To put this issue to the test, we submerged a sample of AirES cable in a water solution with a dye tracer.. For the test we needed a control sample as well and used a competitors cable w
Trang 1This white paper will focus on issues
related to moisture and its effects on
UTP Plenum cabling solutions For the
purpose of argument we will be looking
beyond standards and testing for issues
that, quite frankly, should never happen
under normal circumstances However,
as many of us who have been in the
industry for a number of years realize,
sometimes the unlikely becomes reality!
The industry bodies have this to say about wet and
dry locations:
BICSI TDM manual, 9th edition, Chapter 4 –
Horizontal Distribution Systems, Section 1 –
Horizontal Pathway Systems, final paragraph of page
4-5, which states:
Wet Locations
Intrabuilding horizontal pathways shall be installed
in "dry" locations that protect cables from
mois-ture levels that are beyond the intended operating
range of "inside" premises cables For example,
slab-on-grade construction where pathways are
installed underground or in concrete slabs that are
in direct contact with soil (e.g., sand, gravel, etc.)
are considered to be "wet locations." In the
United States, see the NEC, Article 100, for
defini-tions of damp, dry and wet locadefini-tions.
NEC Article 100 – Definitions
Locations:
Damp locations: Partially protected locations under canopies, marquees, roofed open porches, and like locations, and interior locations subject to moderate degrees of moisture, such as some basements, some barns, and some cold-storage warehouses.
Dry Locations: A location not normally subject to dampness or wetness A location classified as dry may be temporarily subject to dampness or wetness,
as in the case of a building under construction Wet Locations: Installations underground or in concrete slabs or masonry in direct contact with the earth or other liquids, such as vehicle washing areas, and locations exposed to weather and unprotected.
The above being said, let's have some fun.
The AirES cabling innovation incorporates air pockets around the primary conductor They run the entire length of the cable (a bit like rifling) These air pock-ets allow AirES to achieve unparalleled electrical per-formance to overall size This perper-formance is achieved through mixing the dielectric constant of Air and FEP together to make an overall dielectric constant better than that of FEP alone (for more information please see our "Electrical Attributes" white paper on this subject) It is worth noting the dielectric constant of water is terrible when com-pared with most insulation materials Additionally, as many people know, mixing amperage with water is never a good idea For this reason BICSI and the NEC have mandated that UTP cabling be placed in
"dry" locations
The Effect of Moisture Ingress
on AirES™
Cable
Trang 2However we have decided to test how AirES would perform in a "wet" environment Because of Krone's ingen-ious use of air pockets to improve electrical performance, a query has arisen with regards to moisture traveling down the air channels themselves
To put this issue to the test, we submerged a sample of AirES cable in a water solution with a dye tracer For the test we needed a control sample as well and used a competitors cable with solid FEP insulation over the copper conductor As in the image below, both cables were cut to the same length The same amount of solution (5ml) was used for each
We then placed both samples (Green AirES and White Competitor) into the solution for a period of 2 hours It's worth noting that the fluid level in the AirES graduated cylinder with the cable sample was at 5.95ml The com-petitor sample fluid level was at 6.1ml This can be attributed to reduced displacement of fluid with AirES, because of the smaller OD/cross sectional area of the cable
Trang 3After soaking in the solution for 2 hours the cables were removed and the fluid levels were measured to deter-mine how much had soaked into each cable
The competitor sample soaked in 0.15ml of fluid AirES soaked in 0.05ml of fluid
The reason for the fluid absorption difference was obvious once both samples were cut open In order to achieve Cat 6 performance a "star" filler has been used on the competitor cable to separate the pairs (which makes the cable larger) This allows for more "free space" within the cable Therefore, more fluid to be absorbed The AirES cable, by introducing air between the copper conductor and the insulation, has less need for pair separation This allows for the smaller cable size and less absorption
Trang 4The conductors were then inspected to see how much of the solution was absorbed by the conductors themselves.
Above are all 4 pairs of the competitor sample It would be fair to say that none of the solution absorbed was attributed to the conductors themselves No penetration was evident
Even though the amount of fluid absorbed by the airES cable was less, fluid did penetrate the air pockets within the insulation due to capillary action It flowed up to the level of the fluid within the cylinder
Trang 5This is most evident in the orange and green pairs, white conductor, with a color change to blue where the dye has penetrated
Although a fascinating result, it is actually quite meaningless in a real life installation This did, however, prove that the air pockets do exist
We then tested the cable as it is installed e.g with a jack attached A little bit of history about KRONE connectivity first One of our claims has been the 45° IDC With the use of this technology KRONE has been able to achieve
a gas tight seal around the contact and in doing so sealed the cabling conductor to that contact
In the example above, ribs (arrow 1) on either side of the connection point squeeze (hold) the insulation to take any disturbance through movement of the cable away from the contact itself These ribs also help to seal the insulation around the conductor The IDC, or Insulation Displacement Contact, does just that It displaces the FEP insulation around the connection point, which completely seals the junction from gas and/or water ingress
Trang 6To simulate what might happen if a KRONE jack with AirES cable were to be subjected to direct contact with water we submerged a terminated jack into the same water/dye tracer liquid as the first test In this test we let the cable soak for 14 hours This was 7 times longer than the first test
The results were astounding We rinsed the excess dye tracer off of the jack after removal from the liquid (as in the first test conductors) As you can see below, the label to the jack wiring scheme was completely tinted blue
from soaking None of the tracer was evident on any of the pairs The 45° IDC contacts had completely
stopped any penetration whatsoever
For the next part of our investigation we subjected AirES cable to a harsh humid environment and measured the effects To understand the effects, we used an industry standard construction Cat 6 cable with a star filler as a control
For the purpose of extreme conditions 70°C (158°F) at 95% rH were selected as the temperature and humidity The cables were placed into the environmental chamber for a period of 5 days Testing was conducted before the samples were placed in the chamber and one-hour after completion The results were then compared to show any effect the moist heat may have had on the electrical integrity
Trang 7Results for AirES Category 6 cable to TIA/EIA 568B.2.1:
Trang 9Although Attenuation, NEXT and Return Loss were effected slightly by the moist environment, the AirES cable tested passed Category 6 requirements
Trang 10The control sample was then tested in the same manner as the AirES sample.
Trang 13The results were very surprising As in our original
moisture ingress testing, using tracer dye, the control
sample seems to have "taken up" more moisture
during the humidity testing Both the Attenuation
and NEXT differences looked similar to that of AirES
The Return Loss, however, suffered greatly
We thank our competitor for sparking this
investiga-tion Through it we've found yet another advantage
to AirES Moisture ingress appears to be less through
hot humid environments, due to the reduced "free
air" space inside the cabling jacket This is evidenced
in the Return Loss results before and after humidity
testing on "Industry Standard" star filler design
Category 6 cable and that of cable integrating AirES
technology
Even though these were interesting experiments, it is important the user does NOT use this information as
a reason to install cabling in a wet or moist environ-ment! In short, water and networking don't mix With that said, it is worth noting the KRONE cabling solutions will attract less moisture, due to a reduced cabling size The connectors will block any moisture ingress on the conductors at the cable end
Please remember, we do not recommend running your computer while swimming, bathing or taking a shower If you must, please use wireless
KRONE™ Confidential Publication, not for reproduction without expressed written consent
Author: Tim Takala - Director, Support Technologies KRONE Inc