1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 60076 11 2004 (2006)

42 1 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Power Transformers — Part 11: Dry-type Transformers
Trường học British Standards Institution
Chuyên ngành Power Transformers
Thể loại British Standard
Năm xuất bản 2006
Thành phố London
Định dạng
Số trang 42
Dung lượng 465,95 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 4.1 General (9)
  • 4.2 Normal service conditions (9)
  • 4.3 Electromagnetic compatibility (EMC) (10)
  • 4.4 Provision for unusual service conditions (10)
  • 4.5 Transport and storage conditions (11)
  • 8.1 General (12)
  • 8.2 Rated power (12)
  • 8.3 Preferred values of rated power (12)
  • 8.4 Operation at higher than rated voltage (12)
  • 8.5 Operation with fan cooling (12)
  • 8.6 Operation in an enclosure (12)
  • 9.1 Rating plate fitted to the transformer (13)
  • 9.2 Rating plate fitted to the transformer enclosure (13)
  • 10.1 Identification symbols (13)
  • 10.2 Arrangement of symbols (14)
  • 11.1 Normal temperature-rise limits (14)
  • 11.2 Reduced temperature rises for transformers designed for high cooling air (15)
  • 11.3 High altitude temperature rise correction (15)
  • 12.1 General (15)
  • 12.2 Transformers for use at high altitudes (17)
  • 13.1 Climatic classes (17)
  • 13.2 Environmental classes (17)
  • 13.3 Fire behaviour classes (17)
  • 13.4 Test criteria for climatic, environmental and fire behaviour classes (18)
  • 22.1 General (20)
  • 22.2 Basic measuring circuit (typical only) (20)
  • 22.3 Calibration of the measuring circuit (20)
  • 22.4 Voltage application (21)
  • 22.5 Partial discharge acceptance levels (22)
  • 23.1 General (23)
  • 23.2 Methods of loading (23)
  • 23.3 Winding temperature-rise correction for reduced current (26)
  • 23.4 Determination of steady state conditions (26)
  • 26.1 General (27)
  • 26.2 Validity of the test (27)
  • 26.3 Testing procedure (27)
  • 27.1 Thermal shock test (special test) (28)
  • 27.2 Validity of the test (28)
  • 27.3 Thermal shock test for C1 class transformers (29)
  • 27.4 Thermal shock test for C2 class transformers (30)
  • 28.1 General (30)
  • 28.2 Checking of corrosive and harmful gases emission (30)
  • 28.3 Fire behaviour test for F1 class transformer (31)
  • 28.4 Quantities to be measured and measuring devices (33)
  • 28.5 Calibration of the test chamber without test object (33)
  • 28.6 Test method (33)
  • 28.7 Test report (34)
  • 28.8 Criteria for evaluating the test results (34)

Nội dung

untitled Copyright British Standard Provided by IHS under lice No reproduction or network ` , , ` ` ` , , , , ` ` ` ` ` ` , , ` , , ` , ` , , ` BRITISH STANDARD BS EN 60076 11 2004 Power transformers[.]

Trang 1

Power transformers —

Part 11: Dry-type transformers

The European Standard EN 60076-11:2004 has the status of a British Standard

ICS 29.180

12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:

Copyright British Standards Institution

Trang 2

`,,```,,,,````-`-`,,`,,`,`,,` -BS EN 60076-11:2004

This British Standard was

published under the authority

of the Standards Policy and

This British Standard is the official English language version of

EN 60076-11:2004 It is identical with IEC 60076-11:2004 It supersedes

BS EN 60726:2003 which will be withdrawn on 1 July 2007

The UK participation in its preparation was entrusted to Technical Committee PEL/14, Power transformers, which has the responsibility to:

A list of organizations represented on this committee can be obtained on request to its secretary

Cross-references

The British Standards which implement international or European

publications referred to in this document may be found in the BSI Catalogue

under the section entitled “International Standards Correspondence Index”, or

by using the “Search” facility of the BSI Electronic Catalogue or of British

— aid enquirers to understand the text;

