1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 60332 2 1 2004 (2005)

13 0 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Tests on electric and optical fibre cables under fire conditions — Part 2-1: Test for vertical flame propagation for a single small insulated wire or cable
Trường học Not specified
Chuyên ngành Electrical and Optical Fibre Cables, Fire Safety Tests
Thể loại Standard
Năm xuất bản 2004
Thành phố Not specified
Định dạng
Số trang 13
Dung lượng 317,2 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

BS EN 60332 2 1 2004 pdf Collated By Infoeach com BRITISH STANDARD BS EN 60332 2 1 2004 Tests on electric and optical fibre cables under fire conditions — Part 2 1 Test for vertical flame propagation[.]

Trang 1

BRITISH STANDARD BS EN

60332-2-1:2004

Tests on electric and

optical fibre cables

under fire conditions —

Part 2-1: Test for vertical flame

propagation for a single small insulated

wire or cable — Apparatus

The European Standard EN 60332-2-1:2004 has the status of a

British Standard

ICS 13.220.40; 29.020; 29.060.20

12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:

Trang 2

BS EN 60332-2-1:2004

This British Standard was

published under the authority

of the Standards Policy and

Strategy Committee on

18 January 2005

© BSI 18 January 2005

ISBN 0 580 45372 3

National foreword

This British Standard is the official English language version of

EN 60332-2-1:2004 It is identical with IEC 60332-2-1:2004 BS EN 60332-2-1

is technically equivalent to Ignition source 2 (Diffusion flame) of

BS EN 50265-1 Together with BS EN 60332-1-1:2004 it supersedes

BS EN 50265-1:1999 which is withdrawn

The UK participation in its preparation was entrusted by Technical Committee GEL/20, Electric cables, to Subcommittee GEL/20/18, Fire testing, which has the responsibility to:

A list of organizations represented on this subcommittee can be obtained on request to its secretary

Cross-references

The British Standards which implement international or European

publications referred to in this document may be found in the BSI Catalogue

under the section entitled “International Standards Correspondence Index”, or

by using the “Search” facility of the BSI Electronic Catalogue or of British

Standards Online

This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application

Compliance with a British Standard does not of itself confer immunity from legal obligations.

— aid enquirers to understand the text;

— present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the

UK interests informed;

— monitor related international and European developments and promulgate them in the UK

Summary of pages

This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 10, an inside back cover and a back cover

The BSI copyright notice displayed in this document indicates when the document was last issued

Amendments issued since publication

Amd No Date Comments

Trang 3

EUROPEAN STANDARD EN 60332-2-1

NORME EUROPÉENNE

CENELEC

European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members

Ref No EN 60332-2-1:2004 E

ICS 13.220.40; 29.020; 29.060.20 Partially supersedes EN 50265-1:1998

English version

Tests on electric and optical fibre cables under fire conditions

Part 2-1: Test for vertical flame propagation for a single small insulated wire or cable -

Apparatus

(IEC 60332-2-1:2004)

Essais des câbles électriques

et à fibres optiques soumis au feu

Partie 2-1: Essai de propagation verticale

de la flamme sur conducteur

ou câble isolé de petite section -

Appareillage d'essai

(CEI 60332-2-1:2004)

Prüfungen an Kabeln, isolierten Leitungen und Glasfaserkabeln im Brandfall

Teil 2-1: Prüfung der vertikalen Flammenausbreitung an einer kleinen Ader, einer kleinen isolierten Leitung

oder einem kleinen Kabel - Prüfgerät

(IEC 60332-2-1:2004)

This European Standard was approved by CENELEC on 2004-09-01 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom

Trang 4

EN 63302-2-1:0240 - - 2

Foreword

The text of document 20/699/FDIS, future edition 1 of IEC 60332-2-1, prepared by IEC TC 20, Electric cables, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as

EN 60332-2-1 on 2004-09-01

This European Standard, together with EN 60332-1-1, supersedes EN 50265-1:1998

The following dates were fixed:

– latest date by which the EN has to be implemented

at national level by publication of an identical

national standard or by endorsement (dop) 2005-06-01

– latest date by which the national standards conflicting

with the EN have to be withdrawn (dow) 2007-09-01

Annex ZA has been added by CENELEC

Endorsement notice

The text of the International Standard IEC 60332-2-1:2004 was approved by CENELEC as a European Standard without any modification

In the official version, for Bibliography, the following note has to be added for the standard indicated:

IEC 60332-2-2 NOTE Harmonized as EN 60332-2-2:2004 (not modified).

