Trang 11 Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2 If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product Do not try to install the product yourself
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or
contractor to install those parts and accessories Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
R ead the User's Manual carefully before using this product The User's Manual provides important
safety instructions and warnings Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Đại lý phân phối
•HEAD OFFICE
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan
CƠNG TY CỔ PHẦN VIỆT KIM
•VĂN PHỊNG CHÍNH
Tầng 14-15, tịa nhà Nam Á, 201-203 Cách Mạng Tháng 8, P.4, Q.3, TP.HCMTel: (08) 62 504 888 Fax: (08) 62 504 999
Cooling Only / Heat Pump 50 Hz
Miễn phí cước cuộc gọi
TRUNG TÂM DICH VU KHÁCH HÀNG
http://daikinvrv.com.vn
info@daikinvrv.com.vn
Hotline: 0976 173 173
http://daikinvrv.com.vn info@daikinvrv.com.vn Hotline: 0976 173 173
Trang 2Next Generation VRV IV System
* VRV is a trademark of Daikin Industries, Ltd.
INDEX P03 P13 P15 P37 P67
P75 P89
Main Features
Outdoor Unit Lineup
Indoor Unit Lineup
Outdoor Unit Combinations
Air Treatment Equipment Lineup
INDEX P03 P13 P15 P37 P67
P75 P89
Main Features
Outdoor Unit Lineup
Indoor Unit Lineup
Outdoor Unit Combinations
Air Treatment Equipment Lineup
Trang 3Excellent Operation Performance
Higher Coefficient of Performance (COP)
Comfort Ease of installation
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
1,240 mm 765 mm 930 mm 765 mm
Lineup
HP High-COP Type
Standard Type
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
VRV
VRV
VRV
Trang 4Excellent Operation Performance
Higher Coefficient of Performance (COP)
Comfort Ease of installation
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
How is energy reduced?
During cooling, the refrigerant evaporating
temperature (Te) is raised to minimise the
difference with the condensing temperature.
During heating, condensing temperature (Tc) is
lowered to minimise the difference to the
evaporating temperature Compressors work less,
and this reduces power comsumption.
State-of-the-art energy saving technology for VRV system
• Can boost capacity above 100% if needed
The refrigerant temperature can go lower in cooling (higher in heating) than the set minimum (maximum in heating)
• Gives priority to very fast reaction speed.
The refrigerant temperature goes down (or up in heating) fast to keep the room setpoint stable
• Gives priority to fast reaction speed.
The refrigerant temperature goes down (or up in heating) fast to keep the room setpoint stable
• Gives priority to efficiency.
The refrigerant temperature goes down (or up in heating) gradually giving priority to the efficiency of the system instead of the reaction speed
Compressor
(During cooling)
Evaporator Condenser
Evaporating temperature raised Compressor workload reduced
Indoor unit heat exchanger
Compressor
Evaporator
Condenser Indoor unit heat exchanger
(During heating)
Condensing temperature lowered Compressor workload reduced
Mild mode
Quick mode
Powerful mode
Variable Refrigerant Temperature
Fixed Refrigerant Temperature
High Sensible Mode
Fixed target Te
Auto Mode
Floating target Te/Tc depending on heat load
Basic Mode
Fixed Te/Tc - Standard control
(default setting on VRV IV)
Av max temp Av daily temp difference
Av min temp
Av max temp
Heating
Av min temp
25
Fast Medium
VRT offers quicker cool down
to shorten uncomfortable pull down time.
Mild Quick Powerful
Cooling load & capacity
25%
100%
Outdoor Temp
Fine control to match user preference available through mode selection
Recommended for use in these situations
Basic mode is selected to maintain optimal comfort.
VRT is selected to save energy and prevent excessive cooling or heating.
Cooling only regions having differences
in daily temperature Cooling/heating regions having periods of mild outdoor temperatures.
VRT is particularly effective during the intermediate periods.
Selecting VRT enables operation to be optimised for either energy efficiency or rapid cooling/heating.
Outdoor Temp
Customise your VRV system for optimal annual efficiency
The new VRV IV system now features VRT technology.
VRT automatically adjusts refrigerant temperature to individual
building and climate requirement, thus further improving
annual energy efficiency and maintaining comfort.
With this excellent technology, running costs are reduced.
Required capacity changes
as air conditioning load changes according to outdoor temperature.
Energy efficiency is improved without sacrificing comfort.
Automatic control adjusts evaporating temperature
to heat load change.
In case of fixed evaporating temperature, excessive cooling, thermo on-off loss, and other inefficiencies occur.
Trang 5Excellent Operation Performance
Higher Coefficient of Performance (COP)
Comfort Ease of installation
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
VRV
VRV
VRV
More options for installation location
More Flexible System Design
The long piping length provides more design flexibility, which can match even large-sized buildings.
Long piping length
Maximum allowable piping length
Minimum allowable piping length
When a mixed combination of VRV and residential indoor units is connected
or when only residential indoor units are connected
Maximum allowable level difference Between the outdoor unit
and the indoor unit
Between BP unitand indoor unit
Between the indoor unitsBetween BP units
Between the first indoor branch and the farthest BP unit or
between the first indoor branch and the farthest VRV indoor unit
Total piping lengthRefrigerant piping length
Between outdoor unit and the first indoor branch
15 m
15 m
lmnno
Level Difference Example
50 m
If the outdoor unit is above
If the outdoor unit is below
If indoor unit capacity index < 60
If indoor unit capacity index is 60
If indoor unit capacity index is 71
40 m
40 m
*1 When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased Please refer to Engineering Data Book for details
*When a mixed combination of VRV and residential indoor units is connected or when only residential indoor units are connected, connection ratio
must be 50% to 130% for cooling only models and 80% to 130% for heat pump models Refer to page 68 for outdoor unit combination details
Max
50 m
Max
40 m Max
d c
b
g f
For mixed combination of VRV
and residential indoor units
For connection of only VRV
Conditions of VRV indoor unit connection capacity
Connection capacity at maximum is 200%.
Total capacity index of the indoor units
Capacity index of the outdoor units
1 No special requirements up to 40 m The maximum actual piping length can be 90 m, depending on conditions Various conditions and requirements have to be met
to allow utilisation of 90 m piping length Be sure to refer to the Engineering Data Book for details of these conditions and requirements
2 When level differences are 50 m or more, the diameter of the main liquid piping size must be increased and connection ratio must be 80% to 130% If the outdoor unit
is above the indoor unit, a dedicated setting on the outdoor unit is required Refer to the Engineering Data Book and contact your local dealer for more information
Between the first indoor branch and the farthest indoor unitBetween the outdoor branch and the last outdoor unitTotal piping length
Refrigerant piping length
a+b+c+d+e+f+g+h+ia+f+g+h+i
f+g+h+ik+p
1000 m
Actualpiping length Example piping length Equivalent
Level Difference Example
If the outdoor unit is above
If the outdoor unit is below
b
Firstindoor branch
VRV IV outdoor unit has been achieved high
external static pressure up to 78.4 Pa, ensuring the efficient heat dissipation and stable operation of equipment in either hierarchical or intensive arrangement.
78.4 Pa
More options in the opening/angle of louvre Outstanding heat dissipation effect in both hierarchical and intensive arrangement
High external static pressure
Max actual piping length
Max total piping length
30 m
Max level difference
between the indoor units
Max level difference
between the outdoor units
and the indoor units
a
i
s r
h g
f
e d
c b
First indoor branch
Trang 6Excellent Operation Performance
Higher Coefficient of Performance (COP)
Comfort Ease of installation
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Outdoor unit sequencing technology
Daikin VRV IV system incorporates a simplified and efficient test operation function, not only greatly
accelerating the installation process, but effectively improving the field setting quality as well.
Automatically checks the wirings between
outdoor units and indoor units to confirm
whether there is a defective wiring.
Confirms and corrects the actual piping
length.
Automatically check whether the stop
valve in each outdoor unit is in normal
status to ensure the smooth operation of
air conditioning system.
Automatic check
During start-up, Daikin VRV IV unit sequencing operation will be automatically enabled to ensure balanced operation of each outdoor unit to improve longevity of equipment and stable operation.
Double backup operation functions responding resiliently to various unexpected situations
Daikin VRV IV system boasts double backup operation functions, which can secure the use of air conditioners in this area to the greatest extent by emergently enabling double backup operation functions even if failure occurs in a set of air conditioning equipment.
In the event of a failure, emergency operation can be conveniently enabled to allow the remaining system
to operate in a limited fashion.
Double backup operation functions
Simplified commissioning and after-sales service
VRV IV system utilises 7-segment
luminous digital tubes to display system
operation information, enabling the
operational state to be visually displayed
whilst facilitating simplified
commissioning and after-sales service.
