Luận văn, Điện tử công suất, đề tài tốt nghiệp, đồ án, thực tập tốt nghiệp, đề tài
Trang 1Series Connected Power Flow Control using Magnetic Energy Recovery Switch (MERS)
Jan A Wiik*, F Danang Widjaya*, Takanori Isobe*, Tadayuki Kitahara*, and Ryuichi Shimada*
*Solution Research Organization, Tokyo Institute of Technology 2-12-1 O-okayama, Meguro, Tokyo 152-8550, Japan
Abstract—A new series connected power flow controller,
called the Magnetic Energy Recovery Switch, has been inves-
tigated It is characterized by four active switches and a dc-
capacitor in each phase The device is capable of injecting up
to rated voltage within the current rating It behaves similar
to a controllable voltage source and a variable capacitor
connected in series A control algorithm has been developed
in order to facilitate power flow control with these combined
characteristics Experimental results suggest the MERS to be
a promising new power flow controller
Index Terms— Flexible ac transmission systems, power elec-
tronics, power flow control, series compensation
I INTRODUCTION Interconnections in power systems are getting more and
more common Large interconnected power systems have
the advantage of being able to reduce the total needed
generation capacity, while maintaining a secure operation
of the power system At the same time, interconnections
allow power flows over long distances such that natural
resources far away from load centers can be utilized With
the growing installation of renewable energy resources and
the de-regulation of energy markets, transmission flows are
more and more often being pushed towards the transmission
capacity limits
Another growing challenge in this scenario is loop flows
With parallel lines going from supply area to demand area,
the power flow will entirely be according to the impedances
in the grid A lower impedance line is in such a scenario
likely to become overloaded [1] Additionally, in grids with
multiple owners, owners that are not beneficiaries of the
transaction may be injured by loss of use of part or all of
their transmission capacity [2]
Series compensation has been used in transmission sys-
tems for many years, both for increasing transmission
capacity and for controlling power flows The initial uses
were with fixed passive capacitors giving a constant capac-
itive reactance However, fixed series compensation is well
known to potentially give problems with sub-synchronous
resonance (SSR) This was clearly demonstrated at the Mo-
have power station with two turbine-generator shaft failures
in 1970 and 1971 [3] Additionally, fixed passive capacitors
do not give the opportunity to actively improve damping
after transients in the power system or to actively control
the power flow However, they are the most cost effective solution for reducing the equivalent line impedance Research in the area of Flexible AC Transmission Sys- tems (FACTS) led to the development of the Thyristor Controlled Series Capacitor (TCSC) and the first large scale prototype installed in the beginning of the nineties [4] The TCSC consists of a series capacitor with a Thyristor Controlled Reactor (TCR) in parallel By controlling the switching instance of the thyristors, the apparent reactance
of the device can be controlled The TCSC has been shown to be SSR neutral when being controlled in vernier mode [4] The TCSC can control the equivalent reactance, however the operating range is limited
The GTO thyristor-controlled series capacitor or gate commutated series capacitor (GCSC) was introduced in
1992 [5] It consists of two anti-parallel GTOs in parallel with a series capacitor By controlling the timing of the switches, the equivalent reactance can be decreased con- tinuously to zero, Meaning an increase in operating range compared to the TCSC Compared to the TCSC, a smaller capacitor is needed [6]
The Static Synchronous Series Compensator (SSSC) was introduced in the late nineties [7] It consists of a voltage source inverter and a coupling transformer injecting the series voltage into the grid It can provide controllable com- pensating voltage over an identical capacitive and inductive range, independently of the magnitude of the line current Compared to the GCSC, the operating range is significant larger However, due to probable cost reasons, this com- ponent is not widely used today Also a transformerless variation of the SSSC has been suggested, eliminating the bulky transformer used in the SSSC application [8] This paper introduces a new series FACTS device First,
an overview of the device and its characteristics is given Secondly, experimental results are presented with a follow- ing conclusion
Il MAGNETIC ENERGY RECOVERY SWITCH
A Configuration The configuration investigated in this paper is called
use of this switch for power factor correction has been
Trang 2Seeeescecedeoosesecas®
Pewee eeceneseeeeseeecasese?
