FBE 36kV Gas-insulated switchgear Technical characteristics FB >>Lightning impulse withstand voltage >>50Hz 1mm >>Short time withstand current 1 sec.. kA 16 >>Enclosure degree of protect

Trang 1

FBE 36kV Gas-insulated switchgear

Technical characteristics FB

>>Lightning impulse withstand voltage

>>50Hz 1mm

>>Short time withstand current 1 sec kA 16

>>Enclosure degree of protection IP2X

THE FB RING MAIN

UNIT IS INTENDED FOR

INSTALLATION IN A

COMPACT SUBSTATION

UP TO 36KV RATED

VOLTAGE

FEATURES

>Voltage ratings up to 36kV

>Improved personnel safety

through separate devices for

switch disconnectors and

earthingswitches,

>Convenient cable phase exchange

through horizontal arrangement

of outside cone bushings

(i.e three adjacent bushings at

the same level),

>Super easy fuse changing,

>No bridging of the isolating gap

condition throughout its entire

service life,

>Spacious cable connection

compartment - suitable for parallel

cable connection and any additional

surge arrestor - inside the unit

profile,

>Particularly clear control panel

with user control and foolproof

protection against mishandling

2

3 1

Trang 2

OPTIONAL EQUIPMENT

>HV bushings :

• 3 plug-in bushings, for straight

or bracket mobile parts corresponding to the fixed parts

In this case it is imperative to give the cable characteristics (nature, cross-section, diameter

on insulator)

>LV bushings:

• 4 porcelain LV seal-off bushings for Sn = 250kVA,

• 1 interlocking system for the plug-in bushings and the change-over switch, lock is not supplied,

• 1 sealable protection cover on the LV seal-off bushings (only in the case of plug-in HVA bushings),

• 1 collar for LV connection by wiring sheath to : thermometer, thermostat, gas detection relay, multi-function safety relay (DGPT2), etc

MELODY Oil-immersed transformer

STANDARD EQUIPMENT

>HV bushings:

• 3 bushings Can be plugged-in, fixed parts 24/250 on the 24kV series

>Low voltage bushings :

• 4 LV seal-off bushings

Sn = 250kVA,

• 4 multi-directional roller bearings

• 1 filling hole,

• 1 draining stopper,

• 2 lifting and untanking rings,

• 2 earthing points on the lid,

• 1 name and rating plate that can

be moved and positioned on all 4 sides

• RAL 7033 colour shade, standard paint

Rated Rated Load No-load Short circuit Sound pwer Weights power short circuit losses losses current (sound pressure

GENERAL

Three-phase distribution transformers, completely filled, hermetically sealed, immersed in mineral oil, featuring ONAN natural cooling, for continuous service both indoor

and outdoor.

RATED VOLTAGES

• HV: from 5.5 to 33kV Preferential voltages:

30 - 20 - 15 - 10 – 5.5kV, and double voltage applications, 10/20kV and 15/20kV (by change-over switches that can be operated de-energised, without untanking)

Other voltages: please consult us,

• LV: 410V at no-load between phase 237V between phase and neutral

• Rated frequency: 50/60Hz

Trang 3

HARMONY Dry transformer

HARMONY™ THE SAFE

ECO-FRIENDLY SOLUTION

Our HARMONY™ range of

dry type cast resin transformers

complies with all your distribution

transformer requirements.

HARMONY™ is available as

single and three-phase units,

with ratings up to 20MVA and

36kV, 50/60Hz, F class (H class

on request) dry type, AN for

continuous indoor service with

AF and outdoor options, and

with normal or reduced losses.

