Fault Limiters Underground Cable High Reliability Load 3-Phase Pad-Mounted Distribution Transformer Commercial Customer Network Transformer Network Protector Secondary Network Network Tr
Trang 1Filters (Passive)
111.1 Fundamentals111.2 Applications
Simple RL and RC Filters • Simple RLC Filters • Compound Filters • Constant-k Filters • m- Derived Filters
A filter is a frequency-sensitive two-port circuit that transmits with or without amplification signals in
a band of frequencies and rejects (or attenuates) signals in other bands The electric filter was inventedduring the First World War by two engineers working independently of each other — the Americanengineer G A Campbell and the German engineer K W Wagner O Zobel followed in the 1920s Thesedevices were developed to serve the growing areas of telephone and radio communication Today, filtersare found in all types of electrical and electronic applications from power to communications Filterscan be both active and passive In this section we will confine our discussion to those filters that employ
no active devices for their operation The main advantage of passive filters over active ones is that theyrequire no power (other than the signal) to operate The disadvantage is that they often employ inductorsthat are bulky and expensive
111.1 Fundamentals
The basis for filter analysis involves the determination of a filter circuit’s sinusoidal steady state responsefrom its transfer function T(jw) Some references use H(jw) for the transfer function The filter’s transferfunction T(jw) is a complex function and can be represented through its gain ΩT(jw)Ω and phase–T(jw) characteristics The gain and phase responses show how the filter alters the amplitude and phase
of the input signal to produce the output response These two characteristics describe the frequency response of the circuit since they depend on the frequency of the input sinusoid The signal-processingperformance of devices, circuits, and systems is often specified in terms of their frequency response Thegain and phase functions can be expressed mathematically or graphically as frequency-response plots.Figure 111.1 shows examples of gain and phase responses versus frequency, w
The terminology used to describe the frequency response of circuits and systems is often based on theform of the gain plot For example, at high frequencies the gain in Figure 111.1 falls off so that outputsignals in this frequency range are reduced in amplitude The range of frequencies over which the output
is significantly attenuated is called the stopband. At low frequencies the gain is essentially constant andthere is relatively little attenuation The frequency range over which there is little attenuation is called a
passband. The frequency associated with the boundary between a passband and an adjacent stopband iscalled the cutoff frequency (wC=2pf C ) In general, the transition from the passband to the stopband,called the transition band, is relatively gradual, so the precise location of the cutoff frequency is a matter
of definition The most widely used approach defines the cutoff frequency as the frequency at which thegain has decreased by a factor of 1/ 2=0 707 from its maximum value in the passband
Albert J Rosa
University of Denver
1586_book.fm Page 1 Monday, May 10, 2004 3:53 PM
Trang 2111-2 The Engineering Handbook, Second Edition
This particular definition is based on the fact that the power delivered to a resistor by a sinusoidalcurrent or voltage waveform is proportional to the square of its amplitude At a cutoff frequency the gain
is reduced by a factor of and the square of the output amplitude, and thusly also its power, isreduced by a factor of one half For this reason the cutoff frequency is also called the half-power frequency.
There are four prototypical filters These are low pass (LP), high pass (HP), band pass (BP), and bandstop
(BS) Figure 111.2 shows how the amplitude of an input signal consisting of three separate amplitude frequencies is altered by each of the four-prototypical filter responses The low-pass filterpasses frequencies below its cutoff frequency wC, called its passband, and attenuates the frequencies abovethe cutoff, called its stopband. The high-pass filter passes frequencies above the cutoff frequency wC andattenuates those below The band-pass filter passes those frequencies that lie between two cutoff frequen-cies, wC1 and wC2, its passband, and attenuates those frequencies that lie outside the passband Finally,the bandstop filter attenuates those frequencies that lie in its reject or stopband, between wC1 and wC2,and passes all others
equal-The bandwidth of a gain characteristic is defined as the frequency range spanned by its passband Forthe band-pass case in Figure 111.2, the bandwidth is the difference in the two cutoff frequencies
of a logarithmic frequency scale involves some special terminology A frequency range whose end pointshave a 2:1 ratio is called an octave and one with 10:1 ratio is called a decade. Straight-line approximations
FIGURE 111.1 Low-pass filter characteristics showing passband, stopband, and the cutoff frequency, wC.
0 Passband Stopband
ω c
ω ω
Trang 3= 1 — that is, the input and output amplitudes are equal A positive dB gain means the output amplitude
exceeds the input since ΩT(jw)Ω> 1, whereas a negative dB gain means the output amplitude is smaller
than the input since ΩT(jw)Ω< 1 A cutoff frequency usually occurs when the gain is reduced from its
maximum passband value by a factor or 3 dB
Figure 111.3 shows the asymptotic gain characteristics of ideal and real low-pass filters The gain of
the ideal filter is unity (0 dB) throughout the passband and zero (-• dB) in the stopband It also has an
infinitely narrow transition band The asymptotic gain responses of real low-pass filters show that we can
only approximate the ideal response As the order of the filter or number of poles n increases, the
approximation improves since the asymptotic slope or “rolloff ” in the stopband is -20 ¥n dB/decade
On the other hand, adding poles requires additional stages in a cascade realization, so there is a trade-off
between (1) filter complexity and cost and (2) how closely the filter gain approximates the ideal response
Figure 111.4 shows how low-pass filter requirements are often specified To meet the specification, the
gain response must lie within the unshaded region in the figure, as illustrated by the two responses shown
in Figure 111.4 The parameter Tmax is the passband gain. In the passband the gain must be within 3 dB
of Tmax and must equal at the cutoff frequency wC In the stopband the gain must decrease
and remain below a gain of Tmin for all w≥wmin A low-pass filter design requirement is usually defined
by specifying values for these four parameters The parameters TmaxandwC define the passband response,
whereas Tmin and wmin specify how rapidly the stopband response must decrease
FIGURE 111.2 Four prototype filters and their effects on an input signal consisting of three frequencies.
Passband Stopband
LOW PASS GAIN
Passband Stopband
Trang 4111-4 The Engineering Handbook, Second Edition
111.2 Applications
Simple RL and RC Filters
A first-order LP filter has the following transfer function:
(111.3)
FIGURE 111.3 The effect of increasing the order n of a filter relative to an ideal filter.
FIGURE 111.4 Parameters for specifying low-pass filter requirements.
ω C ω
|T(j ω)| dB
TMAX
TMIN3dB
1586_book.fm Page 4 Monday, May 10, 2004 3:53 PM
Trang 5Filters (Passive) 111-5
where for a passive filter K £ a and a = w C This transfer function can be realized in several ways including
using either of the two circuits shown in Figure 111.5
For sinusoidal response the respective transfer functions are
(111.4)
For these filters the passband gain is equal to one and the cutoff frequency is determined by R/L for the
RL filter and 1/RC for the RC filter The gain ΩT( jw)Ω and phase –T( jw) plots of these circuits are
shown back in Figure 111.1
A first-order HP filter is given by the following transfer function:
(111.5)
where, for a passive filter, K £ 1 and a is the cutoff frequency This transfer function can also be realized
in several ways including using either of the two circuits shown in Figure 111.6 For sinusoidal response
the respective transfer functions are
(111.6)
For the LP filters the passband gain is one and the cutoff frequency is determined by R/L for the RL filter
and 1 / RC for the RC filter The gain ΩT( jw)Ω and phase –T( jw) plots of these circuits are shown in
Figure 111.7
FIGURE 111.5 Single-pole LP filter realizations: (a) RL, (b) RC.
FIGURE 111.6 Single-pole HP filter realizations: (a) RL, (b) RC.
R
C L
11
s
( ) =+ a
=
Trang 6111-6 The Engineering Handbook, Second Edition
connected to achieve the transfer functions given in Equation 111.7 The gain ΩT( jw)Ω and phase –T( jw)
plots of these circuits are shown in Figure 111.9 through Figure 111.11
FIGURE 111.7 High-pass filter characteristics showing passband, stopband, and the cutoff frequency, wc.
0
Passband Stopband
22
L
2
Bw = 2zw0
Trang 7FIGURE 111.8 RLC circuit connections to achieve LP, HP, or BP responses.
FIGURE 111.9 Second-order low-pass gain responses.
