The unit transformer in a generating station nects the electric power output of the generating unit to the high-voltage electric transmission gridi the unit auxiliaries transformer, stat
Trang 1Power nansformers
Written by Stone & Webster Engineering Corporation
Trang 2For further information on EPRI's technical grams contact the EPRI Thchnical Information Divi- sion at (415) 855-2411, or write directly to EPRI's Thchnical Information Center at P.O Box 10412, Palo Alto, CA 94303
Taps and connections
Station auxiliary systems
Installation and maintenance
Voltage regulation
Copyright© 1987 Electric Power Research Institute, Inc All rights reserved
Reprinted in 1998 by Energy Conversion Division,
Steam-Turbine, Generator, Balance-of-Plant Target
Electric Power Research Institute and EPRI are registered service marks of Electric Power Research Institute, Inc Notice
This series was prepared by Stone & Webster Engineering Corporation as an account of work sponsored by the Elec- tric Power Research Institute, Inc (EPRI) Neither EPRI, members of EPRI, Stone &, Webster Engineering Corpora- tion, nor any person acting on behalf of any of them: (a) makes any warranty, express or implied, with respect to the use of any information, apparatus, method, or process disclosed in this series or that such use may not infringe privately owned rights, or (b) assumes any liabilities with respect to the use of, or for damages resulting from the use of, any information, apparatus, method, or process dis- closed in this series
Trang 3In the past, several electrical equipment
manufac-turers published reference books dealing with
specific technical areas Many utilities have stated
that these reference books have been very useful
to them in dealing with plant emergencies and in
making decisions on design, system planning, and
preventive maintenance
Unfortunately, manufacturers today seldom
publish or update reference books on electric
power apparatus, mainly because of tighter
bud-get constraints Until now, utilities have had no
up-to-date industrywide practical reference manual
covering the various electric power apparatus and
electrical phenomena commonly encountered in
power plants The Power Plant Electrical
Refer-ence Series was planned to fill this need
EPRI believes that the series will save utilities
time and money It will aid plant engineers in
• Prevention of forced outages through proper
installation, application, and protection of
station auxiliary equipment
• Recognition of potential problems and their
prevention
• Selection of appropriate methods of
main-tenance to ensure trouble-free equipment
This volume deals with power transformers A
power transformer connects the generator to the
high-voltage transmission system Another power
transformer connects the generator to the plant
medium-voltage auxiliary power system
'Irans-former impedance is the major factor in the
volt-age regulation of the auxiliary power system, as
well as in the short-circuit duty of the switchgear
Selection of transformers for use in power stations
requires knowledge of the power system and
var-ious parameters
A wealth of information about transformers is
available in the transactions of the IEEE and in the
ANSI/IEEE standards and applications guides EPRI has also published a great deal of information on transformers, including studies of transformer life characteristics (EL-2622), dielectrics, accessories, and monitoring equipment The purpose of this book is
to bring out the concepts that are most useful to power plant personnel, without requiring an under-standing of the rigorous engineering analysis necessary for the basic design transformers
D K Sharma
Electrical Systems Division Electric Power Research Institute
Trang 5The unit transformer in a generating station nects the electric power output of the generating unit to the high-voltage electric transmission gridi the unit auxiliaries transformer, station service transformer, and secondary-unit substation trans-formers supply the electric auxiliaries required for operation of the power plant In the lower range
con-of sizes, power transformers may be con-of standard design types, but many of the transformers used
in power plants and all of the larger ones are custom-designed-similar, but seldom identical, to others built previously This volume covers the practical aspects of the selection, specification, in-stallation, operation, testing, and maintenance of these power transformers
lransformer designs of particular interest to power plant operators include liquid-immersed, dry-type, and vapor-cooled transformers ranging
in size from 500 kVA to 1200 MVA The function and application of each design are described in detail, from load considerations to noise criteria Photographs show the various types of oil-preservation systems, transformer connections, and bushings A variety of gages, monitors, and indicators may be provided for liquid-immersed transformersi these accessories are also discussed
Trang 7The authors wish to acknowledge the help they received from many technical publications pre-pared by people in the industry They also express their appreciation to the following people for their reviews, suggestions, and guidance in general
Electric Power Research Institute
D K Sharma, Project Manager
R Steiner, Associate Director, Electrical Systems Division
J C White, Program Manager
G Addis, Project Manager
Stone & Webster Engineering
EPRI Review Committee
J R Boyle, Thnnessee Valley Authority
L E Brothers, Southern Company Services
J Erlingsson, Pacific Gas and Electric Company
R G Farmer, Arizona Public Service Company
R G Hodgson, Los Angeles Department of Water
& Power
J A Maxwell, Georgia Power Company
W L Nail, Jr., Mississippi Power& Light Company
D G Owen, Duke Power Company
B K Patel, Southern Company Services
R A Schaefer, Public Service Company of Oklahoma
J E Stoner, Jr., Duke Power Company
D M Van Thssell, Jr., Florida Power& Light Company
J E White, Thmpa Electric Company
The authors owe special thanks to W J McNutt, General Electric Company, member of the Trans-formers Committee of IEEE, who reviewed the final manuscript
Trang 9Application of Loss Values 2·8
2.8 Oil Preservation Systems 2-8
Sealed.:nmk System 2-8
Inert Gas System 2-9
Modified Conservator System 2-9
2.10 Taps 2-14 No-Load Thp Changers 2-14 Load Thp Changers (LTCs) 2-14
2.11 Bushings 2-15
2.12 Accessories 2-18 Liquid Level Gage 2-18 Thmperature Indicators 2-18 Flow Indicator 2-20 Bushing Current 'Iransformers 2-20 Resistance Thmperature
Detectors 2-20 Sudden Pressure Relay 2-20 Gas Detector Relay 2-21 Fault Gas Monitor 2 21 Pressure Relief Device 2 21 Lifting Eyes and Jack Bosses 2-·22-Lightning Arresters 2-22-
2.13 Application Considerations 2 22-Maximum Sustained Load 2 2-2-Altitude 2-25 Ambient Thmperature 2 25 Number of Windings 2-2-5 Voltage Ratings and
Overexcitation 2 25 'Iransient Overvoltage 2·26 Load Current Waveform 2-26 Harmonic Current Derating 2-27 Impedance Voltage and
Regulation 2-28 Impedance and Through-Faults 2-29 Phasing Out Three-Phase
Circuits 2-29 Loss Evaluation 2-30 Noise Criteria 2-30
2.14 Shipping Considerations 2-32
Trang 10Shop Thsting 2-48 Field Thsting 2-49
Trang 11FIGURE PAGE
Oil Preservation System 2·9
2-2 Transformer With Inert Gas Oil
Preservation System 2·10
2-3 Transformer With Modified
Con-servator Oil Preservation System 2-11
2-4 Transformer Terminal Designation
in Accordance With ANSI Standard
C57.12.70-1978 2·12
2-5 Typical Transformer Phase
Relationships , 2-13
2-6 Power Transformer With LTC
2-7 Apparatus Bushing of the
Paper-Oil Capacitor (POC) Type 2·17
2-8 EVH Bushing 2·18
2-9 High-Current Type-A Bushing
25-kV, Class-4500 A and Above 2·19
Relay 2·21
2-15 General Guide for Permissible
Short-Time Overexcitation of
Power Transformers (Rated Volts
per Hertz = 100% Excitation) 2·26
Measure-merits of Large General Electric
Power Transformers (Early 1970s) 2·31
Steam Turbine Generator Unit 2·34
Trang 15Power transformers are used in generating
sta-tions to connect the main generator to the
high-voltage transmission system and to connect
sources of electric power to distribution
sub-systems for operation of plant auxiliary electrical
equipment at medium- and low-voltage levels The
proper selection of transformers for each
appli-cation requires a knowledge of the types available
and their range of applicability It also requires a
knowledge of terms, conventions, tolerances, and
factory tests as established in industry standards
Background
Power plant electrical equipment operating at ac
voltages of 120, 460, 575, 4000, 6600, or 13,200 V
receives its power from higher-voltage sources: the
main generator and the switchyard 'fransformers,
which are located near the load (where possible),
interconnect the voltage levels Although the
smaller sizes of power transformers may be of
standard design types, the larger ones are
custom-designed and similar, but seldom identical, to
others This book provides practical guidance in
the selection of this equipment
Objectives
This volume will provide power station engineers
with a background of transformer knowledge that
will enable them to apply transformers correctly,
assist in understanding existing standards and the
various options required for power transformer
se-lection, and provide guidance to power plant
per-sonnel in planning inspection and testing programs
Approach
A national survey of utility requirements yielded
