Our industrial-mining customers have a clear need for mobile equipment to meet their on-site electrical requirements: > MV/LV distribution, > Temporary power supplies, > MV/LV motor star

Trang 1

Dimensions in mm

(1) MV cubicles (2) Low voltage control board (AC/DC, capacitor bank ).

* extra width available on request (as for the 3m wide container), as well as 10' containers.

12192

>>Container 40’+40’ 12192

>>Container 20’+20’ 6058

>>Container 40’ 12192

>>Container 20’ 6058

Example of arrangement

Example of civil works on site

1

2

1

1

12192

Trang 2

Our industrial-mining customers have a clear need for mobile equipment to meet their on-site electrical requirements:

> MV/LV distribution,

> Temporary power supplies,

> MV/LV motor start-ups,

> Pumping stations,

> Conveyor belts.

Equipment must be easy to use and move around in order to increase a mining site’s productivity.

Our technical designs for mobile substations are carried out in collaboration with our customers, enabling us to offer modern, reliable electrical solutions tailored

to meet everyone’s equipment requirements.

MODULAR SOLUTIONS TAILORED TO YOUR NEEDS

We carry out an electrical study of the project and work hand-in- hand with you to define electrical solutions which will meet your requirements Our service includes providing the equipment (MV switchboards, transformer, etc.) protective devices, supervisors, cabins for MV outlets etc., so as to offer a complete product

MAIN ELECTRICAL CHARACTERISTICS:

>from 3 to 36kV,

>630kVA to 4MVA

Electrical solutions for mining applications

VERSATILE CUSTOMERS AND APPLICATIONS

Long service life and robustness are key elements in meeting the needs of mining sites

From powering-up mining camps

to hoisting engines, MV/LV systems

must display reliability combined with modern technical sophistication in order

to satisfy the require-ments of these pro-duction sites

CD MICOM

R

50KVA

4MVA

15KV SUBSTATION

4.16KV 15KV

4.16KV

Trang 3

OUR KNOW HOW

With the strength of their experience

in the design and manufacture of

substations, our engineering

design offices have developed a

specific range of electrical distribution

which meets the various demands

of the wind farm market

With an enclosure made of concrete,

or GRC (Glass Fibre Reinforced

Cement) we can offer wind farm

solutions adapted to all types of

needs, in 24kV and 36kV

for wind farm applications

2880

3260

3650

6260

1

4 5

4

1

3650

1 - MV cubicles

2 - MV/LV Transformer

3 - Low voltage

4 - Remote control

Dimensions in millimetres

Mistral Alize walk-in substation (up to 800kVA)

Concerto 3 (up to 1600kVA)

Mistral 3W (up to 3000kVA)

Concerto 6 consumer/injection substation with segregated rooms Mistral 4 (up to 1250kVA)

2880

1

2

3260

1

2

3650

3650

1

6260

1 4 5

3 4

Trang 4

A range specifically designed for railway applications has been developed, and it brings together the following applications:

Single or double crossed feeder substations

Supplying power and signalling

to the tracks

CONCERTO 10 SUBSTATION 25KV TESTING SUBSTATION SINGLE PHASE

Developed for:

>Testing the operation of locomotive auxiliaries

>Carrying out traction tests when stopped

>Enables carrying out repairs to engine

>breakdowns in conditions close

to those met on the line

>Proceeding with traction tests whilst running along a test track

>Fixed SDR cubicles for 25kV / 250kV Bil

Electrical solutions for railways applications

CATENARY LINE SUBSTATION 1500VDC/420V

Developed to meet the power supply needs for certain equipment from the 1500V dc catenary system:

CONCERTO 3 type of substation with its direct current protection cubicle, voltage converter and L.V

general transformer

NETWORK WARMING

Designed for heating the points, these substations allow the transformation from the catenary system from 25kV to 220V

A substation with two compartments:

one HVA (with the 25KV transformer) and the other L.V with general protection and consumer feeders

Phase feedback

20kV 25kV/250kV BIL

Trang 5

FAULT DETECTOR

REMOTE CONTROL

SECONDARY DISTRIBUTION SWITCHGEAR

DISTRIBUTION TRANSFORMER MV/LV

LOW VOLTAGE SWITCHBOARD

COMPONENTS

PRIMARY DISTRIBUTION SWITCHGEAR

Trang 6

DAX complies with I.E.C

standards It is designed to detect, and signal by an external light, the passage of a fault current (zero-phase sequence, and/or short circuit) on underground MV grid lines.