FIGURE 111.10 Second-order band-pass gain responses.
|K|
10 ω 0
K dB + 20dB
ω 0
K dB
− 20dB
ω 0 K
dB − 40dB
ω 0
K dB + 0dB
ω 0
ω 0 ω
Bζ=0.5
Trang 8111-8 The Engineering Handbook, Second Edition
Compound Filters
Compound filters are higher-order filters obtained by cascading lower-order designs Ladder circuits are
an important class of compound filters Two of the more common passive ladder circuits are the
constant-k and the m-derived filters (either of which can be configured using a T-section, p-section, or L-section,
or combinations thereof), the bridge-T network and parallel-T network, and the Butterworth and
Chebyshev realizations Only the first two known as image-parameter filters will be discussed in this
section Figure 111.12(a) shows a standard ladder network consisting of two impedances, Z1 and Z2,organized as an L-section filter Figure 111.12(b) and Figure 111.12(c) show how the circuit can beredrawn to represent a T-section or ’-section filter, respectively
T- and ’-section filters (also referred to as “full sections”) are usually designed to be symmetrical sothat either can have its input and output reversed without changing its behavior The “L-section” (alsoknown as a “half section”) is unsymmetrical, and orientation is important Since cascaded sections “load”
each other, the choice of termination impedance is important The image impedance, Z i, of a symmetricalfilter is the impedance with which the filter must be terminated in order to “see” the same impedance
at its input terminals In general the image impedance is the desired load or source impedance to whichthe filter matches The image impedance of a filter can be found from
(111.8)
where Z 1O is the input impedance of the filter with the output terminals open circuited, and Z 1S is itsinput impedance with the output terminals short-circuited For symmetrical filters the output and inputcan be reversed without any change in its image impedance — that is,
(111.9)
The concept of matching filter sections and terminations to a common image impedance permits thedevelopment of symmetrical filter designs
The image impedances of T- and ’-section filters are given as
FIGURE 111.11 Second-order high-pass gain responses.
0.01 0.1 1.0 10 100 1000 0.001
and
Z iT= Z Z1O 1S = Z12+Z Z
1 2
14
Trang 9Since Z1 and Z2 vary significantly with frequency, the image impedances of T- and ’-sections will alsochange This condition does not present any particular problem in combining any number of equivalentfilter sections together, since their impedances va4ry equally at all frequencies But this does make itdifficult to terminate these filters exactly, causing a limitation of these types of filters However, there is
a frequency within the filter’s passband where the image impedance becomes purely resistive It is useful
FIGURE 111.12 Ladder networks: (a) standard L-section, (b) T-section, (c) ’-section.
Z12Z22Z2
Z12Z22Z2
Z12Z22Z2 2Z2
1 2
1 4( / )
Trang 10111-10 The Engineering Handbook, Second Edition
to terminate the filter with this value of resistance since it provides good matching over much of thefilter’s passband
To develop the theory of constant-k and m-derived filters, consider the circuit of Figure 111.13 The current transfer function in the sinusoidal steady state is given by T( jw) = ΩT( jw)Ω–T( jw) = I2/I1:
In modern references an R replaces the k Note that the units of k are ohms The advantage of this type
of filter is that the image impedance in the passband is a pure resistance, whereas in the stopband it ispurely reactive Hence if the termination is a pure resistance and equal to the image impedance, all thepower will be transferred to the load since the filter itself is purely reactive Unfortunately, the value ofthe image impedance varies significantly with frequency, and any termination used will result in amismatch except at one frequency
In LC constant-k filters, Z1 and Z2 have opposite signs, so that Theimage impedances become
(111.15)
Therefore, in the stopband and passband, we have the following relations for standard T- or ’-sections,
where n represents the number of identical sections:
FIGURE 111.13 Circuit for determining the transfer function of a T-section filter.
2
2 1
Trang 11The ultimate roll-off of constant-k filters is 20 dB per decade per reactive element or 60 dB per decade
for the T- or ’-section, 40 dB per decade per L-section Figure 111.14 shows normalized plots of a and
b versus These curves are generalized and apply to low-pass, high-pass, pass, or reject filters Figure 111.15 shows examples of a typical LP ’-section, an HP T-section, and a BP T-section
band-m -Derived Filters
The need to develop a filter section that could provide high attenuation in the stopband near the cutoff
frequency prompted the development of the m-derived filter O Zobel developed a class of filters that had the same image impedance as the constant-k but had a higher attenuation near the cutoff frequency The impedances in the m-derived filter were related to those in the constant-k as
FIGURE 111.14 Normalized plots of attenuation and phase angle for various numbers of sections n.
FIGURE 111.15 Typical sections: (a) LP ’-section, (b) HP T-section, (c) BP T-section.
Trang 12111-12 The Engineering Handbook, Second Edition
(111.17)
where m is a positive constant £ 1 If m = 1 then the impedances reduce to those of the constant-k Figure 111.16 shows generalized m-derived T- and ’-sections.
The advantage of the m-derived filter is that it gives rise to infinite attenuation at a selectable frequency,
w˚, just beyond cutoff, wC This singularity gives rise to a more rapid attenuation in the stopband than
can be obtained using constant-k filters Equation 111.18 relates the cutoff frequency to the infinite
(both normalized) and m In most applications, m is chosen to be 0.6, keeping the image impedance
nearly constant over about 80% of the passband
FIGURE 111.16 m-derived filters: (a) T-section, (b) ’-section.
1 / 2 mZ1
(b) (a)
1 / 2 mZ1(1 − m)Z 1 4m
Z2m
(1 − m)Z 1 4m
mZ1
2Z2m
2Z2m
Trang 13Defining Terms
Bridge-T network — A two-port network that consists of a basic T-section and another element
con-nected so as to “bridge across” the two arms Such networks find applications as band rejectionfilters, calibration bridges, and feedback networks
Butterworth filters — Ladder networks that enjoy a unique passband frequency response characteristic
that remains very constant until near the cutoff, hence the designation “maximally flat.” This
FIGURE 111.17 Attenuation curves for a single-stage filter with m = 0.6 and m = 0.9.
FIGURE 111.18 Z iT /R and Z i’ /R versus normalized frequency for various values of m.
0 0.5 1 1.25 1.5 2 2.29 2.5
Trang 14111-14 The Engineering Handbook, Second Edition
filter has its critical frequency remain fixed regardless of the number of stages employed Itobtains this characteristic by realizing a transfer function built around a Butterworth polyno-mial
Chebyshev filters — A variant of the Butterworth design that achieves a significantly steeper transition
band about its critical frequency for the same number of poles Although the Chebyshev filteralso maintains the integrity of its critical frequency regarding the number of poles, it trades thesteeper roll-off for a fixed ripple — usually specified as 1 dB or 3 dB — in the passband
Chebyshev filters are also called equal-ripple or stagger-tuned filters They are designed by
realizing a transfer function using a Chebyshev polynomial
Parallel-T networks — A two-port network that consists of two separate T-sections in parallel with only
the ends of the arms and the stem connected Parallel-T networks have applications similar tothose of the bridge-T but can produce narrower attenuation bandwidths
References
Herrero, J L and Willoner, G 1966 Synthesis of Filters, Prentice Hall, Englewood Cliffs, NJ.
Thomas, R E and Rosa, A J 2004 The Analysis and Design of Linear Circuits, John Wiley & Sons,
Hoboken, NJ
Van Valkenburg, M E 1955 Two-terminal-pair reactive networks (filters) In Network Analysis, Prentice
Hall, Englewood Cliffs, NJ
Weinberg, L 1962 Network Analysis and Synthesis, W L Everitt (ed.) McGraw-Hill, New York.
Williams, A B 1981 Electronic Filter Design Handbook, McGraw-Hill, New York.
Zobel, O J 1923 Theory and Design of Uniform and Composite Electric Wave Filters Bell Telephone
Syst Tech J 2:1.
Further Information
Huelsman, L P 1993 Active and Passive Analog Filter Design — An Introduction, McGraw-Hill, New York.
Good current introductory text covering all aspects of active and passive filter design
Sedra, A S and Brackett, P O 1978 Filter Theory and Design: Active and Passive, Matrix, Beaverton, OR.