Function of information display
by luminous digital tube
The VRV configurator is an advanced software solution
that allows for easy system configuration and
commissioning.
less time is required on the roof configuring the outdoor
unit.
multiple systems at different sites can be managed in
exactly the same way, thus offering simplified
commissioning for key accounts.
Initial settings on the outdoor unit can be easily retrieved.
VRV configurator
Unit backup operation function
If malfunction occurs in an outdoor unit
Emergency operation can be conveniently set and enabled
by the remote controller for indoor unit (for systems composed of two or more outdoor units ).
If malfunction occurs in a compressor
Emergency operation can be easily set and enabled by the outdoor unit (for a single outdoor unit system RX(Y)Q14-20TY1 models).
Compressor backup operation function
Multiple advanced features ensuring more accurate test operation and stable system
Wiring check
Piping check
Stop valve check
Simplified commissioning
Retrieve initial system settings
Automatic sequencing Automatic
sequencing
Automatic sequencing Automatic
sequencing
Displays system operation information directly
Figures out system operation information by reading light emitting state
of different diodes, which
is both inefficient and fallible.
7-segment digital display Conventional LED display
Trang 7Excellent Operation Performance
Higher Coefficient of Performance (COP)
Comfort Ease of installation
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Improve heat exchanger efficency, helps to reduced operation sound.
Lower operation sound
*12 HP of VRV IV improves more compact design and more saving space than VRV III
*Cooling operation conditions: Indoor temp of 27ºCDB, 19ºCWB, and outdoor temp of 35ºCDB
0 3 3.5 4 4.5
Peak in outdoor temperature
Enable night mode
Outdoor PCB automatically memorises the time when the peak outdoor temperature appears It will enable quiet operation mode after 8 h*1, and return to normal mode after it keeps for 9 h*2.
*1 8 h is the initial setting with 6 h or 10 h also available
*2 9 h is the initial setting with 8 h or 10 h also available
Notes: · This function is available in setting at site
· The operating sound in quiet operation mode is the actual value measured by our company
· The relationship of outdoor temperature (load) and time shown above is just an example
Streamlined air grille
It promotes the discharge of swirling airflow, further reducing the pressure loss
Streamlined scroll fan
The sharp edge of each fan blade has a certain curvature, reducing both the vibration and the pressure loss
Streamlined scroll fan Illustrated fan
0
40 57
Installation Space 0.71 m2
25 % Decrease
Product Weight
195 kg
32 % Decrease
Enables further energy saving
12 HP-50 HP with 4 new models lineup
Energy Saving
20 HP
Offers higher capacity of up to 60 HP
6 HP-60 HP with 3 new models lineup
Product Weight 490 kg
14 % Decrease
22 % Decrease
Installation Space 1.66 m2
380 kg 1.42 m2
Up to
60 HP
Standard Type
20 HP
New series with compact & lightweight design
18 HP-50 HP with 17 new models lineup
320 kg 0.95 m2
Decrease
35 % Decrease
Compact Design
Space Saving Type
COP during cooling operation
COP during cooling operation
3.94 Product Weight 490 kg Installation Space 1.66 m2COP during cooling operation
4.35
3.94
Nighttime quiet operation function
Without increasing operation sound, advanced analytic technologies are utilised to optimise fan design and increase airflow rate and high external static pressure.
Large airflow, high static pressure and quiet technology
Space Saving Type
Product Weight
285 kg
Installation Space 0.95 m2
Cooling Operation COP
Highly integrated heat exchanger
packaging material
*SMT: Surface mounted technology
Computer control board surface adopting SMT packaging technology
Conventional computer control board surface
SMT packaging technology adopted by the whole computer control panel improves the anti-clutter performance.
Protects your computer boards from the adverse effect of sandy and humid weather.
SMT* packaging technology
Large capacity inverter compressor using high tension strength material,
realise 12 HP compressor using 8 HP casing.
Small sizing coil end using concentrated winding, reduce copper loss
(winding resistance).
Improve motor efficiency in low rpm range (improve intermediate efficiency).
Distributed winding motor(Current 8 HP compressor)Concentrated winding motor(New 12 HP compressor)
Coil end
Gives 2.4 times tensile strength compare
to conventional material
New Material: 600 MPa
Conventional Material : 250 MPa
Increase compression chamber volume
by using thin spiral design.
As a result of having thinned a wall -
thickness of the scroll, compression
chamber volume increase 50%
Improve performance by increasing heat exchanger area while maintaining the same installation space.
Change fin shape from fine louvre to waffle fin
Fin pitch can be reduced fin pitch from 2.0 mm to 1.4 mm, to realise unit
Realise highly integrated heat exchanger performance (increase row, reduce fin pitch) by reducing of airflow resistance which changes cooling tube to Ø7.
Heat exchanger area Contribution of COP(cooling)
10 HP
16 HP 13%UP 24%UP 105.5% 111.5%
Fine Louvre Fin Waffle Fin
Downsize electric component, re-locate to dead space of bell mouth side to decrease airflow resistance
Refrigerant cooling technology, ensures stability of PCB temperature
Control board failure ratio at stable operation
is reduced
Improve reliability at high ambient temperature
It is possible to cool the inverter power module stability even at high ambient temperature.
This helps to keep air-conditioning capacity and also reduces failure ratio.
Bell mouth
Electric Component Space
Roof terrace temperature in summer is over 40 C, seriously affecting inverter cooling efficiency, resulting in decline of inverter operating speed Finally device parts response
Trang 8Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Trang 9VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Enhanced range of choices
Daikin air handing units can be connected to VRV IV system
Please refer to page 103 and contact your local sales office for details.
FXVQ-MY1
FXVQ-MY16
(high static pressure type)
Indoor Unit Lineup
A mixed combination of VRV indoor units and residential indoor units
is enabled all in one system Opening the door to stylish and quiet indoor units.
VRV indoor units
Note: BP units are necessary for residential indoor units Only single outdoor unit (RX(Y)Q6-20TY1) can be connected
Type Model Name
*Refer to page 67-68 for the maximum number of connectable indoor units
Type Model Name
Residential indoor units with connection to BP units
25 35
2.5 kW20
202.0 kW 3.5 kW
5.0 kW 6.0 kW 7.1 kWRated Capacity
Capacity Index
(700 mm width type)
(900/1,100 mm width type)
FCQ-BVEFFQ-BV1BFBQ-BV1
Ceiling Mounted Cassette
Ceiling MountedBuilt-in
Slim CeilingMounted Duct
Wall Mounted
Ceiling MountedCassette (Compact Multi Flow)
8 types 23 models
FDKS-EAVMBCDXS-EAVMA
Cooling Only Heat PumpFDKS-C(A)VMBFDXS-CVMA
Cooling Only Heat PumpFTKS-DVMFTXS-DVMAFTXS-EVMA
Cooling Only Heat PumpFTKS-BVMACooling OnlyFTKS-FVMFTXS-FVMA
Cooling Only Heat Pump
Enhanced range of choices
Daikin air handing units can be connected to VRV IV system
Please refer to page 103 and contact your local sales office for details.
FXVQ-MY1
FXVQ-MY16
(high static pressure type)
Indoor Unit Lineup
A mixed combination of VRV indoor units and residential indoor units
is enabled all in one system Opening the door to stylish and quiet indoor units.
VRV indoor units
Note: BP units are necessary for residential indoor units Only single outdoor unit (RX(Y)Q6-20TY1) can be connected
Type Model Name
*Refer to page 67-68 for the maximum number of connectable indoor units
Type Model Name
Residential indoor units with connection to BP units
25 35
2.5 kW20
202.0 kW 3.5 kW
5.0 kW 6.0 kW 7.1 kWRated Capacity
Capacity Index
(700 mm width type)
(900/1,100 mm width type)
FCQ-BVEFFQ-BV1BFBQ-BV1
Ceiling Mounted Cassette
Ceiling MountedBuilt-in
Slim CeilingMounted Duct
Wall Mounted
Ceiling MountedCassette (Compact Multi Flow)
8 types 23 models
FDKS-EAVMBCDXS-EAVMA
Cooling Only Heat PumpFDKS-C(A)VMBFDXS-CVMA
Cooling Only Heat PumpFTKS-DVMFTXS-DVMAFTXS-EVMA
Cooling Only Heat PumpFTKS-BVMACooling OnlyFTKS-FVMFTXS-FVMACooling Only Heat Pump
Trang 10VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Indoor Unit Lineup
Daikin offers a wide range of indoor units includes both VRV and residential
models responding to variety of needs of our customers that require
air-conditioning solutions.
Ceiling Mounted Cassette
(Round Flow with Sensing)
Type
Presence of people and floor
temperature can be detected to
provide comfort and energy savings
Ceiling Mounted Cassette (Round Flow) Type
FXFQ-SVM
FXFQ-LUV1
Ceiling Mounted Cassette
(Compact Multi Flow) Type
Quiet, compact, and designed for
This slim and stylish indoor unit achieves optimum air distribution, and can be installed without the need for ceiling cavity.
