raising standards worldwide™NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW BSI Standards Publication Electric cables — Low voltage energy cables of rated voltages
Trang 1raising standards worldwide™
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
BSI Standards Publication
Electric cables — Low voltage energy cables of rated voltages
up to and including 450/750 V
Part 2-51: Cables for general applications
— Oil resistant control cables with thermoplastic PVC insulation
Trang 2BS EN 50525-2-51:2011 BRITISH STANDARD
National foreword
This British Standard is the UK implementation of EN50525-2-51:2011 It partially supersedes BS6004:2000 andBS7919:2001
The UK participation in its preparation was entrusted to TechnicalCommittee GEL/20/17, Electric Cables - Low voltage
A list of organizations represented on this committee can beobtained on request to its secretary
This publication does not purport to include all the necessaryprovisions of a contract Users are responsible for its correctapplication
© BSI 2011ISBN 978 0 580 64369 9ICS 29.060.20
Compliance with a British Standard cannot confer immunity from legal obligations.
This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2011
Amendments issued since publication
Date Text affected
National foreword
This British Standard is the UK implementation of EN50525-2-51:2011 It partially supersedes BS6004:2000 andBS7919:2001
The UK participation in its preparation was entrusted to TechnicalCommittee GEL/20/17, Electric Cables - Low voltage
A list of organizations represented on this committee can beobtained on request to its secretary
This publication does not purport to include all the necessaryprovisions of a contract Users are responsible for its correctapplication
© BSI 2011ISBN 978 0 580 64369 9ICS 29.060.20
Compliance with a British Standard cannot confer immunity from legal obligations.
This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2011
Amendments issued since publication
Date Text affected
This British Standard is the UK implementation of EN 50525-2-51:2011
In the UK, the BS EN 50525 series of standards contain complex supersession details The table below best summarizes the relationship between these standards:
National Annex NA (informative) gives information on the origins and identification of particular cable types
Trang 3Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members
Ref No EN 50525-2-51:2011 E
ICS 29.060.20 Supersedes HD 21.13 S1:1995 + A1:2001
English version
Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V
(U0/U) -
Part 2-51: Cables for general applications - Oil resistant control cables with thermoplastic PVC insulation
Câbles électriques -
Câbles d’énergie basse tension de tension
assignée au plus égale à 450/750 V
This European Standard was approved by CENELEC on 2011-01-17 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member
This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom
Trang 4or all such patent rights
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-17
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-17
Trang 5
Contents
Page
1 Scope 4
2 Normative references 4
3 Terms and definitions 5
4 General purpose cables 5
4.1 Control cables – H05VV5-F 5
4.2 Screened control cables – H05VVC4V5-K 6
Annex A (normative) Tests for cables to EN 50525-2-51 8
Annex B (normative) General data 9
Annex C (normative) Dimensional calculations for cables with a non-preferred number of cores 13
C.1 Inner sheath 13
C.2 Screen 13
C.3 Sheath 13
Annex D (normative) Requirements for compatibility test 15
D.1 Test conditions 15
D.2 Requirements 15
Bibliography 16
Tables Table A.1 8
Table B.1 – Unscreened cables 9
Table B.2 – Screened cables 11
Table D.1 15
Trang 61 Scope
This European Standard applies to oil resistant polyvinyl chloride insulated and sheathed flexible cables Screened and non-screened types are included
The cables are of rated voltages U0/U 300/500 V
The cables are intended for the interconnection of manufacturing machines
The maximum conductor operating temperature for the cables in this standard is 70 °C
NOTE HD 516 contains extensive guidance on the safe use of cables in this standard
This EN 50525-2-51 should be read in conjunction with EN 50525-1, which specifies general requirements