Modern approach to filter theory and design
Trang 15Power Distribution
112.1 Equipment112.2 System Divisions and Types112.3 Electrical Analysis, Planning, and Design
Phase Balancing • Fault Analysis • Protection and Coordination • Reliability Analysis
112.4 System Control112.5 Operations
The function of power distribution is to deliver to consumers economic, reliable, and safe electricalenergy in a manner that conforms to regulatory standards Power distribution systems receive electricenergy from high-voltage transmission systems and deliver energy to consumer service-entrance equip-ment Systems typically supply alternating current at voltage levels ranging from 120 V to 46 kV
Figure 112.1 illustrates aspects of a distribution system Energy is delivered to the distribution tion (shown inside the dashed line) by three-phase transmission lines A transformer in the substationsteps the voltage down to the distribution primary system voltage — in this case, 12.47 kV Primarydistribution lines leave the substation carrying energy to consumers The substation contains a breakerthat may be opened to disconnect the substation from the primary distribution lines If the breaker isopened, outside the substation there is normally an open supervisory switch that may be closed in order
substa-to provide an alternate source of power for the cussubsta-tomers normally served by the substation Thesubstation also contains a capacitor bank used for either voltage or power factor control
Four types of customers, along with representative distribution equipment, are shown in Figure 112.1
A set of loads requiring high reliability of service is shown being fed from an underground three-phasesecondary network cable grid A single fault does not result in an interruption to this set of loads Aresidential customer is shown being supplied from a two-wire, one-phase overhead lateral Commercialand industrial customers are shown being supplied from the three-phase, four-wire, overhead primaryfeeder At the industrial site, a capacitor bank is used to control the power factor Except for the industrialcustomer, all customers shown have 240/120 V service The industrial customer has 480Y/277 V service.For typical electric utilities in the U.S., investment in distribution ranges from 35 to 60% of totalcapital investment
112.1 Equipment
Figure 112.1 illustrates a typical arrangement of some of the most common equipment Equipment may
be placed into the general categories of transmission, protection, and control
Arresters protect distribution system equipment from transient over-voltages due to lightning orswitching operations In over-voltage situations the arrester provides a low-resistance path to ground forcurrents to follow
Electrical Distribution Design, Inc.
1586_book.fm Page 1 Monday, May 10, 2004 3:53 PM
Trang 16112-2 The Engineering Handbook, Second Edition
Capacitor banks are energy storage devices primarily used to control voltage and power factor Systemlosses are reduced by the application of capacitors
Conductors are used to transmit energy and may be either bare or insulated Bare conductors havebetter thermal properties and are generally used in overhead construction where contact is unlikely.Insulated cables are used in underground/conduit construction and in overhead applications whereminimum right-of-way is available Concentric neutral and tape-shielded cables provide both a phaseconductor and a return path conductor in one unit
FIGURE 112.1 Distribution system schematic.
Fault Limiters
Underground Cable
High Reliability Load
3-Phase Pad-Mounted Distribution Transformer
Commercial Customer
Network Transformer Network
Protector
Secondary Network
Network Transformer
Network Protector
Feed from alternate source
Supervisory Switch (Normally Open)
Voltage Regulator Power
Fuse
Capacitor Bank
Single Phase Pole Mounted Distribution Transformer
Residential Customer
Transmission Line
Transmission Line
Power Transformer
Capacitor Bank Disconnect
Disconnect Disconnect
Disconnect
12.47 KV Bus Breaker
Recloser 1586_book.fm Page 2 Monday, May 10, 2004 3:53 PM
Trang 17Power Distribution 112-3
Distribution lines are made up of conductors and are classified according to primary voltage, thenumber of phases, number of conductors, and return path The three-phase, four-wire, multi-groundedsystem is the most common primary system, where one conductor is installed for each of the three phasesand the fourth conductor is a neutral that provides a return current path Multi-grounded means thatthe neutral is grounded at many points, so that the earth provides a parallel path to the neutral for returncurrent Three-phase, three-wire primary systems, or delta-connected systems, are rarely used becausefaults therein are more difficult to detect A lateral is a branch of the system that is shorter in length,more lightly loaded, or has a smaller conductor size than the primary feeder
Distribution transformers step the voltage down from the primary circuit value to the customerutilization level, thus controlling voltage magnitude Sizes range from 1.5 to 2500 kVA Distributiontransformers are installed on poles, ground-level pads, or in underground vaults A specification of 7200/12,470Y V for the high-voltage winding of a single-phase transformer means the transformer may beconnected in a line-to-neutral “wye” connection for a system with a line-to-line voltage of 12,470 V or
in a line-to-line “delta” connection for a system with a line-to-line voltage of 7200 V A specification of240/120 V for the low-voltage winding means the transformer provides a three-wire connection with
120 V mid-tap voltage and 240 V full-winding voltage A specification of 480Y/277 V for the low voltagewinding means the winding is permanently wye-connected with a fully insulated neutral avilable for athree-phase, four-wire service to deliver 480 V line-to-line and 277 V line-to-neutral
Distribution substations consist of one or more step-down power transformers configured with switchgear, protective devices, and voltage regulation equipment for the purpose of supplying, controlling,switching, and protecting the primary feeder circuits The voltage is stepped down for safety and flexibility
of handling in congested consumer areas Over-current protective devices open and interrupt currentflow in order to protect people and equipment from fault current Switches are used for control tointerrupt or redirect power flow Switches may be operated manually, automatically with PLC control,
or remotely with supervisory control Switches are usually rated to interrupt load current and may beeither pad or pole mounted
Power transformers are used to control and change voltage level Power transformers equipped withtap-changing mechanisms can control secondary voltage over a typical range of plus or minus 10%.Voltage regulators are autotransformers with tap-changing mechanisms that may be used throughoutthe system for voltage control If the voltage at a remote point is to be controlled, then the regulator can
be equipped with a line drop compensator that may be set to regulate the voltage at the remote pointbased upon local voltage and current measurements Modern microprocessor-based controls enableregulators and line capacitors to work together to provide optimal voltage regulation
112.2 System Divisions and Types
Distribution transformers separate the primary system from the secondary Primary circuits transmitenergy from the distribution substation to customer distribution transformers Three-phase distributionlines that originate at the substation are referred to as primary feeders or primary circuits Primary feedersare illustrated in Figure 112.1 Secondary circuits transmit energy from the distribution transformer tothe customer’s service entrance Line-to-line voltages range from 208 to 600 V
Radial distribution systems provide a single path of power flow from the substation to each individualcustomer This is the least costly system to build and operate and thus the most widely used
Primary networks contain at least one loop that generally may receive power from two distinct sources.This design results in better continuity of service A primary network is more expensive than the radialsystem design because more protective devices, switches, and conductors are required
Secondary networks are normally underground cable grids providing multiple paths of power flow toeach customer A secondary network generally covers a number of blocks in a downtown area Power issupplied to the network at a number of points via network units, consisting of a network transformer
in series with a network protector A network protector is a circuit breaker connected between thesecondary winding of the network transformer and the secondary network itself When the network is
Trang 18112-4 The Engineering Handbook, Second Edition
operating properly, energy flows into the network The network protector opens when reverse energyflow is detected, such as may be caused by a fault in the primary system
112.3 Electrical Analysis, Planning, and Design
The distribution system is planned, designed, constructed, and operated based on the results of electricalanalysis Generally, computer-aided analysis is used
Line impedances are needed by most analysis applications Distribution lines are electrically anced due to loads, unequal distances between phases, dissimilar phase conductors, and single-phase ortwo-phase laterals Currents flow in return paths due to the imbalance in the system Three-phase, four-wire, multigrounded lines have two return paths — the neutral conductor and earth Three-phase,multigrounded concentric neutral cable systems have four return paths The most accurate modeling ofdistribution system impedance is based upon Carson’s equations With this approach a 5 ¥ 5 impedancematrix is derived for a system with two return paths, and a 7 ¥ 7 impedance matrix is derived for asystem with four return paths For analysis, these matrices are reduced to 3 ¥ 3 matrices that relate phasevoltage drops (i.e., , , ) to phase currents (i.e., , , ) as indicated by
unbal-Load analysis forms the foundation of system analysis unbal-Load characteristics are time varying and depend
on many parameters, including connected consumer types and weather conditions The load demandfor a given customer or group of customers is the load averaged over an interval of time, say 15 min.The peak demand is the largest of all demands The peak demand is of particular interest since it representsthe load that the system must be designed to serve Diversity relates to multiple loads having differenttime patterns of energy use Due to diversity, the peak demand of a group of loads is less than the sum
of the peak demands of the individual loads For a group of loads,
Loads may be modeled as either lumped parameter or distributed Lumped parameter load modelsinclude constant power, constant impedance, constant current, voltage-dependent, and combinationsthereof Generally, equivalent lumped parameter load models are used to model distributed loads.Consider the line section of length L shown in Figure 112.2(a), with a uniformly distributed load currentthat varies along the length of the line as given by
The total load current drawn by the line section is thus
V V V
I I I
A B C
A B C
È
Î
ÍÍÍÍ
Î
ÍÍÍÍ
Î
ÍÍÍÍ
Diversity factor =Sum of individual load peaks
Trang 19Power flow analysis determines system voltages, currents, and power flows Power flow results arechecked to ensure that voltages fall within allowable limits, that equipment overloads do not exist, andthat phase imbalances are within acceptable limits For primary and secondary networks, power flow
FIGURE 112.2 (a) Line section model with distributed load current; (b) lumped parameter equivalent model.