— present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep UK interests informed;

— monitor related international and European developments and promulgate them in the UK

Amendments issued since publication

Copyright British Standards Institution

Trang 3

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members

Ref No EN 60076-11:2004 E

English version

Power transformers Part 11: Dry-type transformers

This European Standard was approved by CENELEC on 2004-07-01 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom

Copyright British Standards Institution

Trang 4

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 2 –

Foreword

The text of document 14/476/FDIS, future edition 1 of IEC 60076-11, prepared by IEC TC 14, Power

transformers, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as

EN 60076-11 on 2004-07-01

This European Standard supersedes EN 60726:2003

The following dates were fixed:

– latest date by which the EN has to be implemented

at national level by publication of an identical national standard or by endorsement (dop) 2005-04-01 – latest date by which the national standards conflicting

with the EN have to be withdrawn (dow) 2007-07-01 Annex ZA has been added by CENELEC

Endorsement notice

The text of the International Standard IEC 60076-11:2004 was approved by CENELEC as a European

Standard without any modification

Copyright British Standards Institution

Trang 5

`,,```,,,,````-`-`,,`,,`,`,,` -CONTENTS

1 Scope 6

2 Normative references 6

3 Terms and definitions 7

4 Service conditions 7

4.1 General 7

4.2 Normal service conditions 7

4.3 Electromagnetic compatibility (EMC) 8

4.4 Provision for unusual service conditions 8

4.5 Transport and storage conditions 9

5 Tappings 9

6 Connections 9

7 Ability to withstand short circuit 9

8 Rating 10

8.1 General 10

8.2 Rated power 10

8.3 Preferred values of rated power 10

8.4 Operation at higher than rated voltage 10

8.5 Operation with fan cooling 10

8.6 Operation in an enclosure 10

9 Rating plate 11

9.1 Rating plate fitted to the transformer 11

9.2 Rating plate fitted to the transformer enclosure 11

10 Identification according to cooling method 11

10.1 Identification symbols 11

10.2 Arrangement of symbols 12

11 Temperature-rise limits 12

11.1 Normal temperature-rise limits 12

11.2 Reduced temperature rises for transformers designed for high cooling air temperatures or special air cooling conditions 13

11.3 High altitude temperature rise correction 13

12 Insulation levels 13

12.1 General 13

12.2 Transformers for use at high altitudes 15

13 Climatic, environmental and fire behaviour classes 15

13.1 Climatic classes 15

13.2 Environmental classes 15

13.3 Fire behaviour classes 15

13.4 Test criteria for climatic, environmental and fire behaviour classes 16

14 General requirements for tests 16

15 Measurement of winding resistance (routine test) 16

16 Measurement of voltage ratio and check of phase displacement (routine test) 17

17 Measurement of short-circuit impedance and load loss (routine test) 17

18 Measurement of no-load loss and current (routine test) 17

19 Separate-source AC withstand voltage test (routine test) 17

Copyright British Standards Institution

Trang 6

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 4 –

20 Induced AC withstand voltage test (routine test) 17

21 Lightning impulse test (type test) 18

22 Partial discharge measurement (routine and special test) 18

22.1 General 18

22.2 Basic measuring circuit (typical only) 18

22.3 Calibration of the measuring circuit 18

22.4 Voltage application 19

22.5 Partial discharge acceptance levels 20

23 Temperature-rise test (type test) 21

23.1 General 21

23.2 Methods of loading 21

23.3 Winding temperature-rise correction for reduced current 24

23.4 Determination of steady state conditions 24

24 Measurement of sound level (special test) 24

25 Short-circuit test (special test) 25

26 Environmental test (special test) 25

26.1 General 25

26.2 Validity of the test 25

26.3 Testing procedure 25

27 Climatic test (special test) 26

27.1 Thermal shock test (special test) 26

27.2 Validity of the test 26

27.3 Thermal shock test for C1 class transformers 27

27.4 Thermal shock test for C2 class transformers 28

28 Fire behaviour test (special test) 28

28.1 General 28

28.2 Checking of corrosive and harmful gases emission 28

28.3 Fire behaviour test for F1 class transformer 29

28.4 Quantities to be measured and measuring devices 31

28.5 Calibration of the test chamber without test object 31

28.6 Test method 31

28.7 Test report 32

28.8 Criteria for evaluating the test results 32

29 Tolerances 33

30 Protection against direct contact 33

31 Degrees of protection provided by enclosures 33

32 Earthing terminal 33

33 Information required with enquiry and order 33

Annex A (informative) Installation and safety of dry-type transformers 36

Annex ZA (normative) Normative references to international publications with their corresponding European publications 38

Copyright British Standards Institution

Trang 7

`,,```,,,,````-`-`,,`,,`,`,,` -Figure 1 – Basic measuring circuit for the partial discharge test for a single-phase

transformer 19

Figure 2 – Basic measuring circuit for the partial discharge test for a three-phase transformer 19

Figure 3 – Voltage application for routine partial discharge test 20

Figure 4 – Voltage application for special partial discharge test 20

Figure 5 – Example of back-to- back method – Single phase .23

Figure 6 – Example of back-to-back method – Three-phase 23

Figure 7 – Test chamber 34

Figure 8 – Test chamber details 35

Table 1 – Letter symbols 12

Table 2 – Winding temperature-rise limits 13

Table 3 – Insulation levels based on European practice 14

Table 4 – Insulation levels based on North American practice 14

Table 5 – sequence of tests 16

Table 6 – Dimensions of test chamber (see Figures 7 and 8) 30

Copyright British Standards Institution

Trang 8

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 6 –

POWER TRANSFORMERS – Part 11: Dry-type transformers

1 Scope

This part of IEC 60076 applies to dry-type power transformers (including auto-transformers) having values of highest voltage for equipment up to and including 36 kV and at least one winding operating at greater than 1,1 kV The standard applies to all construction technologies

This standard does not apply to:

– gas-filled dry type transformers where the gas is not air;

– single-phase transformers rated at less than 5 kVA;

– polyphase transformers rated at less than 15 kVA;

– instrument transformers (see IEC 60044 and IEC 60186);

– starting transformers;

– testing transformers;

– traction transformers mounted on rolling stock;

– flameproof and mining transformers;

– welding transformers;

– voltage regulating transformers;

– small power transformers in which safety is a special consideration

Where IEC standards do not exist for the transformers mentioned above or for other special transformers, this standard may be applicable as a whole or in parts

2 Normative references

The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition

of the referenced document (including any amendments) applies

IEC 60050 (all parts), International electrotechnical vocabulary (IEV)

IEC 60071 (all parts), Insulation co-ordination

IEC 60076-1:1993, Power transformers – Part 1: General

Amendment 1 (1999)

IEC 60076-2, Power transformers – Part 2: Temperature rise

IEC 60076-3, Power transformers – Part 3: Insulation levels, dielectric tests and external

clearances in air

Copyright British Standards Institution

Trang 9

`,,```,,,,````-`-`,,`,,`,`,,` -IEC 60076-5, Power transformers – Part 5: Ability to withstand short-circuit

IEC 60076-10, Power transformers – Part 10: Determination of sound levels

IEC 60085, Thermal evaluation and classification of electrical insulation

IEC 60270, High-voltage test techniques – Partial discharge measurements

IEC 60332-3-10, Tests on electric cables under fire conditions – Part 3-10: Test for vertical

flame spread of vertically-mounted bunched wires or cables – Apparatus

IEC 60529, Degrees of protection provided by enclosures (IP Code)

IEC 60905:1987, Loading guide for dry-type power transformers

IEC 61330, High-voltage/low voltage prefabricated substations

3 Terms and definitions

For the purpose of this part of IEC 60076, the following terms and definitions apply

totally enclosed dry-type transformer

transformer in an un-pressurised enclosure cooled by the circulation of the internal air

3.3

enclosed dry-type transformer

transformer in a ventilated enclosure cooled by the circulation of the external air