pertinent information, and a search of available
literature on power transformers identified
spe-cific information pertaining to power plant
applications The EPRI Review Committee, with
members from 11 utilities throughout the United
States, and other industry experts reviewed the
material for accuracy and completeness The
resulting information was the basis for this volume
of the Power Plant Electrical Reference Series
Trang 17Spe-ABBREVIATIONS
AA transformer cooling method: ventilated
ac alternating current
ANSI · American National Standards Institute
BIL basic lightning impulse insulation level
Btu British thermal unit(s)
CI present worth of outlay in the year of first
commercial operation (Eq A-1)
EHV extra-high voltage
f annual inflation rate (decimal) (Eq A-1)
FA transformer cooling method: oil immersed,
forced-air cooled
FOA transformer cooling method: oil immersed,
forced-oil cooled with forced-air cooler
FOB free on board
FOW transformer cooling method: forced-water
internal rate of return
internal rate of return expressed as a
decimal rather than as a percentage (Eq A-1)
number of years between the price year
and the year of tiTSt commercial operation
R resistance
REG transformer regulation RIV radio influence voltage rms root-mean-square SCR short-circuit ratio SST station service transformer UAT unit auxiliaries transformer
UT unit transformer
V volt(s)
Z transformer impedance voltage
Trang 19A W Goldman and C G Pebler
2.1 INTRODUCTION
Power-transformers are used in power plants to
connect the main generator to the high-voltage
(HV) transmission system and to connect sources
of auxiliary power to distribution subsystems for
plant auxiliary electrical equipment at lower
volt-age levels Since they are basically static devices,
they require less maintenance than most of the
other apparatus It is important, however, (1) that
each transformer be selected properly for the
in-tended application; (2) that it be protected from
voltage surges, external short circuits, and
prolonged overload; and (3) that it be inspected,
maintained, and tested on a routine basis
The power transformers of particular interest
to the designers and operators of power plants
range in size from 500 kVA to 1200 MVA in
three-phase designs and from 500 kVA to 550 MVA in
single-phase designs 'fransformers installed inside
a building may be dry-type, resin encapsulated,
or liquid immersed in high-fire point or low-heat
release insulating fluids 'fransformers installed
outdoors are generally mineral oil immersed
In the lower size range the transformers may
be of repetitive design, but many of the
transform-ers used in power plants and all of the larger ones
are custom designed-similar, but seldom
identi-cal, to others built previously
'fransformer power and energy losses, though
relatively small, are of interest to the user for two
reasons: They cause increased fuel consumption,
and they result in heat release The fuel consumed
in generating the loss of energy is an important
item in operating cost The heat must be removed
and dissipated by some combination of
conduc-tion, convecconduc-tion, and radiation "Self-cooled"
trans-formers do not require any power-driven cooling
auxiliaries Forced-cooled transformers employ
forced-water or forced-air cooling and may also
use pumps to circulate the insulating fluid The
addition of rotating machinery to an otherwise
static device reduces the physical size and initial
cost of the transformer for a specific output
rating, but it may also reduce reliability and
in-crease maintenance cost and losses
Oil-immersed transformers require oil
preser-vation systems to exclude oxygen and water vapor;
this retards sludging and deterioration of tric properties Gas formation under oil may indi-cate local hot spots or decomposition of solid insulating materials For this reason gas monitors are often installed to detect and collect generated gases for laboratory analysis 'fransformer oil should be sampled and tested at regular intervals The analysis of both the collected gas and the oil samples provides warning of abnormal conditions Power transformers are factory tested to ensure quality of design and manufacture and to demon-strate their ability to meet performance require-ments Data obtained during such tests may also provide benchmarks for later field tests
dielec-A large transformer may be damaged by proper handling during loading, shipment, on-site storage, testing, or installation These operations warrant meticulous attention
im-The application of the above material to unit transformers (U'Th), unit auxiliaries transformers (UA'Th), station service transformers (SS'Th), and secondary unit substation transformers is covered under appropriate headings in this volume
2.2 DEFINITION OF TERMS
Basic lightning impulse insulation level (BIL) A specific insulation level, expressed in kilovolts, of the crest value of a standard lightning impulse
Basic switching impulse insulation level A specific insulation level, expressed in kilovolts, of the crest value of a standard switching impulse
Chopped-wave impulse A voltage impulse that is terminated intentionally by sparkover of a gap Decibel (dB) See Sound pressure level
Demand factor The ratio of the maximum demand
of a system to the total connected load of the system Diversity factor The ratio of the sum of the individ- ual maximum demands of the various subdivisions of
a system to the maximum demand of the whole system Eddy-current loss Power dissipated due to eddy cur- rents This includes the eddy-current losses of the core, windings, case, and associated hardware
Front-of-wave lightning impulse test A voltage impulse with a specified rate of rise that is terminated intentionally by sparkover of a gap that occurs on the
Trang 20rising front of the voltage wave with a specified time
to sparkover and a minimum crest voltage Complete
front-of-wave tests involve application of the following
sequence of impulse waves: (1) one reduced full wave;
(2) two front of waves; (3) two chopped waves; (4) one
full wave
Graded insulation The selective arrangement of the
insulation components of a composite insulation system
to equalize more nearly the voltage stresses
through-ou! the insulation system
Harmonic factor The ratio of the root-mean-square
(rms) value of all the harmonics to the rms value of the
Hot spot temperature The highest temperature
in-side the transformer winding It is greater than the
aver-age temperature (measured using the resistance change
method) of the coil conductors
Hysteresis loss The energy loss in magnetic material
that results from an alternating magnetic field as the
elementary magnets within the material seek to align
themselves with the reversing magnetic field
Impedance voltage The voltage required to circulate
rated current through one of two specified windings
of a transformer when the other winding is
short-circuited, with the windings connected as for rated
volt-age operation It is usually expressed in per unit, or
per-cent, of the rated voltage of the winding in which the
voltage is measured
Insulation level An insulated strength expressed in
terms of a withstand voltage
Insulation power factor The ratio of the power
dis-sipated in the insulation, in watts, to the product of
effective voltage and current, in voltamperes, when
tested under a sinusoidal voltage and prescribed
conditions
Lightning impulse insulation level An insulation
level, expressed in kilovolts, of the crest value of a
light-ning impulse withstand voltage
Liquid-immersed transformer A transformer in
which the core and coils are immersed in an insulating
liquid
Load tap changer (LTC) A selector switch device,
which may include current-interrupting contactors,
used to change transformer taps with the transformer
energized and carrying full load
No-load tap changer A selector switch device used
to change transformer taps with the transformer
deenergized
Oil-immersed transformer A transformer in which
the core and coils are immersed in an insulating oil
Overload Output of current, power, or torque by a
device in excess of the rated output of the device on
a specified rating basis
Overvoltage A voltage above the normal rated
volt-age or the maximum operating voltvolt-age of a device or circuit
Primary winding The winding on the energy input
side
Partial discharge An electric discharge that only tially bridges the insulation between conductors and that may or may not occur adjacent to a conductor Par- tial discharges occur when the local electric field inten- sity exceeds the dielectric strength of the dielectric involved, resulting in local ionization and breakdown Depending on intensity, partial discharges are often accompanied by emission of light, heat, sound, and radio influence voltage (with a wide frequency range)
par-Radio influence voltage A radio frequency voltage
generally produced by partial discharge and measured
at the equipment terminals for the purpose of mining the electromagnetic interference effect of the discharges
deter-Secondary unit substation A unit substation in which the low-voltage (LV) section is rated 1000 V or below
Secondary winding The winding on the energy
output side
Sound level A weighted sound pressure level obtained
by the use of metering characteristics and the ings A, B, or C specified in American National Standards Institute (ANSI) Standard S1.4
weight-Sound pressure level The sound pressure level, in
decibels, is 20 times the logarithm to the base 10 of the ratio of the pressure of the sound to the reference pres- sure of 2 times w-s N/m 2 (0.00002 microbar), also written 20 N/m 2
Station service transformer (SST) A transformer
that supplies power from a station high-voltage (HV) bus
to the station auxiliaries It also supplies power to the unit auxiliaries during unit startup and shutdown and/or when the VAT is not available
Surge arrester, lightning arrester A protective
device for limiting surge voltages on equipment by charging or passing surge current; it prevents continued flow of follow current to ground and is capable of repeating these functions as specified
dis-Switching impulse Ideally, an aperiodic transient
voltage that rises rapidly to a maximum value and falls, usually less rapidly, to zero
Switching surge A transient wave at overvoltage in
an electrical circuit caused by a switching operation
Thp changer See No-load tap changer
Trang 21Temperature rise The difference between the
tem-perature of the part under consideration (commonly the
"average winding rise'' or the "hottest spot winding rise'')
and the ambient temperature
'Iransient overvoltage The peak voltage during the
transient conditions resulting from the operation of a
switching device
Unit auxiliaries transformer (UAT) A transformer
intended primarily to supply all or a portion of the unit
auxiliaries
Unit transformer (UT) A power system supply
trans-former that transforms all or a portion of the unit power
from the unit to the power system
Withstand voltage The voltage that electrical
equip-ment is capable of withstanding without failure or
dis-ruptive discharge when tested under specified
conditions
The industry recognizes two general types of
power transformers: liquid-immersed
transform-ers and dry-type transformtransform-ers
LIQUID-IMMERSED TRANSFORMERS
A liquid-immersed transformer consists of a
mag-netic core-and-coils assembly, either single-phase
or polyphase, immersed in fluid having good heat
transfer and insulating properties The
liquid-immersed transformer permits compact design,
and at this time transformers with ratings above
10,000 kVA or 34.5 kV are always liquid immersed
Initially, the fluid was always a highly refined
mineral oil Since such oils are flammable,
liquid-immersed transformers located within buildings
were installed in fireproof vaults Later,
nonflam-mable fluids were developed for this application,
the most common being an askarel,
polychlori-nated biphenyl (PCB) These fluids have high
specific inductive capacitance (also called relative
dielectric constant or relative capacity) and good
heat transfer properties but are more expensive
and have lower dielectric strength than mineral
oil The Toxic Substances Control Act of 1976 (1)
and the Code of Federal Regulations (2) now
pro-hibit the manufacture of PCBs and limit the use
of PCB-bearing equipment The federal regulation
specifies rigid rules and requirements for marking
PCB-bearing equipment in service and for
dispos-ing of PCB-beardispos-ing equipment and contaminated
materials resulting _from liquid spills (3)
More recently other fluids having high fire points and low rates of heat release, though more expensive than askarels, have been introduced to replace it (for example, silicone, tetrachloroethy-lene, trichlorotrifluoroethane, and highly refined paraffinic oil)
Another recent development, the vapor-cooled transformer, is classified as liquid immersed and
is suitable for indoor installation This design employs a low-boiling point organic fluid for heat transfer The latent heat of vaporization absorbs the heat produced by transformer losses That latent heat is then released in a heat exchanger external to the transformer tank, which condenses the vapor and returns it to the transformer tank
in liquid form Vapor-cooled transformers may be equipped with cooling fans to increase kilovoltam-pere rating up to 50%
The application of high-fire point, low-heat release liquid-insulated transformers versus mineral oil-insulated transformers involves eco-nomic and fire hazard considerations The former are somewhat less hazardous, but they are more expensive than the latter, with silicone liquid-filled being the most expensive
Provisions for containing oil spills, should the tank rupture, are covered in this volume in Sec-tion 2.18
DRY-TYPE TRANSFORMERS Dry-type transformers are generally more expen-sive than oil-immersed transformers and depend
on solid insulation-film coatings, paper tape, or
a combination of the two-for most of their electric strength Single-phase and polyphase dry-type transformers are available in ventilated designs, totally enclosed nonventilated designs, sealed-tank designs, and gas-filled designs, the ventilated type being least expensive Their abil-ity to withstand lightning and switching surge impulse voltages is less than that of liquid-immersed designs It may therefore be prudent to protect their HV terminals with surge arresters, even when the external leads to these terminals are not directly exposed to lightning
di-Ventilated dry-type transformers are suitable for most applications inside buildings In atmospheres heavily loaded with dust or fibers, however, they must be cleaned at regular intervals to keep their ventilation passages clear This type may be equipped with fans to increase their kilovoltam-pere rating by 33%% They have the lowest initial cost of any in the family of dry-type transformers
Trang 22Totally enclosed, nonventilated dry-type
trans-formers are suitable for use in moderately
con-taminated industrial environments Because they
are nonventilated, they are designed to have low
heat losses-that is, very high efficiencies
Sealed-tank transformers have the ability to
function in the severest environments They have
their own sealed atmosphere and can function in
misty, oil-laden, dusty, highly contaminated areas
Tnese transformers also have high efficiencies
be-cause of the necessity of having low heat losses
Dry-type transformers are currently available in
self-cooled ratings up to 10,000 kVA and at voltages
up to 34.5 kV
A variant of the dry-type transformer that is resin
encapsulated has been introduced recently In one
form of this design, "cast-coil;' the coil is placed
in a mold and the resin coating is cast around it
These transformers are available in sizes up to
5,000 kVA and voltages up to 34.5 kV In another
form the coils are dipped in resin The
resin-encapsulated design may be used in harsh
environ-ments where ventilated dry-types may not be
suitable Although their initial cost is higher than
other dry-types, they may nevertheless be
econom-ical in high-load factor applications because of
their lower load losses (Volume 7, Au;te.iliary
Elec-trical Equipment)
Some of the resins used in earlier
resin-encapsulated transformers gave off vapors at high
temperatures that were found to be flammable,
toxic, or both In more recent designs these
con-cerns have been resolved by tests and analysis of
the vapors showing them not to be harmful (4)
The application of a ventilated dry-type versus
a nonventilated type or a sealed, gas-filled
dry-type transformer involves economic and
environ-mental considerations (clean, dust-laden, wet, or
highly contaminated atmosphere) The gas-filled
transformer has the highest initial cost
The application of a ventilated dry-type versus
a ventilated, encapsulated dry-type transformer
also involves these considerations
Volume 7, Section 7.5 gives a comparison of the
relative equipment costs of the various dry-type
transformers
2.4 RATING BASIS AND
TEMPERATURE RISE
Power transformers are output rated They are rated
to deliver specified kilovoltamperes continuously
at a specified secondary voltage and frequency under "usual" operating conditions and with a standard temperature rise When operated within their ratings they have "normal" life expectancies They may be operated beyond their ratings under certain conditions without loss of life expectancy
or under other conditions with a somewhat dictable sacrifice of life expectancy 1tansformers
pre-in power plants generally are selected to operate within their ratings except for brief transient periods, such as during motor starting or during the time required for relay operations to clear through-faults
Usual and unusual operating conditions for liquid-immersed transformers are defmed in ANSI Standard C57.12.00-1980 (5); those for dry-type transformers are defined in ANSI Standard C57.12.01-1979 (6) Some unusual operating con-ditions are:
• Ambient temperature above 40°C or with 24-h average above 30°C
• Altitude above 3300 ft
• Sustained operation at more than 110% (no load) or 105% (loaded) of rated secondary volts or volts per hertz
• Load current waveform distortion (harmonic factor greater than 0.05)
• Primary phase voltage unbalance
• Secondary phase current unbalance
• Damaging fumes or vapors, excessive or abrasive dust, salt spray, or excessive moisture
• Abnormal vibration, shocks, or tilting
• Restricted air circulation These or other unusual operating conditions, if ap· plicable, should be stated in purchase specifications Although transformers are kilovoltampere rated, their true continuous load limits are determined
by secondary winding current ratings Note that the secondary may be either the HV or the LV winding If the secondary winding has taps, then the permissible continuous load is determined by the current rating of the tap in use, though