2 Normative references
The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition
of the referenced document (including any amendments) applies
NOTE One or more references to the standards below are in respect of a specific sub-division of that standard, for instance a clause, a table, a class or a type Cross-references to these standards are undated and, at all times, the latest version applies
EN 50363-3 Insulating, sheathing and covering materials for low voltage energy
cables – Part 3: PVC insulating compounds
EN 50363-4-1 Insulating, sheathing and covering materials for low voltage energy
cables – Part 4-1: PVC sheathing compounds
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 50525-1 Electric cables – Low voltage energy cables of rated voltages up to and
including 450/750 V (U0/U) – Part 1: General requirements
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions –
Part 1-2: Test for vertical flame propagation for a single insulated wire
or cable – Procedure for 1 kW pre-mixed flame (IEC 60332-1-2)
EN 60811-1-2 Insulating and sheathing materials of electric and optical cables –
Common test methods – Part 1-2: General application – Thermal ageing methods (IEC 60811-1-2)
EN 60811-1-4 Insulating and sheathing materials of electric and optical cables –
Common test methods – Part 1-4: General application – Tests at low temperature (IEC 60811-1-4)
HD 308 Identification of cores in cables and flexible cords
IEC 60502-1 2004 Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:
Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
Trang 73 Terms and definitions
For the purposes of this document the terms and definitions given in Clause 3 of EN 50525-1 apply
4 General purpose cables
The sizes of cable shall be 0,5 mm2 to 2,5 mm2
The number of conductors shall be from 2 up to 60
NOTE The preferred number of conductors is one of the following: 2, 3, 4, 5, 6, 7, 12, 18, 27, 36, 48 and 60
4.1.1.3 Insulation
The insulation shall be polyvinyl chloride compound of Type TI 2 to EN 50363-3
4.1.1.4 Assembly
The cables shall be assembled as follows:
The cores shall be twisted together, if necessary in several concentric layers
A tape may be applied over each layer It may cover the cores partly or fully
For two core cables, the space between the cores shall be filled either by separate fillers or
by the sheath filling the interstices
A centre-core is not permitted
NOTE A centre-filler of suitable material may be applied
Assemblies with three or more cores shall have one core coloured green-and-yellow
The sheath shall be polyvinyl chloride compound of Type TM 5 to EN 50363-4-1
It is permitted for the sheath to fill the spaces between the cores, thus forming a filling
Trang 8NOTE For cables with a non-preferred number of cores, see Annex C
The requirements to be met for the compatibility test shall be as given in Annex D
4.2 Screened control cables – H05VVC4V5-K
4.2.1 Construction
4.2.1.1 Conductor
The conductor shall be class 5, according to EN 60228
4.2.1.2 Sizes of cable
The sizes of cable shall be 0,5 mm2 to 2,5 mm2
The number of conductors shall be from 2 up to 60
NOTE The preferred number of conductors is one of the following: 2, 3, 4, 5, 6, 7, 12, 18, 27, 36, 48 and 60
4.2.1.3 Insulation
The insulation shall be polyvinyl chloride compound of Type TI 2 to EN 50363-3
4.2.1.4 Assembly
The cables shall be assembled as follows:
The cores shall be twisted together, if necessary in several concentric layers
A tape may be applied over each layer It may cover the cores partly or fully
For two core cables, the space between the cores shall be filled either by separate fillers or
by the inner sheath filling the interstices
A centre-core is not permitted
NOTE A centre-filler of suitable material may be applied
Assemblies with three or more cores shall have one core coloured green-and-yellow
Trang 9Testing shall be in accordance with Annex A, and the relevant tests indicated in column 7
The dimensions of the cables shall conform to Table B.2 for the relevant size
NOTE For cables with a non-preferred number of cores, see Annex C
The transfer impedance for the cable shall not exceed 250 mΩ/m at 30 MHz
The requirements to be met for the compatibility test shall be as given in Annex D
Trang 102 000 V T, S 50395 6 X X 1.3 Voltage test on cores according to