DAX can as well, through modem, communicate with a

SCAD sytem.

OPERATIONAL ASSISTANCE

Thanks to the use of a micro-controller, the basic DAX offers the possibility of a wide range of adjustments together with additional functions for use by the operator

A COMPLETE OFFER

Anti-vandal or Square light

Straight blade core, Preformed CT CTOP 125, Moulded CT CTOS 45 CTOM 90,

Bundle FCT-LCT

DAX Modern digital fault detector

OPERATING PRINCIPLE

The current is measured by one

or three sensors When the current exceeds a preset threshold, the DAX stores the fault and signals the fault thanks to a flashing light positioned on the outside of the substation

USER-FRIENDLY

The man-machine interface is equipped with an LCD giving DAX considerable flexibility for testing and setting

>Alphanumeric LCD,

>Navigational pushbuttons,

>Display LEDs,

>Main set-up can be modified on site without any tools

Technical characteristics

>> Earth fault thresholds Adjustments of 5 with 180 amps - 16 values

>> Phase thresholds Adjustments of 225 amps to 700 amps - filtering

of the ringing current - 4 values

>> Taking into account time Adjustments of 60ms with 360ms - 5 values

>> Reset mode A detected defect can be reset to zero by one of the

following conditions:

• By the pushbutton

• At the end of the selected time delay

• At the return of the AC voltage (Low voltage - DAX

• At the presence of the current in the cores

• By the external dry contact input.

>> Signalling by external light Duration: setting from 1h to 96 hours;

Flashing frequency: from 2 secs to 9 secs, automatically adapted to the signalling light.

>> Filtering ofcall currents Adjustments: 0 ms (de-activated) or 4 s activated

>> Signalling by dry contacts Inverter contact Open/Close power for 1000 operations:

Trang 7

Remote control solution

Technical characteristics

>> Capacity Modular, up to 4 switches controled,

in a MV/LV substation

>> Enclosure Stainless steel IP2XC for indoor, IP5X for outdoor installations

(contact us for other)

>> Dimension H650 x W300 x D290 mm (up to 2 switches) or,

H650 x W450 x D290 mm (up to 4 switches) or, H200 x W750 x D360 mm (up to 2 switches

to be mounted on top of a RMU) Weight ~ 30kG (batteries included)

>> Power supply 110/230Vac, circuit fuse-protected and transformer-isolated

(10kVrms-1min, 20kVp-1.2/50ms).

Power supply 4 x 12V-7Ah sealed lead acid batteries, capable of assuming

more than 60 switch O/I (Close/Open) operations after 9 hours without power supply

Power consumption <50VA without battery charging,

<80VA with battery charging,

<15VA during AC supply failure.

>> Transmission media Public Switched Telephone Network (PSTN),

Dedicated line, fibre optic or Radio, (please contact us for other media).

Transmission protocol HNZ 45-S-53, IEC 870-5-101,

(please contact us for any other protocols).

Reporting Upon any status change, or cyclical interrogation,

or polling.

>> Analog Inputs Up to 4 current measurements coming from

the current sensors (500/1A);

Digital inputs Up to 4 x 2 O/I (close/open) position of 4 switches;

Up to 3 internal O/I (local, power supply battery ) 8x 1 for general-purpose use.

Digital outputs Up to 4 x 2 O/I (close/open) orders of 4 switches;

MORE THAN A RTU

The constant effort to improve

substation control for many

years now, has brought many

distinct devices into the substation:

> Fault detector and indicator,

> Communication interface with

SCADA centre (Modem cards,

radio transmission devices),

> Specific feeder application

PLCs, such as automatic source

transfer, automatic sectionalizing

control, etc.,

> UPS units,

> Terminal interface with

switches and

> Switch motor driving control

and monitoring device.

A RELIABLE ENERGY

SUPPLY IS A MUST FOR

ALL POWER UTILITIES

The RCX-ITI unit is specially

designed for the remote control

of secondary MV substations

(overhead & underground), and it

provides a cost-effective and

complete solution to reduce:

>The number of customer

interruptions,

>The average number

of customer minutes lost and,

>The crew call-out time

Trang 8

BEST VALUE THROUGH ECONOMY AND

FLEXIBILITY

The FBX gas-insulated ring main unit is a leading product from both an economical and ecological point of view.

