Tài liệu xe ô tô hyundai excel toàn tập hyundai excel
Trang 1CONDITIONING SYSTEM
Return To Main Table of Contents
GENERAL 2
SERVICE ADJUSTMENT PROCEDURES 10
HEATER 30
VENTILATORS 37
COMPRESSOR 40
COOLING UNIT 58
CONDENSER 62
RECEIVER DRIER 63
CONDENSER FAN AND RELAY 64
A/CON RELAY AND RESISTOR 65
Trang 2G E N E R A L
SPECIFICATIONS (DKK)
Heater assembly
Type
Performance Kcal/h (B.T.U./h)
Heater control assembly
Air-mix, warm water type 3,800 (15,000)
Control knob Air-conditioning
Cooling capacity Kcal/h (B.T.U./h)
Compressor
Model
No of cylinders and displacement cc/Rev.
Maximum allowable speed
High pressure switch
Low pressure switch
Fusible plug
OFF: 2,647 kPa (384 psi, 27 kg/cm 2 ), ON: 2,059 kPa (299 psi, 21 kg/cm 2 ) OFF: 206 kPa (30 psi, 2.1 kg/cm 2 ), ON: 196 kPa (28 psi, 2kg/cm 2 ) 103°C (217°F)
Refrigerant and quantity gr (oz., lb) R-12, 850-1,000 (30-35, 1.9-2.2)
3,300 (13,000)
DKS - 15BH
6 cylinders, 153 7,000 rpm
Electromagnetic, single-plate dry clutch
DC 12V, 45W
850-900 rpm Fin mounted thermostat OFF: - 1° - 1°C (30° - 34°F) ON: 3° - 5°C (38° - 41°F)
SERVICE STANDARD
Air-conditioning
Amount of deflection of V belt
Engine idling speed
Clutch clearance
8-10 mm (0.3-0.4 in.) 850-900 rpm
Trang 3S P E C I F I C A T I O N S ( M A N D O )
Heater assembly
Type
Performance kcal/h (B.T.U./h)
Heater control assembly
Air-conditioning
Cooling capacity Kcal/h (B.T.U./h)
Compressor
Model
No of cylinders and displacement cc/Rev.
Maximum allowable speed
High pressure switch
Low pressure switch
Fusible plug
OFF: 2,647 kPa (384 psi, 27 kg/cm 2 ) ON: 2,059 kPa (299 psi, 21 kg/cm 2 ) OFF: 206 kPa (30 psi, 2.1 kg/cm 2 ), ON: 196 kPa (28 psi, 2 kg/cm 2 ) 103°C (217°F)
Refrigerant and quantity gr (oz., lb) R-12, 850-1,000 (30-35, 1.9-2.2)
Air-mix, warm water type 3,800 (15,000)
Control knob
3,300 (13,000) SD-709
7 cylinders, 155.
7,000 rpm Electromagnetic, signal-place dry clutch
DC 12V, 49W
850-900 rpm Fin mounted thermostat OFF: -1° - 1°C (30° - 34°F), ON: 3° - 5°C (38° - 41°F)
S E R V I C E S T A N D A R D S
Air-conditioning
Amount of deflection of V belt
Engine idling speed
Clutch clearance
8-10 mm (0.3-0.4 in.) 850-900 rpm
0.4-0.78 mm (0.016-0.031 in.)
