1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Power Quality Monitoring Analysis and Enhancement Part 10 pot

25 368 0
Tài liệu đã được kiểm tra trùng lặp

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Định dạng
Số trang 25
Dung lượng 650,11 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

Power Quality – Monitoring, Analysis and Enhancement 212 indices accurately represent the transient characters of the transient disturbances.. 4.2 PSCAD/EMTDC simulated disturbances A s

Trang 1

Power Quality – Monitoring, Analysis and Enhancement

212

indices accurately represent the transient characters of the transient disturbances IRMS can accurately represent the RMS accommodating the time information IHDR mainly represents the harmonic component relative to the pure sinusoid fundamental However, IWDR focuses on the fundamental component distortion of the transient disturbances and also the harmonic distortion Therefore there is the similar result between IHDR and IWDR when the transient oscillation is analyzed, that is very different from the results of low frequency disturbances IAF represents the instantaneous average frequency of the transient disturbances and denotes the rated frequency when there is no disturbance occurred

4.2 PSCAD/EMTDC simulated disturbances

A simple distribution model is built in PSCAD/EMTDC and two transient disturbances: voltage sag and capacitor switching which are two most common disturbances are obtained

to illustrate the performance of four power quality indices

-1.5 -1 -0.5 0 0.5 1 1.5

transform based time frequency distribution of voltage sag

Trang 2

S-Transform Based Novel Indices for Power Quality Disturbances 213

A voltage sag caused by A phase grounded fault is simulated and the waveform of A phase voltage is shown in Fig 5(a) Fig 5(b) shows the time frequency distribution based on S-transform The disturbance occurs at 0.082s and ends at 0.313s The four power quality indices: RMS, IHDR, IWDR and IAF are calculated and a summary of these indices is show

in Tab 1 Similar to the results of the voltage sag in case1, the IRMS is 0.3 and the IWDR is 57.6% during the disturbance occurred The steady values of IRMS and IWDR are 0.707 and

0 There are also two peaks in the IHDR and IAF corresponding to the start and end time, which are 28.2% and 190Hz at 0.082s and 22.3% and 109Hz at 0.313s respectively Compared with the voltage sag in case1, this disturbance is not start/end at the zero-crossing point; moreover, there is a larger amplitude change with the IWDR value 57.6% Consequently, more harmonic content is contained in the disturbance signal, leading to a higher IHDR and

Table 1 S-transform based four indices of voltage sag

Another disturbance as transient oscillation due to capacitor switching is showed in Fig.6 and the 0.3MVAR capacitor is put into operation at 0.153s Tab.2 provides the transient peak values and steady values of the four indices The peak value of IRMS is 0.722 at 0.153s and the peak value of IWDR is 20.1% at the same time that is almost equivalent to the IHDR The IAF also has a peak value 98Hz when transient oscillation occurred and maintain at 50Hz once the oscillation ended As the IRMS is a little deviation from the rated value, there

is less harmonic content in the disturbance Accordingly, the value of IHDR, IWDR and IWDR is smaller relative to the disturbance in case2

Obviously, the two transient disturbances as voltage sag and capacitor switching are characterized well by the four power quality indices Therefore one can accurately represent the transient information over the time based on the good time-frequency localization properties of S-transform

Trang 3

Power Quality – Monitoring, Analysis and Enhancement

214

0.15 0.16 0.17 0.18 -1.5

-1 -0.5 0 0.5 1 1.5

5 Conclusion

In this chapter, power quality assessment for transient disturbance signals has been carefully treated based on S-transform The limitations of the traditional Fourier series coefficient based power quality indices, which inherently require periodicity of the disturbance signal, have been resolved by use of time-frequency analysis In order to overcome the limitations of the traditional power quality indices in analyzing transient disturbances which are non-stationary waveforms with time-varying spectral component, four instantaneous power quality indices based on S-transform are presented S-transform is shown to be a new time frequency analysis tool producing instantaneous time frequency representation with frequency dependent resolution In the S-transform domain, new power quality indices: IRMS, IHDR, IWDR and IAF are defined and discussed The effectiveness of these indices was tested using a set of disturbances represented mathematically and

Trang 4

S-Transform Based Novel Indices for Power Quality Disturbances 215 simulated in PSCAD/EMTDC respectively The results show that the instantaneous property of transient disturbance can be characterized accurately

The transient power-quality indices provide useful information about the time varying signature of the transient disturbance for assessment purposes However, if the time-varying signature can be quantified as a single number, it would be more informative and convenient for an assessment and comparison of transient power quality The power quality indices proposed in this chapter can be extended to general indices assessment, which should collapse to the standard definition for the periodic case and also be calculable by a standard algorithm that yields consistent results It is a subject of future research

6 References

Beaulieu, G.; Bollen, M H J.; Malgarotti, S & Ball, R.(2002) Power quality indices and

objectives: Ongoing activates in CIGREWG36-07, Proc 2002 IEEE Power Engineering Soc Summer Meeting, pp 789-794