Ceiling Mounted Cassette
(Double Flow) Type
Thin, lightweight, and easy to install
in narrow ceiling spaces
Ceiling Mounted Cassette Corner Type
Slim design for flexible installation
Slim Ceiling Mounted Duct
Type
Slim design, quietness and
static pressure switching
Ceiling Mounted Duct Type
High external static pressure allows flexible installations
Ceiling Mounted Cassette Type
Specially designed for false ceilings
—for a smooth, modern interior finish
Ceiling Mounted Cassette (Compact Multi Flow) Type
Floor Standing Type
Concealed Floor Standing Type
Suitable for perimeter zone air conditioning
Floor Standing Duct Type
FXLQ-MAVE
FXNQ-MAVE
FXVQ-MY1 FXVQ-MY16
Large airfiow type for large spaces.
Flexible interior design for each tenant.
Ceiling Suspended Type
Slim body with quiet and wide airflow
Wall Mounted Type
Stylish flat panel design harmonised with your interior décor
FXHQ-MAVE
Wall Mounted Type
Stylish flat panel harmonises with your interior décor
FTKS-DVM FTKS-FVM FTKS-BVMA
FTXS-FVMAHeat Pump
Trang 11VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Indoor Unit Lineup
FXFQ25S / FXFQ32S / FXFQ40S FXFQ50S / FXFQ63S / FXFQ80S FXFQ100S / FXFQ125S
Dual sensors detect the presence of people and floor temperature
to provide comfortable air-conditioning and energy savings.
Thanks to the individual airflow direction control function, airflow
direction can be individually adjusted for each air discharge
outlet 5 directions of airflow and auto-swing can be selected
with wired remote controller BRC1E62, which realises the
optimum air distribution.
Presence of people and floor temperature can be detected to provide comfort and energy savings
Infrared presence sensor
Ceiling Mounted Cassette (Round Flow with Sensing) Type
VRV Indoor Units
Presence of people in 4 areas
Detecting the average temperature of indoor floor
Infrared floor sensor
Individual airflow direction control
The sensor detects the floor temperature and automatically
adjusts operation of the indoor unit to reduce the temperature
difference between the ceiling and the floor.
Indoor unit offers 360° airflow discharges air in all directions with more uniform temperature distribution.
Dead spot of airflow
Control of airflow rate can be selected from 3-step control, which provides comfortable airflow Auto airflow rate control can be selected with wired remote controller BRC1E62
Low operation sound level
45/40/35
12544/38/32
10038/35/31
8038/33/28
6336/32/28
5031/29/27
4025/3230/28.5/27Sound
level(H/M/L)FXFQ-S
Drain pump is equipped as standard accessory with 850 mm
Energy efficiency has been improved thanks to the adoption of a new heat exchanger with smaller tubes,
DC fan motor and DC drain pump motor.
The sensor detects human presence and adjusts
the airflow direction automatically to prevent drafts.
Energy saving control can be performed
when no people are detected.
Example: • Cooling setpoint: 26°C
• Shift temperature: 1.0°C • Shift time: 30 min • Limit cooling temperature: 30°C
Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments and 15, 30, 45, 60, 90 or 120 minutes respectively with remote controller
Sensing sensor stop mode
*2 User can set these functions with remote controller
*1 These functions are not available when using the group control system
Sensing sensor low mode*1 2
New airflow block function prevents uncomfortable drafts by reducing air velocity
It can be set using the BRC1E62 remote controller
There is no need for sealing material of air discharge outlet (option).
This function only works when all-round flow
is used It cannot be used when sealing material is used in the air discharge outlet (option).
Total comfort by individual airflow direction control and newly-equipped “airflow block function”
Also can support such this case
Airflow block for cabinet side
Airflow block air velocity
*4 In case of FXFQ63S type (Data is based on Daikin research.)
*3 Works in one direction only
Easy setup with remote controller
500 mm
Wall
Airflow
*5 A gap of 1500 mm is required if the air block function is not used
The airflow block function is useful when rearranging the room layout.
Sensing function
Auto airflow rate mode + Auto airflow direction mode
Floor temperature is detected and over cooling prevented.
Energy savings
The temperature near the person is automatically calculated by detecting the temperature of the floor Energy is saved, because the area around the feet does not get too cold.
Comfortable airflow Airflow rate automatically increases during hot or cold periods (when there
is a large difference with set temperature), and operation is rapidly performed for cooling or heating.When the difference with set temperature becomes small, drafts are prevented by automatically reducing airflow rate, and raising the flap to a horizontal position during cooling operation.
Without sensing function
With sensing function
30°C near ceiling
20°C near floor
Room temperature is detected as 30°C.
Room temperature is calculated as 27°C in the area which
is in the vicinity of the person.
30°C near ceiling
24°C near floor
Automatic control using the temperature near the person
as the room temperature.
The floor temperature, which is lower than near the ceiling, is detected.
Area around feet gets too cold because air conditioner continues until the temperature near the ceiling reaches the set temperature
Sensing sensor mode
Airflow block function
28 27 26 Occupied
Unoccupied
Automatically reverts when people return.
Trang 12VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Indoor Unit Lineup
VRV Indoor Units
360° airflow improves temperature distribution and offers a comfortable living environment.
Note: Whatever the discharge direction, the same type of panel is used If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet
The industry’s first* Round Flow Ceiling Mounted
Cassette type offers 360° airflow with improved
temperature distribution.
The light weight unit at 19.5 kg for FXFQ25-50LU
models makes installation easy.
A modern sophisticated decoration panel has been
applied, with a panel surface that has been treated with
been applied to the drain pan, preventing the growth
of slime, mould and bacteria that cause blockages and odours.
The horizontal louvres prevent dew condensation
Their non-flocking surfaces, which repel dirt, are easy to clean.
The air filter has an anti-mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter.
Example of airflow patterns:
All-round flow is available, as well as 2-way to
4-way flows, so you can choose the most
suitable airflow pattern depending on location or
room layout.
Drain pump is equipped as a
standard accessory with a 850 mm
lift.
Treated surface Untreated surface
Resists soiling
• Condition after exposure to the smoke of 600 cigarettes in 1 m3enclosed space
Dirt andgrime
Control of the airflow rate can be selected from 3-step
control.
4-way flow Round Flow
There are areas of uneven temperature areas of uneven temperature There are much fewer
* As of April 2004, the release date for Japan
44/39/34
12543/37.5/32
10036/33.5/31
8034/31/28
6332/29.5/27
5031/29/27
4025/3230/28.5/27Sound
level
(HH/H/L)
FXFQ-LU
850 mm
Ceiling Mounted Cassette (Round Flow) Type
Quiet, compact, and designed for user comfort
Dimensions correspond with 600 mm X 600 mm architectural module ceiling design specifications.
Wide discharge angle: 0° to 60°
2-, 3-, and 4-way airflow patterns are available, enabling installation in the corner of a room.
Fixed angles: 5 levels
*Angles can be also set on site to prevent drafts (0°-35°)
or soiling of the ceiling (25°-60°), other than standard setting (0°-60°)
FXFQ25LU / FXFQ32LU / FXFQ40LU
FXFQ50LU / FXFQ63LU / FXFQ80LU
Sound level(H/L)
Trang 13VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
VRV Indoor Units
Indoor Unit Lineup
This slim and stylish indoor unit achieves optimum air distribution, and can be installed
without the need for ceiling cavity.
Unit body and suction panel
adopted round shapes and
realised a slim appearance
design The unit can be used
for various locations such as
the ceilings with no cavity and
bare ceilings
Flaps close automatically when
the unit stops, which gives a
simple appearance.
Unified slim height of 198 mm
for all models that gives the
unified impression even when
models with different capacities
are installed in the same area.
Built-in electronic expansion valve eliminates the need
for a BEV unit, which improves flexibility of installation.
With adoption of the individual flap control, airflow
direction adjustment can be individually set for each air
outlet 5 directions of airflow and auto-swing can be
selected with wired remote controller BRC1E62, which
realises the optimum air distribution.
Control of the airflow rate has been improved from 2-step to 3-step control Auto airflow rate control can
be selected with wired remote controller BRC1E62
Energy efficiency has been improved thanks to the adoption of a new heat exchanger with smaller tubes, DC fan motor and DC drain pump motor.
Drain pump is equipped as a standard accessory, and the lift height has been improved from 500 mm to 600 mm.
Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.