it is called a "full-kVA" tap
The kilovoltampere rating does limit permissible load at secondary voltages above tap voltage rating, but at voltages below tap voltage rating the tap cur-rent rating intervenes At 95% secondary voltage the maximum continuous kilovoltampere load is 95% of nameplate kilovoltamperes
Standard temperature rise is the average ing rise (by resistance) that, in "usual" ambient
Trang 23wind-temperature and with suitable allowance for
hot-test spot difference, is within the long-time
with-stand capability of the insulating materials For
liquid-immersed transformers, that rise is 65°C
(15°C hot spot allowance) Liquid-immersed
formers are now rated for 65°C rise Many
trans-formers having 55/65°C-rise ratings, however, are
still in service Both designs are suitable for
con-tinuous operation at their 65°C-rise ratings The
difference between them is that the performance
characteristics, full-load losses, and impedance
voltage drop for the 55/65°C-rise transformer are
based on 55°C-rise loading Where a transformer
must operate in a higher-than-usual ambient
perature, it is customary to specify a reduced
tem-perature rise The result is a larger transformer
that under "usual operating conditions;' carries
more load For example, if the temperature rise
of a liquid-immersed transformer is specified as
55°C, the permissible load increase under 30°C
conditions that permit a 65°C rise will be 12%
The average temperature winding rise for
dry-type transformers, depending on the insulation
system, may be 80°C, l15°C, or 150°C (all with
30°C hot spot allowance) (6)
2.5 INSULATION LEVEL
'Iransformers must be insulated to withstand the
voltages to which their windings and terminals
may be subjected in service These include the
normal ranges of power-frequency voltages
pub-lished in ANSI Standard C84.1-1982, the impulse
overvoltages that may be produced by lightning
strikes on their terminals or on connected
trans-mission lines, and the transient overvoltages that
may be produced by operation of transmission line
circuit breakers Mineral oil-immersed
transform-ers can withstand very high crest voltages if the
duration of the transient is measured in
microseconds
The basic lightning impulse insulation level (BIL)
of a transformer is the crest value of the voltage
it can withstand if the impulse voltage has the
wave shape defined as "full wave" in ANSI
Stan-dards C57.12.00 and C57.12.90 That shape,
in-tended to be representative of a lightning impulse,
has a rise time of 1.2 J.LS and a decay time, or tail,
of 50 J.LS Crest values for other wave shapes are
keyed to the BIL For example, for 900-kV BIL the
associated crest values for front of wave, chopped
wave, switching surge, and low frequency are
1240, 1035, 745, and 395 kV, respectively The wave shapes of these other transients are also de-fined in the standards The front-of-wave shape is intended to be representative of a lightning im-pulse chopped before crest by a rod gap The chopped-wave shape is intended to be represen-tative of a lightning impulse chopped at crest or immediately thereafter The switching surge wave-form is intended to be representative of the tran-sient that may be produced by operation of a transmission line circuit breaker The low-frequency wave shape is sinusoidal at power fre-quency (or a low multiple of power frequency) to avoid core saturation during a factory test The transformer transient voltage strength re-quired in a particular application depends on the lightning arresters that can be installed at the transformer terminals to protect it If the arrester has too low a voltage rating, it may be destroyed
by follow current at power frequency following
a voltage surge Minimum safe arrester voltage ings must be determined by a transient network analysis of the transmission system The trans-former transient voltage strength should then ex-ceed the voltage rating of the arrester by an appropriate margin-usually in the range of 15 to25%
rat-'fransformer price is affected by BIL One facturer has published base price multipliers, show-ing that for 345-kV service the base price would apply without multiplier for a BIL of 1050 kV The multiplier would be less than 1 for 900-kV BIL and greater than 1 for 1175-kV BIL This information
manu-is not based on industry standards, but it does dicate the industry pricing practice
in-BILs for dry-type transformers are given in ANSI Standard C57.12.01-1979 (6), and the wave shapes are defined in ANSI Standard C57.12.91-1979 (7)
DUAL-, AND TRIPLE-RATED TRANSFORMERS
LIQUID-IMMERSED TRANSFORMERS Liquid-immersed transformers larger than 500 kVA may have both a self-cooled rating and one or two additional forced-cooled ratings The rating increase produced by forced cooling varies with transformer size, as shown in 'Th.ble 2-1 (8) At 20,000 kVA and above transformers may have a single forced-cooled rating and no self-cooled rating
Trang 24Table 2.1 Forced-cooled Ratings
P-ercent of Self-cooled Self-cooled kVA kVA Wrth Auxiliary
2500-9999 2500-11 ,999 125 10,000 and up 12,000 and up 133%
OA/FA/FA
- OA/FA!FOA 10,000 and up 12,000 and up 133% 166'%
SOURCE: This material is reproduced by permission of the National
Electrical Manufacturers Association from NEMA Standards
Publi-cation No NEMA TR 1-1980, Transformers, Regulators, and Reactors
© 1980 by NEMA
The standard method of indicating these
multi-ple ratings is to list the rating(s), followed by the
corresponding cooling method(s) For example:
• 2000/2300 kVA, OAIFA indicates a
trans-former with a self-cooled (OA) rating of
2000 kVA and a forced-air-cooled (FA) rating
of 2300 kVA
• 12,000/16,000/20,000 kVA indicates a
trans-former with a self-cooled rating and two
stages of forced cooling Such transformers
have large radiators to produce
thermosi-phon circulation of the oil in the self-cooled
mode They have two banks of fans and oil
pumps These transformers are indicated as
follows:
and the second stage of forced cooling use
forced air The first stage uses half of the
available fans (one bank); the second stage
uses all available fans (both banks)
forced cooling uses forced air and the
sec-ond stage uses forced oil and forced air
o OA!FOAJFOA indicates that both the first
stage and the second stage of forced
cool-ing use forced oil and forced air The first
stage uses half of the available fans and oil
pumps (one bank); the second stage uses
all available fans and pumps (both banks)
• 25,000 kVA, FOA indicates a transformer
with no self-cooled rating It has compact
coolers in place of radiators and cannot
re-main energized, even at no load, without its
fans and pumps in operation Nevertheless,
most UTh and many UATh are of the FOA
type This type is used less frequently for SS'IS, which remain energized continuously but are heavily loaded infrequently In this type of service the triple-rated transformer
is advantageous, because its mechanical ing auxiliaries are required only during the periods of heavy load
cool-A Ucool-AT serving a maximum load of 20 MVcool-A could
be either 12/16/20 MVA, OAIFX!FX, or 20 MVA, FOA The triple-rated transformer can carry 12 MVA with no mechanical cooling auxiliaries in opera-tion In this application that capability may not be
an advantage, since half of the 20-MVA load may
be present when the machine is synchronized and the auxiliaries load is transferred to this trans-former; the 12-MVA self-cooled limit thus is ex-ceeded before the turbine generator reaches half load Although the triple-rated and FOA alterna-tives may have identical core-and-coil assemblies, the FOA transformer is less expensive and requires less space in an area where space is usually limited
On the other hand, if a generator breaker is stalled between the generator and the transform-ers, the triple-rated UAT can operate without mechanical cooling auxiliaries during unit shut-down Volume 7, Auxiliary Electrical Equipment,
in-covers the application of generator breakers, and Volume 8, Station Protection, covers transformer and generator protection
Large UTh are nearly always of FOA (or see below) design Again, this is primarily because
POW-of space considerations In addition it may be more difficult to design a low-impedance transformer
of the triple-rated type, because the oil channels through the windings must be large enough to permit gravity circulation of oil before the oil
Trang 25pumps are brought into operation Larger oil
channels tend to increase leakage reactance
WATER-COOLED TRANSFORMERS
Forced-water-cooled (FOW) transformers are
often used instead of FOA types at hydroelectric
plants because of the ready availability of cooling
water They are also often used at underground
hydro or pumped storage plants, where the
trans-formers must be underground to be near the
equipment they serve Large power transformers
have also been enclosed in masonry vaults for
noise control purposes In such cases water
cool-ing may be the only feasible method of heat
dissi-pation Because of concern for water leakage into
the oil, however, such transformers have specially
designed heat exchangers with double tube sheets
and concentric tubes to provide two metal
barri-ers between the two fluids In this design the
neutral space between the metal barriers can be
monitored and an alarm actuated if either barrier
begins to leak
DRY-TYPE TRANSFORMERS
All dry-type power transformers have self-cooled