Bollen, M and Yu Hua Gu, I (2006) Signal Processing of Power Quality Disturbances, Wiley

IEEE Press, New Jersey

CENELEC EN 50160, Voltage characteristics of electricity supplied by public distribution

systems

Chilukuri, M.V & Dash, P.K.(2004) Multiresolution S-transform-based fuzzy recognition

system for power quality events, IEEE Trans Power Delivery, vol 19, no 1,

pp.323-330

Domijan, A.; Hari, A & Lin, T (2004) On the selection of appropriate wavelet filter bank for

power quality monitoring, Int J Power Energy Syst., Vol 24, pp.46-50

Gallo, D., Langella, R & Testa, A (2002) A Self Tuning Harmonics and Interharmonics

Processing Technique, European Transactions on Electrical Power, 12(1), 25-31

Gallo, D., Langella, R & Testa, A (2004) On the Processing of Harmonics and

Interharmonics: UsingHanning Windowin Standard Framework, IEEE Transactions

on Power Delivery, 19(1), 28-34

Gargoom, A.M., Ertugrul, N and Soong, W.L (2005) A comparative study on effective

signal processing tools for power quality monitoring, The 11th European Conference on Power Electronics and Applications (EPE), pp.11-4

Heydt G T & Jewell W T.(1998) Pitfalls of electric power quality indices, IEEE Trans Power

Delivery, vol 13, no 2, pp 570-578

Heydt, G T.(2000) Problematic power quality indices, IEEE Power Eng Soc Winter Meeting,

IEC 61000-4-7, General guide on harmonics and interharmonics measurements and

instrumentation for power supply systems and equipment connected thereto IEC 61000-4-15, Flickermeter, functional design and specifications

IEC 61000-4-30, Power quality measurement methods

Trang 5

Power Quality – Monitoring, Analysis and Enhancement

216

Jaramillo, S.H.; Heydt, G.T & O’Neill-Carrillo, E (2000) ‘Power quality indices for a periodic

voltages and currents’, IEEE Transactions on Power Delivery, April, Vol 15, No 2, pp.784–790

Lin, T & Domijan, A.(2005) On power quality Indices and real time measurement, IEEE

Trans Power Delivery, vol 20, no 4, pp.2552-2562

Mishra, S.; Bhende, C.N & Panigrahi B.K (2008) Detection and classification of power

quality disturbances using S-transform and probabilistic neural network, IEEE Trans Power Delivery, vol 23, no 1, pp 280-287

Morsi, W G & EI-Hawary, M E (2008) A new perspective for the IEEE standard 1459-2000

via stationary wavelet transform in the presence of non-stationary power quality

disturbance, IEEE Trans Power Delivery, vol 23, no 4, pp 2356-2365

Shin, Y J.; Powers, E J.; Grady, M & Arapostathis, A.(2006) Power quality indices for

transient disturbances, IEEE Trans on Power Delivery, vol 21, no 1, pp.253-261

Stockwell, R G.; Mansinha, L & R P Lowe (1996) Localization of the complex spectrum:

The S-transform, IEEE Trans Signal Processing, vol.144, pp 998–1001

Ward, D.J (2001) Power quality and the security of electricity supply, Proceedings of the

IEEE, pp.1830-1836

Voltage sag indices draft 2, working document for IEEE P1564, December 2001

Zhan, Y.; Cheng, H Z & Ding, Y F.(2005) S-transform-based classification of power quality

disturbance signals by support vector machines, Proceedings of the CSEE, vol 25, no

4, pp 51-56

Trang 6

Part 2

Power Quality Enhancement and Reactive Power Compensation and Voltage Sag Mitigation of Disturbances

Trang 8

a result of asymmetrical spatial positioning of the conductors Also the total length of the conductors on the phases of a network may be different This asymmetry of the network element is reflected in the asymmetry of the phase equivalent impedances (self and mutual, longitudinal and transversal) The impedance asymmetry causes then different voltage drop

on the phases and therefore the voltage unbalance in the network nodes As an example of correction method for this asymmetry is the well-known method of transposition of conductors for an overhead electrical line, which allows reducing the voltage unbalance under the admissible level, of course, with the condition of a balanced load transfer on the phases But the main reason of the voltage unbalance is the loads supply, many of which are unbalanced, single-phase - connected between two phases or between one phase and neutral Many unbalanced loads, having small power values (a few tens of watts up to 5-10 kW), are connected to low voltage networks But the most important unbalance is produced

by high power single-phase industrial loads, with the order MW power unit, that are connected to high or medium voltage electrical networks, such as welding equipment, induction furnaces, electric rail traction etc Current and voltage unbalances caused by these loads are most often accompanied by other forms of disturbance: harmonics, voltage sags, voltage fluctuations etc (Czarnecki, 1995)

