raising standards worldwide™NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW BSI Standards Publication Electric cables — Low voltage energy cables of rated voltages
Trang 1raising standards worldwide™
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
BSI Standards Publication
Electric cables — Low voltage energy cables of rated voltages
up to and including 450/750 V
Part 2-81: Cables for general applications
— Cables with crosslinked elastomeric covering for arc welding
Trang 2National foreword
This British Standard is the UK implementation of EN 50525-2-81:2011 It partially supersedes BS638-4:1996
The UK participation in its preparation was entrusted to Technical Committee GEL/20/17, Electric Cables - Low voltage
A list of organizations represented on this committee can be obtained on request to its secretary
This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application
© BSI 2011 ISBN 978 0 580 64372 9 ICS 25.160.30; 29.060.20
Compliance with a British Standard cannot confer immunity from legal obligations.
This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 September 2011
Amendments issued since publication
Date Text affected
National foreword
This British Standard is the UK implementation of EN 50525-2-81:2011 It partially supersedes BS638-4:1996
The UK participation in its preparation was entrusted to Technical Committee GEL/20/17, Electric Cables - Low voltage
A list of organizations represented on this committee can be obtained on request to its secretary
This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application
© BSI 2011 ISBN 978 0 580 64372 9 ICS 25.160.30; 29.060.20
Compliance with a British Standard cannot confer immunity from legal obligations.
This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 September 2011
Amendments issued since publication
Date Text affected
This British Standard is the UK implementation of EN 50525-2-81:2011
In the UK, the BS EN 50525 series of standards contain complex supersession details The table below best summarizes the relationship between these standards:
2-11 (in part), 2-12, 2-21 (in part), 2-71 BS 6500:2000 2-11 (in part), 2-21 (in part), 2-51 (in part), 2-83, 3-21 BS 7919:2001
NOTE All British Standards will remain current until they are withdrawn on 31 December 2012. British Standards in bold are only partially superseded, and new editions of BS 6004 and BS 7211 will be introduced on 1 January 2013.
National Annex NA (informative) gives information on the origins and identification of particular cable types
Trang 3EN 50525-2-81
NORME EUROPÉENNE
EUROPÄISCHE NORM May 2011
CENELEC
European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members
Ref No EN 50525-2-81:2011 E
ICS 29.060.20 Supersedes HD 22.6 S2:1995 + corr Jun.1995 + A1:1999 + A2:2004
English version
Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V
(U0/U) -
Part 2-81: Cables for general applications - Cables with crosslinked elastomeric covering for arc welding
Câbles électriques -
Câbles d’énergie basse tension de tension
assignée au plus égale à 450/750 V
(U0/U) -
Partie 2-81: Câbles pour applications
générales -
Câbles pour soudage à l’arc isolés en
matériau élastomère réticulé
Kabel und Leitungen - Starkstromleitungen mit Nennspannungen
bis 450/750 V (U0/U) -
Teil 2-81: Starkstromleitungen für allgemeine Anwendungen - Lichtbogenschweißleitungen mit vernetzter Elastomer- Hülle
This European Standard was approved by CENELEC on 2011-01-17 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member
This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom
Trang 4Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric cables
The text of the draft was submitted to the formal vote and was accepted by CENELEC as
EN 50525-2-81 on 2011-01-17
This document, which is one of a multipart series, supersedes HD 22.6 S2:1995 + A1:1999 + A2:2004
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CEN and CENELEC shall not be held responsible for identifying any
or all such patent rights
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-17
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-17
Trang 5
Contents
Page
1 Scope 4
2 Normative references 4
3 Terms and definitions 5
4 Arc welding cables – H01N2-D and H01N2-E 5
4.1 Construction 5
4.2 Requirements 5
Annex A (normative) Tests for cables to EN 50525-2-81 7
Annex B (normative) General data 8
Annex C (normative) Requirements for the voltage test on completed cables 9
Annex D (normative) Requirements for the static flexibility test on completed cables 10
Bibliography 11
Tables Table A.1 7
Table B.1 ― General data for Type H01N2-D 8
Table B.2 ― General data for Type H01N2-E 8
Table C.1 9
Table D.1 10
Trang 61 Scope
This European Standard applies to single core, crosslinked elastomer covered arc welding cables
The cables are of rated voltage U0/U 100/100 V
The cables are intended for connections between the welding power source and the electrode holder and the work piece
Two types of cable are included, with respectively Class D and Class E conductors These conductors are more flexible than Class 6 to EN 60228, with Class E having the greater flexibility
The maximum conductor operating temperature for each of the cables in this standard is
85 °C
NOTE HD 516 contains extensive guidance on the safe use of cables in this standard, and gives specific current ratings and volt drop data
This EN 50525-2-81 should be read in conjunction with EN 50525-1, which specifies general requirements
2 Normative references
The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition
of the referenced document (including any amendments) applies
NOTE One or more references to the standards below are in respect of a specific sub-division of that standard, for instance a clause, a table, a class or a type Cross-references to these standards are undated and, at all times, the latest version shall apply
EN 50363-1 Insulating, sheathing and covering materials for low voltage
energy cables − Part 1: Cross-linked elastomeric insulating compounds
EN 50363-2-2 Insulating, sheathing and covering materials for low voltage
energy cables − Part 2-2: Cross-linked elastomeric covering compounds
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 50525-1 Electric cables − Low voltage energy cables of rated voltages up
to and including 450/750 V (U0/U) − Part 1: General requirements
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions −
Part 1-2: Test for vertical flame propagation for a single insulated wire or cable − Procedure for 1 kW pre-mixed flame
(IEC 60332-1-2)
EN 60811-1-4 Insulating and sheathing materials of electric and optical cables −
Common test methods − Part 1-4: General application − Tests at low temperature (IEC 60811-1-4)
Trang 73 Terms and definitions
For the purposes of this document, the terms and definitions given in Clause 3 of EN 50525-1 apply
4 Arc welding cables – H01N2-D and H01N2-E
4.1 Construction
4.1.1 Conductor
The conductor shall be copper, and generally in accordance with class 6 to EN 60228, except that the maximum diameter of wires in a conductor shall comply with the requirements given in column 2 of Table B.1 for cables with normal flexibility, or of Table B.2 for cables with extra high flexibility
NOTE The individual wires of a conductor may be plain or tinned
A separator of suitable material shall be applied around the conductor
4.1.2 Size of cable
The cable shall consist of a single conductor in accordance with Table B.1 or Table B.2, in sizes from 10 mm2 to 240 mm2
4.1.3 Covering
The covering shall be applied by extrusion around the conductor and may consist of one or two layers
Covering in one layer shall be material type EM 5 to EN 50363-2-2
Covering in two layers shall comprise an outer layer of material type EM 5 to EN 50363-2-2 and an inner layer which shall be either of type EM 5 or of material type EI 7 to EN 50363-1 The ratio of the thicknesses of the two layers is not specified, but the minimum thickness of the outer layer shall not
be less than 0,6 mm
4.1.4 Marking
The cable shall be marked with the CENELEC code H01N2-D for cables with normal flexibility, or H01N2-E for cables with extra high flexibility In addition, the cross-sectional area of the conductor shall be marked The marking shall comply with Clause 6 of EN 50525-1
4.2 Requirements
4.2.1 General
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the particular requirements of this Part