LUBRICANTS
Heater assembly
Heater control lever Multipurpose grease
SAE J310a, NLGI grade #2
As required
Air-conditioner
Trang 4SPECIAL TOOLS
A: DKS-15BH B: SD-709
97-4
Trang 6(Number and name)
09977-21811
Bearing remover and
installer and pulley
Trang 7No ventilation even when
the mode control lever
Remedy Repair or replace the water valve
Incorrect adjust installation of warm Adjust the warm water flow water flow control cable control cable
Incorrect adjustment of water Adjust the mode control cable valve link
Incorrect adjustment of change over dampers
Loose duct connection
Adjust the mode control cable
Connect the duct securely or replace the packing
Foreign material inside blower Incorrect balance of blower motor or fan
Damaged blower Ventilator duct connection malfunction
Incorrect adjustment of inside/
outside air changeover damper
Remove foreign material Replace the blower motor or fan Replace
Connect the duct securely or replace the packing
Adjust the inside/outside fresh air changeover cable
Probable cause Blown “BLOWER” fuse Malfunction blower motor Faulty resistor
Malfunction blower control switch Open or loose connection in electric circuit
Obstruction in the inlet of the blower unit
Clogged evaporator
Frosted evaporator Leaking air
Remedy Replace
Replace Replace Replace Repair open-circuited point
Remove obstruction
Clean evaporator with compressed air Check thermostat Check for leakage on both sides of cooling unit and air ducts
Trang 8Malfunctioning dual pressure switch Malfunctioning thermostat
Malfunctioning A/C switch Malfunctioning blower switch Blown “A/C” fuse and/or “BLOWER”
fuse
Check operation Check operation Check operation Check operation Check operation Replace
Loose compressor drive belt Battery voltage too low Internal malfunction of compressor
Short circuit in the magnet coil Oil on clutch face
Gap between drive plate and pulley too large
Readjust Recharge battery Repair or replace compressor Replace Clean or replace clutch Adjust gap
Open or loose connection in electric Repair open-circuited
Remedy
Normal pressure are:
High pressure 1,470-1,760 kPa (213-256 psi, 15-18 kg/cm 2 ) Low pressure 190-290 kPa (28-42 psi, 1.9-2.9 kg/cm 2 ) When, ambient temperature 35°C (95°F) Engine speed 1,500 rpm Internal malfunction of compressor Repair or replace
compressor Faulty contact at sensing bulb of the
expansion valve Faulty insulation at sensing bulb of the expansion valve
Expansion valve opening is too large Insufficient refrigerant
Receiver-Drier clogged Expansion valve clogged Faulty thermostat Frosted piping
Repair Repair Repair Charge refrigerant Replace
Replace Check operation Clean or replace piping
97-8
Trang 9High pressure is too high
High pressure is too low
Insufficient cooling of the condenser Check and clean condenser
Malfunctioning condenser fan motor Check operation
Internal malfunction of compressor Repair or replace compressor
Trang 10SERVICE ADJUSTMENT PROCEDURES
CHECK AND ADJUSTMENT
After installation, check the following points and confirm that
everything is in order, and then charge the gas, adjust the idling,
and make the adjustment, performance test and the operation
test.
1 Check for any abnormal vehicle performance, etc which might
have been caused by installation of the equipment.
2 Check the magnetic clutch for operation (without turning the
Drive belt 7-9 mm (0.28-0.35 in.)
Air conditioner compressor belt 8-10 mm (0.32-0.40 in.)
97-10
Trang 11ADJUSTMENT OF FAST IDLE CONTROL DEVICE
(F.I.C.D)
The vacuum system is designed to perform the F.I.C.D raises
the idling speed of the engine ensure better to cooling when the
car is stationary.
1 Warm up the engine.
2 Make sure engine is at correct idling speed with air conditioner
in the “OFF” position.
3 Set the engine speed to the specified rpm by adjusting screw
with air conditioner in the “ON” position
Specified rpm: 850-900 rpm
4 Depress and release accelerator pedal several times, and make
sure that engine speed returns to the specified rpm.
Trang 12REFRIGERATION CYCLE
97-12
Trang 13A I R C O N D I T I O N E R C O M P O N E N T S
DUAL PRESSURE SWITCH
Low pressure control
When refrigerant pressure exceeds (206 kPa (2.1 kg/cm 2 , 30
psi), refrigerant pressure overrides the force of spring A In this
case, the metal diaphragm remains intact and the movable
contact point itself moves in the direction of the arrow, thereby
closing the contact point (1), turning on, resulting in normal
operation.
When refrigerant pressure falls below 196 kPa (2.0 kg/cm 2 , 28
psi), the force of spring A opens the contact point (1), turning off,
and therefore turning the compressor off.