Page 2

EN 60332−2−1:2004

Trang 5

-23306-21  4002:CEI – 3 –

CONTENTS

1 Scope 4

2 Normative references 4

3 Terms and definitions 4

4 Test apparatus 4

4.1 Components 4

4.2 Metallic screen 5

4.3 Ignition source 5

4.4 Chamber 5

Annex ZA (normative) Normative references to international publications with their corresponding European publications 9

Bibliography 10

Page 3

EN 60332−2−1:2004

Trang 6

-23306-21  4002:CEI – 4 –

TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES

UNDER FIRE CONDITIONS –

Part 2-1: Test for vertical flame propagation for a single small insulated wire or cable –

Apparatus

1 Scope

This part of IEC 60332 specifies the test apparatus for testing the resistance to vertical flame propagation for a single small vertical electrical insulated conductor or cable, or optical fibre cable, under fire conditions

The procedure, together with an informative annex of recommended requirements for performance, is given in IEC 60332-2-2

2 Normative references

The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies

IEC 60695-4, Fire hazard testing – Part 4: Terminology concerning fire tests

IEC Guide 104, The preparation of safety publications and the use of basic safety publications and group safety publications

3 Terms and definitions

For the purposes of this document, the following definition applies The definition is taken from IEC 60695-4

3.1

ignition source

source of energy that initiates combustion

[IEC 60695-4:1993, definition 2.76]

4 Test apparatus

4.1 Components

The test apparatus shall comprise the following:

a) a metallic screen (4.2);

b) an ignition source (4.3);

c) a suitable chamber (4.4)

Page 4

EN 60332−2−1:2004

Trang 7

-23306-21  4002:CEI – 5 –

4.2 Metallic screen

A metallic screen (1 200 ± 25) mm high, (300 ± 25) mm wide and (450 ± 25) mm deep with

open front and closed top and bottom, (see Figure 1), shall be used

4.3 Ignition source

The ignition source shall be a propane burner complying with Figure 2

NOTE In order to obtain the 8 mm bore, as shown in Figure 2, it is permitted to fit an adaptor to burners not

otherwise complying

The burner shall be fed with technical grade propane of greater than 95 % purity, and shall

produce a luminous flame when in a vertical position with the air inlet closed The gas flow

shall be adjusted so that the total length of the luminous flame is (125 ± 25) mm (see Figure 3)

4.4 Chamber

The metallic screen and ignition source shall be contained within a suitable chamber,

substantially free from draughts during the test duration, but with facilities for disposing of

noxious gases resulting from burning The chamber shall be maintained at a temperature of

(23 ± 10) °C

NOTE 1 If the requirement for the draught-free closed area is met by the use of a standard fume cupboard, it must

be capable of independent operator control of the extractor fan such as to permit operation with the extractor "OFF"

Some fume cupboards may not be supplied with this facility

NOTE 2 If a fume cupboard is used as the draught-free test area, the following safe operating practice is

recommended:

a) turn off extractor fan, seal the outlet;

b) pull down front door of fume cupboard to leave a gap sufficient to manipulate burner into position;

c) ensure operator is protected;

d) do not move the door of the fume cupboard during the test;

e) at the end of the test evacuate the fume cupboard fully before opening the door

Page 5

EN 60332−2−1:2004

Trang 8

-23306-21  4002:CEI – 6 –

Dimensions in millimetres

1

300 ± 25

450 ± 25

Key

1 front open space (all other sides closed)

Figure 1 – Test apparatus – Metallic screen

IEC 999/04

Page 6

EN 60332−2−1:2004

Trang 9

-23306-21  4002:CEI – 7 –

Dimensions in millimetres

∅11

∅9,5

∅8

∅4

∅0,4

Tolerances ±5 %

Figure 2 – Details and dimensions of propane burner (diffusion flame)

