Licensee Conditions of use This is a licensed electronic copy of a document where copyright is owned or managed by Standards Australia International.. You may also make one paper copy
Trang 1Licensee
Conditions of use
This is a licensed electronic copy of a document where copyright is owned or managed by
Standards Australia International Your licence is a single user licence and the document may not
be stored, transferred or otherwise distributed on a network You may also make one paper copy
of this document if required.
Web Check-up
AS 1851.6 Supp 1-1997 Maintenance of fire protection equipment - Management
procedures for maintaining the fire and smoke control features of air-handling
systems - Typical maintenance schedule (Supplement to AS 1851.6-1997)
Licensed to LUU MINH LUAN on 25 Feb 2002
Trang 2MAINT EN AN CE OF FIRE PROT EC TION EQU IPME NT PAR T 6: MAN AG EM ENT PRO CE DU RE S FOR MAINT AINING THE FIRE AN D SMOK E CON TR OL FEAT UR ES OF AIR-HAN DL ING
SYSTE MS—T YPICAL MA INTE NA NC E SCHE DU LE (SUPPLEME NT TO AS 1851.6—1997)
A S 1851.6 Supp 1 Tabulated version of maintenance schedule of
A S 1851.6—1997 ITEM DESCRIPTION MONTHLY QUARTERLY HALF-YEARLY YEARLY TWO-YEARLY FIVE-YEARLY
As requir ed, or when unable to perf orm duty,
or if inspection indicates necessity
FANS
SUPPLY AN D RETU RN AI R
L evel 1
(a) C heck beari ngs for noise and overheati ng
(b) C heck fans for exce ssive vibration
(c) C heck guards a nd other safe ty featu res for sati sfac tory
c ondition
(d) C heck fan belts for wea r
(e) C heck flexi ble co nnec tions,
w here fitted , for l eaks , t eari ng
or fraying
L evel 2
(a) C heck l ubricati on of bea rings and
a pply as ne cess ary
(b) C heck fan belts for correct
t ensi on
(c) C heck c ouplings for t ightness (d) O n fan e nergizat ion, ope rati on
a nd de-ener giza tion, che ck t hat
t he flexi ble con nect ions are not overstres sed owing to fan movement
L evel 3
(a) C heck pulle y whee ls for
a lignment (b) C heck c ouplings for a lignment (c) V erify t hat fan output meet s desig n requi reme nts
L evel 4
(a) C heck c asin g an d i mpel ler for
c orrosion and treat as nec essa ry (b) C heck balan ce of impe ller if work
c arried out on it
(c) C heck l ubricati on of bea rings and
a pply as ne cess ary
(d) C heck fan belts if a pplicabl e (e) C heck reass embl ed unit for
e xces sive vibration (f) C heck t hat guards an d other s afet y featu res are s atis fact ory (g) C heck for co rrect rotati on (h) Measu re a nd rec ord fan output (i) R epai r or replac e fle xible
c onnectio ns as nece ssary
SMOK E-SPILL
A ND A IR PRESSU RIZ A-TION
L evel 1
(a) C heck beari ngs for noise and overheati ng
(b) C heck fans for exce ssive vibration
(c) C heck guards a nd other safe ty featu res for sati sfac tory con diti on
(d) C heck fan belts for wea r
(e) C heck flexi ble co nnec tions, wher e fitte d, for le aks, tea ring or fraying
L evel 2
(a) C heck l ubricati on of bea rings
a nd app ly as ne cess ary
(b) C heck fan belts for correct
t ensi on
(c) C heck c ouplings for t ightness (d) O n fan e nergizat ion, ope rati on
a nd de-ener giza tion, che ck t hat
t he flexi ble con nect ions are not overstres sed owing to fan movement
L evel 3
(a) C heck pulle y whee ls for
a lignment (b) C heck c ouplings for a lignment (c) V erify t hat fan output meet s desig n requi reme nts
MOTO RS, IN DUC TION