L-shaped 2-way flow
198 mm
BEV unit is not needed
BEV unit is
needed
4-Way Flow Ceiling Suspended Type
Position 0 Position 2
Individual airflow direction example case
Thin, lightweight, and easy to install in
narrow ceiling spaces
305 mm
The thin unit (only 305 mm high) can be installed in a ceiling space as narrow as 350 mm All models feature a compact design with a depth of only 600 mm.
(When a high-efficiency filter is attached, the unit's height is
Two types of optional high-efficiency filter are available (65% and 95%, colourimetric method).
A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
Major maintenance work can be performed by removing the panel A flat-type suction grille and a detachable blade make cleaning easy
Ceiling Mounted Cassette (Double Flow) Type
FXCQ20M / FXCQ25M / FXCQ32M FXCQ40M / FXCQ50M / FXCQ63M FXCQ80M / FXCQ125M
6337/32
40/5034/29
8039/34
12544/38Sound level
(H/L)
Trang 14VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Trang 15VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
VRV Indoor Units
Indoor Unit Lineup
Slim body with quiet and wide airflow
Adoption of QUIET STREAM FAN
Drain pump kit (option) can be easily incorporated.
Easy-to-clean flat design Maintenance is easier because everything can be performed from below the unit.
Non-dew Flap with no implanted bristles
Uses the quiet stream fan and many more advanced technologies
Sound absorptionmember
* 8 hr/day, 25 day/month For dust concentration of 0.15 mg/m3
Ceiling Suspended Type Ceiling Mounted Duct Type
Middle and high static pressure allows for flexible duct design
Built-in Drain Pump (Option) Housing the drain pump inside the unit reduces the space required for installation.
All models are only 300 mm in height, an
improvement over the 390 mm height of
conventional models The weight of the
FXMQ40P has been reduced from 44 kg to 28 kg.
A DC fan motor increases the external static
pressure capacity range to include middle to high
static pressures, increasing design flexibility.
Simplified Static Pressure Control External static pressure can be easily adjusted using
a change-over switch inside the electrical box to meet the resistance in the duct system.
FXMQ200MA/FXMQ250MA
Drain pump is equipped as
standard accessory with
700 mm lift.
Control of the airflow rate has been improved
from 2-step to 3-step control.
(dB(A))
46/45/43
14042/40/38
6343/41/39
80/10041/39/37
5039/37/35
4034/32/30
3233/31/29
20/25Sound
Low operation sound level
Improved ease of installation
Improved ease of maintenance
Airflow rate can be controlled using a remote controller during test operation With the conventional model, the airflow rate was controlled from the PC board It is automatically adjusted to the range between approximately ±10% of the rated HH tap airflow for FXMQ20P–125P.
The drain pan can be detached for easy cleaning An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.
Energy-efficient
The adopted DC fan motor is much more efficient than
the conventional AC motor, yielding an approximate
20% decrease in energy consumption (FXMQ125P).
44/42/40125
FXHQ32MA / FXHQ63MA FXHQ100MA
FXHQ-MASound level(H/L)Sound level(H/L)
3236/31
6339/34
10045/37
(dB(A))Low operation sound level
FXMQ20P / FXMQ25P / FXMQ32P
FXMQ40P / FXMQ50P / FXMQ63P
FXMQ80P / FXMQ100P / FXMQ125P
FXMQ140P
Trang 16VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
VRV Indoor Units
Indoor Unit Lineup
Stylish flat panel design harmonised
with your interior décor
Drain pan and air filter can be kept clean by mould-proof
polystyrene.
Vertical auto-swing realises efficiency of air distribution
The louvre closes automatically when the unit stops.
5 steps of discharge angle can be set by remote
controller.
Discharge angle is automatically set at the same angle
as the previous operation when restarting (Initial setting:
10° for cooling and 70° for heating)
Flexible installation
Drain pipe can be fitted to from either left or
right sides.
Stylish flat panel design creates a graceful harmony that
enhances any interior space.
Flat panel can be cleaned with only the single pass of a
cloth across their smooth surface.
Flat panel can also be easily removed and washed for
more thorough cleaning.
Wall Mounted Type
Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.
Drain pump kit1,000 mm
Height of drain-up
Indoor unit
Suitable for perimeter zone air conditioning
Wall hanging Floor installation
Floor Standing types can be hung on the wall for easier cleaning Running the piping from the back allows the unit to be hung on walls Cleaning under the unit, where dust tends to accumulate, is considerably easier.
A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier.
Designed to be concealed in the perimeter skirting-wall
Connecting portRefrigerant piping
* Applies also to Floor Standing type (FXLQ-MA).
The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.
The connecting port faces downward, greatly facilitating on-site piping work.
A long-life filter (maintenance free up
to one year*) is equipped as standard accessory.
Floor Standing Type
Concealed Floor Standing Type
FXNQ20MA / FXNQ25MA FXNQ32MA / FXNQ40MA FXNQ50MA / FXNQ63MA
FXLQ20MA / FXLQ25MA FXLQ32MA / FXLQ40MA FXLQ50MA / FXLQ63MA
FXAQ20P / FXAQ25P FXAQ32P / FXAQ40P FXAQ50P / FXAQ63P
47/41
6342/37
5039/34
4038/31
3236/31
2535/31
20Sound level
(H/L)
Sound level
(H/L)
FXAQ-P
Trang 17VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Indoor Unit Lineup
Note: Wireless remote controllers and signal receiver units are sold
as a set
Specially designed for false ceilings
—for a smooth, modern interior finish
All models feature a decoration panel with the same compact size and simple design for easier planning
of lighting systems and harmonising of interior décor.
The indoor units weigh only 24 kg and require an installation space with a height of just 245 mm.
FCQ50B 33/29 dB (A)
FCQ60B 35/30 dB (A)
FCQ71B 35/30 dB (A) (H/ L )
Drain pump is equipped as standard with 750 mm.
Three convenient patterns for auto-swing operation
These models have the power to provide a comfortable airflow even with a ceiling height of up to 3.8 m.
750 mm
Max 3.8 m
Low operation sound level
Ceiling Mounted Cassette Type
FCQ35B / FCQ50B FCQ60B / FCQ71B
VRV Indoor Units
FXVQ125M / FXVQ200M FXVQ250M / FXVQ400M FXVQ500M
Floor Standing Duct Type
Large airflow type for large spaces.
Flexible interior design for each tenant.
Large airflow type that fits for spacious areas such as factories
and large stores.
Various installations can be supported from full-scale duct
connection airflow to direct airflow that allows for easy
installation.
The high static pressure type driven by the belt drive
system allows for use of air discharge outlets in various
shapes as well as long ducts Highly flexible installation
is possible.
Design with high maintainability that allows major
services and maintenance services to be performed at
the front.
A long-life filter (maintenance free up to one year*) is
equipped as a standard accessory
* 8 hr/day, 26 day/month For dust concentration of 0.15 mg/m3
A wide range of optional accessories are available such
as high-efficiency filters.
Outdoor air intake mode is
useable as an outdoor-air
processing air conditioner.
*When using the unit as an outdoor-air
processing unit, there are some
restrictions Strictly follow the restrictions
specified in the Engineering Data Book
All-fresh (using outdoor air only) system Return + Outdoor air mixed system
Outside
Air conditioning
Outdoor air introduction
Air conditioning
Outdoor air introductionOutside
* Air introduced from the outside and circulated air must be mixed in the air conditioner primary side before introduction into the air conditioner.
Adding the plenum chamber (option)
allows for simple operation with direct
airflow.
* Note that the operation sound increases by
approximately 5 dB(A)
Direct airflow type
Full-scale duct connection airflow
allows for air conditioning evenly in
spacious areas.
Duct connection airflow type
Trang 18VRV Indoor Units
Indoor Unit Lineup
Slim design, quietness and static pressure switching
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
* The values of operation sound level represent those for rear-suction operation
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A)
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
Suited to use in drop-ceilings!
Set for front discharge using a suspended ceiling
Downward discharge is shut off and air is blown straight out (front discharge)
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Main body
Downward discharge
Air discharge grille (Option)
332˚C 30˚C28˚C 26˚C 24˚C
22˚C20˚C
21
(m)
500 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Panel spacer
20 mmMin.195 mm
Slim body needs only 220 mm space above the
ceiling If you use a panel spacer (option), the
unit can be installed in the minimum space of
36/34/32
63
35/33/31
5034/32/30
4033/31/29
20/25/32Sound level
(HH/H/L)FXDQ-PB/NB
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models
FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessoryFXDQ-PB/NBVET: without a drain pump
Indoor Unit Lineup
Quiet, compact, and designed for user comfort
T-bar grid does not need to be cut.
designed for your comfort.
Comfortable across all areas
Low operation sound level
Option
Signal receiver unitNote: Wireless remote controllers and signal receiver units are sold
as a set
OptionNote: Remote controller cables not included
Cables should beobtained locally
FFQ50B 36/27 dB (A)
FFQ60B 41/32 dB (A) (H/ L )
Horizontal Flow
Less draught Ceiling Mounted Cassette (Compact Multi Flow) Type
Auto-swing between 0 and 60
Auto-swing between 25 and 60
Draft prevention setting (Set on site)
(Set on site)
Standard setting
Setting to prevent soiling of ceiling
Conditioned air is distributed evenly by Auto-swing operation.Adjustable airflow angle to suit all room conditions
25 60
FBQ60B 41/35 dB (A)
FBQ71B 41/35 dB (A)
(H/ L )
To cope with the challenges of L-shaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit This extends the possibilities for coping with human gathering patterns or sun lighting At the same time, different types of architectural space can be kept comfortable.
Flexible air discharge unit to fit various forms of space
Drain pump is equipped as standard accessory with
250 mm lift.
250 mm
L-shaped room U-shaped room Long room
Low operation sound level
Ceiling Mounted Built-in Type
FBQ60B / FBQ71B
Note: Remote controller cables not included
Cables should beobtained locally
Option
The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab.
It also works with both flexible and ordinary ducts
1
1 3
8
7
4 6
5
Air conditioner Long-life filter Air blow Air intake
425 mm or more 4
6 5
Long-life filter Air blow Air intake
5
Air conditioner Long-life filter
(procured locally)
Air blow Air intake
460 mm or more
8 Air intake
Ceiling return with high-efficiency filter With ordinary ducts
9 4
2
3 7 1
With high-efficiency filter
4 6 5
Air conditioner
Air blow Air intake
540 mm or more 13
7High-efficiency filter 10Air discharge opening flange
13Low-draft filter chamber
12Branch duct
11Rear intake filter chamber
4Flexible duct
5Air discharge grille
6Air discharge chamber
Trang 19Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Trang 20Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
0.0310.027
2.82,80010,9003.2
9,6002,400
FXFQ25SVM
441/406/35330/28.5/2712.5/11.5/10.0
0.0310.027
3.63,40013,6004.0
12,3003,100
FXFQ32SVM
512/459/38831/29/2714.5/13.0/11.0
0.0410.037
4.54,30017,1005.0
15,4003,900
FXFQ40SVM
23
777/618/47736/32/2822.0/17.5/13.5
0.0800.075
5.65,40021,5006.3
19,100 4,800
FXFQ50SVM
BYCQ125B-W1
6.412.7I.D 25×O.D 32(VP25)
15.99.5
7.16,90027,3008.0
24,200 6,100
FXFQ63SVM
830/653/47738/33/2823.5/18.5/13.5
0.0950.090
11.210,80042,70012.5
38,2009,600
FXFQ100SVM
1,165/918/67144/38/3233.0/26.0/19.0
0.1940.180
9.08,60034,10010.0
30,7007,700
FXFQ80SVM
830/688/53038/35/3123.5/19.5/15.0
0.0950.090
14.013,80054,60016.0
47,800 12,000
FXFQ125SVM
1,218/971/74145/40/3534.5/27.5/21.0
0.2190.199
26
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•
• Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
cfmdB(A)mmkgmm
mmkg
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)DrainModelColourDimensions(H×W×D)Weight
Power consumptionCasing
Sound level (H/M/L)Airflow rate (H/M/L)
Dimensions (H×W×D)Machine weightPiping connections
Panel(Option)
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
Ceiling Mounted Cassette (Round Flow) Type
1-phase, 220-240 V, 50 Hz2,400
9,6002.82,80010,9003.20.0330.027
3,10012,3003.63,40013,6004.00.0330.027
3,90015,4004.54,30017,1005.00.0470.034
4,80019,1005.65,40021,5006.30.0520.03813/11.5/10
459/406/35330/28.5/27
15/13/11530/459/38831/29/27
16/13.5/11565/477/38832/29.5/27
FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1
Galvanised steel plate
6,100 7,700 9,600 12,00024,200 30,700 38,200 47,800
6,90027,3008.00.0660.053
8,60034,10010.00.0930.075
10,80042,70012.50.1870.174
13,80054,60016.00.2090.20019/16.5/13.5
671/583/47734/31/28
32/26/201,130/918/70643/37.5/32
33/28/22.51,165/989/79444/39/34
21/18/15742/636/53036/33.5/31
FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1
9.5 15.9VP25 (External Dia, 32/Internal Dia, 25)
BYCP125K-W1Fresh white50X950X9505.5
6.4 12.7
13/11.5/10459/406/35330/28.5/27
cfmdB(A)mmkgmm
mmkg
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)DrainModelColourDimensions(H×W×D)Weight
Casing
Sound level (HH/H/L)Dimensions (H×W×D)Machine weight
Piping connections
Panel(Option)
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeatingAirflow rate (HH/H/L)
19.5
Ceiling Mounted Cassette (Compact Multi Flow) Type
4-way Flow Ceiling Suspended Type
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
• Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
During actual operation, these values are normally somewhat higher as a result of ambient conditions
1-phase, 220-240 V/220 V, 50/60 Hz1,900
7,5002.22,2008,5002.5
2,4009,6002.82,80010,9003.2
3,10012,3003.63,40013,6004.00.0760.068
3,90015,4004.54,30017,1005.00.0890.080
4,80019,1005.65,40021,5006.30.1150.107Galvanised steel plate
286×575×575186.412.7VP20 (External Dia, 26/Internal Dia, 20)
BYFQ60B8W1White (6.5Y9.5/0.5)55×700×7002.7
FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
1-phase, 220-240 V/220-230 V, 50/60 Hz
8.07,70030,7009.00.0900.073
11.210,80042,70012.50.2000.179Fresh white
0.0730.064
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
cfmdB(A)mmkgmm
mmkg
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)DrainModelColourDimensions(H×W×D)Weight
Casing
Dimensions (H×W×D)Machine weightPiping connections
Panel(Option)
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
cfmdB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Casing
Sound level (H/M/L)Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeatingAirflow rate (H/L)
Airflow rate (H/M/L)
Sound level (H/L) 230 V
Power consumption
Power consumptionPower consumption
During actual operation, these values are normally somewhat higher as a result of ambient conditions
Trang 21Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Specifications
Ceiling Mounted Cassette (Double Flow) Type
Ceiling Mounted Cassette Corner Type
FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE
2,80010,9003.20.0920.059
3,40013,6004.00.0920.059
4,30017,1005.00.1300.097
5,40021,5006.30.1300.097
6,90027,3008.00.1610.126
8,60034,10010.00.2090.176
13,80054,60016.00.2560.223Galvanised steel plate
VP25 (External Dia, 32/Internal Dia, 25)
White (10Y9/0.5)53×1,030×680 53×1,030×680 53×1,030×680 53×1,245×680 53×1,245×680 53×1,430×680 53×1,920×680 53×1,920×680
FXKQ25MAVE
9,6002,400
Galvanised steel plate11/9
FXKQ32MAVE
12,3003,100
FXKQ40MAVE
15,4003,900
FXKQ63MAVE
24,2006,100
215X1,110X71031 6.4 12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYK45FJW1White (10Y9/0.5)
70X1,240X8008.5
215X1,110X71031 6.4 12.7
70X1,240X8008.5
215X1,110X71031 6.4 12.7
70X1,240X8008.5
215X1,310X71034 9.5 15.9BYK71FJW1
70X1,440X8009.5
1-phase, 220-240 V/220 V, 50/60 Hz
Note: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward
During actual operation, these values are normally somewhat higher as a result of ambient conditions
2,80010,9003.20.0660.046
3,40013,6004.00.0660.046
4,30017,1005.00.0760.056
6,90027,3008.00.1050.085
cfmdB(A)mmkgmm
mmkg
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)DrainModelColourDimensions(H×W×D)Weight
Power consumptionCasing
Sound level (H/L)Dimensions (H×W×D)Machine weightPiping connections
Panel(Option)
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
cfmmmkgmm
mmkg
kcal/hBtu/hkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)DrainModelColourDimensions(H×W×D)Weight
Power consumptionCasing
Sound level (H/L)Dimensions (H×W×D)Machine weightPiping connections
Panel(Option)
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
kW
220 V dB(A)Airflow rate (H/L)
Airflow rate (HH/M/L)
Slim Ceiling Mounted Duct Type (700 mm width type)
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
FXDQ40NBVE FXDQ40NBVET
FXDQ50NBVE FXDQ50NBVET
FXDQ63NBVE FXDQ63NBVET
1-phase, 220-240 V/220 V, 50/60 Hz1,900
7,5002.22,2008,5002.5
12,3003.63,40013,6004.00.0700.070
9,6002.82,80010,9003.20.0670.067
0.0860.0670.0670.067
VP20 (External Dia, 26/Internal Dia, 20)
• Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent piping length: 7.5m, Level difference: 0m
Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
5.65,40021,5006.30.1650.1520.1520.152
7.16,90027,3008.00.1810.1680.1680.1680.160
Galvanised steel plate
VP20 (External Dia, 26/Internal Dia, 20)
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
During actual operation, these values are normally somewhat higher as a result of ambient conditions
1: Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa
2: External static pressure is changeable to set by the remote controller This pressure means "High static pressure - Standard" (Factory setting is
10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.) 3: The values of operation sound level represent those for rear-suction operation Sound level values for bottom-suction operation can be Heating: Indoor temp.: 20℃DB, Outdoor temp.: 7℃DB, 6℃WB, Equivalent piping length: 7.5 m, Level difference: 0 m
cfmPadB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumption(FXDQ-PBVET)
Power consumption(FXDQ-PBVE)
Casing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
CoolingHeating
with drain pumpwithout drain pump
External static pressureSound level (HH/H/L)
cfmPadB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumption(FXDQ-PBVET)
Power consumption(FXDQ-PBVE)
Casing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
CoolingHeating
with drain pumpwithout drain pump
External static pressureSound level (HH/H/L)
2
1 1
220 V
Trang 22Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Specifications
Ceiling Mounted Duct Type
Note: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
During actual operation, these values are normally somewhat higher as a result of ambient conditions
1 : Power consumption values are based on conditions of rated external static pressure
2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen 125P) or ten (FXMQ140P) levels of control These values indicate the lowest and highest possible static pressures The standard static pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P
(FXMQ50-15,4003,900
565/459/388
19,1004,800
635/582/530
6.4 12.7
6.4 12.7
16/13/11 18/16.5/15
1 1
1 1
1
1 1
1 1
1
1 1
1 1
1
1 1
1 1
1
7,5001,900
318/265/2302.2
6.4 12.79/7.5/6.5
9,6002,400
318/265/2302.8
6.4 12.79/7.5/6.5
12,3003,100
335/282/2473.6
6.4 12.79.5/8/7
VP25 (External Dia, 32/Internal Dia, 25)
24,2006,100
688/618/565
9.5 15.9
30,7007,700
883/794/706
9.5 15.9
38,2009,600
1,130/953/812
9.5 15.9
47,80012,000
1,377/1,165/988
9.5 15.9
54,60013,800
1,624/1,377/1,130
9.5 15.9
6,90027,3008.00.1380.218
8,60034,10010.00.1850.286
10,80042,70012.50.2150.364
13,80054,60016.00.2840.449
15,50061,40018.00.4050.449
2,80010,9003.20.0560.069
3,40013,6004.00.0600.073
4,30017,1005.00.1510.182
5,40021,5006.30.1280.203
300X1,000X700300X700X700
300X550X700300X550X700
300X550X700
3628
2525
25
41/39/3739/37/35
34/32/3033/31/29
33/31/29
cfmPadB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumptionCasing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
External static pressureSound level (HH/H/L)
cfmPadB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumptionCasing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
1-phase, 220-240 V/220 V, 50/60 Hz
Galvanised steel plate
300X1,400X70046
300X1,000X70036
300X1,000X70036
300X1,400X70046
300X1,400X70047
FXMQ125PVE FXMQ140PVE
CoolingHeating
External static pressureSound level (HH/H/L)Airflow rate (HH/H/L)
Galvanised steel plate
VP25 (External Dia, 32/Internal Dia, 25)
6,90027,3008.00.1150.115
10,80042,70012.50.1350.135White (10Y9/0.5)
VP20 (External Dia, 26/Internal Dia, 20)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
• Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
• Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre
(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions
1 : Power consumption values are based on conditions of standard external static pressure
2 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure"
76,40019,300
95,50024,1001-phase, 220-240 V/220 V, 50/60 Hz
Galvanised steel plate58/50
2,047/1,765
470X1,380X1,100137 9.5 19.1
PS1B
72/622,542/2,189
470X1,380X1,100137 9.5 22.2
27,100107,50031.51.4651.465
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
cfmPammkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumptionCasing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
External static pressureSound level(H/L)
cfmdB(A)mmkgmm
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumptionCasing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
Sound level (H/L)
220 V dB(A)Airflow rate (H/L)
Airflow rate (H/L)
Ceiling Mounted Duct Type
Ceiling Suspended Type
6.4
Trang 23Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Specifications
Wall Mounted Type
Floor Standing Type/Concealed Floor Standing Type
FXLQ
FXNQ
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•
•Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
• Sound level: (FXAQ-P) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions
FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
2,80010,9003.20.0280.034
3,40013,6004.00.0300.035
4,30017,1005.00.0200.020
5,40021,5006.30.0330.039
6,90027,3008.00.0500.060
2,2008,5002.50.0490.049
2,80010,9003.20.0490.049
3,40013,6004.00.0900.090
4,30017,1005.00.0900.090
5,40021,5006.30.1100.110
6,90027,3008.00.1100.110
FXLQ40MAVE FXNQ40MAVE
FXLQ32MAVE FXNQ32MAVE
FXLQ25MAVE FXNQ25MAVE
FXLQ20MAVE FXNQ20MAVE
FXLQ63MAVE FXNQ63MAVE
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Power consumptionCasing
Dimensions (H×W×D)Machine weightPiping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
Sound level (H/L)
Power consumptionCasing
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
Airflow rate (H/L)
Rp1 (PS 1B internal thread)Long-life filter (anti-mould resin net)
Belt drive system
3-phase 4-wire system, 380–415 V, 50 Hz
Ivory white (5Y7.5/1)
FXVQ125MY1
1,670×750×51011552 15.9 (Brazing)
FXVQ250MY1 FXVQ400MY1
1,900×1,470×720
27061
1,900×1,170×72022564 12.7 (Brazing) 28.6 (Brazing)
FXVQ200MY1
0.590.59
12,00047,80014.013,80054,60016.0
19,30076,40022.421,50085,30025.0
24,10095,50028.027,100107,50031.5
38,700154,00045.043,000171,000
48,200191,000
1.681.68
50.03.973.97
2.622.62
1.411.411,670×1,170×51016559 22.2 (Brazing)
1,670×950×51014055 9.5 (Brazing) 19.1 (Brazing)
FXVQ500MY1
5.025.02
5.51726,072
FXVQ500MY16
56.054,200215,00063.0
15.9 (Brazing) 28.6 (Brazing)
0.75431,518
1.5692,436
1.5863,036
3.71344,730
3.71655,825
480
29567
Notes: Specifications are based on the following conditions;
•Cooling : Indoor temp of 27°CDB, 19°CWB, and outdoor temp of 35°CDB
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m
•Capacity of indoor unit is only for reference Actual capacity of indoor unit is based on the total capacity index
(See Engineering Data Book for details.)
*1 Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value)
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow
*2 The value is the external static pressure with standard pulley
mmkgdB(A)
mmmmmm
kW
m3/mincfmPa
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
LiquidGasDrain
TypeMotor outputAirflow rateExternal static pressure *2Drive system
Power consumption
Casing colour
Sound level *1
Dimensions (H×W×D)Machine weight
Piping connections
Power supply
Heating capacityCooling capacity
MODEL
CoolingHeating
Air filter
Fan
Floor Standing Duct Type
cfmdB(A)
kcal/hBtu/hkWkcal/hBtu/hkWkWkW
m3/min
Liquid (Flare)Gas (Flare)Drain
Machine weightPiping connections
Sound level (H/L)Dimensions
220 VFXNQFXLQFXNQ
mmkgmmAirflow rate (H/L)
Trang 24Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
Slim Ceiling Mounted Duct Type
Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for F(C)DK(X)S-EA and
40 Pa for FDK(X)S-C(A) Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C
Note: * For Heat Pump type only
Wall Mounted Type
Ceiling Mounted Cassette Type
Ceiling Mounted Cassette (Compact Multi Flow) Type
BP Units for connection to residential indoor units
8.7 (307)
200X700X620 200X900X620 200X1,100X620
3027
40
25
VP20 (External Dia 26/Internal Dia 20)Both liquid and gas pipes21
30
9.5 (335) 10.0 (353) 12.0 (424)
37/33/3135/31/29
16.0 (565)38/34/321-phase, 220-240 V/220-230 V, 50/60 Hz
5 steps, quiet and automaticMicrocomputer control
CDXS25EAVMA CDXS35EAVMA FDXS25CVMA FDXS35CVMA FDXS50CVMA FDXS60CVMA
MODEL Cooling Only Heat Pump
Power supplyAirflow rates (H) m3/min (cfm)Sound levels (H/L/SL)* dB (A)Fan speed
Temperature controlDimensions (HXWXD) mm
kgmm
Pa
Machine weightLiquid (Flare)Gas (Flare)Drain
PipingconnectionsHeat insulationExternal static pressure
Note: * For 220 V operation
Ceiling Mounted Built-in Type
17.0 (600) 1-phase, 220-240 V, 50 Hz 19.0 (670)
41/35
2 stepsMicrocomputer control
300X1,000X80041
I.D ø25XO.D ø32Both liquid and gas pipesBYBS71DJW1White
55X1,100X5004.5
Power supplyAirflow rates (H)Sound levels (H/L)*
Fan speedTemperature controlDimensions (HXWXD)Machine weightLiquid (Flare)Gas (Flare)DrainModelColourDimensions (HXWXD)Weight
PipingconnectionsHeat insulationPanel(Option)
mmkg
Note: * Total auxiliary piping length
1-phase, 220-240 V/220-230 V, 50/60 Hz
100.05
180X294 (+356*)X350
3 for power supply (including earth wiring), 2 for interunit wiring (outdoor unit-BP, BP-BP),
4 for interunit wiring (BP-indoor unit)
Both liquid and gas pipes2.5 kW class to 7.1 kW class residential indoor units
2.5
Power supplyNumber of portsPower consumptionRunning currentDimensions (HXWXD)Machine weightNumber of wiring connectionsPiping
connections(Brazing)
Liquid MainBranchMainBranchGasHeat insulationConnectable indoor unitsMin rated capacity of connectable indoor unitsMax rated capacity of connectable indoor units
mmmmmmmm
kWkWkg
1-phase, 220-240 V, 50 Hz
2 stepsMicrocomputer control
286X575X57517.5
VP20 (External Dia 26/Internal Dia 20)Both liquid and gas pipesBYFQ60B8W1White
55X700X7002.7
9.0 (318)29.5/24.5 32/25
10.0 (353)
9.5
12.0 (424)36/27
15.0 (530)41/32
FFQ60BV1B
Power supply
dB (A)
mmkgmm
mmkg
Airflow rates (H)Sound levels (H/L)*
Fan speedTemperature controlDimensions (HXWXD)Machine weightLiquid (Flare)Gas (Flare)DrainModelColourDimensions (HXWXD)Weight
PipingconnectionsHeat insulationPanel(Option)
6.4
12.7
6.4 12.7
9.5 15.9
283X800X195 290X795X2389
8.7 (307) 8.9 (314) 14.7 (519) 16.2 (572) 17.4 (614)9.4 (332) 9.7 (342) 16.2 (572) 17.4 (614) 21.5 (759)37/25/22 39/26/23 43/34/31 45/36/33 46/37/3437/28/25 38/29/26
11.4 (402)
–
44/35/32
– 42/33/30 44/35/32 46/37/341-phase, 220-240 V/220-230 V, 50/60 Hz
5 steps, quiet and automaticMicrocomputer control
Both liquid and gas pipes
White
6.4 18.0 9.5
9.5X119.1X16.4X3
15.9X3
6.4X215.9X2
12.7 15.9
290X1,050X23812
FTXS20DVMA FTXS25EVMA FTXS35EVMA FTXS50FVMA FTXS60FVMA FTXS71FVMA
Power supplyFront panel colourAirflow rates (H) Cooling m3/min (cfm)
dB (A)
mmkgmm
Heating*
Cooling Heating*
Sound levels (H/L/SL)Fan speedTemperature controlDimensions (HXWXD)Machine weightLiquid (Flare)Gas (Flare)Drain
PipingconnectionsHeat insulation
Note: * For 220 V operation
1-phase, 220-240 V/220 V, 50/60 Hz
2 stepsMicrocomputer control
230X840X84024
I.D ø25XO.D ø32Both liquid and gas pipesBYC125K-W1White
40X950X9505
FCQ71BVE
Power supplyAirflow rates (H)Sound levels (H/L)*
Fan speedTemperature controlDimensions (HXWXD)Machine weightLiquid (Flare)Gas (Flare) DrainModelColourDimensions (HXWXD) mm
mmkgmm
dB (A)
kgWeight
PipingconnectionsHeat insulationPanel(Option)
FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
MODEL Cooling Only Heat Pump – FTKS25DVM FTKS35DVM FTKS50BVMA FTKS50FVM FTKS60FVM FTKS71FVM –
Trang 25Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
RXQ8TY1(E) RXQ8TY1(E)
RXQ6TY1(E) RXQ8TY1(E)
RXQ6TY1(E) RXQ6TY1(E)
RXQ16THY1(E) RXQ18THY1(E) RXQ20THY1(E) RXQ22THY1(E) RXQ24THY1(E) RXQ12THY1(E) RXQ14THY1(E)
RXQ6TY1(E) RXQ6TY1(E) RXQ6TY1(E)
RXQ6TY1(E) RXQ6TY1(E) RXQ8TY1(E)
RXQ6TY1(E) RXQ8TY1(E) RXQ8TY1(E)
RXQ8TY1(E) RXQ8TY1(E) RXQ8TY1(E)
RXQ8TY1(E) RXQ8TY1(E) RXQ12TY1(E)
RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E)
RXQ8TY1(E) RXQ12TY1(E) RXQ12TY1(E)
RXQ8TY1(E) RXQ12TY1(E) RXQ14TY1(E)
RXQ8TY1(E) RXQ14TY1(E) RXQ14TY1(E)
RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E)
RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E)
RXQ8TY1(E) RXQ8TY1(E) RXQ10TY1(E) RXQ26THY1(E) RXQ28THY1(E) RXQ30THY1(E) RXQ32THY1(E) RXQ34THY1(E) RXQ36THY1(E) RXQ38THY1(E) RXQ40THY1(E)
Note: 1 Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution Please contact Daikin for more information
2 Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Cooling Only
http://daikinvrv.com.vn info@daikinvrv.com.vn Hotline: 0976 173 173
Trang 26Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
108,000 427,000 125 34.8 3-100
112,000 444,000 130 36.9 3-100
116,000 461,000 135 39.0 3-100
120,000 478,000 140 41.4 3-100
RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E)
RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E)
RXQ14TY1(E) RXQ16TY1(E) RXQ16TY1(E)
RXQ16TY1(E) RXQ16TY1(E) RXQ16TY1(E)
RXQ16TY1(E) RXQ16TY1(E) RXQ18TY1(E) RXQ42THY1(E) RXQ44THY1(E) RXQ46THY1(E) RXQ48THY1(E) RXQ50THY1(E)
65 10.3+10.3+10.3
285+285+285 65 10.3+10.3+10.4
RXQ6TY1(E) RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ16TY1(E)
233+233+233 233+233+233
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 285+285+285 65 10.3+10.4+10.4
233+233+233
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 285+285+285 66 10.4+10.4+10.4
233+233+233
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 285+285+285 66 10.4+10.4+10.5 233+233+233
13,800 54,600 16.0 3.63 20-100
19,300 76,400 22.4 5.21 20-100
24,100 95,500 28.0 7.29 16-100
28,800 114,000 33.5 9.01 15-100
34,400 136,000 40.0 10.9 11-100
38,700 154,000 45.0 13.0 10-100
185 55 5.9
185 56 5.9
195 57 6.0
195 59 6.3
285 60 10.3
285 61 10.4
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
12.7 (Brazing) 28.6 (Brazing)
19.1 (Brazing)
9.5 (Brazing)
22.2 (Brazing)
%
kg dB(A) ºCDB kg
kW m³/min mm
Charge
Type
Type Liquid Gas
mm mm
MODEL
Power supply
Power consumption Capacity control
Compressor
Dimensions (H × W × D) Machine weight Sound level Refrigerant
Piping connections
kcal/h Btu/h kW kW
%
kg dB(A) ºCDB kg
kW m³/min mm
Charge
Type
Type Liquid Gas
mm mm
Combination units
Cooling capacity
Motor output Airflow rate
Operation range
Combination units
Cooling capacity
Motor output Airflow rate
Operation range
Casing colour Casing colour
Note: 1 Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution Please contact Daikin for more information
2 Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Note: 1 Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric component box, in addition to the fins of the heat exchanger These models are designed specifically for use in areas which are
subject to salt damage and atmospheric pollution Please contact Daikin for more information
2 Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Cooling Only
http://daikinvrv.com.vn info@daikinvrv.com.vn Hotline: 0976 173 173
Trang 27Outdoor Units
Outdoor Unit Lineup
Cooling Only / Heat Pump
The outdoor unit capacity is up to 60 HP in increment of 2 HP.
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution
12, 14, 16 HP
RX(Y)Q36THY1(E) RX(Y)Q40THY1(E)
RX(Y)Q12THY1(E) RX(Y)Q14THY1(E) RX(Y)Q16THY1(E)
18, 20, 22, 24, 26, 28, 30, 32 HP 36, 40 HP
42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
Triple Outdoor Units
Triple Outdoor Units
Triple Outdoor Units
Double Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP
18, 20 HP 22, 24 HP 26, 28, 30, 32 HP 34, 36, 38, 40 HP
High-COP Type
Standard Type
Space Saving Type
RX(Y)Q34THY1(E) RX(Y)Q38THY1(E)
RX(Y)Q28TNY1(E) RX(Y)Q30TNY1(E) RX(Y)Q32TNY1(E)
RX(Y)Q22TNY1(E) RX(Y)Q24TNY1(E) RX(Y)Q26TNY1(E)
RX(Y)Q34TNY1(E) RX(Y)Q36TNY1(E) RX(Y)Q38TNY1(E) RX(Y)Q40TNY1(E) RX(Y)Q42TNY1(E) RX(Y)Q44TNY1(E)
RX(Y)Q54TNY1(E) RX(Y)Q56TNY1(E) RX(Y)Q58TNY1(E) RX(Y)Q60TNY1(E)
RX(Y)Q18THY1(E) RX(Y)Q20THY1(E) RX(Y)Q22THY1(E) RX(Y)Q24THY1(E)
RX(Y)Q26THY1(E) RX(Y)Q28THY1(E) RX(Y)Q30THY1(E) RX(Y)Q32THY1(E)
RX(Y)Q42THY1(E) RX(Y)Q44THY1(E) RX(Y)Q46THY1(E)
RX(Y)Q48THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q34TSY1(E) RX(Y)Q36TSY1(E) RX(Y)Q38TSY1(E) RX(Y)Q40TSY1(E)
RX(Y)Q26TSY1(E) RX(Y)Q28TSY1(E) RX(Y)Q30TSY1(E) RX(Y)Q32TSY1(E)
Lineup
HP High-COP Type Standard Type Space Saving Type
Indoor Unit Lineup
Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room When there is no movement, it adjusts the temperature
by 2˚C for energy savings.
3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTK(X)S50/60/71F.
FTK(X)S20/25 37/25/22 dB (A)
FTK(X)S35 39/26/23 dB (A)
FTK(X)S50 43/34/31 dB (A)
FTK(X)S60 45/36/33 dB (A)
FTK(X)S71 46/37/34 dB (A) (H/L/ SL )
When you are in the room When you go out
A uniform temperature
is achieved throughout the entire room
Stylish flat panel harmonises with your interior décor
Wall Mounted Type
Titanium apatite is a photocatalytic material with high adsorption power Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface The photocatalyst is activated simply by exposure to light.
These filters are not medical devices Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal TestTesting method: dropping methodResult certificate: No 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation
Titanium Apatite Photocatalytic Air-purifying Filter
Air filter
Catches dust
Slim and smooth design suits your shallow ceiling
Signals from the wireless remote controller are
transmitted to the signal receiver
240 mm
200 mm
Only 700 mm
FDKS-EA CDXS-EA
FDXS60 38/34/ 32 dB (A)
(H/L/ SL )
Low operation sound level
Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home This means that
an air-conditioned welcome awaits when you wake or return It also means that the indoor temperature can quickly return to your favourite comfort setting.
Models in the FDKS-EA and CDXS-EA series are
only 700 mm in width and 21 kg in weight, so are
easily installed in limited spaces Just 200 mm in
height, all models can be installed in rooms with
as little as 240 mm depth between the drop
ceiling and ceiling slab, making them ideal for
even shallow ceilings
Notes:
1 To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber
2 Grilles, piping connections, ducts, and installation parts should be obtained locally Slim Ceiling Mounted Duct type models do not have drain-up pumps
3 The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature
Suction grille (KDGF19A45)
Option
* Locally obtained parts
AIR
Air suction grille*
Suction duct*
Signal receiver
Air discharge duct* Suspension bolt*
Air discharge grille*
Signal receiver wire Chamber
Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used
Great for hotel use!
Slim Ceiling Mounted Duct Type
Cooling Only
Heat Pump
FDKS25EA / FDKS35EA FDKS25CA / FDKS35CA FDKS50C / FDKS60C CDXS25EA / CDXS35EA FDXS25C / FDXS35C FDXS50C / FDXS60C
Cooling Only Heat Pump FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only Heat Pump FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
FTKS50B Cooling Only
48,100 191,000 55.9 14.2 8-100
53,700 213,000 62.4 16.1 7-100
58,500 232,000 68.0 18.2 6-100
63,200 251,000 73.5 19.9 6-100
68,800 273,000 80.0 21.8 5-100
73,100 290,000 85.0 23.9 5-100
RXQ8TY1(E) RXQ14TY1(E)
RXQ8TY1(E) RXQ12TY1(E)
RXQ8TY1(E) RXQ10TY1(E)
RXQ10TY1(E) RXQ12TY1(E) RXQ12TY1(E)
RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E)
RXQ8TY1(E) RXQ12TY1(E) RXQ18TY1(E)
RXQ12TY1(E) RXQ12TY1(E) RXQ16TY1(E)
RXQ12TY1(E) RXQ14TY1(E) RXQ16TY1(E)
RXQ12TY1(E) RXQ16TY1(E) RXQ16TY1(E)
RXQ14TY1(E) RXQ14TY1(E) RXQ18TY1(E)
RXQ22TNY1(E) RXQ24TNY1(E) RXQ26TNY1(E) RXQ28TNY1(E) RXQ30TNY1(E) RXQ18TNY1(E) RXQ20TNY1(E)
(3.4 X 1)+
(4.1 X 1) (3.4 (5.2 X X 1)+ 1)
(1,657 X 930 X 765)+
(1,657 X 930 X 765) (1,657 (1,657 X X 930 930 X X 765)+ 765) (1,657 (1,657 X X 1,240 930 X 765)+ X 765) (1,657 (1,657 X X 1,240 930 X 765)+ X 765) (1,657 (1,657 X X 1,240 930 X 765)+ X 765) (1,657 (1,657 X X 1,240 1,240 X X 765)+ 765) (1,657 (1,657 X X 1,240 1,240 X X 765)+ 765) 185+195
60 5.9+6.0
185+195 61 5.9+6.3
185+285 61 5.9+10.3
195+285 62 6.0+10.3
195+285 63 6.3+10.3
285+285 63 10.3+10.3
285+285 64 10.3+10.4
RXQ10TY1(E) RXQ14TY1(E)
RXQ12TY1(E) RXQ14TY1(E)
RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ14TY1(E) RXQ18TY1(E)
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 285+285 64 10.3+10.5
81,700 324,000 95.0 25.3 5-100
(1,657 X 930 X 765)+
(1,657 X 930 X 765)+
(1,657 X 930 X 765) 195+195+195 63 6.0+6.3+6.3 165+178+178
86,900 345,000 101 27.0 5-100
(1,657 X 930 X 765)+
(1,657 X 930 X 765)+
(1,657 X 930 X 765) 195+195+195 64 6.3+6.3+6.3 178+178+178
91,200 362,000 106 29.6 4-100
(1,657 X 930 X 765)+
(1,657 X 930 X 765)+
(1,657 X 1,240 X 765) 185+195+285 64 5.9+6.3+10.5 157+178+233
96,300 382,000 112 31.0 4-100
(1,657 X 930 X 765)+
(1,657 X 930 X 765)+
(1,657 X 1,240 X 765) 195+195+285 65 6.3+6.3+10.4
102,000 406,000 119 32.9 4-100
(1,657 X 930 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 195+285+285 65 6.3+10.3+10.4 178+233+233
107,000 423,000 124 35.0 4-100
(1,657 X 930 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 195+285+285 65 6.3+10.4+10.4 178+233+233
112,000 444,000 130 37.2 3-100
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765)+
(1,657 X 1,240 X 765) 285+285+285 66 10.3+10.3+10.5
233+233+233
(2.9 X 1)+(3.3 X 1)+
(2.9 X 1)+(3.3 X 1) (2.9 (3.6 X X 1)+(3.3 1)+(3.7 X X 1)+ 1) (2.9 (4.4 X X 1)+(3.3 1)+(4.0 X X 1)+ 1)
15.9 (Brazing) 28.6 (Brazing)
15.9 (Brazing) 28.6 (Brazing)
15.9 (Brazing) 28.6 (Brazing)
15.9 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 34.9 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
19.1 (Brazing) 41.3 (Brazing)
3-phase 4-wire system, 380–415 V, 50 Hz
Hermetically Sealed Scroll Type
-5 to 43 R-410A
3-phase 4-wire system, 380–415 V, 50 Hz
Hermetically Sealed Scroll Type
-5 to 43 R-410A
%
kg dB(A) ºCDB kg
kW m³/min mm
Charge
Type
Type Liquid Gas
mm mm
Combination units
Cooling capacity
Motor output Airflow rate
Operation range
Casing colour
Note: 1 Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution Please contact Daikin for more information
2 Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Cooling Only