FIGURE 112.3 Representative diversified load curve for a residential customer type.
(a) Line Section Model With Distributed Load Current
(b) Lumped Parameter Equivalent Model
Distributed Load Current
2IL3
IL3
0 2 4 6 8 10 12 14 16 18 20 22 24 300
600 900
1500
1200
Hours Peak Day of the Month Hourly Load Curves
Trang 20112-6 The Engineering Handbook, Second Edition
methods used in transmission system analysis are applied For radially operated systems, the laddermethod is used The actual implementation of the ladder method may vary with the type of load modelsused All ladder load flow methods assume the substation bus voltage is known An algorithm for theladder method consists of the following five steps:
1 Step 1. Assume a value for all node voltages throughout the circuit Generally, assumed voltagesare set equal to the substation voltage
2 Step 2. At each load in the circuit, calculate the current from the known load value and assumedvoltage
3 Step 3. Starting at the ending nodes, sum load currents to obtain line section current estimates,performing summation until the substation is reached
4 Step 4. Having estimates of all line section currents, start at the substation and calculate linesection voltage drops and new estimates of node voltages
5 Step 5. Compare new node voltages with estimates of previous iteration values The algorithmhas converged if the change in voltage is sufficiently small If the algorithm has not converged,return to Step 2
Dynamic load analysis includes such studies as motor-starting studies Rapid changes in large loadscan result in large currents, with a resultant drop in system voltage If the dip in voltage is too large ortoo frequent, then other loads are adversely affected, such as in an annoying flicker of lights This studygenerally employs a power flow calculation that is run at a number of points along the dynamic charac-teristic of the load
Planning involves using load forecasting and other analysis calculations to evaluate voltage level,substation locations, feeder routes, transformer/conductor sizes, voltage/power factor control, and res-toration operations Decisions are based upon considerations of efficiency, reliability, peak demand, andlife cycle cost
Phase Balancing
Phase balancing is used to balance the current or power flows on the different phases of a line section.This results in improved efficiency and primary voltage level balance The average current in the threephases is defined as
The maximum deviation from Iavg is given by
FIGURE 112.4 Representative diversity factor curve for a residential customer type.
1 1 1.20 1.40 1.60
Trang 21At a multi-phase grounded node in a linear distribution system, post-fault voltages are related to fault voltages and fault currents as given by
where Vfdenotes phase voltages (voltages between phase A and ground, B and ground, and C and ground)
of the node during the fault, V0 is the array of phase voltages before the fault occurs, I is the array offault currents that will flow out of the phases of the node during the fault, and Zth (a 3 ¥ 3 matrix)represents the phase Thevenin matrix looking into the node
Once Zth and pre-fault voltages at the node are available, Vf can be written in terms of I dependinguponconditions imposed by the fault Then Equation (112.1) can be solved for I The pre-fault systemmodel represents the system behavior before the fault occurs On the pre-fault model, a power flowcalculation may be used to obtain the voltages V0
The post-fault model represents the system behavior during the fault For fault calculations, the circuitmodel used is modified in several ways from the pre-fault model Usually, load currents are neglected inthe post-fault model, and instead superposition is used to add load currents obtained from the pre-faultpower flow analysis to fault currents For the fault calculations, the circuit model is assumed to be linear.Other changes for the post-fault circuit analysis include neglecting slow-acting control devices (such assubstation transformer tap changers) that do not have time to react during the time of the fault; andinserting appropriate Thevenin equivalent source impedances, representing the Thevenin impedance seen
by the distribution substation looking back into the transmission or subtransmission system Using thepost-fault circuit model assumptions, a power flow calculation using constant current injections at thefault point may be used to perform the fault calculations This is the approach described here
The calculation of Zth may be performed by inserting a small test load sequentially at every individualphase of the faulted node Prior to any test load insertion, the phase voltages of the node are obtainedfrom a power flow solution Let these voltages be Vi After inserting a test load, the power flow is usedagain to obtain the current flowing into the test load and the voltages at all phases of the node Ratios
of changes in Vi to the current drawn by the test load constitute the columns of Zth For instance, if thetest load is inserted between phase A and ground at grounded node N, the results calculated are the firstcolumn of Zth
To elaborate, refer to Figure 112.5 where a grounded node N is considered Here, a general node atwhich any phase may exist is assumed The power flow is run on the post-fault system model, and phase-to-neutral voltages at node N are obtained as V an, V bn, and V cn for the phases A, B, and C, respectively
DIdev=maximum of {Iavg-I A,Iavg-I B,Iavg-I C }
Phase imbalance dev
avg
=DI
I
Trang 22112-8 The Engineering Handbook, Second Edition
[Figure 112.5(a)] The neutral n is regarded to be the same as ground A test load will be inserted between
A and n, B and n, and C and n sequentially [Figure 112.5(b) through Figure 112.5(d)] During each load
insertion, line currents and phase-to-neutral voltages may be obtained from a power flow calculation
The elements z ij of Zth may be determined in the following manner:
, ,
, ,
, ,
Zth represents the relationship between the voltage changes and the current changes at N. Suppose
phase-to-neutral voltages at N before the fault are Assume that a fault occurs at N and causes
currents to flow out of phases A, B, and C, respectively, resulting in phase-to-neutral voltages
.Then voltage changes at N are related to the currents drawn, via Zth as
(112.2)
where
Equation (112.2) denotes a general case Suppose node N is a double-phase location having phases A
and B but no phase C Then, all the elements in the third row and third column of Zth are zero
FIGURE 112.5 Constructing Zth at a grounded node N (a) Voltages before inserting any test load (b) A test load
being inserted between phase A and ground (c) A test load being inserted between phase B and ground (d) A test
load being inserted between phase C and ground.
Post-fault System Model
Post-fault System Model
Phases present
at node N
a + b + c + n
Post-fault System Model n
(2) (2) (2)
Van(1)(1) (1)
(1)
Vbn
Vcn
(3) (3) (3) (3)
-( ) ( )
-( ) ( )
-( ) ( )
bn i
cn i
, , and
DDD
V V V
I I I
an bn cn
a b c
È
Î
ÍÍÍ
Î
ÍÍÍ
= - for k=a,b,c
1586_book.fm Page 8 Monday, May 10, 2004 3:53 PM
Trang 23Various fault cases at N are shown in Figure 112.6 A general case of a three-phase-to-ground fault at
N is represented in Figure 112.6(a) Here, each phase has its own fault impedance (Z a , Z b , and Z c for
phases A, B, and C, respectively) to the common point p Z f is the impedance between p and n Consider solving for a three-phase-to-ground fault Let V i
kn and V f
kn denote pre-fault and post-fault
phase-to-ground voltages of phase k, respectively Then the boundary conditions are:
sub-Any fault event imposes a set of boundary conditions Initial voltages (pre-fault voltages) can be readilycalculated from the power flow The final voltages are expressed under the boundary conditions in terms
of the fault currents and fault impedances Then, Equation (112.2) is solved for fault currents Using thisapproach, fault currents for cases b through d shown in Figure 112.6 may be evaluated For an ungroundednode, the phase-to-phase voltages instead of phase-to-neutral voltages are employed
FIGURE 112.6 Various faults at a grounded node N (a) Three-phase fault (b) Phase-to-phase fault (c) phase-to-ground fault (d) Single-phase-to-ground fault.
p
p
Post-fault System Model
Post-fault System Model
Post-fault System Model
Post-fault System Model
DV cn V cn i V V I Z I Z
cn f cn i
I I I
V V V
a b c
an i bn i cn i
È
Î
ÍÍÍ
Î
ÍÍÍ
Trang 24112-10 The Engineering Handbook, Second Edition
Protection and Coordination
Over-current protection is the most common protection applied to the distribution system With current protection, the protective device trips when a large current is detected The time to trip is afunction of the magnitude of the fault current The larger the fault current is, the quicker the operation.Various types of equipment are used A circuit breaker is a switch designed to interrupt fault current,the operation of which is controlled by relays An over-current relay, upon detecting fault current, sends
over-a signover-al to the breover-aker to open A recloser is over-a switch thover-at opens over-and then recloses over-a number of timesbefore finally locking open A fuse is a device with a fusible member, referred to as a fuse link, which inthe presence of an over current melts, thus opening up the circuit
Breakers may be connected to reclosing relays, which may be programmed for a number of openingand reclosing cycles With a recloser or a reclosing breaker, if the fault is momentary, then the powerinterruption is also momentary If the fault is permanent, then after a specified number of attempts atreclosing the device locks open Breakers are generally more expensive than comparable reclosers Breakersare used to provide more sophisticated protection, which is available via choice of relays Fuses aregenerally used in the protection of laterals
Protective equipment sizing and other characteristics are determined from the results of fault analysis.Moving away from the substation in a radial circuit, both load current and available fault current decrease.Protective devices are selected based on this current grading Protective devices are also selected to havedifferent trip-delay times for the same fault current With this time grading, protective devices arecoordinated to work together such that the device closest to a permanent fault clears the fault Thusreclosers can be coordinated to protect load-side fuses from damage due to momentary faults
Reliability Analysis
Reliability analysis involves determining indices that relate to continuity of service to the customer.Reliability is a function of tree conditions, lightning incidence, equipment failure rates, equipment repairtimes, and circuit design The reliability of a circuit generally varies from point to point due to protectionsystem design, placement of switches, and availability of alternative feeds Many indices are used inevaluating system reliability Common ones include system average interruption frequency index (SAIFI),system average interruption duration index (SAIDI), customer average interruption frequency index(CAIFI), and customer average interruption duration index (CAIDI) as defined by
SAIFI = Total number of customer interruptions
Total number of customers served
SAIDI = Sum of customer interruption durations
Total number of customers
CAIFI = Total number of customer interruptions
Total number of customers affected
CAIDI = Sum of customer interruption durations
Total number of customers affected
Trang 25112.4 System Control
Voltage control is required for proper operation of customer equipment For instance, in the U.S., “voltagerange A” for single-phase residential users specifies that the voltage may vary at the service entrance from114/228 V to 126/252 V Regulators, tap-changing under load transformers, and switched capacitor banksare used in voltage control
Power factor control is used to improve system efficiency Due to the typical load being inductive,power factor control is generally achieved with fixed and/or switched capacitor banks
Power flow control is achieved with switching operations Such switching operations are referred to
as system reconfiguration Reconfiguration may be used to balance a load among interconnected bution substations Such switching operations reduce losses while maintaining proper system voltage.Load control may be achieved with voltage control and also by remotely operated switches thatdisconnect load from the system Generally, load characteristics are such that if the voltage magnitude
distri-is reduced, then the power drawn by the load will decrease for some period of time Load control withremotely operated switches is also referred to as load management
Effective system control is essential to provide adequate power quality Power quality may be defined
as the absence of service interruptions, voltage dips and sags, and voltage spikes and surges Propercontrol of system voltage is more critical now than ever before because many microprocessor-basedcontrols and adjustable speed drives have voltage tolerances less than 10%
112.5 Operations
The operations function includes system maintenance, construction, and service restoration nance, such as trimming trees to prevent contact with overhead lines, is important to ensure a safe andreliable system Interruptions may be classified as momentary or permanent A momentary interruption
Mainte-is one that dMainte-isappears very quickly — for instance, a recloser operation due to a fault from a tree limbbriefly touching an overhead conductor Power restoration operations are required to repair damagecaused by permanent interruptions
While damaged equipment is being repaired, power restoration operations often involve tion in order to restore power to interrupted areas With reconfiguration, power flow calculations may
reconfigura-be required to ensure that equipment overloads are not created from the switching operations
Defining Terms
Current return path — The path that current follows from the load back to the distribution substation.
This path may consist of either a conductor (referred to as the neutral) or earth, or the parallelcombination of a neutral conductor and the earth
Fault — A conductor or equipment failure or unintended contact between conductors or between
con-ductors and grounded objects If not interrupted quickly, fault current can severely damageconductors and equipment
Phase — Relates to the relative angular displacement of the three sinusoidally varying voltages produced
by the three windings of a generator For instance, if phase A voltage is 120– 0˚ V, phase Bvoltage 120– -120˚ V, and phase C voltage 120– 120˚ V, the phase rotation is referred to asABC Sections of the system corresponding to the phase rotation of the voltage carried are
commonly referred to as phase A, B, or C.
Tap-changing mechanism — A control device that varies the voltage transformation ratio between the
primary and secondary sides of a transformer The taps may only be changed by discreteamounts, say 0.625%
Trang 26112-12 The Engineering Handbook, Second Edition
References
Broadwater, R P., Shaalan, H E., Oka, A., and Lee, R E 1993 Distribution system reliability and
restoration analysis Electric Power Sys Res J 29(2):203–211.
Carson, J R 1926 Wave propagation in overhead wires with ground return Bell System Tech J 5:40–47.
Engel, M V., Greene, E R., and Willis, H L (Eds.) 1992 IEEE Tutorial Course: Power DistributionPlanning Course Text 92 EHO 361-6-PWR IEEE Service Center, Piscataway, NJ
Kersting, W H and Mendive, D L 1976 An Application of Ladder Network Theory to the Solution ofThree-Phase Radial Load Flow Problems IEEE Winter Meeting, New York
Further Information
Redmon, J R 1988 IEEE Tutorial Course on Distribution Automation Course Text 88 EH0 280-8-PWRIEEE Service Center, Piscataway, NJ
Electric Utility Engineers, Westinghouse Electric Corporation 1950 Electrical Transmission and
Distri-bution Reference Book, Westinghouse Electric Corporation, Pittbsurgh, PA.
Kersting, W H 2002 Distribution System Modeling and Analysis, CRC Press, Boca Raton, FL.
Lakervi, E and Holmes, E J 1989 Electricity Distribution Network Design, Peter Peregrinus, London Pansini, A J 1992 Electrical Distribution Engineering, Fairmont Press, Liburn, GA.
Trang 27What Is Electromagnetic Interference? • Causes of EMI •
Solutions to EMI Problems
113.2 Grounding
Characteristics of Ground Conductors • Ground-Related EMI Coupling • Grounding Configurations • Summary of Grounding Considerations
113.3 Shielding
Radiated Electromagnetic Waves • Shielding Theory •
Reflection Loss • Absorption Loss • Shielding Material Characterization • Conductive Coatings • Aperture Leakages •
Summary of Shielding Considerations
113.4 Using Shielded Isolation Transformers to ImproveEquipment Compatibility
Shielded Isolation Transformers
113.5 Using Filtering Technologies to Improve EquipmentCompatibility
An Overview of the Current Standard • Limitations of
MIL-STD- 220B 2• IEEE P1560: A Step Forward
Many electromagnetic compatibility problems are caused by low immunity to emissions and poor facilityand data wiring and grounding which further affect equipment performance Besides, radiated andconducted emissions generated by a piece of equipment may also affect that equipment’s own perfor-mance To avoid problems, electromagnetic interference (EMI) control measures must be incorporatedinto the initial circuit design Grounding, shielding, and filtering are some of the important factors thatmust be considered during the initial design of electronic circuits
The purpose of this chapter is to give engineers and facility engineers who are unfamiliar with related problems insights and information necessary to improve equipment compatibility The goal here
EMI-is not to duplicate information currently available, but rather to collect information in a single locationand then supplement it to provide adequate information and procedures to applications personnel ineffectively limiting the spurious emissions given off by electronics and ensuring that electronic equipment
is not adversely affected by such emissions
William G Duff(First Edition)
Computer Sciences Corporation
Arindam Maitra(Second Edition)
EPRI PEAC Corporation
Kermit Phipps(Second Edition)
EPRI PEAC Corporation
Anish Gaikwad(Second Edition)
EPRI PEAC Corporation
1586_book.fm Page 1 Monday, May 10, 2004 3:53 PM
Trang 28113-2 The Engineering Handbook, Second Edition
113.1 Analyzing and Solving Problems Associated with
Electromagnetic Interference
What Is Electromagnetic Interference?
