Transformer Parts and Their Possible Faults Transformer diagnostic set: see pages 6-21 Dielectric response analysis instrument: see pages 22-23 Frequency response analysis instrument: se
Trang 1Diagnostic Testing Solutions for Power Transformers
Trang 2testing during manufacturing
factory acceptance testing
commissioning acceptance testing
Prevention is Better than Cure - Know More About the Condition of Your Transformer
Taking the right action at the right time
> periodic testing
> testing after an event - relocation, protection trip or warning, overcurrent, overvoltage, earthquake
Keep your transformer in good condition
with testing
factors causing deterioration
mechanical impacts
>transportation event
>post fault event
>seismic activity event
Trang 3Prevention is Better than Cure - Know More About the Condition of Your Transformer
replacementoperation
> periodic testing
> testing after an event - relocation, protection trip or warning, overcurrent, overvoltage, earthquake
Keep your transformer in good condition
>pumps, fans, etc
and subsequent preventive actions
transformer life expectancy
Trang 4Transformer Parts and Their Possible Faults
Bushings
Partial breakdown between capacitive graded layers,
Bushing CTs Current ratio or phase error considering burden, excessive residual magnetism, non-compliance to relevant IEEE or IEC standard xInsulation materials
Aging, moisture, contamination of insulation fluids x x x
preventative autotransformer, series autotransformer or series transformer x x x
Windings
Core
Trang 5Transformer Parts and Their Possible Faults
Transformer diagnostic set:
see pages 6-21
Dielectric response analysis instrument:
see pages 22-23
Frequency response analysis instrument:
see pages 24-25
Partial discharge analysis system:
Bushings
Partial breakdown between capacitive graded layers,
Bushing CTs Current ratio or phase error considering burden, excessive residual magnetism, non-compliance to relevant IEEE or IEC standard xInsulation materials
Aging, moisture, contamination of insulation fluids x x x
preventative autotransformer, series autotransformer or series transformer x x x
Windings
Core
Notes:
1) Power factor / dissipation factor measurements at 50 Hz or 60 Hz can detect high moisture contents, but have a blind spot for low moisture contents Measuring power factor / dissipation factor at
Trang 6All in One: the Multi-Functional Transformer Test Set CPC 100 / CP TD1
Leakage reactance/short-circuit impedance measurement instrument
DC winding resistance measurement instrument
I
Frequency response of stray losses measurement instrument
winding strands
TRV
I
+ more substation diagnostics
> Ground impedance measurement
> Line impedance and ground factor
in wave form and frequency
Weight of units
CPC 100: 29 kg / 65 lbs
CP TD1: 26 kg / 56 lbs
Trang 7All in One: the Multi-Functional Transformer Test Set CPC 100 / CP TD1
IR ICV
I
Insulation
+ more substation diagnostics
> Current transformer testing
> Voltage transformer testing
Power factor / dissipation factor measurement instrument
Transformer ratio measurement instrument
Transformer exciting current test instrument
f
coreI
Trolley
to conveniently transport:
CPC 100,
CP TD1, measurement cable, high voltage cable
Trang 8Surge arresters Bushings OLTC Leads Insulation materials Windings Core
Capacitance and power factor / dissipation factor (PF / DF) measurements are performed
to investigate the condition of bushings as well
as the transformer overall insulation Aging and decomposition of the insulation, or the ingress
of water, increase the energy that is turned into heat in the insulation The level of this dissipation
is measured by the PF / DF
On surge arresters, currents and watt losses of identical units can be compared Deviations may indicate aging effects, poor contacts or open circuits between elements
Capacitance values of bushings show if there
have been breakdowns between capacitive
layers For resin bonded paper bushings, cracks
into which oil has leaked, can also change the
value of the capacitance
A rise in capacitance of more than 10 % is
normally considered to be dangerous, since it
indicates that a part of the insulation distance is
already compromised and the dielectric stress to
the remaining insulation is too high
Preventing bushings from exploding
Increased heat dissipation accelerates the
aging of the insulation If an aged insulation
can no longer withstand the electrical stress,
bushings explode
Better understanding of losses
At line frequency, conductive losses can be
represented with a parallel equivalent circuit
Polarization losses can be represented by a series
equivalent circuit consisting of an ideal capacitor
and a resistor
Increased losses may pass a test at line
frequency unnoticed, leaving the tester unaware
of an insulation in distress Measuring the DF /
PF over a broad frequency range helps to better
understand both types of losses
Measuring Capacitance & Power Factor / Dissipation Factor
Typical loss shapes in 15 - 400 Hz range
conductive lossespolarization losses
superposition of both effects
equivalent circuits *)
typical loss shapes
Damaged TR after bushing explosion
Capacitive layers in bushings
Trang 9Measuring Capacitance & Power Factor / Dissipation Factor
High voltage is applied to the insulation to
be tested, i.e the bushing tip, and a low loss reference capacitor (integrated in CP TD1) is connected in parallel The currents flowing through the insulation and through the reference capacitor are measured and the time difference between their zero crossings is determined The loss angle d
is then calculated from this time difference The tangent of this angle is the dissipation factor The cosine of the angle between voltage and current is the power factor Results are compared with values given in IEEE C57.10.01 and IEC 60137, and can
be compared with a base measurement, another phase, or a sister transformer
If values deviate more than indicated by the standards, then dielectric response analysis can be performed to check for increased moisture
Chemical tests can be performed to verify the quality of the insulation fluid (DGA, dielectric breakdown strength, interfacial tension, etc.) Measuring the power factor / dissipation factor of the insulation fluid can also be done with a CPC 100 accessory, the
CP TC12 oil test cell
Capacitive layers in bushings
CA
center conductor
grounded layer and tap electrode
on flange
OIP bushing: PF / DF tip up test
*) at 50 / 60 Hz and 20 °C
Dissipation factor / power factor in % *)
OIP bushing: PF / DF variable frequency test
Trang 10Measuring Capacitance & Power Factor / Dissipation Factor
Power factor / dissipation factor (PF / DF)
measurement indicates the condition of the
liquid and solid insulation within a transformer
Power and accuracy
The CPC 100 / CP TD1 can measure capacitance
and PF / DF (tan d) in laboratories, test fields
and on site
A powerful test voltage source (12 kV, 100 mA
continuous, 300 mA short-term load current)
with variable frequency (15 - 400 Hz), combined
with high accuracy measuring inputs allows fast,
effective and accurate measurements
Prepared test procedures can guide the user
through the testing process and offer a basis for
comprehensive reporting
Modular equipment
The modular equipment (CPC 100: 29 kg /
65 lbs, CP TD1: 26 kg / 56 lbs) can be easily
transported thanks to its sturdy cases, which
can also be used to place the instruments onto
them for working at a comfortable height, as
shown on page 12
For convenient transport or mobile use such as
in test fields or in substations/power plants, the
instruments can be mounted onto a trolley
The CPC 100 is used to control the test, i.e.:
> entering the voltage and frequency values
where C and cos j / tan d shall be measured
> starting and stopping the test
> supervising the measurement progress and
intermediate results
> storing results on flash disk and
USB memory stick
The CP TD1 includes
> a high voltage step-up transformer
> a reference capacitor (pressurized gas type)
> the unit to measure and compare currents in
amplitude and phase
Power factor / dissipation factor tip up results
Energize HV to measure CH + CHL | CH | CHL, then energize LV to measure CL + CHL | CL | CHL - thanks to internal switching logic with guard
LV
IN A
Trang 11Measuring Capacitance & Power Factor / Dissipation Factor
Your Benefits
> perfect digitally generated sine wave test signal that is independent from power quality and line frequency
> laboratory precision for on-site use:
< 0.05 % error for capacitance Cp
> automatic tests at different voltages
> automatic tests at different frequencies: early detection of insulation stress due
to the improved sensitivity provided by measurements made in the range of
> temperature correction according
to type of insulation and relevant standard
> internal recalibration of electronic circuits of the CP TD1 with each measurement
> automatic reporting of capacitance
Cp, DF (tan d), PF (cos j), power (active, reactive, apparent), impedance (absolute value, phase, inductivity, resistance, Q)
> automatic assessment if reference values for capacitance and power factor / dissipation factor are known
> less wiring effort through two measurement inputs (IN A, IN B) that can be used to measure for example the capacitance of a bushing at the same time as the main insulation
Energize HV to measure CH + CHL | CH | CHL, then energize LV to measure CL + CHL | CL | CHL - thanks to internal switching logic with guard
Trang 12Measuring Ratio & Exciting (No-Load) Current
Ratio measurement with the CPC 100
The CPC 100 measures the transformer ratio by
applying a high voltage at the HV winding of
one transformer leg In amplitude and phase, it
measures the applied voltage and the voltage at
the LV winding, as well as the exciting (no-load)
current The deviation from rated values is
displayed as a percentage
Measuring ratio per tap
The CPC 100 measures ratio and excitation
current at each tap position Each time the
user operates the tap changer, the CPC 100
automatically starts a new measurement and
measures and displays ratio, phase angle, and
for each tap, the deviation from nominal ratio is
displayed as a percentage
For automatically measuring winding resistance
and ratio of all phases and all taps, see page 16
The measurement is performed for assessing possible winding damage, such as turn-to-turn short circuits, comparing the measured ratio and magnetizing currents to specifications, factory measurement results, and/or across phases
In the factory, this measurement is performed to verify that ratio and the vector group is correct
Setup for automatically measuring ratio and resistance per tap (see page 16)
Trang 13Measuring Ratio & Exciting (No-Load) Current
Setup for automatically measuring ratio and resistance per tap (see page 16)
of the mains wave form
> convenient and quick testing by automatic detection of tap changer operation as trigger for the next tap measurement
> exciting current measurement
in amplitude and phase
> variable frequency for measurements outside mains frequency for noise suppression,
if selected by the user
> accuracy and safety
> automatic reporting of measured voltage values and phase angles, measured ratio and deviation as
a percentage, exciting current in amplitude and phase
> tabular and graphical result representation for every tap
The winding ratio between primary and secondary windings is measured for each transformer leg, applying high voltage at the
HV side and measuring on the LV side The ratio
of these voltages, equalling the turns ratio, is calculated Results are compared with name-plate values and across phases
The exciting current is the corresponding current flowing in the HV winding if the LV winding is open Results are compared with a reference measurement, or a measurement performed on
a sister transformer; in three phase transformers, the two outer phases can also be compared
With the turns-ratio test, shorted turns can
be detected If a problem is suspected from
a DGA, a dissipation factor test, or a relay trip, a turns-ratio test can be performed to rule out / verify if turns are shorted
If the exciting current test shows deviations, and DC winding resistance and ratio test do not show errors, then the cause may be a core failure or unsymmetrical residual flux
CPC 100 TRRatio test card
Exciting current [mA] per tap
Trang 14Winding resistance per tap
Measuring DC Winding Resistance and OLTC
Measuring resistance with the CPC 100
The CPC 100 injects DC current into the
winding, measures current and voltage and then
calculates and displays the resistance When the
resistance value is stable, the CPC 100 makes the
final measurement, and reduces the test current
to zero to discharge the energy saved in the
winding When it is safe to remove test leads,
the CPC 100 illuminates its green safety light
Tapped windings and OLTC
In semi-automatic mode, the CPC 100 measures
the resistance of each subsequent tap position
Each time the user operates the OLTC, the
CPC 100 waits until the values stabilize, and
then measures and displays the winding
resistance at this tap position When all taps
have been measured, the CPC 100 discharges
the inductive energy stored in the winding and
indicates when this process is completed For
automatically measuring static and dynamic
winding resistance and ratio of all phases and
all taps, see page 16
Dynamic resistance measurement
The OLTC has to switch from one tap position
to another without interrupting the load
current When switching the tap changer during
winding resistance measurement, the DC current
temporarily decreases This current decrease
should be measured and compared across
Winding resistance measurements are performed for assessing possible winding damage It is also used to check the On-Load Tap Changer (OLTC) - to know when to clean
or replace OLTC contacts, or to know when
to replace or refurbish the OLTC itself, which has a shorter life span than the active part of the transformer
In the factory, this measurement is performed to calculate the I2R component of conductor losses and to calculate winding temperature at the end
of a temperature test
Table in CPC 100 TRTapCheck test card
Switching process
Trang 15Measuring DC Winding Resistance and OLTC
Slope per tap
Ripple per tap
Your Benefits
> convenient and quick testing by using OLTC operation as a trigger for the next tap measurement
> additional condition assessment of the individual OLTC taps through dynamic resistance measurement, recorded
as a part of “classical” resistance measurement, without extra effort
> high accuracy and safe testing through the use of a 4-wire connection The CPC 100 visually indicates when it
is safe to remove test leads, even
if its power supply is interrupted during testing If the test leads are removed or interrupted accidentally, the test current will flow through the voltage path, preventing dangerous overvoltages If the CP SA1 accessory
is in use during such an accidental interruption of test leads, damage to the CPC 100 will be prevented
> automatically created report showing the test duration, the resistance value at measurement and reference temperature, etc
> tabular and graphical results are produced for every tap for easy visual comparison
To measure the winding resistance, the winding under test must first be loaded with energy (E=1/2*L*I2) until the inductance of the winding is saturated Then the resistance can be determined by measuring DC current and DC voltage For tapped windings, this should be done for every tap position, hence testing the OLTC and the winding together
Results should be compared to a reference measurement, across phases, or with a sister transformer In order to compare measurements, the resistance values have to be re-calculated,
to reflect different temperatures during the measurements
Results should not differ more than 1 % compared to the reference measurement Differences between phases are usually less than 2 - 3 %
Transformer turns ratio or frequency response analysis can be used to confirm contact problems In both cases, hot spots
in the transformer will result in a DGA indicating increased heat However, gas signatures are not unique and thus do not allow for the identification of the root cause
Burn-off at a diverter switch
Switching process
Trang 16Automatically Measuring Ratio & Winding Resistance of All Taps and All Phases
Using the CP SB1 accessory, the CPC 100 can
automatically
> measure ratio and the exciting current of all
of the taps and all phases
> confirm the vector group
> measure static and dynamic winding
resistance of all of the taps and all phases
This accessory helps to save a lot of time as
wiring is only necessary once With the same
cabling, both ratio and resistance measurements
can be performed
Through the CP SB1, the CPC 100 is connected
to all phases of a transformer The up and down
command inputs of the OLTC are also connected
and controlled by the CPC 100 and the CP SB1
Ratio measurement
The CPC 100 only requires the user to enter
ratio and the vector group to measure the
ratio and the exciting current for each tap of
each phase automatically For each tap, results
are compared to the specified ratio and the
deviations are displayed
Winding resistance measurement
With the CP SB1, the CPC 100 injects DC current
into each tap of each winding The CPC 100
then waits for the current to stabilize and
measures the resistance value, as well as the
data describing the switching process (dynamic
resistance measurement)
The tap changer is then operated automatically
until the measurement on one transformer
phase is finished Between measuring the
different phases, the energy stored in the
windings is quickly discharged When the
windings are fully discharged, the CPC 100 /
CP SB1 automatically switches to the next phase
At the end of the measurement, the last winding
is discharged and the operator is notified visually
that it is safe to remove the wiring
LV