Multi Pump Compatibility Offer Mono-joker with auxiliary pump permutation Multi-joker with auxiliary pump permutation Mono-Joker with continuous operating time limitation Multi-joker

Trang 2

I Multi Pump Compatibility Offer

Application Card

Trang 3

I Multi Pump Compatibility Offer

Trang 4

I Multi Pump Compatibility Offer

1 Compatibility with ATV38 & Multi-pump card

 The main objective of this card is to drive a whole pumping installation through only one Altivar 61 and to insure :

the flow

installation through the Altivar 61

 ATV38 Multi pump 600 pieces each year

Trang 5

1 Typical Application

I Multi Pump Compatibility Offer

Trang 6

I Multi Pump Compatibility Offer

 Mono-joker with auxiliary pump permutation

 Multi-joker with auxiliary pump permutation

 Mono-Joker with continuous operating time limitation

 Multi-joker with continuous operating time limitation

 Mono-joker with auxiliary pump permutation and continuous operating time limitation

 Multi-joker with auxiliary pump permutation and continuous operating time limitation

 Reference:

 VW3A3502 : multipum card to develop AT38 to ATV61

 VW3A3503 : multipum card for ATV61

Trang 7

 Control the Starting and stopping of an auxiliary pump

 The PI regulator output (frequency reference

of the variable pump) is used to control starting or stopping of an auxiliary pump with hysteresis

I Multi Pump Compatibility Offer

2 Features

Trang 8

 Sleeping / Wake up functions

 It allows the joker pump stop when the flow is equal

to zero ( all auxiliary pump at stop)

 It allows the restarting of the Joker pump when a flow

is requested by the installation

Seuil sommeil

Retour PI

T Seuil Réveil

Fréquence

Moteur

T LSP

Temps de prise en compte

I Multi Pump Compatibility Offer

2 Features

Trang 9

 Friction loss compensation

losses in the reticulation system A step compensation is available.

I Multi Pump Compatibility Offer

2 Features

Trang 10

 Pumps working time

 Pressor sensor calibration

 Reference given by the Keypad

 The time scale of the counter pumps can be change

for the commissioning phases of the installation : Hours    Minutes

I Multi Pump Compatibility Offer

2 Features

Trang 11

System overview I Multi Pump Compatibility Offer

Trang 12

I Multi Pump Compatibility Offer

3 New feature

 Spanish English German French Italian

 For all the other languages the Menu will be in English

 Dedicated Screen

RUN Term + 50.00Hz 1250A

1.14 Multi Pompes

Mode Fonct : 5

Nb de pompes : 3

Tempo Ppe On : 10s Tempo PpeOff : 15s TempoFctSom : 20s CODE << >> Quick RUN Term + 50.00Hz 1250A 1.14 Multi Bombas Modo func : 5

Nº bombas : 3

T.Con.B.Aux : 10s T.Desc.B.Aux : 15s Temp.Dormir : 20s CODE << >> Quick RUN Term + 50.00Hz 1250A 1.14 Multi Pump Working Mode : 5

Nbr of Pumps : 3

Time On Paux : 10s Time Off Paux : 15s Time Sleep : 20s CODE << >> Quick RUN Term + 50.00Hz 1250A 1.14 Controller Inside O01 : 5

O02 : 3

O03 : 10

O04 : 15

O05 : 20

CODE << >> Quick

Trang 13

I Multi Pump Compatibility Offer

4 Field test result

 Available for field test  Contact the Product Manager for ATV61 S.BOIS

 e.g Spain

 AGROHERNI S.L

 Pumping for Fields irrigation

Trang 14

I Multi Pump Compatibility Offer

Trang 15

II New Multi Pump Offer

1 Why a new card ?

Trang 16

II New Multi Pump Offer

2 New card features

 Wide Application Coverage

 High Performance

 Compatibility with a larger variety of pumps

 Superior Pump System Protection

 Better User Interface

 Customer language

Trang 17

II New Multi Pump Offer

 Irrigation

 Fast acting PID control

- Fast shut down algorithm prevents pressure overshoots when fast acting valves close

 Auto Shut Down Algorithm

- The system will pump unsupervised for a selected time, after which it will automatically stop

Wide Application Coverage

Trang 18

II New Multi Pump Offer

 Irrigation

 Flow Limitation

- Used when flow must be restricted to a particular level The system operates in pressure control as long as the measured flow is below the flow limit At that point speed is adjusted to stay below the allowable flow

 Set point range limitation

- Irrigation pumps may be able to pump up pressure to above the withstand pressure of the weakest part of the distribution system Unwanted high setpoint selection can be prevented by dialling the correct range

Wide Application Coverage

Trang 19

II New Multi Pump Offer

Flow limit active

Flow limit Reset

Flow

Set-point limit

Flow limit disabled

Flow limit active

Flow limit Activate level

Applied set-point

Trang 20

II New Multi Pump Offer

 Jockey Pump control

- For low demand situations, a jockey pump can be used

in conjunction with a lead pump system The Jockey pump works in on-off control between two pressure setpoints

 Night and Day algorithm

- During night time, the system operates in fixed speed between two pressure setpoints In case of excessive demand, the system reverts back to normal lead pump operation

Wide Application Coverage

Trang 21

II New Multi Pump Offer

Controller

Inside ATV61 or ATV71

Contactor or soft starter

Non return valve

Pressure transducer

Isolating valve

Optional flow switch

Jockey / joker pump (1 only)

Optional flow meter

Variable speed pump

Fixed speed pump (Maximum of 3)