3.4

non-enclosed dry-type transformer

transformer supplied without a protective enclosure cooled by natural or forced air ventilation

Copyright British Standards Institution

Trang 10

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 8 –

4.2.2 Altitude

A height above sea level not exceeding 1 000 m

4.2.3 Temperature of cooling air

The temperature of cooling air not exceeding:

40 °C at any time;

30 °C monthly average of the hottest month;

20 °C yearly average

and not below:

–25 °C in the case of outdoor transformers;

–5 °C in the case of indoor transformers

where the monthly and yearly averages are as defined in 3.12 of IEC 60076-1

4.2.4 Wave-shape of supply voltage

A supply voltage of which the waveshape is approximately sinusoidal

NOTE This requirement is normally not critical in public supply systems but may have to be considered in installations with considerable converter loading In such cases, there is a conventional rule that the deformation shall neither exceed 5 % total harmonic content nor 1 % even harmonic content, see IEC 61000-2-4 Also note the importance of current harmonics for load loss and temperature rise, see IEC 61378-1

4.2.5 Symmetry of polyphase supply voltages

For three-phase transformers, a set of three-phase supply voltages which are approximately symmetrical

4.2.6 Humidity

The relative humidity of the surrounding air shall be less than 93 % No drops of water shall

be present on the surface of the coils

4.3 Electromagnetic compatibility (EMC)

Transformers shall be considered as passive elements in respect to emission and immunity to electromagnetic disturbances

4.4 Provision for unusual service conditions

The purchaser shall identify in his enquiry any service conditions not covered by the normal service conditions in 4.2 Examples of such conditions are:

– high or low ambient temperature outside the limits prescribed in 4.2.3;

– restricted ventilation;

– altitude in excess of the limit prescribed in 4.2.2;

– damaging fumes and vapours;

Trang 11

`,,```,,,,````-`-`,,`,,`,`,,` -– excessive and abrasive dust;

– high harmonic content of the load current;

– distortion of the supply voltage waveform;

– fast transient overvoltages over the limits prescribed in 12.1 and Clause 21;

– associated power factor correction and method of capacitor switching to limit inrush current;

Supplementary requirements, within defined limits, for the rating and testing of transformers designed for other than normal service conditions listed in 4.2, such as high temperature of

cooling air or altitude above 1 000 m are given in 11.2 and 11.3

4.5 Transport and storage conditions

All transformers shall be suitable for transportation and storage at ambient temperatures down to –25 °C

The supplier shall be informed of anticipated high levels of shock, vibration and inclination during transportation to site

5 Tappings

The requirements in IEC 60076-1 Clause 5 applies The preferred tapping range is either:

± 5 % in steps of 2,5 % (5 tap positions);

be capable of carrying full phase rated current

7 Ability to withstand short circuit

Transformers shall fulfil the requirements in IEC 60076-5 If the purchaser requires a test to demonstrate this fulfilment, this shall be stated in the contract

Copyright British Standards Institution

Trang 12

8.2 Rated power

The transformer shall have an assigned rated power for each winding which shall be marked

on the rating plate The transformer shall be fully rated when supplied in an enclosure The rated power refers to continuous loading This is a reference value for guarantees and tests concerning load losses, temperature rises and short-circuit impedance

NOTE A two-winding transformer has only one value of rated power, identical for both windings When the transformer has rated voltage applied to the primary winding, and rated current flows through the terminals of that winding, the transformer receives the relevant rated power for both windings

The rated power corresponds to continuous duty; nevertheless, dry-type transformers complying with this standard can be overloaded and guidance on overloads is given in IEC 60905

8.3 Preferred values of rated power

The preferred values shall be in accordance with 4.3 of IEC 60076-1 starting from 50 kVA

8.4 Operation at higher than rated voltage

Within the prescribed value of Um, a transformer shall be capable of service without damage under conditions of overfluxing where the ratio of voltage over frequency exceeds the corresponding ratio at rated voltage and rated frequency by no more than 5 %