ratings Those commonly used indoors in power
plants are ventilated (rated AA) Some are
equipped with fans to give them a dual rating
(AA!FA) A common size for LV secondary unit
sub-station transformers is 1000/1333 kVA, AAIFA Note
that the forced-cooled rating is one-third larger
than the self-cooled rating
'Iransformers are very efficient Large
liquid-immersed transformers may have efficiencies
higher than 99% Nevertheless, it may be
worth-while to pay an initial price premium for loss
reduction, which will result in still higher efficiency
'Iransformer losses can be divided into three
general categories: no-load losses, load losses, and,
for forced-cooled transformers, cooling-system
losses The no-load losses are mainly core hysteresis
and eddy-current losses, which are incurred as
long as the transformer is energized They remain
essentially constant The load losses are due to the
heating of winding conductors by the passage of
current and by other stray losses in conductors
and tank walls, which are load related These losses
increase as the square of load current The cooling
system losses are power used to drive the ical cooling auxiliaries-fans and oil pumps-where these auxiliaries are present
mechan-In medium and large power transformers the load losses are much greater than the no-load losses The ratio of load losses to no-load losses will be influenced by the loss evaluation figures
in the purchaser's bidding documents 1b simplify
a generalization of available data, one can pare values on the basis of core-and-coils rating
com-On this basis a 20-MVA FOA transformer, a 12/16-MVA OAIFA transformer, and a 12/16/2Q-MVA OAIFOAIFOA transformer are directly comparable
At 12 MVA such a transformer would have a ratio of load losses to no-load losses on the order
of 3.5:1 At 16 MVA this ratio would be greater by
a factor of 1 777; and at 20 MVA (if permissible) the factor would be 2.779
Very large pbwer transformers, nearly always
FOA, have loss ratios on the order of 7:1 Lower ratios might be economical in many cases, but such ratios may not be achievable within shipping limitations
EVALUATION METHOD Loss evaluation is the process of estimating the amount of initial outlay justified to avoid future costs Specifically, it answers the questions: "What price premium are we justified in paying to reduce transformer no-load loss by 1 kW? What premium for 1 kW of load loss?" When the initial cost pre-mium (a single payment amount) is compared with the future costs avoided thereby (a nonuniform series of annual amounts), it is convenient to use life-cycle cost methods, which convert all cash flows to present worth It is, for example, not justifiable to spend $100 today to avoid a $100 ex-pense ten years from today; a far smaller amount invested in some other aspect of the company's business would grow to $100 in ten years It is the smaller amount that is the present value of the future cost
Loss evaluation seeks to determine how much the purchaser would be justified in paying for the transformers to reduce no-load loss by 1 kW and how much per kilowatt for a similar reduction in load loss Since the premium would be a single payment on delivery and the savings that justify
it are a nonuniform series of future costs, their equivalence must be found by present-worth methods These methods, which involve the capi-tal structure of the company, the estimated load-ing schedule for the transformer, and the present
Trang 26and anticipated future cost of the fuel used for
generation, are discussed in Appendix A
APPLICATION OF LOSS VAWES
With no guidance about how losses are to be
evalu-ated, each transformer bidder will offer the
de-sign that meets its temperature rise guarantee at
minimum initial cost For large power
transform-ers that are expected to operate at high load
fac-tors, this is not the most economical choice A
better design would have more iron, more copper,
and less cooling equipment Although this design
would increase initial cost, it would reduce losses
As was pointed out previously, transformer
losses are partially avoidable Estimating loss
values and including them in the invitations for
competitive bids effectively make the supplier and
the purchaser partners in determining what
frac-tion of the losses is economically avoidable In the
case of smaller transformers the cost per
kilovolt-ampere is so large that any significant fraction
added to it in order to reduce losses would
out-weigh the future savings attributable to the loss
For certain large transformers, notably SSTh, the
load factor is so low that load losses have small
economic value But SSTh are energized for
essen-tially the entire year, and their no-load losses are
incurred at full strength all of that time For these
transformers the no-load losses have significant
economic value Therefore, a design in which core
flux density is reduced below conventional levels
may well justify its higher cost, because a small
reduction in flux density produces a large
reduc-tion in hysteresis loss and a larger reducreduc-tion in
core eddy-current loss This reduction in flux
den-sity also significantly reduces magnetostriction
noise In the case of these medium power
trans-formers the large-volume market is in substation
transformers of fairly uniform design Not all
sup-pliers are in a position to tailor their basic designs
closely to the special needs of every purchaser For
that reason each manufacturer will make its own
decision on the design to be offered and the prices
For transformers installed indoors losses have
a significant indirect cost due to the fact that the
heat released by the transformer must be removed
by the ventilating system and may represent an
appreciable portion of the load on that system For
this reason some purchasers prefer 80°C-rise
dry-type transformers to the less expensive, but less
efficient, 115°C- and 150°C-rise designs
2.8 OIL PRESERVATION SYSTEMS
Mineral oils used in power transformers degrade
in prolonged exposure to oxygen or moisture Water suspended in the oil reduces its dielectric strength and that of cellulosic insulation to which the water may migrate Oxidation may affect di-electric properties and may cause sludge forma-tion Sludge, in turn, clogs small oil passages through the windings and impairs heat removal, allowing hot spots to develop Solid insulation may
be degraded rapidly in the hot spots, and such degradation reduces insulation life expectancy Oil preservation systems have been developed to pre-vent such degradation (8)
Mineral oil has a relatively large thermal cient of expansion, and therefore the oil level in
coeffi-a trcoeffi-ansformer tcoeffi-ank rises coeffi-and fcoeffi-alls with coeffi-ambient temperature and with load If the oil level becomes too low, the bottom portions of HV bushings and the current transformers that are often fitted around them are left without the oil immersion
on which they may depend for voltage gradient control and for cooling The oil level cannot rise
· above the top of the tank unless external sions are made for expansion
provi-The oil preservation system must allow for the oil expansion and contraction and must prevent moisture and oxygen from being drawn into the tank Three general types of oil preservation sys-tems are in common use: the sealed-tank system, the inert gas system, and the modified conservator system
One manufacturer provides, as standard, the oil preservation system for the following various volt-ages and ratings:
Three-phase,
Operating Voltage Class (kV) 650C MVA Rating Up to 138 161 to 230 Above 230
Up to 67.2 OA sealed-tank inert gas modified
Above 67.2 OA modified modified modified
or 112 FOA conservator conservator conservator
SEALED-TANK SYSTEM
In the sealed-tank system the interior of the tank
is sealed from the atmosphere The gas-plus-oil ume remains constant over the temperature
Trang 27vol-range The transformer tank and lead entrance
bushings are tightly sealed Contamination of the
oil proceeds very slowly because of the careful
drying and vacuum filling done before the tank
is sealed
This system has one limitation: With time the
pressure tends to become negative whenever oil
temperature falls below the temperature at which
the tank was filled When this happens moisture
and a1r will be drawn into the transformer if a leak
does occur
Maintenance of this system is minimal The
pressure-vacuum gage can be obtained with alarm
contacts to alarm when overpressure or excessive
negative pressure occurs
Figure 2-1 shows a transformer with a
sealed-tank system
INERT GAS SYSTEM
In the inert gas system a blanket of dry nitrogen
is maintained over the oil in the transformer tank
at a pressure slightly higher than atmospheric
pressure Thus, any leakage is outward and does
not contaminate the oil
During cooling periods nitrogen is fed from
metal bottles near the transformer through a
regulating valve, which maintains a slight positive
gage pressure at the top of the tank During
heat-ing periods a discharge regulator releases surplus
gas to prevent overpressure There must be a
suffi-cient "dead-band" between the settings of the two
regulators to allow for drift and random variation
of set points and to ensure that in-feed and
dis-charge never occur at the same time If that were
to occur, the entire contents of the gas bottles
could be lost
The inert gas system requires regular
main-tenance: depleted gas bottles must be replaced,
nitrogen use must be recorded, and the settings
of the pressure regulators must be verified
Another possible disadvantage of the inert gas
system involves formation of bubbles in the oil
There is always a small but measurable quantity
of gas-nitrogen or other gases-dissolved in the
oil During a coolin_g period and resultant
depres-surization some of the gas comes out of solution
in the form of bubbles Migration of gas bubbles
into regions of high dielectric stress may cause
ionization of the voids within the bubbles because
the dielectric strength of the voids is lower than
that of the sUITOtmding oil A chain of ionized voids
can produce dielectric failure The seriousness of
Courtesy of McGraw-Edison Co., Pittsburgh, Pa
this threat is controversial; many transformer users continue to have satisfactory experience with inert gas systems
A transformer using the inert gas system is shown in Figure 2-2 The control cabinet and nitro-gen gas piping are visible
MODIFIED CONSERVATOR SYSTEM Because of the perceived disadvantages of the in-ert gas system, a competing system has been de-veloped in which the transformer tank is kept completely filled with oil from a conservator (tank) above the level of the transformer tank cover A
portion of the volume of the conservator is pied by air, which breathes in and out as the oil volume changes with temperature The air is prevented from contact with the oil by an imper-vious diaphragm or air cell
occu-This system has its own drawbacks The vator must be configured and located with respect
conser-to the HV bushing terminals conser-to maintain the quired air-strike distance from terminals to grounded metal Given the manholes, pressure
Trang 28re- ·
.f I
- - - · >
· ··
Courtesy of Westinghouse Electric Corp., Pittsburgh, Pa
Figure 2-2 Transformer With Inert Gas Oil PreseNation System relief diaphragms, lightning arresters, and, in
some cases, isolated-phase bus enclosures on and
around the top of the transfonner, the proper
con-figuration and location of the conservator may be
difficult to achieve in some applications In
addi-tion the diaphragm or air cell may not remain
per-manently impervious The bottom of the air cell
rests on the surface of the oil The float of the
liq-uid level gage, also riding at the oil surface, rests
against the underside of the air cell If the air cell
develops a leak, it will gradually fill with oil and
sink below the surface of the oil, carrying the float
downward The liquid level gage alann will
oper-ate indicating either a damaged cell or low oil level
Access openings are provided at both ends of the
tank for tank cleaning or air cell inspection This
system has been widely accepted
A transformer using the modified conservator system is shown in Figure 2-3
2.9 TRANSFORMER CONNECTIONS
Any three-phase transfonner winding may be nected in delta, wye, or zigzag; it may even be con-nected in aT connection, which is sometimes used for grounding transformers The relative phasing between primary and secondary may be zero or any
con-multiple of 30 electrical degrees Few of the many possible combinations are used in power plants
· A UT, also called a generator step-up or main transformer, is a transfonner (or bank) used to connect the generator to the HV system
Trang 29Courtesy of General Electric Co Bridgeport, Conn
A VAT, also called a normal station service
trans-former, is one (usually fed from the main
genera-tor leads) that supplies power to the unit
auxiliaries
An SST, also called a reserve station service
transformer or startup transformer, is one that
supplies power from a station HV bus to the plant
auxiliaries
The phasing relationship between primary and
secondary windings of a three-phase transformer
is expressed in terms of terminal designations, for
which the standard convention is as follows: If one
is facing the LV side of the transformer, the HV
terminals are Hl, H2, and H3 from left to right and
the LV terminals are Xl, X2, and X3 from left to
right, as shown in Figure 2-4 More extensive
in-formation may be obtained from Reference 9
'Iransformer winding phase relationships are
shown on the transformer nameplate
The terms primary (winding) and secondary
(winding) are necessary in discussing transformer ratings A transformer is fully loaded when its secondary winding is carrying full-load current The terms HV and LV are necessary in discussing phasing, because ANSI standard phasing requires the HV to lead the LV by 30 electrical degrees, regardless of whether the HV winding is the pri-mary or the secondary
'IJpical phasor diagrams of connections used for transformers in power plants are shown in Fig-ure 2-5
UTs Most UTh, whether three-phase units or banks of three single-phase units, are connected in delta on the primary (LV) side and in grounded wye on the secondary side In any wye-delta, delta-wye, or
Trang 30wye-zigzag transformer, unless otherwise
speci-fied, the secondary voltages at terminals Hl, H2,
and H3 lead the primary voltages at terminals Xl,
X2, and X3, respectively, by 30 electrical degrees
(Figure 2-5)
The grounded wye connection of the HV
wind-ing permits gradwind-ing its insulation from specified
BIT at the terminals to a lower BIT at the grounded
neutral The delta connection of the LV windings
provides a low-impedance path for zero-sequence
and third-harmonic currents, thereby facilitating
selective relay tripping for single phase-to-ground
faults on the HV system and improving secondary
voltage waveform The UT primary is usually
im-pedance grounded at the generator neutral For
other types of transformer neutral grounding see
Volume 8, Station Protection
UATs
UA'IS are most frequently connected in delta on
the primary side and in wye on the secondary side
but with Hl, H2, and H3 voltages lagging Xl, X2,
and X3 voltages by 30 electrical degrees The
wye-connected LV windings permit some form of
neu-tral grounding to facilitate selective relay tripping
for single phase-to-ground faults on the
medium-voltage auxiliary power system The lagging phase
angle may be the simplest method of placing UAT secondary voltages in phase with SST secondary voltages in typical cases (Figure 2-5b)
SSTs SS'Th are usually connected in grounded wye on the HV side to permit the use of graded insula-tion The LV windings may also be wye connected
to provide for a three-phase, four-wire system or for neutral grounding If the source of the SST is the same HV bus as the one receiving the genera-tor output, the phasing shown in Figure 2-5c may
be used This connection results in a secondary voltage in phase with the output of a UAT phased
as shown in Figure 2-5b
A wye-wye transformer in this application does not necessarily require a delta tertiary to provide
a low-impedance path for zero-sequence currents
A three-legged core design, most frequently offered in this size range, provides a virtual ter-tiary sufficiently well coupled to the other wind-ings to present a low impedance as compared with the neutral grounding resistor usually applied on the secondary side
If the HV source is different from the one to which the UT is connected, it may be necessary
to use a delta-connected secondary for correct
Trang 31H1 X1
H1
a Unit transformer b Unit axiliaries transformer
c Station service transformer d Station service transformer
e Station service transformer Ill f Secondary unit substation transformer I
g Secondary unit substation transformer II h T-connected grounding transformer
Figure 2-5 Typical Transformer Phase Relationships
phasing, in which case a separate grounding
trans-former is required to derive a neutral Alternatively,
a zigzag-connected secondary can provide the
same phasing as a delta and would provide the
neu-tral, but it may be the more expensive alternative
Figure 2-Sd) If the voltage of the other source is less than 230 kv; a delta-connected HV winding (which sacrifices the graded-insulation advantage) with a wye-connected secondary permits the same phasing at a lower cost than a wye-zigzag design
Trang 32SECONDARY UNIT SUBSTATION TRANSFORMERS
Secondary unit substation transformers are nearly
always connected in delta on the primary side, the
source voltage being low enough to remove any
advantage in grading the insulation (that is, using
a lower voltage insulation at the end of each
wind-ing) The secondary may be either delta or wye
The wye connection is required if the LV neutral
is tQ be grounded, if a voltage regulator is to be
connected into the phase windings at the neutral
ends, if a four-wire system for phase-to-neutral
single-phase loads is required (Figures 2-5f and
2-5g) Relative phasing of LV networks in power
stations is seldom important, because they are
seldom interconnected
GROUNDING TRANSFORMERS
A zigzag-connected autotransformer may be used
on a three-wire system to derive a neutral for
grounding The T connection is sometimes
pre-ferred when there are no phase-to-neutral loads,
because it permits the use of a two-legged core
with a single winding on each core leg, resulting
in a less expensive design The neutral connection
is made to a tap on the stem of the T (Figure 2-5h)
2.10 TAPS
A power transformer may have taps in either
pri-mary or secondary windings so that its effective
turns ratio may be changed In power plants such
changes are not usually required to establish a
new output voltage; instead they are needed to
reestablish the desired output voltage after a
departure due to a change in source voltage or
in load-related impedance voltage drop If tap
changing must be done while the transformer is
loaded, special switching equipment is required
to transfer load current from one tap to another
without an interruption of service This is called
tap changing under load
NO-LOAD TAP CHANGERS
No-load tap changers employ manually operated
switching equipment that changes the turns ratio
of the three phases simultaneously and by the
same amount In the case of single-phase
trans-formers, each has its own manually operated
no-load tap changing-switching device The no-no-load
tap changing-switching device is in the tank with the core and coils in both three-phase and single-phase transformers The no-load tap changer can
be operated only when the transformer is gized Conventionally, a transformer has two full-capacity 2%% taps above and two below rated volt-age In a step-down transformer the taps above rated primary voltage are less likely to be used than those below it For that reason some pur-chasers prefer to specify one tap above and three taps below rated voltage, an option available at no change in price The taps may also be ordered closer together than 2%%, an option usually avail-able without price premium The taps can be omit-ted altogether with a saving in the price of the transformer Both of these last two options are worth serious consideration in power plants The use of no-load taps in a UT (generator step-up transformer) is a special case, because the
deener-HV winding that nearly always contains the taps
is the secondary This case is discussed in greater detail in Section 2.13
LOAD TAP CHANGERS (LTCs) LTCs are often used in distribution substations but are seldom used in power plants (10) In the United States the conventional LTC has 32 taps at %% spac-ing, 16 above and 16 below rated voltage, to pro-duce a voltage range of ± 10% The transformer may have reduced capacity on taps below rated voltage Where an LTC is used on a power plant transformer, its purpose is not to alter the volt-age supplied to utilization equipment but to re-store that voltage after a change in load or in the source voltage supplied to the transformer wind-ing has occurred The tap changer should be on the transformer primary whenever possible If it
is on the secondary, the rated kilovoltamperes may not be available under heavy load conditions
As an illustration of this point consider a 12-MVA, 24- to 4.16-kV transformer connected to the leads of a 24-kV generator and fitted with a secondary LTC The (full-kVA) tap voltage and cur-rent ratings will be as shown in the following abbreviated table:
Trang 33Assume, for simplicity, that generator voltage
remains at 24 kV and that the set point of the
contact-making voltmeter controlling the LTC is
4.16 kV
At no load the tap changer would remain in the
neutral position because secondary voltage would
match set point At full load the secondary voltage
at the 4-kV bus might be reduced 5% by voltage
drops in the transformer impedance and
second-ary leads impedance The LTC would compensate
by moving to Thp R8, which has a voltage rating
of 4.368 kV and a current rating of 1586 A The
actual load current is 1665 A, a 5% overload The
situation becomes worse if the generator is
oper-ating at 95% voltage
This problem does not arise if the taps are on
the primary The secondary voltage rating and the
voltmeter set point would both be 4160 V The LTC
tap required to produce rated secondary current
(assuming power factor 0.8 or higher) must be
within the tap rating, because the transformer is
output rated
LTCs are usually equipped with automatic
con-trol equipment to maintain a manually preset
secondary voltage This equipment usually
pro-vides for remote control and indication of tap
position The control typically includes an
auto/manual transfer switch, a raise/lower control
switch, a set-point adjuster, a tap position indicator,
and position limit-indicating lights The equipment
also provides maintenance adjustments for
dead-band, starting time delay, and time delay between
tap changes The dead-band and time delays
re-duce wear and tear from unnecessarily frequent
operation during brief voltage transients With
usual adjustments the dead-band is on the order
of 1 %; the starting time delay is about 30 s, and the
time between tap changes is 1 to 1 Yz s
Addition of an LTC to a power transformer
in-creases its cost by approximately 40% The
addi-tion of electromechanical switching equipment to
an otherwise essentially static device increases
maintenance cost In addition the moving parts
and the extra winding taps, which raise
mechani-cal and electrimechani-cal stress, may have a significant
im-pact on reliability
If an LTC is used on a power plant SST, the time
delays may have special significance, as discussed
in Section 2.15
The LTC switching equipment is located in a
sep-arate oil-filled compartment connected to the
transformer main tank
Figure 2-6 shows a power transformer with an
LTC The latter is located in a separate
compart-ment, throat connected to the transformer tank, below the top of the tank
2.11 BUSHINGS
Bushings are used on liquid-immersed ers to carry the winding terminal connections through the grounded metal cover or sidewall of the tank A porcelain rain shield over the exter-nal portion is skirted to provide a long surface creepage path from terminal to ground flange The internal portion below the ground flange is generally immersed in the transformer insulating fluid This portion may also be encased in porcelain
transform-HV bushings are of the condenser type, ated with layers of oil-impregnated kraft paper Copper or aluminum foil layers of graded axial length in the paper insulation structure distrib-ute electrical stresses and control voltage gra-dients The shell is filled with oil to keep the paper saturated, and the outer terminal is fitted with an oil level gage or sight glass A cushion of dry nitro-gen above the oil allows for thermal expansion and contraction of the oil This cushion is sealed at a pressure above atmospheric pressure to exclude air and moisture Bushings of this type must be shipped and stored in a nearly upright position
insul-to prevent dryout of any of the layers of paper
In bushings rated 115 kV and higher one of the foil layers is made available as a bushing potential tap through an insulated conductor just above the ground flange This tap must be impedance grounded through an external potential device or solidly grounded by a grounding cap whenever the bushing is energized Condenser-type bushings (Figure 2-7) rated below 115 kV, down to and including 15 kV, have a power factor tap The power factor tap connects to the ground layer of the capacitor core An aluminum cap covers the insulated power factor tap assembly and grounds the tap connection when it is not in use Bushings are of two types, depending on their provision for connection to the transformer wind-ings In a fixed-conductor type the central tube or rod conducts current from the top terminal to the bottom terminal The winding lead is connected
to the bottom terminal In a draw-lead type the winding lead is drawn upward through the cen-tral tube and connected to the top terminal Fig-ure 2-7 shows a bushing with a threaded copper tube that can be used with a fixed-conductor or
Trang 34a draw-lead type connection Figure 2-8 is an
extra-high voltage (EHV) bushing of the draw-lead type
HV bushings are generally selected to have the
same BIL as that of the transformer HV winding
For situations in which the atmosphere is highly
contaminated with particulate matter or for
high-altitude installations it may be desirable to use
bushings having a longer porcelain rain shield If
this aim is achieved by using bushings with a
higher BIL than that of the winding, the lower
por-tion of the bushing will also be longer, requiring
a taller tank, which may exceed shipping
limita-tions The alternative is an extra-creep design, in
which the rain shield is taller but the portion
in-side the tank is not extended
Lower-voltage high-current bushings, which are
used on the primary terminals of UTh, are generally
fixed-conductor, bulk type, again with porcelain
rain shields and oil impregnated (Figure 2-9) Such
bushings are not usually equipped with oil level
Courtesy of McGraw-Edison Co., Pittsburgh, Pa
gages, but oil leakage has occasionally been a lem There could also be a heat dissipation problem
prob-if bushings with a lower temperature rating are connected to isolated phase bus conductors oper-ating at 105°C 'll'ansformer specifications should state terminal conditions
Secondary bushings on UATh and SSTh are of the porcelain type, at least 110 kV BIL, and are some-times mounted in the sidewalls of the tank below transformer oil level Faulty seals in such bushings have caused fires in a few cases when transformer oil leaked through a bushing seal into a cooler con-trol cabinet
Bushings are manufactured in accordance with the requirements of ANSI/IEEE Standard 24-1984
(11) and tested in accordance with requirements and test procedures of ANSI/IEEE Standard 21-1976 (12)
See Section 2.22 for bushing maintenance
Figure 2-6 Power Transformer With LTC
Trang 35* POC design
Clear/view oil reservoir
Nameplate
Mounting flange/ground sleeve assembly
Bottom coo assembly*
Courtesy of Lapp Insulator Co LeRoy, N.Y
Gaskets High compression coil springs *
housing