IEC 1002/04

Page 7

EN 60332−2−1:2004

Trang 10

-23306-21  4002:CEI – 8 –

Dimensions in millimetres

Figure 3 – Luminous flame

IEC 1003/04

Page 8

EN 60332−2−1:2004

Trang 11

EN 63302-2-1:0240 - - 3

Annex ZA

(normative)

Normative references to international publications with their corresponding European publications

The following referenced documents are indispensable for the application of this document For dated

references, only the edition cited applies For undated references, the latest edition of the referenced

document (including any amendments) applies

NOTE Where an international publication has been modified by common modifications, indicated by (mod), the relevant

EN/HD applies

Publication Year Title EN/HD Year

IEC 60695-4 - 1) Fire hazard testing

Part 4: Terminology concerning fire tests

EN 60695-4 1995 2)

IEC Guide 104 - 1) The preparation of safety publications

and the use of basic safety publications and group safety publications

- -

1)

Undated reference

2)

Valid edition at date of issue

Page 9

EN 60332−2−1:2004

Trang 12

-23306-21  4002:CEI – 9 –

Bibliography

IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions – Part 2-2: Test for vertical flame propagation for a single small insulated wire or cable – Procedure for diffusion flame

_

Page 10

EN 60332−2−1:2004

Trang 13

BS EN

60332-2-1:2004

BSI

389 Chiswick High Road

London

W4 4AL

BSI — British Standards Institution

BSI is the independent national body responsible for preparing British Standards It presents the UK view on standards in Europe and at the international level It is incorporated by Royal Charter

Revisions

British Standards are updated by amendment or revision Users of British Standards should make sure that they possess the latest amendments or editions

It is the constant aim of BSI to improve the quality of our products and services

We would be grateful if anyone finding an inaccuracy or ambiguity while using this British Standard would inform the Secretary of the technical committee responsible, the identity of which can be found on the inside front cover

Tel: +44 (0)20 8996 9000 Fax: +44 (0)20 8996 7400

BSI offers members an individual updating service called PLUS which ensures that subscribers automatically receive the latest editions of standards

Buying standards

Orders for all BSI, international and foreign standards publications should be addressed to Customer Services Tel: +44 (0)20 8996 9001

Fax: +44 (0)20 8996 7001 Email: orders@bsi-global.com Standards are also available from the BSI website at http://www.bsi-global.com

In response to orders for international standards, it is BSI policy to supply the BSI implementation of those that have been published as British Standards, unless otherwise requested

Information on standards

BSI provides a wide range of information on national, European and international standards through its Library and its Technical Help to Exporters Service Various BSI electronic information services are also available which give details on all its products and services Contact the Information Centre

Tel: +44 (0)20 8996 7111 Fax: +44 (0)20 8996 7048 Email: info@bsi-global.com Subscribing members of BSI are kept up to date with standards developments and receive substantial discounts on the purchase price of standards For details

of these and other benefits contact Membership Administration

Tel: +44 (0)20 8996 7002 Fax: +44 (0)20 8996 7001

Email: membership@bsi-global.com

Information regarding online access to British Standards via British Standards Online can be found at http://www.bsi-global.com/bsonline

Further information about BSI is available on the BSI website at http://www.bsi-global.com

Copyright

Copyright subsists in all BSI publications BSI also holds the copyright, in the

UK, of the publications of the international standardization bodies Except as permitted under the Copyright, Designs and Patents Act 1988 no extract may be reproduced, stored in a retrieval system or transmitted in any form or by any means – electronic, photocopying, recording or otherwise – without prior written permission from BSI

This does not preclude the free use, in the course of implementing the standard,

of necessary details such as symbols, and size, type or grade designations If these details are to be used for any other purpose than implementation then the prior written permission of BSI must be obtained

Details and advice can be obtained from the Copyright & Licensing Manager Tel: +44 (0)20 8996 7070 Fax: +44 (0)20 8996 7553

Email: copyright@bsi-global.com

Ngày đăng: 14/04/2023, 14:33

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN