initializes the parameter values and calibration values to the factory settings.

Cancel

SET

SET

Flicker

SET

1.5sec

Note: 1. In the FR-E520-0.1K to 7.5K-NA and FR-E510W-0.1K to 0.75K-NA, Pr. 122

"communication check time interval" setting is "0". (Factory setting: 9999) 2. The Pr. 75 "reset selection/PU disconnection detection/PU stop selection"

value is not initialized.

3