Testing shall be in accordance with Annex A
The conductor resistance shall not exceed the relevant value given in column 6 or 7 of Table B.1 or Table B.2 as appropriate
The thickness of the covering in one layer or the combined thickness of covering in the two layers shall comply with the specified value given in column 3 of either Table B.1 or Table B.2 as appropriate
The dimensions of the cables shall be within the limits specified in columns 4 and 5 of either Table B.1
or Table B.2 as appropriate
Trang 8The requirements for the voltage test at 1 000 V on completed cables shall be in accordance with Annex C
The requirements for the static flexibility test on completed cables shall be in accordance with Annex D
4.2.2 Two-layer coverings
Samples for non-electrical tests on covering in two layers shall be prepared and tested in accordance with EN 50525-1, 5.7.2.3, c)
Full testing shall be carried out on both layers, except where the resulting sample from the inner layer
is below 0,8 mm thickness In this case full testing shall be carried out on the outer layer, but only the hot set test shall be carried out on the inner layer
Trang 9Annex A
(normative)
Tests for cables to EN 50525-2-81
Table A.1
Ref
No Tests
a Category
of test Test method described in
EN (Sub)clause
1 Electrical tests b
1.1 Resistance of conductors T, S 50395 5
1.2 Voltage test at 1 000 V c T, S 50395 6
1.3 Absence of faults in covering R 50395 10.2
2 Constructional and dimensional
tests
2.1 Checking of compliance with
constructional provisions T, S 50525-1 and manual Inspection
tests 2.2 Measurement of thickness of covering T, S 50396 4.1
2.3 Measurement of overall diameter T, S 50396 4.4
3 Covering material tests d T 50363-1 and
50363-2-2 e
-
4 Static flexibility test T 50396 6.1
5 Impact test at - 20 °C T 60811-1-4 8.5
6 Test for resistance to hot particles T 50396 7.1
7 Test under fire conditions T 60332-1-2 -
a All tests are applicable to these cables The order given does not imply a sequence of
testing
b Particular test conditions and requirements are given in Table 1 of EN 50525-1
c See also Annex C
d See 4.2.2 of this EN 50525-2-81 in respect of tests and requirements for coverings in two
layers
e These ENs includes all the test methods and requirements for the material Material to be
tested is taken from the finished cable
Trang 10Annex B
(normative)
General data
NOTE The overall dimensions of cables have been calculated in accordance with EN 60719
Table B.1 ― General data for Type H01N2-D
1 2 3 4 5 6 7 Nominal
cross-sectional area
of conductor
Maximum diameter of wires in conductor
Thickness
of covering Specified value
Mean overall diameter Maximum conductor resistance at 20 °C a
Lower limit Upper limit Tinned wires Untinned wires
10
16
25
35
50
70
95
120
150
185
240
0,21 0,21 0,21 0,21
0,21 0,21 0,21 0,51
0,51 0,51 0,51
2,0 2,0 2,0 2,0
2,2 2,4 2,6 2,8
3,0 3,2 3,4
7,7 8,8 10,1 11,4
13,2 15,3 17,1 19,2
21,1 23,1 25,8
9,7 11,0 12,7 14,2
16,5 19,2 21,4 24,0
26,4 28,9 32,1
1,95 1,24 0,795 0,565
0,393 0,277 0,210 0,164
0,132 0,108 0,081 7
1,91 1,21 0,780 0,554
0,386 0,272 0,206 0,161
0,129 0,106 0,080 1
a Conductor resistance is according to EN 60228 for class 6
Table B.2 ― General data for Type H01N2-E
1 2 3 4 5 6 7 Nominal
cross-sectional area
of conductor
Maximum diameter of wires in conductor
Thickness
of covering Specified value
Mean overall diameter Maximum conductor resistance at 20 °C a
Lower limit Upper limit Tinned wires Untinned wires
10
16
25
35
50
70
95
120
150
185
240
0,16 0,16 0,16 0,16
0,16 0,16 0,16 0,21
0,21 0,21 0,21
1,2 1,2 1,2 1,2
1,5 1,5 1,8 1,8
1,8 1,8 2,0
6,2 7,3 8,6 9,8
11,9 13,6 15,6 17,2
18,8 20,4 23,0
7,8 9,1 10,8 12,3
14,8 17,0 19,5 21,6
23,5 25,5 28,0
1,95 1,24 0,795 0,565
0,393 0,277 0,210 0,164
0,132 0,108 0,081 7
1,91 1,21 0,780 0,554
0,386 0,272 0,206 0,161
0,129 0,106 0,080 1
a Conductor resistance is according to EN 60228 for class 6
Annex C
(normative)
Requirements for the voltage test on completed cables
Table C.1
Unit Value Minimum length of
the sample m 20 Minimum period of
immersion in water h 1 Temperature of the
water °C 20 ± 5
Duration of each application of voltage, minimum
Result to be obtained No breakdown