has performed numerous site surveys of end-user networks over the past year, and it has come to our attention that many users are upgrading to new 100Base-T switches that utilize the RJ-

Trang 1

Use of RJ-21 Connectors in 100Base-T

Active Connectivity

KRONE, Inc has performed numerous site surveys of end-user networks over the past year, and it has come to our attention that many users are upgrading to new 100Base-T switches that utilize the RJ-21 connector, also commonly known as a “Telco” connector, or “Amphenol” type It consists of

a 50 pin connector that accepts 25 pairs of cable simultaneously

KRONE has not been recommending this type of interface to our customers due to serious technical limitations of this connector, as described in this paper All versions of the RJ-21 that we have seen do not conform to the impedance matching requirements of KRONE’s TrueNetTM system, and consequently can seriously effect network performance

Figure 1 shows a TrueNet impedance matched

channel All components are matched for

optimum performance together, and the distance

plot shows a clean trace centered around a

nominal 100 ohms

Impedance matching of cabling and components

is critical for efficient data transmission

Research conducted by KRONE and Anixter

shows that mismatched systems can be

standards-compliant, and still allow frame error

rates approaching 25% of packets sent!

(source-Anixter)

Figure 2 shows the frequency trace of the channel

shown in Figure 1 The impedance stays tightly

controlled across the entire range of 100Base-T

operation, from approximately 1 to 125 Megahertz

These charts are displayed to show a baseline for the

comparisons that we will make to the RJ-21 interfaces

that we have seen in the field

Figure 1: A TrueNet Matched-Impedance Channel

RJ-21

Figure 2: Frequency Trace

of a TrueNet Channel

KRONE, Inc.

6950 S Tucson Way, Suite R

Englewood, Colorado 80112

1-800-775-5766

www.kroneamericas.com

www.truenet-system.com

Trang 2

Figure 3 shows a close-up of an RJ21

harness that was connected to a switch at

an actual user site The impedance spike

here is enormous—far greater than the 100

Ohms +/- 15 called out in the standard

(notice the orange and brown pair actually

fall to 60 ohms!)

When viewed in the frequency domain in

figure 4, we see wild oscillations in the

orange and brown pair, as we might have

predicted from the previous picture It is

these sorts of oscillations from mismatch that

have the potential to cause such high frame

error rates as previously noted

Figures 5 and 6 show the same type of

problem with a different RJ-21 assembly at

another site The effects of the mismatch on

the frequency trace are the same

The inherent problem with the RJ-21

connector is that it was never designed to run

data It is referred to as a “telco” connector

for good reason—it’s typically used for

telephone connections, not high frequency

data signals Several vendors claim to have

upgraded these connectors to Category 5

performance, but no one has reported

meeting the more stringent category 5e

standard, which is now the de-facto minimum

requirement for data (the TIA has dropped

Category 5 from the standard) Furthermore,

the 25 pair cables used in these assemblies is

not category 5e compliant either, nor has the

TIA established a standard for 25 pair cables

above category 5

Tempting as it may be to install this type of

infrastructure for its high density, KRONE

believes that the performance degradation is

not worth the convenience The high error

rates this sort of mismatch can cause

contributes to increased troubleshooting,

network drag, and possibly a shorter upgrade

cycle, as a loss of bandwidth due to errors saps

overall network capacity KRONE

recommends an impedance matched system

using RJ-45 connectors instead

Figure 3: An

RJ-21 Assembly

Figure 4: An

RJ-21 Assembly

Figure 5: An

RJ-21 Assembly

Figure 6: An

RJ-21 Assembly