specified insulation thickness:
1.3.1 - at 1 500 V up to and including
1.3.2 - at 2 000 V above 0,6 mm T, S 50395 7 - X 1.4 Insulation resistance at 70 °C T, S 50395 8.1 X X 1.5 Long term resistance of insulation to
2.1 Checking of compliance with
constructional provisions T, S 50525-1 and manual Inspection
tests
X X
2.2 Measurement of thickness of
insulation T, S 50396 4.1 X X 2.3 Measurement of thickness of inner
sheath and/or sheath T, S 50396 4.2 X X 2.4 Measurement of overall dimensions
2.4.1 Mean value T, S 50396 4.4.1 X X 2.4.2 Ovality T, S 50396 4.4.2 X X
3 Insulation material tests T 50363-3 c - X X
4 Inner sheath material tests T 50363-4-1 c - - X
5 Sheath material tests T 50363-4-1 c - X X
6 Compatibility test T 60811-1-2 8.1.4 X X
7 Impact test at - 5 °C T 60811-1-4 8.5 X X d
8 Mechanical strength of completed
cable e
8.1 Flexing test followed, after
immersion in water, by a voltage test at 2 000 V on cores
9 Test under fire conditions T 60332-1-2 - X X
a The order given does not imply a sequence of testing
b Particular test conditions and requirements are given in Table 1 of EN 50525-1
c This EN includes all the test methods and requirements for the material Material to be tested is taken from the finished cable
d The inner sheath shall also be checked
e Not applicable to cables with more than 18 cores laid up in more than two concentric layers
Trang 11Annex B
(normative)
General data
NOTE The overall dimensions of cables have been calculated in accordance with EN 60719
Table B.1 – Unscreened cables
Sheath thickness Specified value
Mean overall diameter Minimum
insulation resistance at
70 °C Lower limit Upper limit
0,7 0,8 0,8 0,8 1,0
5,2 5,7 5,9 6,8 8,4
6,6 7,2 7,5 8,6 10,6
0,013 0,011 0,010 0,010 0,009 5
0,7 0,8 0,8 0,9 1,1
5,5 6,0 6,3 7,4 9,2
7,0 7,6 8,0 9,4 11,4
0,013 0,011 0,010 0,010 0,009 5
0,8 0,8 0,8 0,9 1,1
6,2 6,6 6,9 8,2 10,1
7,9 8,3 8,7 10,2 12,5
0,013 0,011 0,010 0,010 0,009 5
0,8 0,9 0,9 1,0 1,2
6,8 7,4 7,8 9,1 11,2
8,6 9,3 9,8 11,4 13,9
0,013 0,011 0,010 0,010 0,009 5
0,9 0,9 1,0 1,1 1,2
7,6 8,1 8,7 10,2 12,2
9,6 10,1 10,8 12,6 15,1
0,013 0,011 0,010 0,010 0,009 5
0,9 1,0 1,0 1,2 1,3
8,3 9,0 9,5 11,3 13,6
10,4 11,3 11,8 14,1 16,8
0,013 0,011 0,010 0,010 0,009 5
Trang 12Table B.1 – Unscreened cables (concluded)
Sheath thickness Specified value
Mean overall diameter Minimum
insulation resistance at
70 °C Lower limit Upper limit
1,1 1,1 1,2 1,3 1,5
10,4 11,0 11,8 13,8 16,8
12,9 13,7 14,6 17,0 20,6
0,013 0,011 0,010 0,010 0,009 5
1,2 1,3 1,3 1,5 1,8
12,3 13,2 14,0 16,5 20,2
15,3 16,4 17,2 20,3 24,8
0,013 0,011 0,010 0,010 0,009 5
1,4 1,5 1,5 1,8 2,1
15,1 16,2 17,0 20,3 24,7
18,6 19,9 21,0 24,9 30,2
0,013 0,011 0,010 0,010 0,009 5
1,5 1,6 1,7 2,0 2,3
17,0 18,2 19,4 23,0 28,0
20,9 22,4 23,8 28,2 34,2
0,013 0,011 0,010 0,010 0,009 5
1,7 1,8 1,9 2,2 2,4
19,8 21,2 22,5 26,6 32,1
24,3 25,9 27,6 32,5 39,1
0,013 0,011 0,010 0,010 0,009 5
1,8 2,0 2,1 2,4 2,4
21,7 23,4 24,9 29,4 35,0
26,6 28,7 30,5 35,8 42,6
0,013 0,011 0,010 0,010 0,009 5
Trang 13Table B.2 – Screened cables
Inner sheath thickness Specified value
Maximum diameter
of the wires
of the screen
Sheath thickness Specified value
Mean overall diameter insulation Minimum
resistance
at 70 °C Lower
limit Upper limit
0,7 0,7 0,7 0,7 0,7
0,16 0,16 0,16 0,16 0,16
0,9 0,9 0,9 1,0 1,1
7,7 8,0 8,2 9,3 10,7
9,6 10,0 10,3 11,6 13,3
0,013 0,011 0,010 0,010 0,009 5
0,7 0,7 0,7 0,7 0,7
0,16 0,16 0,16 0,16 0,16
0,9 0,9 1,0 1,0 1,1
8,0 8,3 8,8 9,7 11,3
10,0 10,4 11,0 12,1 14,0
0,013 0,011 0,010 0,010 0,009 5
0,7 0,7 0,7 0,7 0,8
0,16 0,16 0,16 0,16 0,16
0,9 1,0 1,0 1,1 1,2
8,5 9,1 9,4 10,7 12,6
10,7 11,3 11,7 13,2 15,5
0,013 0,011 0,010 0,010 0,009 5
0,7 0,7 0,7 0,8 0,8
0,16 0,16 0,16 0,16 0,21
1,0 1,0 1,1 1,2 1,3
9,3 9,7 10,3 11,8 13,9
11,6 12,1 12,8 14,7 17,2
0,013 0,011 0,010 0,010 0,009 5
0,7 0,7 0,7 0,8 0,8
0,16 0,16 0,16 0,16 0,21
1,0 1,1 1,1 1,2 1,4
9,9 10,5 11,0 12,7 15,2
12,4 13,1 13,6 15,7 18,7
0,013 0,011 0,010 0,010 0,009 5
0,7 0,7 0,8 0,8 0,8
0,16 0,16 0,16 0,21 0,21
1,1 1,2 1,2 1,3 1,5
10,8 11,5 12,2 14,1 16,5
13,5 14,3 15,1 17,4 20,3
0,013 0,011 0,010 0,010 0,009 5
0,8 0,8 0,8 0,8 0,9
0,21 0,21 0,21 0,21 0,21
1,3 1,3 1,4 1,5 1,7
13,3 13,9 14,7 16,7 19,9
16,5 17,2 18,1 20,5 24,4
0,013 0,011 0,010 0,010 0,009 5