Fig 1 Configuration of Magnetic Energy Recovery Switch
demonstrated for various loads [10], [11] In this paper
it is suggested to use the same configuration for series
compensation in power systems, however, with a different
control
The circuit configuration of the MERS is shown in Fig
1 It consists of 4 forced commutated switches (such as
GTOs), 4 diodes and a dc-capacitor For a three phase
circuit there will be one MERS per phase In principle,
the MERS configuration is the same as a single-phase full
bridge inverter, but the application and operation principle
differs Compared to a conventional single phase full bridge,
the capacitance of the dc-capacitor is several times smaller
and line frequency switching is used
B Operation Principle
The operation principle can be explained with illustra-
tions as shown in Fig 2 Fig 2(a) shows the case when
both switch S1 and S3 are on In this case the current will
flow as indicated by the main dotted line, as long as there is
a voltage across the capacitor The current will flow through
the diodes when the capacitor is charged and through the
active switches when being discharged For the case when
the dce-capacitor voltage becomes zero, the current will flow
in two parallel paths The same explanation applies for
Fig 2(b) Fig 2(c) shows the by-pass mode In this case
the injected series voltage can be zero even with voltage
remaining on the dc-capacitor
By using the described switching patterns, it is possible to
control the minimum dc-capacitor voltage and to control the
size of the zero voltage area The control is illustrated in Fig
3 The control of the minimum capacitor voltage, Vc min 18
achieved by entering the by-pass mode when the capacitor
voltage goes below Vo min In the by-pass mode, the series
injected voltage will be zero while the dc-capacitor voltage
will keep its value at Vomin The length of the by-pass
mode is adjusted with the phase lag control variable, +,
which has a zero reference when the current is 90 degrees
When the current phase passes the + set-point, a new pair
switching mode is entered (S1-S3 or S2-S4), and the dc-
capacitor voltage will again increase
Fig 2 Switching combination for the control of MERS
A special case can be achieved by controlling the Vo min
to zero For this case, the voltage across the capacitor will
be zero for parts of the period The control of the by-pass area will then directly result in the same operation as for the GCSC
C Series Voltage Characteristics and Harmonics The rms value of the injected series voltage, V, is given
by (1) All values are given in per unit and a sinusoidal current is assumed The voltage consists of a distortion component, Vpisr, and a first harmonic component, Vj
It can be found that the expressions have been divided by
the square of the current, /* By doing this, the expressions
on the right are simplified and only depends on two vari- ables, the minimum capacitor voltage related to the current, Vo.min/I, and the phase lag, y (Capacitor reactance, Xo,
is constant)
The equation of the MERS reactance, X,\erg, is given
Trang 312
© œ
© +
oO
Ă
œ
3
£
©
>
5
> amen,
a
time (s) Fig 3 Ilustration of minimum de-capacitor voltage and phase lag control
by (2) Again, the expressions on the right depends on the
same two variables, Vo min/{ and +
V” Verse , Ve 1 f** 4
T2 = T2 T2 = mp Umers (z)dz
Da sin 2+ + 4X⁄2cos +XcB]
(2)
AVo min Cosy
X mers(Pu)
Fig 4 Optimal combination of minimum capacitor voltage reference and phase lag for relative voltage injection sizes
Ww way
oO NA
= 10F iat 7
BE 0 1
Current (pu) Fig 5 The harmonic distortion for various currents with rated series voltage applied
From (2) it can be found that + directly translates to an equivalent reactance, X.,, and that Vomin translates to a series voltage Vsprips(with a dependency also on y) Due
to this, the MERS can be said to have similar characteristics
to a voltage source and a capacitor connected in series For a given MERS reactance, Xyyers, various combina- tions of Vo min/J and y will be solutions to (2) The optimal combination, seen from a voltage distortion point of view, can be found by using both (1) and (2), and minimizing the Viftsr/12 Due to the relative complexity of the equations, a numerical approach was used to find the optimal parameter combinations The benefit of dividing the expression in (1) with the square of the current is now a more simple optimization with two variables instead of three The results, with Xc equal one, are shown in Fig 4
The harmonic distortion has been calculated for various currents with the series voltage, V1, set equal to one (Fig 5) One line shows the distortion with optimized Vo min/I and -y combinations, and the other shows the case with + equal zero The reduction in harmonic distortion by using optimized combinations is clear, especially for low currents The size of the distortion in the series voltage is shown with contour lines in Fig 6 for the whole operating range