FANS DRI VES , FREQ UE NT U SE
L evel 1
(a) C heck for noisy running
(b) C heck for ex cess ive vibration
(c) C heck for ex cess ive he atin g
L evel 2
(a) C heck t hat ex ternal vent ilat ion
a irwa ys are clea r
(b) A pply lubricat ion if nece ssary
L evel 3
(a) Measu re a nd rec ord i nsulatio n resis tanc e of s tato r wind ings
N OTE: Manufactu rer’s
c auti onary notes should be observed espe cial ly whe re solid
s tate devi ces are use d
(b) Measu re a nd rec ord running
c urrent
(c) C heck s tart er, protect ion
s etti ngs, con tact s and t erminals
w here ap propriat e
L evel 4
(a) O verhaul or replace with ex chan ge unit
(b) Measu re a nd rec ord t hermisto r resis tanc es wher e fitte d (c) Test run
(d) Measu re a nd rec ord i nsulatio n resis tanc e of s tato r wind ings
FAN DR IVE S, TEST AN D EMER GE NCY
U SE O NLY
L evel 1
(a) C heck for noisy running
(b) C heck for ex cess ive vibration
(c) C heck for ex cess ive he atin g
L evel 2
(a) C heck t hat ex ternal vent ilat ion
a irwa ys are clea r
(b) A pply lubricat ion if nece ssary
L evel 3
(a) Measu re a nd rec ord i nsulatio n resis tanc e of s tato r wind ings
N OTE: Manufactu rer’s caut iona ry notes should be observe d
e spec iall y wher e solid sta te devic es are used
(b) Measu re a nd rec ord running
c urrent
(c) C heck s tart er, protect ion se ttin gs,
c onta cts an d te rminals wher e
a ppropriate
BATT ER IES FOR FIRE/
SMOKE CO NT ROL
SERV IC ES
V ENT ED CE LLS C arry out maint enan ce in acco rdance with the provisions of AS 2676.1 or NZS 4512 a s a pplicabl e
SEAL ED CE LLS C arry out maint enan ce in acco rdance with the provisions of AS 2676.2 or NZS 4512 a s a pplicabl e
Trang 3FIRE DAMPERS (INCL UDING INTUM ESCENT
D AMP IERS)
(a) Inspect for obstructi ons
(b) C onfirm positio n c orrect
N OTE: Inspect 20% of the tota l
s o t hat al l fire da mpers ha ve been
c overed at the end of the fifth
i nspectio n
(a) C heck for co rrosion
(b) C heck t hat mounting is s ound
(c) C heck t hat integrity of fire w all
i s not impa ired wher e ap plic able (d) C heck c orrect ope rati on (excl uding intumesc ent fire dampe rs)
(e) R esto re t o c orrect posit ion (excl uding intumesc ent fire dampe rs)
R epla ce as a ppropriate
FIRE MO DE AIR D AMP ERS FOR SMOKE
SPILL, FRESH AI R AND RE CYC LE A IR ,
COMP LETE WI TH THE IR AU TO MAT IC
CONT RO L G EAR
L evel 1
(a) Inspect for obstructi ons
(b) Ensure drive force is ava ilab le from t he motors
L evel 2
(a) Ensure da mper(s) moves t o its fire mode posit ion upon removal
of pow er source
(b) C heck t hat there is no ex cess ive
l eaka ge past dam pers when in the
c lose d position
(c) C heck a nd ad just a ll motor drive
l inka ges and en sure no ‘slippage’
or exc essi ve hysteres is i s occur ring
(d) C heck l inka ge and da mper beari ngs a nd l ubricate as neces sary
(e) Ensure that a ny damper positio n
i ndic ators are ope rati onal and
c orrectly posit ione d wh ere fitted
(f) If motors are pneumatic , c heck for air l eaks in the air l ines and
c onnectio ns
(g) If co ntrol system is pne umat ic,
c heck for c orrect ope rati on of a ir
c ompresso rs, filters, dryers and pressure reducing systems
L evel 4
R epla ce as a ppropriate
A UTO MA TIC SMO KE DET ECT OR S FOR
FIRE /SMOK E CONT ROL SERV ICE S C arry out maint enan ce in acco rdance with the provisions of AS 1851.8 or NZS 4512 a s a pplicabl e.