High pressure control
When refrigerant pressure exceeds 2,647 kPa (27 kg/cm 2 , 284
psi), refrigerant pressure overrides the metal diaphragm
resist-ance The metal diaphragm deforms and moves the pin in the
direction of the arrow, thereby opening the contact point (2),
turning off, and therefore turning the compressor off.
When pressure falls below 2,059 kPa (21 kg/cm 2 , 300 psi), the
metal diaphragm returns to the original state, closing the
con-tact point (2), turning on, resulting in normal operation.
Trang 14SERVICE ADJUSTMENT PROCEDURES
SAFETY PRECAUTIONS
1 The R-12 liquid refrigerant is highly volatile A drop on the skin
of your hand could result in localized frostbite When handling
the refrigerant, be sure to wear gloves.
2 If the refrigerant splashes into your eyes, wash them with clean
water immediately It is standard practice to wear goggles or
glasses to protect your eyes, and gloves to protect your hands.
3 The R-12 container is a highly pressurized vessel Never leave it
in a hot place, and check to be sure that the storage temperature
is below 52°C (126°F).
4 A halide leak detector is often used to check the system for
refrigerant leakage Bear in mind that R-12, upon coming into
contact with flame (this detector burns like propane to produce
a small flame), produces phosgene, a toxic gas.
INSTALLATION OF MANIFOLD GAUGE SET
1 Close both hand valves of the manifold gauge fittings.
2 Install the charging hoses of the gauge set to the fittings.
Connect the low-pressure hose to the low-pressure service
port, and the high-pressure hose to the high-pressure service
port.
Tighten the hose nuts by hand.
NOTE
Fittings for attaching the manifold gauge set and located on
the compressor and the high pressure hose.
9 7 - 1 4
Trang 15HANDLING REFRIGERANT SERVICE TAP VALVE
1 Before connecting the valve to the refrigerant container, turn
the handle fully counterclockwise.
2 Turn the disc counterclockwise until it reaches its highest
position.
3 Connect the center hose to the valve fitting Turn the disc fully
clockwise by hand.
4 Turn the handle clockwise to make a hole in the sealed top.
5 Turn the handle fully counterclockwise to fill the center hose
with air Do not open the high-and low-pressure hand valves.
6 Loosen the center hose nut connected to the center fitting of the
manifold gauge.
7 Allow air to escape for a few seconds, and then tighten the nut.
DISCHARGING THE REFRIGERATION SYSTEM
1 Connect the manifold gauge set to the system.
2 Place the free end of the center hose on a shop towel.
3 Slowly open the high-pressure hand valve to adjust the
refrig-erant flow Open the valve only slightly.
CAUTION
If refrigerant is allowed to escape too fast, compressor oil
will be drawn out of the system.
4 Check the shop towel to make sure no oil is being discharged.
If oil is present, partially close the hand valve.
5 After the manifold gauge reading drops below 434 kPa (3.5
kg/cm*, 50 psi), slowly open the low-pressure hand valve.
6 As the system pressure drops, gradually open both the high-and
the low-pressure hand valves until both gauges read 0 kPa (0
kg/cm 2 , 0 psi).
Trang 16EVACUATING REFRIGERANT SYSTEM
NOTE
It is necessary to evacuate the air conditioning system any
time the system has been serviced to the extent that it has
been discharged Evacuation is necessary to rid the system
of all air and moisture that may have been allowed to enter
the unit.
After installation of a component, the system should be
evacuated for approximately 15 minutes A component in
service that has been opened for repair should be evacuated
for 30 minutes.
1 Engine should be off.
2 Connect manifold gauge set to compressor gauge fittings.
Close both high and low pressure valves.
3 Make sure refrigerant has been discharged from system.
4 Connect the center hose of the gauge set to the vacuum pump
inlet.
5 Start the vacuum pump and then open the high and low
mani-fold pressure valves.
6 After about ten minutes, check that the low pressure gauge
reads more than 94.39 kPa (0.96 kg/cm*, 13.7 psi) vacuum If
the pressure rises or the specified negative pressure can not
be obtained, there is a leak in the system In this case, repair
the leak as described in the following.
(a) Close both the manifold valves and stop the vacuum pump.
(b) Charge system with a can of refrigerant [about 0.4 kg (0.9
Ibs.)] Refer to Charging Refrigerant.
(c) Check for refrigerant leakage with a leak detector.
Repair any leakage found Refer to Checking Refrigerant
leak.
(d) Discharge refrigerant again, and then evacuate system.
If not leaks found, continue evacuating the system.
7 One again, operate the vacuum pump.
8 Open both manifold pressure valves to obtain 94.39 kPa (0.96
kg/cm*, 13.7 psi) of vacuum.
9 After low pressure manifold gauge indicates as close to 94.39
kPa (0.96 kg/cm*, 13.7 psi) as possible, continue evacuating
for 15 minutes.
10 After evacuating for 15 minutes, close both manifold pressure
valves and stop the vacuum pump Disconnect the hose from
the vacuum pump The system is new ready for charging.
97-16
Trang 17CHARGING REFRIGERANT SYSTEM (Vapor)
NOTE
This step is to charge the system through the low pressure
side with refrigerant in a vapor state When the refrigerant
container is placed rightside up, refrigerant will enter the
system as a vapor.
1 Install the refrigerant can tap valve as described in Handling the
Refrigerant Service Tap Valve section.
2 Open the low pressure valve Adjust the valve so that the low
pressure gauge does not read over 412 kPa (4.2 kg/cm*, 60 psi).
3 Put the refrigerant container in a pan of warm water (maximum
temperature 40°C or (104°F) to keep vapor pressure in the
container slightly higher than vapor pressure in the system.
4 Run the engine at fast idle, and operate the air conditioner.
CAUTION
Be sure to keep the container upright to prevent liquid
refrig-erant being charged into the system through the suction side,
resulting in possible damage to the compressor.
5 Charge the system with more than one container (400g, 0.9 lb)
to the specified amount Then, close the low pressure valve.
Specified amount: 0.85-1.0 kg (1.9-2.2 lb)
NOTE
A fully charged system is indicated by the receiver sight glass
being free of any bubbles.
When refrigerant charging speed is slow, immerse
refriger-ant can in water, heated to a temperature of about 40°C
(104°F).
WARNING
o Under any circumstances the refrigerant can must not be
warmed in water heated to a temperature of over 52°C
(125°F).
o A blow torch or stove must never be used to warm up the
can.
Trang 18CHARGING REFRlGERANT SYSTEM (LIQUID)
NOTE
This step is to charge an empty system through the high
pressure side with refrigerant in a liquid state When the
refrigerant container is held upside down, refrigerant will
enter the system as a liquid.
CAUTION
Never run the engine when charging the system through the
high pressure side.
Do not open the low pressure valve when the system is being
charged with liquid refrigerant.
1 Close both high and low pressure valves completely after the
system is evacuated.
2 Install the refrigerant can tap valve as described in Handling the
Refrigerant Service Tap Valve secton.
3 Open the high pressure valve fully, and keep the container
upside down.
4 Charge the system with more than one container (400 g, 0.9
lb) to the specified amount by weighing charged refrigerant
with a scale Overcharging will cause discharge pressure (high
side) to rise then, close the high pressure valve.
Specified amount: 0.85-1.0 kg (1.9-2.2 lb)
NOTE
A fully charged system is indicated by the receiver sight glass
being free of any bubbles.
If the low pressure gauge does not show a reading, the
sys-tem is clogged and must be repaired.
5 After the specified amount of refrigerant has been charged into
system, close manifold gauge valve.
6 Confirm that there are no leaks in system by checking with a
leak detector Refer to Checking Refrigerant Leak.
NOTE
Conducting a performance test prior to removing manifold
gauge is a good service operation Refer to Performance
Test.
COMPRESSOR OIL LEVEL CHECK
The oil used to lubricate the compressor circulates into system
from the oil pump while compressor is operating.
Whenever replacing any component of the system or when a
large amount of gas leakage occurs, add oil to maintain the
original total amount of oil.
Total amount of oil in the system:
150cc (5.1 fl oz, 5.3 Imp fl oz)
LOW HIGH
9 7 - 1 8
Trang 19Oil return operation
Before checking and adjusting oil level, operate compressor at
engine idling speed, with controls set for maximum cooling and
high blower speed, for 20 to 30 minutes in order to return oil to
compressor.
Checking and adjusting for used compressor
1 After oil return operation; stop the engine and discharge
refrig-erant and then remove compressor from the vehicle.
2 Drain compressor oil from the oil drain plug and measure the
amount.
Oil is sometimes hard to extract when compressor is cooled.
Remove oil while compressor is warm [maintained to
40-50°C (104-122°F).
3 If the amount is less than 90 cc (3.0 US fl oz, 3.2 Imp fl oz), some
refrigerant may have leaked out Conduct leak tests for
connec-tions of each system, and if necessary, repair or replace faulty
parts.
4 Check the purity of the oil and then adjust oil level following the
procedure below.
Pour in same amount of oil as was drained out
Pour in 90 cc (3.0, 3.2) of oil
Trang 20(b) Oil contains chips or other foreign material After air
condi-tioner system has been flushed with refrigerant, replace
receiver dryer Then pour 150 cc (DKK), 120-150 cc
(SD-709).
Charging oil of replacement component parts
When replacing the system’s component parts, be sure to
supply the following amount of oil to the component parts to be
Trang 21REFRIGERANT LEVEL CHECK
1 Start the engine and hold engine speed at 1,500 rpm.
2 Set A/C switch to “ON” position.
3 Set temperature lever to maximum cold position.
4 Set blower to maximum speed.
5 Check sight glass after the lapse of about five minutes Judge
according to the following table.
High pressure side is High pressure side is High pressure side is warm and low pressure hot and low pressure abnormally hot side is fairly cold side is cold
State in sight glass Bubbles flow
continu-ously Bubbles will disappear and some- thing like mist will flow when refrigerant
is nearly gone
The bubbles are seen
at intervals of 1-2 seconds
Almost transparent No bubbles can be Bubbles may appear seen
when engine speed is raised and lowered
No clear difference exists between these two conditions
Both pressure on high and low pressure sides are slightly low Check for gas leakage, repair as required, re- plenish and charge system
Both pressure on high and low pressure sides are normal
Both pressure on high and low pressure sides are abnormally high Discharge refrigerant from service valve of low pressure side
(a) The bubbles seen through the sight glass are influenced by
the ambient temperature Since the bubbles are hard to
show up in comparatively low temperatures below 20°C
(68°F), it is possible that a slightly larger amount of frigerant
would be filled, if supplied according to the sight glass Be
sure to recheck the amount when exceeds 20°C (68°F) In
higher temperature the bubbles are easy to show up.
(b) When the screen in the receiver drier is clogged, the bubbles
will appear even if the amount of refrigerant is normal In
this case, the outlet side pipe of the receiver drier becomes
considerably cold.
Trang 22HOSE AND PIPE CHECK
Check heater and air conditioner for damaged hoses or pipes
due to interference or friction with adjoining parts If damage is
minor, repair those affected hoses or pipes If damage is major
and if there is the possibility of encountering holes, replace the
affected parts.
Carefully check hoses and pipes, especially those located
close to moving parts or sharp edge of panel.
CHECKING REFRIGERANT LEAKS
Conduct a leak test with electric leak detector whenever
leak-age of refrigerant is suspected and when conducting service
operations which are accompanied by disassembly or loosening
of connection fittings.
Electric leak detector
The leak detector is a delicate device that detects small amounts
of halogen In order to use the device properly, read the
manuals put out by each maker and perform the specified
maintenance and inspections.
If a gas leak is detected, proceed as follows:
1 Check torque on the connection fitting and, if too loose, tighten
to the proper torque Check for gas leakage with a leak detector.
2 If leakage continues even after fitting has been retightened,
discharge refrigerant from system, disconnect the fittings, and
check its seating face for damage Always replace even if
dam-age is slight.
3 Check compressor oil and add oil if required.
4 Charge refrigerant and recheck for gas leaks If no leaks are
found, evacuate and charge system.
O F F - S E A S O N M A I N T E N A N C E
Even in the off-season, turn the compressor for 10 minutes at
least once a month by running the engine at idling rpm.
PROPANE LEAK DETECTOR
ELECTRIC LEAK DETECTOR
97-22
Trang 23PERFORMANCE TEST
1 Install the manifold gauge set.
2 Run the engine at 2,000 rpm and set the controls for maximum
cooling and high blower speed.
3 Keep all window and doors open.
4 Place a dry-bulb thermometer in the cool air outlet.
5 Place a psychrometer close to the inlet of the cooling unit.
6 Check that the reading on the high pressure gauge is
1,373-1,575 kPa (14-16 kg/cm 2 , 199-228 psi).
If the reading is too high, pour water on the condenser.
If the reading to too low, cover the front of the condenser.
7 Check that the reading on the dry-bulb thermometer at the air
inlet at 25-35°C (77-95°F).
8 Calculate the relative humidity from the psychrometric graph
by comparing the wet-and dry-bulb reading of the
psychrome-ter at the air inlet.
9 Measure the dry-bulb temperature at the cool air outlet, and
calculate the difference between the inlet dry-bulb and outlet
dry-bulb temperatures.
10 Check that the intersection of the relative humidity and
temperature difference is between the two hatched lines If
the intersection is within the two lines, cooling performance is
satisfactory.
Trang 24PERFORMANCE TEST DIAGNOSIS
The test gauge indicators shown on the following chapter are to be
used as typical examples of common problems which you may
Low side
NORMAL
High side NORMAL
and “OFF” cycle.
o Sight glass: Tiny bubbles.
o Discharge air:
Becomes warm as low side cycles into vacuum.
o Discharge air:
Becomes warm all the time during hot part of day.
o Compressor: Cycles
on and off too fast.
o Low side gauge:
Not enough range shown on low side gauge.
DIAGNOSIS Some air and mois- ture in system.
Excessive moisture in system
Defective thermostatic switch
CORRECTION
1 Leak test system.
2 Discharge refrigerant from system.
3 Repair leaks as located.
4 Replace receiver-drier The drier is probably saturated with moisture.
5 Evacuate the system for
5 Operate system and check performance.
1 Stop engine and turn air conditioner “OFF”
2 Replace thermostatic switch when installing new thermostatic switch, make sure that capillary tube is installed in the same position and to the same depth in eva- porator core as old switch tube.
3 Operate system and check performance.
9 7 - 2 4
Trang 25GAUGE READINGS
Low side
LOW
High side LOW
Low side
LOW
High side LOW
OTHER SYMPTOMS
o Compressor: low side pressure builds too high before compressor turn on (cycle “ON” point too high)
o Discharge air:
Slightly cool.
o Sight glass:
Some bubbles.
o Discharge air: Warm
o Sight glass: Clear
o Discharge air:
Slightly cool.
o Expansion valve:
Sweating or frost build up.
DIAGNOSIS Faulty thermostatic switch
o System slightly low on R-12
o System very low
on R-12
o Possible leak in system.
o Expansion valve stuck closed.
o Screen plugged.
o Sensing bulb mal- function.
so that no short circuiting can occured.
3 Operate system and check performance.
1 Check leaks.
2 Discharge refrigerant.
3 Repair leaks.
4 Check compressor oil level.
5 Evacuate system using a vacuum pump.
6 Charge system with R-12
7 Operate system and check performance.
1 Check leaks.
2 Leak test compressor seal area very carefully.
3 Discharge refrigerant.
4 Check compressor oil level.
5 Evaporate system using a vacuum pump.
6 Charge system with R-12.
7 Operate system and check performance.
1 Discharge system.
2 Disconnect inlet line
at expansion valve and remove and inspect screen.
3 Clean and replace screen and reconnect inlet line.
4 Evacuate system using a vacuum pump.
5 Charge system with R-12.
Trang 26GAUGE READINGS OTHER SYMPTOMS
Low side
LOW
High side LOW
Low side
HIGH
High side LOW
Low side
HIGH
High side HIGH
Low side
HIGH
High side HIGH
9 7 - 2 6
o Discharge air:
slightly cool.
o High side pipe:
Cool and also shows sweating or frost.
0 ssor malfunc- tion
Compre-o tioning condenser overch- arge.
Malfunc-0 Large amount
of air and moisture
CORRECTION
1 Discharge system.
2 Remove and replace receiver-drier, liquid pipes or other defective components.
3 Evacuate system using a vacuum pump.
4 Charge system with R-12
5 Operate system and check performance.
1 Isolate compressor.
2 Remove compressor der head and inspect compressor.
cylin-3 Check compressor oil level.
mount-4 Check for refrigerant overcharge.
5 Operate system and check performance.
1 Discharge refrigerant from system.
2 Replace receiver-drier which may be saturated with moisture.
3 Evacuate system using vacuum pump.
4 Charge system with R-12.
5 Operate system and check performance.
Trang 27o Expansion valve sutck open
CORRECTION
1 Discharge system.
2 Replace expansion valve, making sure all contacts are clean and secure.
3 Evacuate system using vacuum pump, then rech- arge system with R-12.
4 Operate system and check performance.
Trang 28AIR CONDITIONING INSTALLATION
PRECAU-T I O N S
1 Refrigerant Lines
(a) Always use two wrenches when disconnection or
connect-ing lines.
(b) Protective plugs are used to prevent contamination and
moisture from entering disconnected air conditioning
com-ponents and lines Always install plugs on fittings that are
exposed to the atmosphere.
(c) Clean contaminated o-rings during installation Never use
compressed air.
(d) Use only new o-rings during installation.
The o-ring should be lubricated with compressor oil to the
area shown.
(e) Install the o-ring against the shoulder to ensure proper
seating as shown.
(f) Insert tube into union First tighten nut by hand as much as
possible Then, tighten nut to specified torque.
Trang 292 Compressor
Compressor oil and during agent (n 2 ) are sealed in the
compres-sor and attention must be paid to the following.
(a) During handling and installation, the compressor must be
kept perfectly level.
If you suspect that the compressor has not been kept level,
manually rotate the compressor shaft 5 to 6 times before
installing to return any oil at the head of the compressor to
the oil reservoir If the compressor is started suddenly with
the oil in the compressor head, the valve may be damaged.
(b) Do not remove plugs from fittings just prior to connecting
lines.
3 Condenser
(a) The condenser is made completely of aluminium, so be
careful not to damage the tube or fins.
(b) When connecting pipe, tighten initially by hand, then be
sure to use two wrenches to tighten.
If tightened with only one wrench, the outlet/inlet port will
be strained, causing gas leakage or damage to the line or
condenser.
4 Receiver-drier
The receiver drier contains dry agent (N 2 ) desiccant, etc
Atten-tion must be paid to the following points.
(a) Do not remove plugs until just before connecting.
The connection of the outlet and inlet port of the
receiver-drier is the final step of the pipe installation procedure.
(b) Do not mistake the inlet (Marked IN) and the outlet
connec-tions.
Trang 30HEATER KIT
9 7 - 3 0
Trang 31O P E R A T I O N
The door (D1) is used to select either fresh air from (a) On setting the lever to “VENT” position, air flows
Setting the RECIRC/FRESH control lever to “FRESH” (b) On setting the lever to “BI-LEVEL” position, air position, will allow outside air to enter Setting the flows to the ventilator outlets, to the floor outlets RECIRC/FRESH control lever to “RECIRC”, will allow and to the defroster outlets.
inside air to recirculate (c) On moving the lever to “HEAT” position, air flows
2 The door (D2) is always opened and admitting
recir-culated air regardless of the position of D1 door.
3 Outlet air flow is controlled by the doors (D4, D5 and
D6).
The mode control lever opens and shuts the doors
(D4, D5 and D6) and establishes the air passage
according to the lever position.
to the floor outlets and to the defroster outlets (d) On moving the lever to “DEF” position, air flows to the defroster outlets.
4 The cooling or heating temperature is controlled by the door (D3) The door (D3) is connected to the tempera- ture control lever by a cable.
(The water valve is also connected to the temperature control lever by a cable.)