Trang 4
Current (pu)
Fig 6 Harmonic distortion contour lines for the whole voltage-current
operating range
Primary control
|
|
| Ve min,ret RO
Fig 7 Illustration of the primary control system for the MERS in a
3-phase system
By limiting the maximum allowable series voltage for low
currents, the maximum distortion can be reduced With a
limit set to 15% distortion, the rating area is reduced with
approximately 15%
D Primary Control
The basic operation principle was described in section
II-B and consists of controlling the minimum capacitor
voltage and the phase lag The basic task of the primary
control system is to perform this control with given Vo min
and 7 set-points in a three phase system (Fig 7) The
gate logic block performs this action by using current
phase information, performing dc-capacitor voltage check
in defined phase periods, and change from by-pass to next
pair switching mode when current phase passes the + set-
point
Accurate current phase information is important for such
an application and is calculated with a phase locked loop
(PLL) The PLL implementation has been based on a dq-
transform type configuration [12], and was tuned such that
View With limited
4°
order
LP filter
Fig 8 Block diagram of phase lag limiter
phase lock could be achieved for a large range of current magnitudes The dq-transform PLL uses a feedback loop
to control the d-axis current to zero This means that when phase-lock is achieved the q-current will be a good estimation of the rms value of the current
Another important task for the primary control system is
to make sure that the voltage limits of the devices are not violated An example of a potential voltage limit violation is when rated voltage is injected at low current and the current suddenly increases If constant y and Vo min references are kept, the voltage might exceed the rating of the device In
order to avoid this, quick control action is performed in the
phase lag limiter block (Fig 8)
The phase lag limiter uses a feedback control structure, where the voltage peak across the capacitor is estimated and the deviation between the estimated and the limitation
voltage, Vuimit, is fed into a PI controller The resulting reactance set-point, X.,, is filtered and used in the voltage
peak estimation The limited reactance set-point always
chooses the minimum between the actual set-point, Xy rer,
and the limitation control set-point, X j;m Together with
logic for avoiding integral wind up, a smooth transition from normal mode to limitation mode and back can be achieved With the use of a look-up table, the resulting reactance set- point can be translated to a +y set-point
The first part of the primary control is the translation of
an input variable, Us, to X- and Vo min Set-points This is performed such that the reactance first is linearly increased, with the Vomin being zero, and after rated reactance has been reached, Vo min is linearly increased and 7 is adjusted
to reduce the harmonic content (Fig 9) The reason this translation is performed is to simplify the implementation
of the secondary control system Alternatively, the look-up
table can be skipped and y and Vo min set-points can be
generated directly from the secondary control system
Il] EXPERIMENTAL SETUP
In order to investigate the performance and stability of the proposed configuration, some experiments were conducted The configuration of the experimental setup is shown in
Trang 5
¬
3 | 3
a =<
£ i £
1 a =
=
oO L 4
>
Control set-point, Uset (—)
Fig 9 Lookup table for converting Uset to y and Vo min
3*MERS
Inductor
MERS
` *eesesee=e=e=es=se=“=s=ss=s=6se=ss=e=se=sse=s=se=se6sa6sse=se=6ss=s=6s=ss6=se=6ss=s==ee“
Fig 10 ¬ 8 Illustration of experimental setup
Fig 10 and with picture in Fig 11 It consists of a
controllable 3-phase ac power supply, which can control the
applied voltage with good response The MERS, a Y — A
transformer and inductors are connected in series to form
a loop The transformer connection shifts the voltage 30
degrees, meaning that power will automatically flow in the
circuit when voltage is applied In result, the equivalent of
the configuration is as shown in the lower part of Fig 10,
meaning a good representation of a transmission line
The specifications of the experimental circuit are given in
Table I The leakage inductance of the transformer and the
resistance of the transformer and inductor is negligible com-
— - BF
›@wxEX —
Fig 11 Picture of experimental setup
pared to the inductor reactance and has not been included in the specification Virtual rating means a MERS rating set in proportion to the other parts of the experimental setup The actual voltage rating of the MERS device is substantially higher