CONFORMITY

WITH SPECIFICATIONS/

STANDARDS

>IEC 60726 and IEC 60076-11

>HD 464.S1+A2 + A3 and

HD 538.1 S1

>EN 60726

>NF C 52-726 and NF C 52-115

>VDE 0532 part 6

>DIN 42523

>ANSI C57.12.01

SAFETY &

RELIABILITY FIRST

HARMONY™ transformers have

been put through the most stringent

series of tests

HARMONY™ is one of few

transfor-mers having successfully passed

these tests and is characterized by

the following features:

>C 2 Insensitive to thermal shocks

Withstands overloads and frequent

changes in loading Dielectric tests

of standard and partial discharges

=10pC

>Highly resistant to polluted

environments and humidity E 2

Immune to corrosive environments

>Reduced flammability and

self-extinguishing

Excellent classification according

to the HD464 S1

Standard: F 1 Fire behaviour

Rated Losses High Voltage Short-circuit No-load Short-circuit Sound power/ Weights power (Suitable for UM voltage losses losses sound pressure level

12kV/24kV) Pk at 1 m distance

Trang 4

>Outgoing feeders equipped with NH2, NH00 or NH1 type fuses

>Measurement and processing unit (U, I, P, cos w)

>Device which can receive a set

of connectors used for energised connections (electrical generating set) This device occupies the space for a monobloc outgoing feeder

>Supply and RCX/ITI protection circuit, fault detector, power socket and measurement and

processing unit

TFD Low voltage DIN fuse board

SAFETY AND OPERATION

IP2X protection against front panel direct contacts

>Insulated operating key (Torx type terminal end)

>Reserve and insulation panels

>Re-supply interface for emergency connection (electrical

generating sets),

CONNECTION AND FIXING

The MV/LV TFD transformer connec-tions are in aluminium or copper with

a 240mm2cross-section

>The cables for public distribution outgoing feeders are equipped with a cross-section of 95 to 240mm2for the phases and

50 to 95mm2for the neutral

>Fixing using M12 type threaded bolts

>Fixing the switchboard to the wall using 4 M12 type threaded bolts

STANDARD

IEC 60439-1/ IEC 60947

Main electrical characteristics TUR 4x800 TUR 8x1200 TUR 8x1800

Rated voltage at 50Hz-1mn (kV)

Impulse whistand rated voltage (kV)

Rated current of the incoming

Short time withstand current (A)

GENERAL CHARACTERISTICS

The TFD switchboards are made

up of the following elements:

• 1 three-pole incoming

• Disconnector

• 1200A Switch

- 1000A circuit breaker

• 1 to 8 DIN NH2 three-pole

IP2X 400A outgoing feeders

of the type:

• Open

• 1 pole switching

• 3 poles switching (outgoing feeders NH00 or NH1 by request)

• 1 main busbar

• Tinned aluminium

• Tinned copper

Trang 5

TD Low voltage circuit breaker board

Main electrical characteristics TD direct incoming break switch TD load TD circuit breaker

Rated voltage at 50Hz-1mn (kV)

Impulse whistand rated voltage (kV)

Rated current of the incoming

Short time withstand current (A)

SAFETY AND OPERATION

IP2X protection against front panel direct contacts

>Possibility of tripping on temperature rise

>Improvement to and selective capability of the outgoing feeders’

protection in the case of an upst-ream circuit breaker

CONNECTION AND FIXING

The MV/LV TD transformer connections are in aluminium

or copper with a 240mm2cross-section

>Fixing the switchboard to the wall using 4 M12 type threaded bolts

STANDARD

IEC 60439-1/ IEC 60947

OPTIONS

>Measurement and processing unit (U, I, P, cos w)

>Supply and remoe control protection circuit (TN, TT or IT), fault detector,

socket and CMT device

INDUSTRIAL APPLICATIONS

By specific demand

GENERAL

CHARACTERISTICS

The TD switchboards are made

up of the following elements:

• 1 three-pole or four-pole

general power

interruption device

• Direct incoming

• Switch

• Circuit breaker 100 to 400

A branch circuit breaker

out-going feeders for distribution or

public lighting.

• 1 main busbar

• Tinned aluminium

• Tinned copper

Trang 6

FDW FUSES HVA Fuses according to the International

Standards

Standards These fuses meet the Standard requirements: IEC 60-282-1 and DIN 43625

Important Following the blowing of one (or two) fuses in a three-phase assembly, it is necessary and essential to replace all 3 fuses Accessories

Single pole or three pole fuse-base with insulators (please consult us) 7.2 to 36kV HVA fuses

• FD w

These FD w fuses of the associated type have a current limiter effect The rapidity of current interruption in the case of a short circuit is such that the fault current cannot reach its natural maximum value

They are generally used for the protection of transformers and the

FD 3M type is intended for the protection of motors or capacitors

VARISIL - FDw Surge arresters - Fuses

VARISIL LIGHTNING ARRESTERS

Standards Complies with the IEC 99-4 Standard and its latest additions

Technical characteristics Rated voltage: 6 and 42kV

Rated current: 10kA

Energy capacity: 4.8kJ/kV (HD) disconnector (20A sensitivity)

or indicator (10A) as an option in the vertical, inclined or

horizontal position

HE type VARISIL lightning arresters in zinc oxide and silicon casing for the protection

of distribution networks.

Lightning arresters in the VARISIL

HE range are reliable and their high performance has been proven under the most critical conditions.

Available for all levels of voltage and all neutral operating condi-tions, these lightning arresters are suitably adapted for regions frequently hit by lightning.

They can be equipped with a fault indicator (priority given to the continuity of protection) or a disconnector system (priority given to the continuity of service).

Various single pole or three-pole mounting fittings are on offer to permit their installation in the vertical, inclined or horizontal position, on the majority of existing utility poles.

Additional accessories (support base for a fit-on mounting, discharge counter, etc) are also available.

Trang 7

PTS - RCX OSCT - VPR

MV outdoor switchgear

RCX – OSCT REMOTE CONTROL BOX

As leader in the field of DAS/DMS (automation management systems/distribution management systems), we offer a full range of systems and equipment that operate in many different countries

The remote control unit, specially designed for the remote control of overhead HV power lines, provides

a profitable and complete solution

in order to reduce:

>The number of client current interruptions,

>The average duration of non-distributed energy,

>The time needed for repairs by service teams,

>Its modular architecture provides

a solution that is totally compatible with specific or future applications

The remote control box is in full conformity with both EDF and IEC Standards

VPR - POLE-MOUNTED

RECLOSER

Technology

>Vacuum interrupters

>Magnetic actuator

>316L stainless steel tank

>Sealed for life

>Zero maintenance

>Low pressure SF6 insulation

>Local and remote control

>Internal arc fault containment to

IEC 60298

Technical characteristics

>12.5kA

PTS OVERHEAD SWITCH AND DISCONNECTOR

A new generation of switches combining proven technologies for outdoor distribution applications up

to 36kV – 400 and 630A

Particularly suited to difficult climate environments, it integrates well-proven current interruption and insulation technologies in AREVA

SF6gas

The light-weight design of the switch and its choice of technologies, make it easy to handle and install

Its manufacture, in a watertight stainless steel tank and anti-corrosion treatment, gives it an increased service life

The switch requires no maintenance

A mechanical indicator of certain current interruption directly connected to the operating shaft is visible from the ground

The mechanism is a tumbler system with operation independent from the operator The switch is equipped with flexible bushings in a synthetic material which helps make it light-weight and resistant to vandalism

Operation is carried out manually or

by remote control

Trang 8

GMB Gas-insulated switchgear

GMB - THE UNIVERSAL SWITCHGEAR CONCEPT FOR APPLICATIONS WORLD-WIDE

Thanks to its extremely small dimensions, the compact design is very well suited for installation in:

>Prefabricated concrete stations

>Confined areas, to replace old stations

>Rated voltages up to 24kV

>Rated currents up to 1250A

>Rated peak currents up to 63kA

>Rated short-time withstand currents up to 25kA 3s

OPTIMUM SAFETY

>All active medium voltage components, including the busbar system, are installed in hermetically enclosed, gas-insulated, cladded compartments and are thus insensitive to:

– An aggressive atmosphere – Dirt

– Dust – Vermin and rodents

>Tested and approved according to IEC 60298

>IVIS Integrated voltage detection system for verification of safe isolation from supply and terminal connections

>Central gas monitoring thanks to the digital, autonomous monitoring and sensor system IGIS

Technical data (according to IEC 60298) GMB

>>Rated power frequency withstand voltage Hz 28 38 (42) 38 (42) 50

>>Rated lightning impulse

>>Rated peak withstand current up to kA 80 63 63 80

>>Rated current, busbar up to A 1250 1250 1250 1250

>>Rated current, circuit breaker up to A 1250 1250 1250 1250

>>Rated current disconnector up to A 1250 1250 1250 1250

>>Rated current load disconnector up to A 630 630 630 630

>>Rated short circuit making current up to kA 63 63 63 63

>>Rated short circuit breaking current up to kA 25 25 25 25

>>Rated short time current up to kA (3s) 25 (3s) 25 (3s) 25 (3s) 25 (3s)

>>Rated peak withstand current up to kA 63 63 63 63

>>Behaviour in case of internal fault

Degree of protection

For the main current circuit IP64; for drives IP2X (optional IP5X), for the cable connection compartment IP3X (optional IP5X)

Trang 9

WS Gas-insulated switchgear

The SF6gas is used as an insulation medium The gas insulated units are insensitive to environmental influences such as moisture, dust and aggressive gases and ensure maximum personnel protection

The synoptical overall design ensures simple, problem-free control

FEATURES

WS is a gas-insulated

metal-enclosed and metal-clad

switchgear and controlgear in

conformity with IEC 60298,

VDE 0670, part 6 and is designed

for installation in transformer

substations, industrial plants

and infrastructure

The WS switchgear, with its

vacuum circuit breaker provides

equipment featuring maximum

availability, optimum staff safety

and synoptical design

Technical data WSA / WSB

>>Rated frequency Hz 50/60 50/60 50/60 50/60

>>Rated power frequency

>>Rated lightning impulse

>>Rated peak withstand current up to kA 80 63 63 80

>>Rated norm curr busbar system up to kA 3000 3) 2500 2500 2500

>>Rated norm curr feeder

>>Rated short time current 1s up to kA 31.5 25 1) 25 1) 31.5

>>Rated short time current 3s up to kV 31.5 25 1) 25 1) 31.5

>>Width Standard WSA, WSB mm 600 600 600 600

>>Height Single busbar WSA mm 2300 2300 2300 2300

>>Standard Depth WSA, WSB mm 1200 1200 1200 1200

1) Higher ratings on request.

2) Changes in dimensions in case of voltage transformer on outgoing feeder and on the busbar

and in case of multiple cable connection possible on request.

3) On request

Trang 10

VACUUM OR SF6 SWITCHING, IT’S UP

TO YOU

The PIX range can be fitted with two types of circuit breakers mounted on a withdrawable trolley with disconnecting contacts :

fitted with a conventional spring operating mechanism

or the innovative AMD magnetic actuator and our latest range

of interrupters

combining two breaking techniques for more reliability: thermal expansion and auto-pneumatic puffing

PIX Air insulated metal-clad switchgear, with a vacuum or SF 6 circuit breaker

SAFETY & EASE OF OPERATION

For safety reasons all operations are performed with the front door closed

Operation is simple and logical, with clear status indication of all functions

Comprehensive electrical interlocking through the user-friendly DCX digital controller in combination with robust mechanical interlocks ensures the maximum of safety for both plant and personnel

THE KEY LINK FOR ALL YOUR DISTRIBUTION NEEDS

Part of a large variety of MV & LV products to equip, modify, upgrade

or optimize your distribution network, this complete range of versatile air insulated cubicle configurations up to 24kV can

be supplied in many different versions, fitted with circuit breakers

or contactors using either SF 6 or vacuum switching technology.

As a result, PIX’s design meets

or exceeds the latest requirements

of all relevant IEC, ANSI, PEHLA, EA-TS standards and many other national specifications.

>>Rated power frequency withstand voltage kV 28 38 50

>>Rated lightning impulse withstand voltage kV peak 75 95 125

>>Rated short time withstand current - 3s Up to kA 40*/50 40*/50 31,5

>>Rated peak withstand current Up to kA 100/125 100/125 80

>>Internal arc withstand Up to kA 40/50 40/50 31,5

>>Rated current - busbar Up to A 3150/5000** 2500

*Earthing switch 1 sec or 31,5 kA 3 sec - **With forced ventilation