Current unbalance, which can be associated with negative and zero sequence components flow, lead to increased longitudinal losses of active power and energy in electrical networks, and therefore lower efficiency

Voltage unbalance causes first negative effects on the rotating electrical machines It is associated with increased heating additional losses in the windings, whose size depends on amount of negative sequence voltage component It also produces parasitic couples, which

is manifested by harmful vibrations Both effects can reduce the useful life of electrical machines and therefore significant material damage

Transformers, capacitor banks, some protection systems (e.g distance protection), phase converters (three-phase rectifiers, AC-DC converters) etc are also affected by a three-phase unbalanced system supply voltages

Trang 9

three-Power Quality – Monitoring, Analysis and Enhancement

220

Regarding limiting voltage unbalances, as they primarily due to unbalanced loads, the main methods and means used are aimed at preventing respectively limiting the load unbalances From the measures intended to prevent load unbalances, are those who realize a natural balance It may mention here two main methods:

• balanced repartition of single-phase loads between the phases of the three-phase network This is particularly the case of single-phase loads supplied at low voltage;

• connecting unbalanced loads to a higher voltage level, which generally corresponds to the solution of short-circuit power level increasing at their terminals Is the case of industrial loads, high power (several MVA or tens of MVA) to which power is supplied

by its own transformer, other than those of other loads supplied at the same node Under these conditions the voltage unbalance factor will decrease proportionally with increasing the short-circuit power level

From the category of measures to limit unbalanced conditions are:

• balancing circuits with single-phase transformers (Scott and V circuit) (UIE, 1998);

• balancing circuits through reactive power compensation (Steinmetz circuit), single and three phase, which may be applied in the form of dynamic compensators type SVC (Static Var Compensator) (Gyugyi et al., 1980; Gueth et al., 1987; San et al., 1993; Czarnecki et al., 1994; Mayordomo et al., 2002; Grünbaum et al., 2003; Said et al., 2009)

• high performance power systems controllers - based on self-commutated converters technology (e.g type STATCOM - Static Compensator) (Dixon, 2005)

This chapter is basically a theoretical development of the mathematical model associated to the circuit proposed by Charles Proteus Steinmetz, which is founded now in major industrial applications

2 Load balancing mechanism in the Steinmetz circuit

As is known, Steinmetz showed that the voltage unbalance caused by unbalanced currents produced in a three-phase network by connecting a resistive load (with the equivalent conductance G) between two phases, can be eliminated by installing two reactive loads, an inductance (a coil, having equivalent susceptanceB L=G/ 3) and a capacitance (a capacitor with equivalent susceptance B C = −G/ 3) The ensemble of the three receivers, forming a delta connection (Δ), can be equalized to a perfectly balanced three-phase loads, in star connection (Y), having on each branch an equivalent admittance purely resistive (conductance) with the value G (Fig 1)

Fig 1 Steinmetz montage and its equivalence with a load balanced, purely resistive

Trang 10

Active Load Balancing in a Three-Phase Network by Reactive Power Compensation 221

To explain how to achieve balancing by reactive power compensation of a three-phase network supplying a resistive load, it will consider successively the three receivers, supplied individually For each receiver will determine the phase currents, which are then decomposed by reference to the corresponding phase to neutral voltages, to find active and reactive components of currents, which are used then to determine the active and reactive powers flow on the phases of the network It is assumed that the phase-to-neutral voltages and phase-to-phase voltages at source forms perfectly symmetrical three-phase sets Also conductor’s impedances are neglected

Therefore, for the case of supplying the resistive load having equivalent conductance G between R and S phases (Fig 2.), a current in phase with the applied voltage is formed on the R phase conductor:

a)

b) Fig 2 Resistive load supplied between R and S phases

Trang 11

Power Quality – Monitoring, Analysis and Enhancement

222

positive direction It is noted that the current phasor on the phase R, I R R( )=I RS, is leading the corresponding phase-to-neutral voltage phasor, U R, with an phase-shift equal to π/6rad, which means that the reactive component has capacitive character:

calculation with the above, active and reactive powers flow on the S phase are obtained:

On this ensemble, result:

The current formed on the S phase conductor is leading the voltage with a phase-shift equal

to /2π rad (the complex plane associated to the phase-to-phase voltageU ST):

Trang 12

Active Load Balancing in a Three-Phase Network by Reactive Power Compensation 223

It is noted that the capacitive load absorbs the same reactive power on the two phases at

which it is connected It occurs also on the active powers flow, absorbs active power on

phase T, but returns it to the source on the phase S On all three phases of the network,

The same method applies now to the case of inductive load, having equivalent susceptance

/ 3

L

The current formed on the T phase conductor is lagging the supplying voltage with an

phase-shift equal to /2π rad:

Ngày đăng: 19/06/2014, 11:20

TỪ KHÓA LIÊN QUAN

🧩 Sản phẩm bạn có thể quan tâm