The control system was implemented using SH7045 microcontroller and was implemented as described in sec- tion II-D The control algorithm was performed 512 times every 50 Hz cycle Monitoring and giving set-points were performed from a desktop pc
IV EXPERIMENTAL RESULTS
A Response During Set-point Changes to Primary Control The set-point to the primary control, U , was varied in steps in order to investigate the response The power supply voltage was set constant to 60V during the test Fig 12 shows the case when a step was applied to U;.¢ from 0.6 to 0.75 The main observation is that the minimum capacitor
Trang 6TABLE I SPECIFICATIONS OF EXPERIMENTAL CIRCUIT FOR POWER FLOW
CONTROL
Transformer power rating 3000 VA
Transformer rated excitation current 0.325 A
Virtual MERS voltage rating, ViwERS,N 40V
| ƠI oO
.04 S)
0 (
time Fig 12 Response during Use, set-point change from 0.6 to 0.75
voltage, Vomin, is controlled to a new value very rapidly
However, the by-pass period is longer immediately after the
VG min increase is performed, due to faster entry into the
by-pass mode while keeping constant + This means that
the series injected voltage will be smaller for the given half
cycle, initially reducing the current amplitude a few percent
A set-point point change from 0.3 to 0.45 is shown in
Fig 13 For Use, lower than 0.5, the Vomin reference is
zero The resulting step in phase lag reference can be seen
to quickly be adjusted There is no reduction in current after
the step change as could be seen when Vo min was larger
than zero The length of the bypass period uses two cycle to
stabilize When the current increases, the bypass period will
be longer than the set-point due to the decrease of capacitor
voltage being faster than the increase
B Phase Lag Limitation
A limitation control, as shown in Fig 8, was implemented
in the microcontroller The parameters used in the control
are given in Table II The gain is related to a per unit
peak voltage estimation The tuning of the parameters was
performed with the simulator called PSIM, and then applied
to the experiment
20
10
I nN ©
Fig 13 Response during Use, set-point change from 0.3 to 0.45
TABLE II PARAMETERS USED FOR PHASE LAG LIMITATION TEST
Limitation voltage, Vi imit V2VMERS,N
Integral time constant, 7} 0.01 Reactance feedback filter constant, Tp 0.005
A step in input voltage from 87 V to 156 V was applied while keeping a fixed U4 equal 0.71 The results are shown
in Fig 14 The R-phase input voltage is shown in top of the plot The response of the voltage increase is limited by the power supply, with a steady state reached after a bit more than 2 cycles The three MERS capacitor voltages are plotted for both the case with and without limitation control For the case without control, the voltage quickly passes the voltage limit By using the limitation control, the maximum voltage can be kept close to the limit The peaks of the capacitor voltages for the two cases are compared in the lower plot The test indicates that the limitation control is effective at avoiding over-voltages
C Steady State Current Flow Control
The relationship between the loop current flow and the primary control set-point, Use, was investigated for three different power supply voltages The test was performed by applying different U,., and recording the rms value of the series injected voltage and the current
The results are shown in Fig 15 The current is, as expected, increasing for increasing set-points The current increase characteristic is different in the reactance control area and the Vo min control area An irregular shape can
be seen when entering the Vo.min control area This is due
to rather quick reduction in reactance set-point when first
Trang 7
N ro) oO
Nh oO Oo
/) oO oO
S100
— V
0
time (S)
Fig 14 Phase lag limitation control
increasing the Vo.min set-point The irregular characteristic
is more significant for higher power supply voltages, which
is natural since reactance reduction is more visible when the
current is higher To improve the power flow characteristic,
it is possible to change the speed of the reactance decrease
when entering the Vo min area
For high U,.¢ set-points, the voltage is limited The
limitation control limits the peak voltage This means that
various rms voltages can be found for the same peak voltage
depending on the Vc min and reactance set-point This is the
reason the rms voltages in Fig 15 not has a fixed maximum
voltage
D Current Feedback Control
In order to test a simple secondary control system with
the given primary control, a current flow control loop was
implemented as illustrated in Fig 16 The q-axis current
calculated in primary control PLL algorithm was used as a
current measurement The control parameters were adjusted
T
| 40V
5 L @ 30 V is ° s
> 20Ƒ oye? 1
œ L ‡ a 3 > : ye ee * © +
i Aa A Aa a
š oo ¢ ¢@ °
< a a + °
cL at 0? 2° ^60V
= oe, & c7 e
O ee ® °° M
Uset (-)
Fig 15 Current flow and injected series voltage for various Uset set- points and three different power supply voltages
+
Iset
U PID -
Iq
Fig 16 Block diagram of curren flow feedback control
based on Ziegler-Nichols method The maximum gain was found to be more restricted for high Vo min than for low The slope of the U,.¢ - current curve in Fig 15 changes dependent on the voltage between the two line ends and the size of the U,.4 This also indicates dependency between maximum gain and operating point The parameters used are given in Table III, assuming per unit input and output values
A step was applied in current reference from 0.24 to 0.63pu The response in R-phase capacitor voltage and R- phase current are shown in Fig 17 The current reaches
a steady state value after approximately 0.3 seconds A smaller current step is shown in Fig 17 For this case, the response is slower and illustrates the difference in response when being in different operating area In order
to improve the response, gain scheduling could be used, with changing control parameters depending on operating point In summary, stable response of the current feedback control could be demonstrated
V CONCLUSION The characteristics of a new power flow controller, the Magnetic Energy Recovery Switch(MERS), have been in-
Trang 8TABLE III PARAMETERS USED FOR CURRENT FLOW FEEDBACK CONTROL
Proportional gain, P 0.32
Integral time constant, ‘Tj 0.03
Derivative time constant, Tq 0.0074
= |
= -
= 20
= oll |
a 0 HN k | Ht TT rrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrr - —]
— 2b
-4 l 1 1 1 1 L 1 1 1 1 L 1
time (s) Fig 17 Current flow control when applying step in current reference
from 0.24 to 0.63pu
vestigated The device is capable of injecting up to rated
voltage within the current rating The device has found to be
similar to a voltage source and a capacitor in series, with the
possibility of both controlling the equivalent reactance and
the series voltage A control algorithm has been developed
in order to facilitate power flow control with these combined
characteristics The control has been optimized in order to
reduce injection of voltage harmonics
Experiments have been conducted in order to demonstrate
the characteristics of the MERS The challenge of injecting
rated voltage at lower currents has been addressed, and a
control method for avoiding overvoltage has been success-
fully demonstrated Also, steady state and step-response
current control experiments suggests that the MERS is a
promising new power flow controller
REFERENCES
[1] N G Hingorani and L Gyugyi, Understanding FACTS, Concepts
and Technology of Flexible AC Transmission Systems JTEEE Press,
1999
[2] J M Miller, B M Balmat, K N Morris, J H Malinowski, B M
Pastemack, and L E Eilts, “Operating problems with parallel flows,”
IEEE Trans on Power Systems, vol 6, pp 1024-1034, 1991
[3] M C Hall and D A Hodges, “Experience with 500kv subsyn-
chronous resonance and resulting turbine generator shaft damage at
mohave generating station,’ IEEE Publication 76 CHIO66-0-PWR,
pp 22-29, 1976
E
£
‘Oo |
O 1 1 1 l L L
' ' ' Ỉ ' ' ' ' Ĩ ' ' ' ' Ĩ
2L
= 5 0 | | |
c3 -
time (S) Fig 18 Current flow control when applying step in current reference from 0.24 to 0.39pu
[4] R J Piwko, C A Wegner, S J Kinney, and J D Eden, “Subsyn-
chronous resonance performance tests of the slatt thyristor-controlled
series capacitor,’ IEEE Trans on Power Delivery, vol 11, 1996 [5] G G Karady, T H Ortmeyer, B R Pilvelait, and D Maratukulam,
“Continuously regulated series capacitor,’ JEEF Trans on Power
Delivery, vol 8, no 3, 1993
[6] L F W de Souza, E H Watanabe, J E R Alves, and L A S
Pilotto, “Thyristor and gate controlled series capacitors: comparison
of components rating,” Power engineering society general meeting,
2003, IEEE, vol 4, 2003
[7] L Gyugyi, C D Schauder, and K K Sen, “Static synchronous compensator: a solid state approach to the series compensation of
transmission lines,” IEEE Trans on Power Delivery, vol 12, no 1,
January 1997
[8] H Stemmler and A Beer, “Transformerless reactive series compen- sators with voltage source inverters,’ PCC-Nagaoka’97, 1997 [9] K Shimada, T Takaku, T Matsukawa, and R Shimada, “Bi-
directional current switch with snubber regeneration using p-
mosfets,” Proc International Power Electronics Conference, no 4,
pp 102-103, April 2000
[10] J Narushima, K Inoue, T Takaku, T Isobe, T Kitahara, and
R Shimada, “Application of magnetic energy recovery switch for
power factor correction,’ IPEC 2005
[11] J Wiik, T Isobe, T Takaku, T Kitahara, and R Shimada, “Appli-
cation of series connected current control switches for power factor
correction,” PCIM Europe, 2006
[12] S.-K Chung, “Phase-locked loop for grid-connected three-phase power conversion systems,” JFE Proc.-Electr Power Appl, vol 147,
pp 213-219, 2000