FBX meets the IEC, EN, China National Standards (CNS), the GOST standards of the Russian Federation and all the national specifications to these national regulations.

FBX can be supplied as a panel of

up to four switching units within a gas-filled compartment.

Available in two variants - FBX-C

as a non-expandable and FBX-E

as an expandable variant – the switchgear can be used in all secondary electricity distribution applications.

FBX 24kV Gas-insulated switchgear

MAIN FEATURES

>Ring main cable connection

For cable feeders with switch disconnector

>Transformer cable connection

For transformer feeders (T1) with fused switch combination

>Transformer cable connection

For the transformer feeder (T2) with vacuum circuit-breaker

CONFORMITY WITH SPECIFICATIONS/

STANDARDS

>IEC 60298

Trafo Cable Cable

Technical data FBX

>>Rated lightning impulse withstand voltage kV 75 95 125

>>Rated power frequency withstand voltage kV 28 38 (42) 50

>>Rated nominal current of busbar A 630 630 630

>>Rated nominal current for cable feeders max A 630 630 630

>>Rated nom current for transf feeders max A 200/400 200/400 200/400

>>Rated short time withstand current 1s kA 16/20 1) 16/20 1) 20

>>Rated short time withstand current 3s kA 16/20 1) 16/20 1) 16 1)

>>Rated peak withstand current kA 40/50 40/50 40/50

>>Rated making withstand current kA 40/50 40/50 40/50

>>Rated frequency Hz 50/60 50/60 50/60

>>Cable testing (DC) voltage 15 min kV 48 60 96

>>Rated filling pressure SF 6 at 20°C MPa 0.03 Performance in case of an internal fault acc to IEC 60298 (criteria 1-6, 1s) 20 kA (1s)

1) For higher ratings or detailed information, please contact us

Trang 9

24kV Gas-insulated switchgear

A wide choice of options

to meet your specific requirements

720

680

RE T1

RE T2

C C

Variants:

C RE T1

C RE T2

R RE T1

R RE T2

Variants:

C T1 C T1

C T2 C T2

Variants:

3 functional units

1 + 4 functional units

720

690 720

500 T1 720

370

C

C RE T1

R RE T1

C RE T2

R RE T2

Variants:

RE T1

RE T1

RE T2

C C

Variants:

C

R

RE

Variants:

1 functional unit

C C C T1

C C C T2

C T1 C T1

C T2 C T2

Variants:

4 functional units

Variants:

T1 C T1 C T1 T2 C T2 C T2

C

Variants:

T1 T2

Trafo Cable Cable

L1 L1 L1

FBX-C versions (non-extendable)

FBX-E versions (extendable)

720

720 1010

1330

Trang 10

THE ANSWER TO ALL YOUR NEEDS

The FLUOKIT M+ range is a set of prefabricated MV distribution cubicles designed for indoor use.

It includes all basic cubicles used

to design MV modular switch-boards from 7.2kV up to 24kV for :

> Public distribution substations,

> Delivery substations with low voltage metering,

> Delivery substations with high voltage metering,

> Substations in industry

or tertiary internal networks.

Furthermore, in cubicles with load-break switches, the position

of this earthing switch can be seen unambiguously from the front of the cubicle through an inspection window in the cable compartment access door

Cubicles in the FLUOKIT M+ range all have functional mechanical inter-locks required by the IEC standard:

>Interlock between the breaking

or isolating device and the earthing switch

>Interlock between the earthing switch and the cable compartment access door

>Interlock between the main disconnector and the circuit breaker for cubicles with circuit breaker (key locking)

>Interlock holding the load-break switch in the open position when the cable compartment access door is removed The earthing switch can then be operated for the cable test

Fluokit M+

24kV Air insulated switchgear

CONFORMITY WITH SPECIFICATIONS/

STANDARDS

>IEC 298 Standards

SIMPLE AND SAFE

IN OPERATION

All operations and access to the compartments are made from the front of the cubicles

FLUOKIT M+ cubicles include the following features:

>Operating devices include a mimic diagram showing the position of each breaking, isolation or earthing device, in complete reliability due

to its robustness of the kinematics chain

>An earthing switch with making capacity, equipped with a closing operating device independent from the operator

Lighting impulse (kVp)

To earth and between poles 60 75 95 125 Isolating distance 70 85 110 145