Bushing potential tap
.,_ _ Paper-foil capacitor core
+ Lower porcelain assembly *
Trang 36Courtesy of Lapp Insulator Co., LeRoy, N.Y
Figure 2-8 EHV Bushing
2.12 ACCESSORIES
The accessories described individually in the lowing subsections are available for large liquid-immersed transformers Few of them are applica-ble to dry-type transformers
fol-LIQUID LEVEL GAGE
The typical liquid level indicator is a sealed ment body Inside, an indicating needle sweeping
instru-a cinstru-alibrinstru-ated scinstru-ale is minstru-agneticinstru-ally coupled to instru-an ternal pivoted float arm, with the float at the top surface of the insulating fluid The scale is marked
ex-to indicate high, low, and 25°C levels The dicator includes alarm switches
in-For a transformer with an inert gas oil vation system, the indicator is mounted at the top
preser-of the transformer tank wall For a transformer with a conservator or constant oil pressure sys-tem, the indicator is mounted on the conservator
One indicator (Figure 2-lOa) displays the top oil temperature In the other indicator, called a wind-ing temperature or hot spot temperature indicator (Figure 2-lOb), the well is heated electrically by current proportional to transformer load, supplied
by a current transformer The electric heating simulates the winding hot spot rise over top liq-uid temperature In some cases the heater leads are extended to an external terminal box for shunting by a calibrating resistor The initial value
of the resistor is calculated, but it may change ing the temperature rise test, if made There have been instances in which no temperature rise test was made on a particular transformer and the hot spot indicator gave false indications of overheat-ing in service until the calibrating resistor was replaced
Trang 37dur-Oil filler cap
Trang 38J
Switch-setting tabs
Indicating unit
reading pointer Credl Reset-shaft cap and gasket
Maximum-Temperature detector
Union connector
a Courtesy of Westinghouse Electric Corp., Pittsburgh, Pa.; b Courtesy
of General Electric Co., Bridgeport, Conn
Figure 2-10 Temperature Indicator Relay
FLOW INDICATOR
'Ii'ansformers employing forced-oil cooling may be
equipped with a flow indicator, including alarm
switches, for each pump 'JYpically, the indicator
is a vane-operated instrument mounted on the
pump discharge pipe The scale is not calibrated;
it merely shows whether there is oil flow from the
pump
BUSHING CURRENT TRANSFORMERS
A bushing current transformer consists of a short sleeve of magnetic material with a distributed toroidal secondary winding It is supported below the cover of the transformer tank at the bushing opening so that the bushing lead, passing through
it, acts as a single-turn primary Where required, two or three current transformers can be installed
at each bushing One of them is likely to be used for transformer differential relays Good relaying practice prohibits putting any other burden on such current transformers (Volume 8, Station Pro-
tection) Another might be used for other relays, and a third might be used for metering Most bushing current transformers are provided with taps for multiratio ratings
As with other current transformers, bushing current transformer secondary windings must be short-circuited when no burden is connected, be-cause their open-circuit voltages may be high enough to be dangerous to personnel They may also cause insulation failure
RESISTANCE TEMPERATURE DETECTORS Where remote indication, recording, or data log-ging of top oil or winding hot spot temperature
is desired, the local temperature indicators can be supplemented or replaced by 10-0 copper resis-tance temperature detectors In general it is not feasible to embed such detectors in the trans-former windings They should be located in the wells just below minimum oil level (13)
SUDDEN PRESSURE RELAY
A sudden pressure or fault pressure relay ure 2-11) responds by rapid closure of an electrical contact to sudden pressure rise in the liquid in which its sensing element is immersed Designed for mounting on the transformer tank wall near the base or on a valve body, it senses the pressure transient produced by an internal arc
(Fig-Because some of the early sudden pressure relays were prone to operate erroneously under other conditions, many users wired them for alarm only The modern relay has been made in-sensitive to mechanical shock and vibration, pump surges, and normal pressure variations caused by transformer temperature changes User confi-dence has been restored; some users now regard
it as a sensitive and reliable primary protective device and wire it for breaker tripping to isolate
a faulted transformer
Trang 39Courtesy of General Electric Co Bridgeport Conn
GAS DETECTOR RELAY
A gas detector relay (Figure 2-12) collects bubbles
of gas generated below liquid level and closes an
electrical contact when a significant gas volume
has accumulated Since most of the combustible
gas is generated by the decomposition of oil or of
solid insulating materials, relay operation may
pro-vide warning of incipient dielectric failure Gas
bubbles that do not indicate decomposition may
form when there is a rapid change in temperature
Since the gas detector relay does not discriminate
between combustible and noncombustible gas, it
might operate in either case Determining whether
the gas evolution is a matter of concern requires
that a sample be collected for mass spectrometric
analysis in a laboratory
FAULT GAS MONITOR
A combustible gas monitor that continually
monitors the levels of dissolved hydrogen, carbon
monoxide, acetylene, and ethylene gas in oil is
available commercially The device mounts on the
transformer with the electrochemical sensor below
the oil level It is provided with dual-stage alarm
circuitry for early incipient fault warning The
monitor is shown in Figure 2-13 Sixty of these units
have been installed at a major American utility to
protect current transformers that have a history
of generating high quantities of hydrogen before
failure These monitors have operated flawlessly
to indicate sudden increases in hydrogen As a sult it was possible for the current transformers
re-to be removed from the circuit before failure Information on combustible gas analysis and in-terpretation is given in Kelley's article "'Transformer Fault Diagnosis by Dissolved Gas Analysis" and in ANSI Standard C57.104-1978 (14)
PRESSURE RELIEF DEVICE One or more pressure relief devices (Figure 2-14) may be installed in openings in the transformer cbver to relieve dangerous pressure that may build
up within the tank The device consists of a loaded diaphragm, automatically reset, with a mechanical semaphore to indicate that it has oper-ated, and alarm contacts Because these devices are of a standard size, with limited relieving ca-pacity, it may be advisable to install several on a very large transformer to prevent a rupture of the tank during a transformer fault
spring-Courtesy of General Electric Co Bridgeport Conn
Trang 40
_
\
Courtesy of Syprotec Corp., Rouses Point N.Y
LIFTING EYES AND JACK BOSSES
Lifting eyes and jack bosses facilitate the handling
of the transformer during manufacture, loading
for shipment, unloading at destination, and
instal-lation In some cases jack bosses have been
mounted so low on the assembly as to require
toe-jacks, which are less commonly available t1:J.an
con-ventional hydraulic jacks Large transformers can
be damaged seriously when conventional jacks are
applied under protrusions not designed for this
purpose
'Iransformer outline drawings should be
exam-ined carefully for these features In some cases the
manufacturer may be able to revise the design to
provide greater clearance under jack bosses if the
problem is identified before tank fabrication
LIGHTNING ARRESTERS
Lightning arresters are most effective in
protect-ing transformer insulation from surge voltages if
they are installed very close to the winding
ter-minals For this reason it is common practice to
purchase the arresters with the transformer and
to require mounting brackets for them on the transformer tank For selection of arrester ratings see Section 2.5
2.13 APPLICATION CONSIDERATIONS
When a source of electric power at one voltage level is required to serve utilization equipment designed for another (usually lower) voltage level,
a transformer is required between source and· load Selection of the proper transformer requires consideration of the following elements:
• Maximum sustained load
by chemical processes at a rate that is a function
of absolute temperature The relationship of time-to-end of life versus temperature is linear when plotted on appropriate scales This line is called an Arrhenius curve For a particular insulat-ing compound or system the slope of the Arrhen-ius curve is determined at two or more elevated temperatures The temperatures are selected to produce failure (end of life) in an acceptable time period, but the temperatures are not so high that they produce phase changes in the material An
end-of-life condition is usually defined in terms of mechanical properties of the insulation When the insulation becomes too brittle to remain in place during the vibration, shock, and thermal expan-sion that are charactistic of a normal load cycle,
a dielectric failure is imminent (13, 15)
When transformer windings are below the perature for which they were designed (because
tem-of low ambient temperature or because of a prior