Electromagnetic interference (EMI) is any natural or manmade electrical or electromagnetic energy thatresults in unintentional and undesirable equipment responses Electromagnetic energy travels in the form
of emissions, either conducted or radiated
Conducted emissions are generated inside electrical or electronic equipment and may be transmittedoutward through the equipment’s data input or output lines, its control leads, or its power conductors.Conducted emissions may cause an EMI problem between equipment that generates useful emissionsand other equipment with low immunity to those same emissions
Radiated emissions are radio-frequency electromagnetic energy that travels through the air Radiatedemissions are also generated by electrical or electronic equipment and may be emitted from power anddata cables that are poorly shielded or unshielded, leaky equipment apertures, equipment housings thatare inadequately shielded, or equipment antennae that may or may not be operating normally.Current trends in the electronics industry (such as increases in the quantity of electronic equipment,reliance on electronic devices in critical applications, higher clock frequencies of computing devices,higher power levels, lower sensitivities, increased packaging densities, use of plastics, etc.) will tend tocreate more EMI problems Whether conducted or radiated, emissions include three properties: ampli-tude, frequency, and waveform EMI can occur in equipment with low immunity to emissions when any
or all of these properties vary from normal, for example, emissions that are too high in amplitude, aretoo low or too high in frequency, or whose waveforms are distorted EMI can also occur when theseproperties are within normal operating parameters, usually resulting from equipment’s low immunity
to emissions Examples of intentional and unintentional conducted and radiated emissions are illustrated
in Table 113.1
Causes of EMI
EMI is generally common-mode (CM) noise, which is induced onto a signal with respect to a referenceground The noise is coupled to ground from the power cables through the capacitance between thepower cable and ground Figure 113.1 demonstrates this principle
The capacitance between the cable and ground increases as the length of cable increases Therefore,short lengths of cable have a low risk of common-mode noise As the length of cable increases, the risk
of common-mode noise increases and the need for EMI solutions rises
As shown in Figure 113.2, the common-mode ground current Iao = Cl-g dv/dt This characteristic ofcommon-mode current makes the adjustable-speed drive a prime source of common-mode noise because
of its abrupt voltage transitions on the drive output terminal The conducted noise will be created as theindividual pulses on the drive output couple with the ground conductor Some common symptoms ofEMI-related problems are:
• Unexplained drive trips with no correlation with voltage disturbances
• Malfunctions of barcode/vision systems, ultrasonic sensors, and weighing and temperature sensors
• Intermittent data errors in drive-control interfaces such as encoder feedback, I/O, and 0-10-Vanalog out
• Interference with TV, AM radio, and radio-controlled devices
Radiated emissions from many types of electronic equipment, including ASDs, lighting systems,broadcast communication equipment, and medical equipment, have been shown to cause electromag-netic interference with other types of sensitive electronic equipment Figure 113.1 shows how conductedand radiated emissions propagated through the electromagnetic environment may interfere with sensitiveelectronic medical equipment that is microprocessor based
1586_book.fm Page 2 Monday, May 10, 2004 3:53 PM
Trang 30113-4 The Engineering Handbook, Second Edition
Ungrounded shields or floating shields can act like an antenna to unwanted radiated emissions In thecase of a shielded cable, a cable connector also helps to connect the cable shield to the equipment enclosureelectromagnetically Connectors are used to mechanically secure a cable to a piece of equipment Thepieces of a connector must fit together properly and securely to ensure the electromagnetic integrity ofthe connector Particular attention must be paid to how the pieces fit together during connector instal-lation Improperly fitted or loose connector joints can cause electromagnetic leaks in the connector,which can allow unwanted radiated electromagnetic energy from the electromagnetic environment topenetrate the cable system
Solutions to EMI Problems
Methods to mitigate EMI in an industrial facility could include proper grounding and shielding of sensitiveequipment, attenuating emissions at the source, capturing and returning emissions to the source, etc
FIGURE 113.1 Capacitive-coupling from phase-to-ground conductor.
FIGURE 113.2 Examples of conducted and radiated emissions interfering with equipment.
Incoming Conducted Emissions
Conducted Emissions Coupled to Sensitive Electronics by Transformer
Clock Signal Optional Filter Capacitor 5V Energy Storage Capacitor
Optional Battery
120 Vac
Conducted Emissions Filter (Capacitance Values Leakage Current)
Conducted Emissions After Filtering
Frequency Coupling
Frequency Coupling
High-Display Power (Not Affected by Conducted Emissions When Not Powered by Line Voltage)
Analog Processing Circuitry
Patient Computer Data Cables
Radiated Emissions Source
Interface Card Input/Output
User Inputs (Buttons & Switches)
Display Drive Standby Oscillator
Microprocessor (Powered During Emissions)
ag
netic
Energy
Unshielded Phase Conductor Stray Capacitive Coupling Phase-Ground
Comon Mode Voltage V12
Ground Potential #1
Ground Potential #2 Comon Mode Noise Current
Trang 31Grounding, Shielding, and Filtering 113-5
Proper Grounding and Shielding of Sensitive Equipment
The practice of using unshielded phase conductors in a cable tray from an ASD to a motor couldintroduce common-mode noise into the system The use of a shielded-armor power cable from a drive
to a motor will provide a path for the common-mode noise to return to the source Figure 113.3demonstrates this concept
Signal shields reduce external coupling but may introduce EMI if the shield is connected to a noisyground potential The standard practice is to ground the shield at the source side of the cable If thestandard practice does not eliminate the EMI, it becomes necessary to do whatever it takes to fix theproblem, including grounding on both ends, grounding on the other end, or not grounding at all.The path of common-mode emissions can be diverted from sensitive equipment by separating controland signal cables from high-voltage wires It is also best if the power conductors include a ground wireand are placed in a conduit The conduit should be bonded to an ASD cabinet, the motor junction box,and the ground wire should be connected to the cabinet ground bus and motor ground stud The groundwire and conduit setup parasitic capacitive paths within the conduit and couple high dV/dt pulses andreturn them back to the source of emissions
Often it is necessary to isolate the conduit coupling at the point of the motor to prevent the coupledemissions from traveling on the outer surface of the conduit Insulated motor pairs and ground arerecommended to prevent inadvertent grounding of the conduit where new ground loops may beestablished to radiate the noise In this practice, it is critical to carry the safety ground within theconduit and ensure proper bonding at the motor ground stud to ensure NEC compliance This practice
is usually necessary where interference levels may be in the low frequency band, for example, 10 to
100 kHz
Another often-recommended and important practice is to separate control and signal cables frompower cables in cable trays The practice of placing covers on a signal cable tray will further reduce thenoise coupled to the signal cables from the power cables
Attenuating Emissions at the Source
The best way to eliminate system emissions is to attenuate emissions at the source The use of a mode choke (CMC) is one way to achieve this A CMC is an inductor with phases A, B, and C conductorswound in the same direction through a common magnetic core It provides high impedance and highinductance to any line-to-ground capacitive current emissions Unlike a line reactor/inductor, a CMCdoes not affect the power-line circuit This device is available from drive vendors Figure 113.4 shows anexample of a CMC application
common-Capturing and Returning Emissions to the Source
Another method to reduce EMI is to capture emissions and return them to the source This can beaccomplished with an EMI filter Figure 113.5 demonstrates the use of an EMI filter This figure showsthat the CM current Iao will collect in the ground conductors and return to the drive through the EMIfilter The filter contains a large common-mode core inductance and individual phase capacitors thatlimit the high frequency ground return current to low levels in the main AC supply
FIGURE 113.3 Use of a shielded/armor cable to reduce EMI.