NOTE This requirement is not meant to be systematically utilised in normal service The consequential increase in iron losses under these conditions will have adverse effects and such operation should be of limited duration This condition should be reserved for relatively rare cases of service under limited periods of time, for example emergency service or extreme peak loading

8.5 Operation with fan cooling

When additional cooling by means of fans is provided, the nominal power rating with and without fans shall be subject to agreement between purchaser and supplier

The rating plate shall indicate both the power rating without fans and the maximum power rating with fan cooling

Trang 13

9 Rating plate

9.1 Rating plate fitted to the transformer

Each transformer shall be provided with a rating plate of weatherproof material, fitted in a visible position, showing the items indicated below The entries on the plate shall be indelibly marked (that is, by etching, engraving, stamping or by a photo-chemical process)

g) number of phases;

h) rated power for each kind of cooling;

i) rated frequency;

j) rated voltages, including tapping voltages, if any;

k) rated currents for each kind of cooling;

t) fire behaviour class

The rated withstand voltages for all windings shall appear on the rating plate The principles

of the standard notation are illustrated in Clause 5 of IEC 60076-3

9.2 Rating plate fitted to the transformer enclosure

Each transformer enclosure shall be provided with a rating plate of weatherproof material, fitted in a visible position, showing the items indicated in 9.1 The entries on the plate shall be indelibly marked (that is, by etching, engraving, stamping or by a photo-chemical process)

10 Identification according to cooling method

Trang 14

– A transformer designed for natural air ventilation is designated AN

– A transformer designed for natural air ventilation up to specified rating and with forced cooling to a higher rating is designated AN/AF

11 Temperature-rise limits

11.1 Normal temperature-rise limits

The temperature rise of each winding of the transformer, designed for operation at normal service conditions, shall not exceed the corresponding limit specified in Table 2 when tested

in accordance with Clause 23

The maximum temperature occurring in any part of the winding insulation system is called the hot-spot temperature The hot spot temperature shall not exceed the rated value of the hot-spot winding temperature specified in Table 1 of IEC 60905 This temperature could be measured, however an approximate value for practical purposes can be calculated by using

equation 1 in 4.2.4 of IEC 60905 with the values for Z and q given in 7.2 of IEC 60905

Components used as insulating material may be used separately or in combination providing that their temperature does not exceed the values given for the appropriate insulation system temperature in accordance with the requirements as prescribed in the left hand column of Table 2

The temperature of the core, metallic parts and adjacent materials shall not reach a value that will cause damage to any part of the transformer

Copyright British Standards Institution

Trang 15

`,,```,,,,````-`-`,,`,,`,`,,` -Table 2 – Winding temperature-rise limits

Insulation system temperature

(see Note 1)

°C

Average winding temperature rise limits at rated current (see Note 2)

NOTE 1 Letters refer to the temperature classifications given in IEC 60085

NOTE 2 Temperature rise measured in accordance with Clause 23

11.2 Reduced temperature rises for transformers designed for high cooling air

temperatures or special air cooling conditions

When the transformer is designed for service where the temperature of the cooling air exceeds one of the maximum values specified in 4.2.3, the temperature rise limits shall be reduced by the same amount as the excess The values shall be rounded to the nearest whole number of K

Any site conditions that may either impose restrictions on the cooling air or produce high ambient air temperatures should be stated by the purchaser

11.3 High altitude temperature rise correction

Unless otherwise agreed upon between the supplier and the purchaser, for transformers designed for operation at an altitude greater than 1 000 m but tested at normal altitudes, the limits of temperature rise given in Table 2 shall be reduced by the following amounts for each

500 m by which the intended working altitude exceeds 1 000 m:

Trang 16

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 14 –

Table 3 – Insulation levels based on European practice

Rated lightning impulse withstand voltage

≤ 1,1 3,6 7,2 12,0 17,5 24,0 36,0

Table 4 – Insulation levels based on North American practice

Dielectric insulation levels for dry type transformers used on system with BILs 200 kV and below