AIR FILTERS
L evel 1
(a) Inspect upstream and downstre am
of the filter an d remove any la rge
i tems obstructin g the ai r flow
(b) C heck filte r inte grity (filter
s eali ng) and any signs of filte r deter ioration
L evel 3
(a) C heck t he pressure differential
a cross the filter aga inst t he filter manufactu rer’s instruction
(b) C heck t hat an y adh esiv e liquid or
c oati ng be ing used has been
s upplied i n a cont aine r indicati ng
a c erti fied flas hpoint not les s than
160°C
L evel 4
(a) R epla ce filter s a s per manufactu rer’s instructions (b) R enew any liq uid and recoa t
a ny coa ting using an adh esiv e
w ith a cert ifie d fla shpoint not
l ess than 160°C Re plac e any fabric w ith correct type or was h
a s app ropriate
ELECTR IC DUCT HE ATE RS
L evel 1
(a) C heck t he outside s urface of the heate r casi ng for disc olourati on
or any indicat ion that ove rhea ting has take n plac e
(b) C heck for an y l oose exte rnal
c onnectio ns an d fitti ngs
L evel 2
(a) C heck for an y l oose inte rnal
t hermal i nsulatio n
(b) C heck t he ele ment s for obstructi ons and a ccum ulat ion of foreign matt er
(c) C heck t hat the heat er sw itch es off upon sw itch ing off the fan
(d) C heck opera tion of ai rflow
s ensi ng dev ice by sim ulat ing l oss
of air flow
(e) C heck opera tion of
over-t empe raover-ture cu over-touover-t by s imulaover-tin g overheati ng of t he heate r bank
L evel 4
R epai r or replac e as nec essa ry
K ITC HE N EXH AUS T SY STEMS
NOTE : Fire protection or s uppressi on sys tems
installed wit hin kitchen exhaust s ystems may have
special requirements.
L evel 1
(a) C heck greas e-arrest ing filters for
e xces sive greas e a ccum ulat ion
(b) C heck hood a nd its exha ust plenu m for exc essi ve greas e
a ccum ulat ion
(c) C heck t hat grease -arresti ng filte rs
a re s ecur ed i n posit ion a nd free
of dam age
(d) C heck greas e gutter s for an y
e xces sive greas e a ccum ulat ion
L evel 3
(a) C lean hood and i ts ex haust plenu m
(b) C heck for ex cess ive ai r l eaks a t greas e-arrest ing filte rs
(c) C heck duct for accu mula ted greas e and clea n it
L evel 2
C lean grease- arrestin g filters
N OTE: O wing to t he wi de varia tion i n usa ge, the frequenc y
of thi s routine is subject to the requi reme nts of t he regulato ry
a uthority This is a ca se whe re a Level 2 routine may be more frequent than a Level 1 in some
c ircumsta nces
L evel 4
R epla ce an y damag ed grease -arresti ng filte rs
Trang 4MAINT EN AN CE OF FIRE PROT EC TION EQU IPME NT PAR T 6: MAN AG EM EN T PRO CE DU RE S FOR MAINT AINING THE FIRE AN D SMOK E CON TR OL FEAT UR ES OF AIR-HAN DL ING
SYSTE MS—T YPICAL MA INTE NA NC E SCHE DU LE (SUPPLE ME NT TO AS 1851.6—1997)
A S 1851.6 Supp 1 Tabulated version of maintenance schedule of
A S 1851.6—1997 ITEM DESCRIPTION MONTHLY QUARTERLY HALF-YEARLY YEARLY TWO-YEARLY FIVE-YEARLY
As requir ed, or when unable to perf orm duty,
or if inspection indicates necessity
A IR- HA NDL ING CHAN GE OVE R UN DE R
FIRE /SMOKE COND ITI ON S
N OTES :
1 These routines a re to en sure sati sfac tory c hangeove r and
opera tion of t he air -handling install atio n The maint enan ce of
a re c overed under the routines for t he individual ite ms
2 A rrangeme nts should be made for the Fire Brigad e t o be
notified w hene ver a n auto mati c a ctiv atio n tes t is to be
c onducted t o adv ise that the al arm wil l sound and t o advi se
t hat the system may be inoperat ive for a cert ain ti me
L evel 1
(a) S imulate fire/sm oke s itua tion (for each system whe n sepa rate )
t o e ffect cha ngeover or shutdown
a s app ropriate
N OTE: The purpose of a
s imulated tes ting routine i s t o
c heck the functi oning of the ai r-handl ing chan geover system
c omplete wi th it s asso ciat ed dedic ated s moke detec tor cir cuit s
It is not recom mended practi ce in
t his ca se t o si mula te the fire/ smoke s itua tion by bringing a heat, flame or smoke source up to
t he detec tors
(b) S witc h system back to ‘normal’
a nd che ck that a ll e quipment i s i n
t he c orrect desig nate d mode
(c) C heck t hat ap propriat e indica ting
l ights si gnify normal opera tion
C heck t he followi ng during au toma tic
a ctiv atio n of fire/ smoke con diti ons
L evel 2
(a) Each it em of e quipment a nd any
a ssoc iate d indicat ors ha ve opera ted correct ly a nd t hat fans
a ccor danc e wit h the correct opera tional s eque nce for the air-handl ing system(s) c once rned
(b) Motorized outside -air, recyc
le-a ir, le-air-cont rol le-and spill-le-air dampe rs and thei r asso ciat ed motors are ope rati ng correct ly
(c) O pera tion of the ma nual sw itch provided for fire brigade personnel de -ene rgizes s
upply-a ir fupply-ans
(d) The system pe rformanc e criter ia
of zon e smoke c ontrol systems
s hould be verified bet ween ea ch
z one
N OTES :
1 W here t here hav e been no
c hanges to the building
s tructure, int erna l l ayout and
a ir-handl ing system in t he period sinc e the last te st,
a pproval may be given t o
t esti ng l ess than al l zon es
W here a pproval is given to
t esti ng a proportion of z ones
a repre sent ativ e number of
z ones s hould be te sted Te st
z ones s hould be se lect ed a t
t he e xtremes of the s yste m performance criter ia
2 W hen te stin g i s c arried out
on a proportional number of
z ones basis it i s recom mended t hat the sam e
z ones be sele cted an d test ed
e ach t ime
3 The purpose of an aut omat ic
t esti ng routine is to ch eck the funct ioning of the air -handl ing chan geover system
by the ac tiva tion of a fiel d devic e It is reco mmen ded pract ice in this c ase to bring
a heat, flame or smoke
s ource t o t he dete ctor or t o flow w ater a nd reduce pressure to ope rate flow/ pressure sw itch es
4 S ome buildings may have
s tand by pow er gen erat ion provisions w hich a re required
t o opera te fire a nd s moke
c ontrol eq uipment and
c ontrols in t he e vent of a normal powe r failu re
Level 2 routine main tena nce
s hould the refore a lso incl ude
t esti ng under st andby power
t o verify fire mode performance
L evel 4
(a) A djust or repair as neces sary (b) C arry out t he Level 2 routines
Trang 5FIRE -ISOL ATE D ESCAPE
ROUT ES PRO TEC TED BY
A IR- PRESSURI ZA TIO N
SYST EMS
(a) S imulate ini tiat ion of opera tion of
a ll system s
(b) W hile al l air -pressurizat ion
s yste ms a re operatin g, ch eck t he following for each system:
(i) Exces sive noise (Re fer
A S 1668.1.) (ii) Ease of opening doors
(iii) Movement of ai r from each pressurized are a t hrough a
s elec ted open door
N OTES :
1 In order to as sess the performance of t he system,
i t is recom mended that the
s ame door be used e very
t ime
2 The use of an elem enta ry
s ensi ng dev ice, e g ribbon,
i s sufficient (c) S witc h al l systems ba ck to normal
(a) C heck t hat the fans of all air -pressurizatio n system s s tart under a utomatic act ivat ion
w hen—
(i) t he building fire ala rm is
a ctua ted by the auto mati c fire sprinkle r system of the building, or by an y s moke
or the rmal alar m group forming pa rt of t he building auto mati c fire detec tion system;
(ii) a ny rec ycle -air sens or group, or a ny s upply-air
s ensor group is ac tuat ed;
a nd (iii) a ny rec ycle -air sens or group and a ny supply-air
s ensor group are a ctua ted
(b) W ith all air -pressurizat ion and other system s, requi red to opera te in the fire mode, opera ting sim ulta neously, measu re an d recor d for eac h air-pressurizatio n system — (i) t he a vera ge flowra te
t hrough a sele cted ope n door, w hen t he doors
l eadi ng from ev ery
s tair way t o two sele cted
s ucce ssive storeys a nd the main dischar ge doors a re fully open simultan eously;
N OTE: In order to asse ss
t he performance of the
s yste m, it i s recom mended
s ame meas uring tec hnique
be used eve ry time (ii) t he force required t o open
e ach door;
(iii) t he t ime take n for
c onditions found in Items (i) a nd (ii) above to be resto red afte r ope ning an d reclo sing up to three doors; an d (iv) t he noise leve l at doorways
i dent ifie d as subjec t to the highe st noise le vel, at t he relev ant points of e ntry
i nto fire-isol ated es cape route s, with the a ssoc iate d door open
(c) C heck t hat wh en the s moke
s ensor group of any a ir-pressurizatio n system is
a utomatic ally act uate d, the
a ssoc iate d pressurizat ion fan is
s hut down
N OTE: A ny fan sta rting and
s topping che cks under Ite ms (a) out in s uch a ma nner as will
a void ove rhea ting of motors due
t o e xces sive ly frequent st arts (d) C heck t hat operat ion of the manua l swit ch provided for fire brigade personnel de-ener gize s fans s upplying air t o the pressurized fire-is olat ed esca pe route s
(a) S imulate act ivat ion of all air -pressurizatio n an d othe r systems requi red to ope rate in the fire mode W hen operatin g
s imultane ously, mea sure a nd recor d the following for e very door:
(i) A mbie nt noise lev el
(ii) D oor opening force (iii) A ir velo city through door
N OTES :
1 W here t here hav e been no
c hanges to the building
s tructure, int erna l l ayout
a nd air -handling system in
t he period sinc e the l ast tes t,
a pproval may be given t o
t esti ng l ess than al l doors
W here a pproval is given to
t esti ng a proportion of doors
a repre sent ativ e number of doors should be t este d Tes t doors should be s elec ted at performance criter ia i.e high noise lev el, high openi ng force and low air veloc ity
2 W hen te stin g i s c arried out
on a proportional number of doors bas is it is recom mended t hat the sam e doors be s elec ted a nd te sted
e ach t ime
(b) W ith all air -pressurizat ion and other system s operat ing
s imultane ously, che ck that any
s peci fic a ir relie f is fully opera tional a nd enab les the requi red airflow from pressurized
a reas to be sustain ed
R epai r or replac e any item s not capa ble
of bei ng ad just ed for sat isfa ctory performance
A UTO MA TIC SMO KE/ HEA T
V ENT IN G SYST EMS C arry out maint enan ce in acco rdance with the provisions of AS 1851.5
O UTD OO R AI R IN TAK ES
L evel 2
(a) R emove any com bustible mater ial from t he vicin ity of
t he i ntak es
(b) C heck i ntak e louvres for
c orrosion and da mage (c) C heck a nd cl ean insect s cree ns, repla ce if da mage d