ASD
Armor
lao
C1-g PVC
C1-g C1-g
Trang 32113-6 The Engineering Handbook, Second Edition
conduc-a zero-voltconduc-age reference for conduc-an electricconduc-al power distribution system Fundconduc-amentconduc-al design principles forsystem and equipment grounding and the basic factors that influence the selection of the type of system/equipment grounding are extensively covered in IEEE Color books, including IEEE Std 141-1993, IEEEStd 142-1991, IEEE Std 446-1995, IEEE Std 1100-1999, NFPA 70-1999 National Electric Code (NEC),and Federal Information Processing Standards (FIPS) 1994
Note that the basic objectives for grounding circuits, cables, equipment, and systems are to prevent ashock hazard; to protect circuits and equipments; and to reduce EMI due to electromagnetic field,common ground impedance, or other forms of interference coupling However, grounding is one of theleast understood and most significant factors in many EMI problems Most equipment manufacturerswill provide details on grounding of their equipment and may often violate NEC and other importantstandards The EMI part of the problem is emphasized in the subsequent sections
Characteristics of Ground Conductors
Ideally, a ground conductor should provide a zero-impedance path to all signals for which it serves as areference If this were the situation, signal currents from different circuits would return to their respectivesources without creating unwanted coupling between circuits Many interference problems occur because
FIGURE 113.4 Application of a common-mode choke.
FIGURE 113.5 Application of EMI filter.
ASD
ASD Input
CMC
Motor
Motor Leads
EMI/RFI Filter
ASD
lao Motor
1586_book.fm Page 6 Monday, May 10, 2004 3:53 PM
Trang 33Grounding, Shielding, and Filtering 113-7
designers treat the ground as ideal and fail to give proper attention to the actual characteristics of theground conductor
A commonly encountered situation is that of a ground conductor running along in the proximity of
a ground plane as illustrated in Figure 113.6 The ground conductor and ground plane may be represented
as a short-circuited transmission line At low frequencies the resistance of the ground conductor willpredominate At higher frequencies the series inductance and the shunt capacitance to ground will becomesignificant, and the ground conductor will exhibit alternating parallel and series resonance as illustrated
in Figure 113.7 To provide a low impedance to ground, it is necessary to keep the length of the groundingconductor short relative to wavelength (i.e., less than 1/20 of the wavelength)
Ground voltage equalization of voltage differences between parts of an automated data processing(ADP) grounding system is accomplished in parts when the equipment-grounding conductors are con-nected to the grounding point of a single power supply However, if the equipment grounding conductorsare long, it is difficult to achieve a constant potential throughout the grounding system, particularly forhigh frequency noise Supplemental conductors, low-inductance ground plates, and grounding and bond-ing of raised floor pedestals may be necessary Detailed discussions and standard practices and proceduresare extensively covered in IEEE Color books, including IEEE Std 142-1991 and IEEE Std 1100-1999
Ground-Related EMI Coupling
Ground-related EMI involves one of two basic coupling mechanisms The first mechanism results fromcircuits sharing the ground with other circuits Figure 113.8 illustrates EMI coupling between culprit and
FIGURE 113.6 Idealized equipment grounding.
FIGURE 113.7 Typical impedance versus frequency behavior of a grounding conductor.
Trang 34113-8 The Engineering Handbook, Second Edition
victim circuits via the common-ground impedance In this case, the interference current flowingthrough the common-ground impedance (Z g) will produce an interfering signal voltage (V i) in the victimcircuit This effect can be reduced by minimizing or eliminating the common-ground impedance.The second EMI coupling mechanism involving ground is a radiated mechanism whereby the groundloop, as shown in Figure 113.9, acts as a receiving or transmitting antenna Ground loops are probablythe most common cause of interference in network systems and also the most common problem withmulti-port devices in general For this EMI coupling mechanism the induced EMI voltage (for thesusceptibility case) or the emitted EMI field (for the emission case) is a function of the EMI drivingfunction (field strength, voltage, or current), the geometry and dimensions of the ground loop, and thefrequency of the EMI signal
Common wisdom on electromagnetic compatibility recommends that radiated effects can be mized by routing conductors as close as possible to ground and minimizing the ground-loop area Eventhough theory holds up that closely routing conductors next to a ground plane will reduce the effects ofcoupling, however, where building steel and in particular in cases of lightning where large currents mayflow, the coupling will still occur The coupling effect applies to stray common-mode currents also Theprimary factor is that in practical installations, ideal placement of the conductor next to the surface ofthe ground plane is difficult Examples of this may be the upgrade of existing plant operation toincorporate multiple remote PLC systems communicating to a central control room These cable runsare seldom able to achieve the ideal installation
mini-Figure 113.10 uses linear scales to emphasize the very rapid rise of induced voltage near a conductorand the small additional gain after a few meters However, if “close to” were interpreted by an installer
as a few centimeters, all the expected benefits from the “close” installation would be lost — in otherwords, it is not very effective to attempt minimizing induced voltages by casual routing of unshielded
FIGURE 113.8 Common-ground impedance coupling between circuits.
FIGURE 113.9 Common-mode radiations into and from ground loops.
Radiation or Pick Up by Ground Loop
1586_book.fm Page 8 Monday, May 10, 2004 3:53 PM
Trang 35Grounding, Shielding, and Filtering 113-9
cables “near” the ground planes From Figure 113.10 it can be clearly seen that when a cable is just a fewcentimeters above the ground plane, the cable will still have significant amounts of induced noise
Grounding Configurations
Typical electronic equipment may have a number of different types of functional signals as shown in
Figure 113.11 To mitigate interference due to common-ground impedance coupling, as many separategrounds as possible should be used
The grounding scheme for a collection of circuits within equipment can assume any one of severalconfigurations Each of these configurations tends to be optimum under certain conditions and maycontribute to EMI problems under other conditions In general, the ground configurations are a floatingground, a single-point ground, a multiple-point ground, or some hybrid combination The determi-nation to use single-point grounding or multiple-point grounding typically depends on the frequencyrange of interest Analog circuits with signal frequencies up to 300 kHz may be candidates for single-point grounding Digital circuits with signal frequencies in the MHz range should utilize multiple-point grounding
FIGURE 113.10 Voltage induced by the field into the loop.
FIGURE 113.11 Grounding hierarchy.
0 0
100 80 60 40 20 R
di dt
Induced voltage (%)
Radius in meters
Lightning, EMP Ground (Tens of kA,
dc to a few tens of MHz)
Relays, etc , Signaling Grounds (5 V to 50 V
dc to a few kHz)
Low-Level, Low-Frequency Ground ( µV to mV
dc to a few 100 kHz)
Low-Level, High-Frequency Ground.
Radio Communication ( µV to mV, kHz to GHz)
Digital Levels, High-Frequency Ground (Volts dc to 100 MHz)
DC Power Ground (Returns for Loads > 1A)
AC Power Safety Ground (50 Hz/60 Hz or 400 Hz)
Trang 36113-10 The Engineering Handbook, Second Edition
A floating ground configuration is illustrated in Figure 113.12 The signal ground is electrically isolatedfrom the equipment ground and other conductive objects Hence, equipment noise currents present inthe equipment and power ground will not be conductively coupled to the signal circuits
The effectiveness of floating ground configurations depends upon their true isolation from othernearby conductors; that is, to be effective, floating ground systems must really float It is often difficult
to achieve and maintain an effective floating system A floating ground configuration is most practical
if only a few circuits are involved and power is supplied from either batteries or DC-to-DC converters
A single-point ground configuration is illustrated in Figure 113.13 An important advantage of thesingle-point configuration is that it helps control conductively coupled interference As illustrated inFigure 113.13, EMI currents or voltages in the equipment ground are not conductively coupled into thesignal circuits via the signal ground Therefore, the single-point signal ground network minimizes theeffects of any EMI currents that may be flowing in the equipment ground
The multiple-point ground illustrated in Figure 113.14 is the third configuration frequently used forsignal grounding With this configuration, circuits have multiple connections to ground Thus, in equip-ment, numerous parallel paths exist between any two points in the multiple-point ground network.Multipoint grounding is more economical and practical for printed circuits and integrated circuits
FIGURE 113.12 Floating signal ground.
FIGURE 113.13 Single-point signal ground.
1586_book.fm Page 10 Monday, May 10, 2004 3:53 PM
Trang 37Grounding, Shielding, and Filtering 113-11
Interconnection of these components through wafer risers, mother boards, and so forth should use ahybrid grounding approach in which single-point grounding is used to avoid low-frequency ground loopsand/or common-ground impedance coupling; multipoint grounding is used otherwise
Summary of Grounding Considerations
It should be noted that both the conducted and radiated EMI coupling mechanisms identified earlierinvolve a “ground loop.” It is important to recognize that ground loop EMI problems can exist without
a physical connection to ground In particular, at RF frequencies, capacitance-to-ground can create aground loop condition even though circuits or equipments are floated with respect to ground
A properly designed ground configuration is one of the most important engineering elements inprotecting against the effects of EMI The ground configuration should provide effective isolation betweenpower, digital, high-level analog, and low-level analog signals In designing the ground it is essential toconsider the circuit, signal characteristics, equipment, cost, maintenance, and so forth In general, eitherfloating or single-point grounding is optimum for low-frequency situations, and multiple-point ground-ing is optimum for high-frequency situations In many practical applications, a hybrid ground approach
is employed to achieve the single-point configuration for low frequencies and the multiple-point figuration for high frequencies
con-113.3 Shielding
Shielding is one of the most effective methods for controlling radiated EMI effects at the component,circuit, equipment, subsystem, and system levels Good EMC design reduces EMI signals to a level wherethey do not cause problems within the equipment or with any other equipment
Shielding effectiveness is a measure of how well a shield blocks radiated emissions Reducing the level
of radiated emissions incident upon the equipment requires selecting the proper shielding material (see
Figure 113.15), and correct installation and maintenance to ensure the integrity of the shield
Radiated Electromagnetic Waves
The performance of shields is a function of the characteristics of the incident electromagnetic fields Allelectromagnetic waves consist of two oscillating fields that operate at right angles to each other One ofthese fields is the electric (E) field, whose strength is measured in volts per meter Perpendicular to the
E field is the magnetic (H) field, whose strength is measured in amps per meter H fields usually aregenerated by high current, low voltage, low impedance circuits In contrast, E fields are produced by
FIGURE 113.14 Multiple-point ground configuration.
Trang 38113-12 The Engineering Handbook, Second Edition
devices that have high voltage, but relatively low current and high impedance The ratio of E field to Hfield is called the wave impedance The H and E fields vary in relative magnitude according to the distance
of the wave from the generating source and the nature of the source itself
The material selected for the shield depends upon characteristics of the source of the radiated emissionsand the reflective and absorbent properties of the shielding material (see Figure 113.16) These includethe impedance of the electromagnetic fields of the source creating the emissions, which depends on thedistance from the emissions source to the malfunctioning equipment In most cases, this distance (referred
to as the “far-field”) is such that the emissions are primarily due to electric fields resulting in fieldimpedance that is constant and can be easily approximated If the equipment is relatively close to thesource of emissions, the impedance will be lower where the equipment is referred to as being in the
“near-field,” and where the magnetic field component must be considered Before a shielding materialcan be selected, one must determine whether the affected equipment is in the “near-” or “far-field.”
In the “far-field,” a moderately good conductor may be used to shield against radiated emissions fromelectric fields For emissions above about 1 MHz, the conductivity of the material, which is partiallybased on its thickness, does not have a significant effect on the material’s ability to block electric fields.The primary dependence is on conductivity, which is the material’s ability to carry electrons from thefield and thus, provide a low impedance path to ground for the radiated emissions However, at distancescloser to the source of the emissions, more attention must be placed on selecting the shielding material
FIGURE 113.15 A variety of shields can be used to solve EMI problems.
FIGURE 113.16 Diagram of a shielding material absorbing and reflecting emission.
Incident Radiated Electromagnetic Energy
Reflected Radiated Electromagnetic Energy
Radiated Electromagnetic Energy that Passes Through the Shield
Absorbed within Shielding Material
Shielding Material 1586_book.fm Page 12 Monday, May 10, 2004 3:53 PM
Trang 39Grounding, Shielding, and Filtering 113-13
Unlike the mitigation of electric fields in the “far-field,” which only requires the shield to be reflective,
equipment in the “near-field,” which may be in an area containing both electric and magnetic-field
components, requires a material that will reflect and absorb electromagnetic energy Therefore, shielding
considerations in the near-field region of an EMI source may be significantly different from shielding
considerations in the far-field region
Shielding Theory
If a metallic barrier is placed in the path of an electromagnetic field as illustrated in Figure 113.17, only
a portion of the electromagnetic field may be transmitted through the barrier Several effects may occur
when the incident wave encounters the barrier First, a portion of the incident wave may be reflected by
the barrier Second, the portion of the incident wave that is not reflected will penetrate the barrier interface
and may experience absorption loss while traversing the barrier Third, additional reflection may occur
at the second barrier interface, where the electromagnetic field exits the barrier Usually, this second
reflection is insignificant relative to the other effects that occur, and it may be neglected
The shielding effectiveness of the barrier may be defined in terms of the ratio of the impinging field
intensity to the exiting field intensity For high-impedance electromagnetic fields or plane waves, the
shielding effectiveness is given by
(113.1)
where E1 is the impinging field intensity in volts per meter and E2 is the exiting field intensity in volts
per meter For low-impedance magnetic fields, the shielding effectiveness is defined in terms of the ratio
of the magnetic field strengths
The total shielding effectiveness of a barrier results from the combined effects of reflection loss and
absorption loss Thus, the shielding effectiveness, S, in dB is given by
where RdB is the reflection loss, AdB is the absorption loss, and BdB is the internal reflection loss
Charac-teristics of the reflection and absorption loss are discussed in the following sections
Reflection Loss
When an electromagnetic wave encounters a barrier, a portion of the wave may be reflected The reflection
occurs as a result of a mismatch between the wave impedance and the barrier impedance The resulting
reflection loss, R, is given by
FIGURE 113.17 Shielding of plane waves.
B A
TRANSMITTING WAVE INSIDE OF ENCLOSURE
REFLECTED WAVE OUTSIDE
WORLD BARRIER OF FINITE THICKNESS
ATTENUATED INCIDENT WAVE INCIDENT WAVE
E
Trang 40113-14 The Engineering Handbook, Second Edition
(113.3)
where Z w is the wave impedance =E/H, and Z b is the barrier impedance
Absorption Loss
When an electromagnetic wave encounters a barrier, a portion of the wave penetrates the barrier As the
wave traverses the barrier, the wave may be reduced as a result of the absorption loss that occurs in the
barrier This absorption loss, A, is independent of the wave impedance and may be expressed as follows:
(113.4)
where t is the thickness in mm, fMHz is the frequency in MHz, mr is the permeability relative to copper,
and sr is the conductivity relative to copper
Shielding Material Characterization
The ability of a material to absorb radiated emissions depends on the frequency of the source, and the
conductivity, permeability, and thickness of the shielding material An increase in any of these variables
will increase absorption However, the variables of concern when selecting a material to absorb emissions
in the “near-field” are the ones that vary widely among available materials These are permeability, which
is the extent to which a material can be magnetized, and thickness Thus, to mitigate against low-frequency
magnetic fields in the “near-field” such as those originating from power distribution equipment such as
transformers from some medical equipment utilizing 60-hertz power and from electrical appliances, a
material of the proper thickness such as iron, which can be magnetized and provide a path for the
magnetic field emissions, is required A screened or solid shield made of copper or other material to
attenuate electric fields, some type of steel composite or other material to attenuate magnetic fields, or
a combination of both may be installed around equipment or inside the walls of the room where
equipment is used
The total shielding effectiveness resulting from the combined effects of reflection and absorption loss
are plotted in Figure 113.18 for copper and iron materials having thicknesses of 0.025 mm and 0.8 mm,
having electric and magnetic fields and plane-wave sources, and having source-to-barrier distances of
2.54 cm and 1 m
As shown in Figure 113.18, good shielding efficiency for plane waves or electric (high-impedance)
fields is obtained by using materials of high conductivity, such as copper and aluminum However,
low-frequency magnetic fields are more difficult to shield because both the reflection and absorption loss of
nonmagnetic materials, such as aluminum, may be insignificant Consequently, to shield against
low-frequency magnetic fields, it may be necessary to use magnetic materials
Conductive Coatings
Conductive coatings applied to nonconductive materials such as plastics will provide some degree of
EMI shielding The principal techniques for metalizing plastic are the following:
w b w