Basic Lightning Impulse Insulation Levels (BILs)

in common use (peak value 1,2 μs) Max LL

kV

Low frequency voltage insulation level

Impulse chopped wave:

minimum time to flash over ( μ s) 1 1 1 1,3 2 2 1,8 2 2,3 2,7

1 = Optional higher levels where exposure to overvoltage occurs and higher protective margins are required

2 = Lower levels where surge arrester protective devices can be applied with lower spark-over levels

Copyright British Standards Institution

Trang 17

`,,```,,,,````-`-`,,`,,`,`,,` -12.2 Transformers for use at high altitudes

When the transformers are specified for operation at altitudes between 1 000 m and 3 000 m

above sea-level, but tested at normal altitude, the rated short duration separate source AC

withstand voltage shall be increased by 1 % for each 100 m above 1 000 m Above 3 000 m,

the insulation level shall be defined by agreement between supplier and purchaser

13 Climatic, environmental and fire behaviour classes

13.1 Climatic classes

Two climatic classes are defined:

Class C1: The transformer is suitable for operation at ambient temperature not below –5°C

but may be exposed during transport and storage to ambient temperatures down

Environmental conditions for dry-type transformers are identified in terms of humidity,

condensation, pollution and ambient temperature

NOTE These are important not only during service but also during storage before installation

With regard to humidity, condensation and pollution, three different environmental classes are

defined:

Class E0: No condensation occurs on the transformers and pollution is negligible This is

commonly achieved in a clean, dry indoor installation

Class E1: Occasional condensation can occur on the transformer (for example, when the

transformer is de-energised) Limited pollution is possible

Class E2: Frequent condensation or heavy pollution or combination of both

Special tests according to the procedure of Clause 26 shall confirm the conformity of E1 or E2

class transformers

13.3 Fire behaviour classes

Two fire behaviour classes are defined:

Class F0: There is no special fire risk to consider Except for the characteristics inherent in

the design of the transformer, no special measures are taken to limit flammability

Nevertheless, the emission of toxic substances and opaque smoke shall be

minimized

Class F1: Transformers subject to a fire hazard Restricted flammability is required The

emission of toxic substances and opaque smokes shall be minimised

Copyright British Standards Institution

Trang 18

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 16 –

Special tests according to the procedure of Clause 28 shall confirm the conformity of class F1

transformers

NOTE Measurements made in conformity with Clause 28 tend to result in a standard deviation ≤ 10 K

13.4 Test criteria for climatic, environmental and fire behaviour classes

When a transformer is declared as suitable for a combination of climatic, environmental and

fire behaviour classes, those tests which prove compliance with said classes, are to be

carried out on the same transformer in the sequence given in Table 5

The tests specified in Clauses 26, 27 and 28 shall be carried out as specified on one

transformer being representative of the design type

Table 5 – Sequence of tests

1 Thermal shock at –5 °C 27.3 Yes No - - - - -

2 Thermal shock at –25 °C 27.4 No Yes - - - - -

3 Condensation test 26.3.1 - - No Yes No - -

4 Condensation and

humidity penetration test

5 Fire behaviour test 28.3 - - - No Yes

14 General requirements for tests

New transformers shall be subjected to tests as specified in Clauses 15 to 23 Transformers

which have been in service may be tested in accordance with this specification but dielectric

test levels should be reduced to 80 %, however, the guarantee levels of the transformer when

new do not apply

Tests shall be made by the manufacturer or at an approved laboratory, unless otherwise

agreed between the supplier and the purchaser at the tender stage

Dielectric tests in accordance with Clauses 19, 20 and 21 shall be made with the transformer

at approximately the temperature of the test house

Tests shall be performed on a completely assembled transformer including relevant

accessories supplied

Tapped windings shall be connected on their principal tapping unless the supplier and the

purchaser agree otherwise

The test basis for all characteristics other than insulation is the rated condition, unless the

test Clause states otherwise

15 Measurement of winding resistance (routine test)

The test described in 10.2 of IEC 60076-1 applies

Copyright British Standards Institution

Trang 19

`,,```,,,,````-`-`,,`,,`,`,,` -16 Measurement of voltage ratio and check of phase displacement (routine test)