Trang 22

II New Multi Pump Offer

Set-point

Jockey start pressure

t

AAA

Demand increasing Jockey not adequate

Jockey on Jockey off Jockey on

Main system wakeup

Jockey stop pressure

Jockey pump

Pressure

Trang 23

II New Multi Pump Offer

Wide Application Coverage

 Crops can be protected from frost damage by sprinkler or mist systems

 If enabled, this feature will automatically start the pump

if the temperature, measured via an analogue input, decreases below the frost setpoint for a certain time period

 An instant start temperature can also be set for protection against rapid temperature changes

 Once run is initiated only manual shutdown is possible

heat

Trang 24

II New Multi Pump Offer

 Pressure Boost mode

- For long supply lines or high rise buildings, it may be required to boost the pressure at regular intervals The inlet pressure is monitored and the pressure reference

is reduced if the inlet pressure is low

Wide Application Coverage

Trang 25

II New Multi Pump Offer

Controller Inside ATV61

Pressure

Non return valve

Pressure setpoint = Pressure setpoint - Low inlet pressure

Compensation

Primary pump

Booster pump

Booster pump

Trang 26

II New Multi Pump Offer

Controller

Contactor or Soft Starter

Pressure Transducer

Optional Flow Switch

Controller Inside ATV61

Contactor or Soft Starter

Non return valve

Pressure Transducer

Isolating valve

Optional flow meter

Pressure Transducer

Trang 27

II New Multi Pump Offer

Booster pump

Inlet (suction)

pressure

Outlet pressure

Inlet pressure low, pump

will enter sleep mode after

booster sleep delay

Set point upper limit

Inlet(suction) pressure lower limit

Pressure

t

Inlet(suction) pressure acceptable level

Set-point

Suction pressure acceptable, restart after wake up delay

t

A

AA

A

Feature / level is

adjustable

AA

Trang 28

II New Multi Pump Offer

 Slow response for staging and de-staging

- Staging and de-staging is triggered by pump speed and pump pressure error and can be delayed to guarantee smooth action

 Friction compensation

- The pressure setpoint is adjusted to overcome losses in the reticulation system Continuous adjustment and/or step compensation can be selected

Wide Application Coverage

Trang 29

II New Multi Pump Offer

Flow (Friction Loss) Stepped

Compensation

II New Multi Pump Offer

Lead Pump Speed

Feed Back

Lead pump only compensetion

Pump 1

compensation

Pump 2 compensation

Pump 3 compensationA

A

A

Trang 30

II New Multi Pump Offer

A

Lead Pump Speed

Pressure Feed Back

Flow (Friction Loss) Hazen-Williams

Compensation

Flow Feed Back

Trang 31

II New Multi Pump Offer

3 High Performance

 Setpoint Ramping

 On transition from any state into PID control, the reference is ramped from the current feedback level to the required setpoint This prevents an unwanted initial large error

 Pipe fill algorithm

 On initial start-up pipes may be empty Starting PID control under these conditions would result in the PID ramping up, due to a low feedback Pipe fill runs the system at a preset speed until a start pressure is reached and then transfers into PID control.

System Drained

Trang 32

II New Multi Pump Offer

Set-point

System run command

Trang 33

II New Multi Pump Offer

Pressure Pipe fill Plus Set-point Ramp

Feature / level is

adjustable

AA

Trang 34

II New Multi Pump Offer

 2 modes available, mono joker and auxiliary pumps permutation

or mono joker and auxiliary pumps permutation with the limitation of the operating time

 Staging and de staging

 Staging and de staging conditions can be based on speed, pressure, PID error or any combination of these A delay allows for further fine tuning During this operation, the speed of the variable speed pump is set to adjustable values This ensures smooth pick up and drop off for fixed speed pumps

Reduced Overshoot

Reduced Undershoot

Trang 35

II New Multi Pump Offer

4 Pump Compatibility

 If pumps with a flat H-Q curve are used, it may be difficult to identify a no demand situation.This algorithm detects a no demand situation via the response to a step decrease in setpoint.

 Some pump systems require the main pump to

be primed with fluid prior to starting to prevent them from running dry for too long

H

Q

Standard no demand

detection impossible

Trang 36

II New Multi Pump Offer

5 Enhanced System Protection

 Cavitation protection

Trang 37

II New Multi Pump Offer

6 User Friendly HMI and set-up

 Screens in clear text

 Set-up screens only visual if required

requires

Trang 38

II New Multi Pump Offer

DESTAGE JOCKEY

SENSORS FLOW LMT PID

STAGE

>>

EXPANDED

RUN TIMES NIGHT & DAY FLOW COMP BOOSTER

RUN Term +0.0Hz OFF

Feedback Pres

>>

1.14 PUMP CONTROL TIME: 11:23

Flow Display

Act PID Ref

System Status EXPANDED Modbus add Prg C DATE/TIME SETTINGS

Trang 39

II New Multi Pump Offer

Help Screen

Drive state ::::

ETA status word ::::

ETI status word ::::

Reset Flt Hi P Fbk T/O Reset Flt High Pressure

TK

F1

Press

 Help available on fault

 If the fault is not genuine use the help key to see sugestions for further application tuning

Trang 40

II New Multi Pump Offer

System Overview

Controller Inside ATV61

Contactor or soft starter

Non return valve

Pressure transducer

Isolating valve

Flow switch

Jockey / joker pump (1 only)

Analogue flow meter

Variable speed pump

Fixed speed pump (Maximum of 3)

High pressure switch

Low pressure switch

Auto run

Pulse flow meter Frost protection

Fault Fault

Fault

Low well switch

Protective manual

Overide manual

Fault reset

Trang 41

for your attention

Thanks

Thanks

Trang 42

I- Launching product features II- Programing lab on ATV21 III- Harmonic solution

IV- HVAC, Engergy saving V- Water solution with multipump card

inside card