The test described in 10.3 of IEC 60076-1 applies

17 Measurement of short-circuit impedance and load loss (routine test)

The test described in 10.4 of IEC 60076-1 applies

The reference temperature of the short-circuit impedance and load loss shall be the permitted average winding temperature rise as given in column 2 of Table 2 plus 20 °C

When a transformer has windings of different insulation system temperatures, the reference temperature relating to the winding having the higher insulation system temperature shall be used

18 Measurement of no-load loss and current (routine test)

The test described in 10.5 of IEC 60076-1 applies

19 Separate-source AC withstand voltage test (routine test)

The test described in Clause 11 of IEC 60076-3 applies

The test voltage shall be in accordance with Table 3 or Table 4 for the specified insulation level of the transformer,

The full test voltage shall be applied for 60 s between the winding under test and all the remaining windings, core, frame and transformer enclosure, connected to earth

20 Induced AC withstand voltage test (routine test)

The test described in 12.2.1 of IEC 60076-3 applies

The test voltage shall be twice the rated voltage

The duration of the test at full voltage shall be 60 s for any test frequency up to and including twice the rated frequency When the test frequency exceeds twice the rated frequency, the duration of the test shall be:

sfrequencytest

frequencyrated

120× , but not less than 15 s

Copyright British Standards Institution

Trang 20

`,,```,,,,````-`-`,,`,,`,`,,` -EN 60076-11:2004

– 18 –

21 Lightning impulse test (type test)

The test described in Clause 13 of IEC 60076-3 applies

The test voltage shall be in accordance with Table 3 or Table 4 for the specified insulation level of the transformer

The test impulse wave shape shall be 1,2 μs ± 30 %/50 μs ± 20 %

The test voltage shall be of negative polarity The test sequence per line terminal shall be one calibration impulse at a voltage between 50 % and 75 % of the full voltage followed by three impulses at full voltage

NOTE In dry-type transformers, the lightning impulse test can give rise to capacitive partial discharges in the air which do not endanger the insulation These partial discharges lead to changes in the current waveform, whilst the voltage waveform varies only slightly or not at all In this case, the separate source voltage withstand test and induced overvoltage withstand test should be repeated Taking into account the above statement, slight deviations

in current wave-form are not reasons for rejection

22 Partial discharge measurement (routine and special test)

22.2 Basic measuring circuit (typical only)

A basic measuring circuit for the partial discharge test is shown in Figures 1 and 2

In the Figures, a partial discharge-free high voltage capacitor, C of suitable voltage rating

(having a capacitance value large in comparison with the calibration generator capacitance,

C0) in series with a detection impedance, Zm, is connected to each of the high-voltage winding terminals

22.3 Calibration of the measuring circuit

Attenuation of the discharge pulses occurs both within the windings and in the measuring circuit Calibration is carried out as described in Annex A of IEC 60076-3, by injecting simulated discharge pulses from a standard discharge calibrator at the transformer high voltage winding terminals It is convenient if the calibration generator has a repetition frequency of the order of one impulse per half cycle of the power frequency used for the test

on the transformer

Copyright British Standards Institution

Trang 21

Figure 1 – Basic measuring circuit for the partial discharge test

for a single-phase transformer

Figure 2 – Basic measuring circuit for the partial discharge test

for a three-phase transformer 22.4 Voltage application

The partial discharge measurement shall be carried out after all dielectric tests are completed The low-voltage winding shall be supplied from a three-phase or single-phase source, depending on whether the transformer itself is three-phase or single-phase The voltage shall be as nearly as possible of sine-wave form and of a frequency suitably increased above the rated frequency to avoid excessive excitation current during the test The procedure shall be as in 22.4.1 or 22.4.2

22.4.1 Three-phase transformers

22.4.1.1 Routine test

The following test shall be performed on all dry type transformers

Copyright British Standards Institution

Ngày đăng: 14/04/2023, 14:32

TỪ KHÓA LIÊN QUAN

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN