Tiêu đề Multi-element metallic cables used in analogue and digital communication and control part 11-1: sectional specification for unscreened cables characterised up to 500 MHz — horizontal and building backbone cables
Trường học British Standards Institution
Chuyên ngành Standards Publication
Thể loại publication
Năm xuất bản 2012
Thành phố Brussels
Định dạng
Số trang 22
Dung lượng 0,98 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

BSI Standards PublicationMulti-element metallic cables used in analogue and digital communication and control - Part 11-1: Sectional specification for screened cables characterised up to

Trang 1

BSI Standards Publication

Multi-element metallic cables used in analogue and digital communication and control -

Part 11-1: Sectional specification for screened cables characterised up to 500 MHz — Horizontal and building backbone cables

Trang 2

A list of organizations represented on this committee can beobtained on request to its secretary.

This publication does not purport to include all the necessaryprovisions of a contract Users are responsible for its correctapplication

© The British Standards Institution 2013 Published by BSI StandardsLimited 2013

ISBN 978 0 580 64594 5ICS 33.120.10

Compliance with a British Standard cannot confer immunity from legal obligations.

This British Standard was published under the authority of theStandards Policy and Strategy Committee on 31 January 2013

Amendments issued since publication

Trang 3

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members

Ref No EN 50288-11-1:2012 E

ICS 33.120.10

English version

Multi-element metallic cables used in analogue and digital communication

and control - Part 11-1: Sectional specification for un-screened cables characterised

up to 500 MHz - Horizontal and building backbone cables

Câbles métalliques à éléments multiples

utilisés pour les transmissions et les

commandes analogiques et numériques -

Partie 11-1: Spécification intermédiaire

pour câbles non-blindés, pour applications

Teil 11-1: Rahmenspezifikation für ungeschirmte Kabel bis 500 MHz - Kabel für den Horizontal- und Steigbereich

This European Standard was approved by CENELEC on 2012-11-12 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member

This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified

to the CEN-CENELEC Management Centre has the same status as the official versions

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom

Trang 4

Contents

Foreword 3

1 Scope 5

2 Normative references 5

3 Terms, definitions, symbols and abbreviations 6

3.1 Terms and definitions 6

3.2 Symbols and abbreviations 6

4 Cable construction 6

4.1 Conductor 6

4.2 Insulation 6

4.3 Cabling elements 6

4.4 Identification of cabling elements 6

4.5 Screening of cabling elements 6

4.6 Cable make-up 6

4.7 Filling compound 6

4.8 Interstitial fillers 6

4.9 Screening of the cable core 7

4.10 Moisture barriers 7

4.11 Wrapping layers 7

4.12 Sheath 7

5 Test methods and requirements for completed cables 7

5.1 General 7

5.2 Electrical tests 7

5.3 Mechanical tests 10

5.4 Environmental tests 11

5.5 Fire performance tests 11

Annex A (informative) Maximum voltage, current and temperature rating for cables used for POE applications 12

Annex B (informative) Blank Detail Specification 13

B.1 General 13

B.2 Document Details 13

B.3 Generic specification EN 50288-1 14

Trang 5

Foreword

This document (EN 50288-11-1:2012) has been prepared by CLC/SC 46XC, "Multicore, multipair and quad data communication cables"

The following dates are fixed:

• latest date by which this document has to be

implemented at national level by publication of

an identical national standard or by

endorsement

(dop) 2013-11-12

• latest date by which the national standards

conflicting with this document have to

The EN 50288 series is divided into the following parts:

EN 50288-1, Multi-element metallic cables used in analogue and digital communication and control

Part 1: Generic specification;

EN 50288-2-1, Multi-element metallic cables used in analogue and digital communication and control

building backbone cables;

EN 50288-2-2, Multi-element metallic cables used in analogue and digital communication and control

patch cord cables;

EN 50288-3-1, Multi-element metallic cables used in analogue and digital communication and control

building backbone cables;

EN 50288-3-2, Multi-element metallic cables used in analogue and digital communication and control

patch cord cables;

EN 50288-4-1, Multi-element metallic cables used in analogue and digital communication and control

building backbone cables;

EN 50288-4-2, Multi-element metallic cables used in analogue and digital communication and control

patch cord cables;

EN 50288-5-1, Multi-element metallic cables used in analogue and digital communication and control

building backbone cables;

EN 50288-5-2, Multi-element metallic cables used in analogue and digital communication and control

patch cord cables;

Trang 6

EN 50288-6-1, Multi-element metallic cables used in analogue and digital communication and control

building backbone cables;

− EN 50288-6-2, Multi-element metallic cables used in analogue and digital communication and control 

patch cord cables;

EN 50288-7, Multi-element metallic cables used in analogue and digital communication and control

Part 7: Sectional specification for instrumentation and control cables;

EN 50288-8, Multi-element metallic cables used in analogue and digital communication and control

Part 8: Specification for type 1 cables characterised up to 2 MHz;

EN 50288-9-1, Multi-element metallic cables used in analogue and digital communications and control

Horizontal and building backbone cables (the present document);

EN 50288-10-1, Multi-element metallic cables used in analogue and digital communications and control

Horizontal and building backbone cables;

EN 50288-11-1, Multi-element metallic cables used in analogue and digital communication and control

Horizontal and building backbone cables (the present document)

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights

Trang 7

1 Scope

EN 50288-11-1 is a sectional specification for un-screened cables, characterised from 1 MHz up to 500 MHz,

to be used in horizontal and building backbone wiring for Information Technology generic-cabling systems This sectional specification contains the electrical, mechanical, transmission and environmental performance characteristics and requirements of the cables when tested in accordance with the referenced test methods This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application

The cables covered in this sectional specification are intended to operate with voltages and currents normally encountered in communications systems These cables are not intended to be used in conjunction with low impedance sources, for example the electrical power supplies of public utility mains

2 Normative references

The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies

EN 50288-1 Multi-element metallic cables used in analogue and digital communication and

control Part 1: Generic specification

EN 50289-1-4 Communication cables Specifications for test methods Part 1-4: Electrical test

EN 50289-3-2 Communication cables – Specifications for test methods Part 3-2: Mechanical test

EN 50289-3-4 Communication cables – Specifications for test methods Part 3-4: Mechanical test

EN 50289-3-5 Communication cables Specifications for test methods Part 3-5: Mechanical test

EN 50289-3-6 Communication cables Specifications for test methods Part 3-6: Mechanical test

EN 50289-3-8 Communication cables Specifications for test methods Part 3-8: Mechanical test

EN 50289-3-9:2001 Communication cables  Specifications for test methods Part 3-9: Mechanical test

EN 50289-3-16 Communication cables Specifications for test methods Part 3-16: Mechanical test

EN 50289-4-6 Communication cables Specifications for test methods Part 4-6: Environmental

EN 50290-2

(all parts) Communication cables Part 2: Common design rules and construction

EN 60708 Low-frequency cables with polyolefin insulation and moisture barrier polyolefin sheath

(IEC 60708)

Trang 8

IEC 60189-2 Low-frequency cables and wires with PVC insulation and PVC sheath Part 2: Cables

in pairs, triples, quads and quintuples for inside installations

3 Terms, definitions, symbols and abbreviations

3.1 Terms and definitions

For the purposes of this document, the terms and definitions of EN 50288-1, Clause 3 apply

3.2 Symbols and abbreviations

For the purposes of this document, the following abbreviations apply

EX Exogenous (derived or originating externally)

POE Power Over Ethernet

4 Cable construction

4.1 Conductor

The conductor shall be solid annealed copper and comply with the requirements of EN 50288-1, 4.1

The nominal conductor diameter shall be ≥ 0,50 mm and ≤ 0,80 mm

NOTE Constructions with ‘copper clad’ conductors do not meet the requirements

4.2 Insulation

The insulation shall be of a suitable material in accordance with the appropriate part of the EN 50290-2 series

4.3 Cabling elements

The cable element shall be a pair or quad

4.4 Identification of cabling elements

Unless otherwise specified, the colour coding for identification shall be as specified in IEC 60189-2 or

EN 60708, as appropriate The colours shall comply with the requirements of EN 50288-1, 4.4

4.5 Screening of cabling elements

Trang 9

4.9 Screening of the cable core

The sheath shall be of a suitable material and comply with the appropriate part of the EN 50290-2 series

5 Test methods and requirements for completed cables

5.1 General

The following tables specify the tests that shall be applied to the completed cable, together with the requirements to demonstrate compliance with this sectional specification

5.2 Electrical tests

5.2.1 Low-frequency and d.c electrical measurements

Table 1  Low-frequency and d.c electrical measurements

EN 50288-1

Subclause Parameter Requirement

5.1.1.1 Conductor loop resistance The maximum value shall be ≤ 19 Ω/100 m

EN 50289-1-4 5.1.1.5 Mutual capacitance No requirement specified

5.1.1.6 Capacitance unbalance to

Trang 10

5.2.2 High-frequency electrical and transmission measurements

Table 2  High-frequency electrical and transmission measurements

Attenuation b, c, f 1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz

2,1 3,8 5,9 7,5 8,4 10,5 15,0 19,1 24,1 27,6 34,3 45,3 dB/100 m

α ≤ 1,82 √f + 0,0091 f + 0,25/√f, 1 MHz ≤ f ≤ 500 MHz 5.1.2.4 Near End

Unbalance Attenuation

Level 1 ≥ 40 - 10 log (f) dB, 1 MHz ≤ f ≤ 250 MHz ; 250 MHz ≤ f ≤ 500 MHz Level 2 ≥ 50 - 10 log (f) dB, 1 MHz ≤ f ≤ 250 MHz ; 250 MHz ≤ f ≤ 500 MHz 5.1.2.5 Near-end

Crosstalk (NEXT) b

1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz 75,3 66,3 60,3 57,2 55,8 52,9 48,4 45,3 42,4 40,8 38,1 34,8 dB

≥ 75,3 – 15 log f, 1 MHz < f ≤ 500 MHz 5.1.2.6 Attenuation to

crosstalk ratio at the far end b, d

(ACR-F)

1 4 10 16 20 31.25 62,5 100 155 200 300 500 MHz 68,0 56,0 48,0 43,9 42,0 38,1 32,1 28,0 24,2 22,0 18,5 14,0 dB

≥ 68 - 20 log f, 1 MHz ≤ f ≤ 500 MHz , values referenced to 100 m

5.1.2.7.1 Power sum

Near-end Crosstalk b

(PSNEXT)

1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz 72,3 63,3 57,3 54,2 52,8 49,9 45,4 42,3 39,4 37,8 35,1 31,8 dB

≥ 72,3 – 15 log f, 1 MHz ≤ f ≤ 500 MHz 5.1.2.7.2 Power Sum

Attenuation to crosstalk ratio at the far end b, d (PSACR-F)

1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz 65,0 53,0 45,0 40,9 39,0 35,1 29,1 25,0 21,2 19,0 15,5 11,0 dB

≥ 65 - 20 log f, 1 MHz ≤ f ≤ 500 MHz , values referenced to 100 m

5.1.2.7.4 Power Sum

Exogenous Crosstalk PSExNEXT b, e

1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz 67,0 67,0 67,0 67,0 67,0 67,0 65,6 62,5 59,6 58,0 55,3 52,0 dB

≥ 92,5 - 15 log f, 1 MHz ≤ f ≤ 500 MHz (67 dB max.)

5.1.2.7.6 Power Sum

Attenuation to crosstalk ratio at the far end Exogenous Crosstalk PSExACR-F b, c, d, e

1 4 10 16 20 31,25 62,5 100 155 200 300 500 MHz 67,0 66,2 58,2 54,1 52,2 48,3 42,3 38,2 34,4 32,2 28,7 24,2 dB

≥ 78,2 - 20 log f, 1 MHz ≤ f ≤ 500 MHz (67 dB max.) values referenced to 100 m

5.1.2.8 Mean Characteristic

Impedance (100 ± 5) Ω, at 100 MHz

Trang 11

≥ 20 + 5 log (f), 4 MHz ≤ f ≤ 10 MHz; 25 dB, 10 MHz ≤ f < 20 MHz;

25 - 7 log (f /20), 20 MHz < f ≤ 250 MHz; 17,3 dB, 250 MHz ≤ f ≤ 500 MHz 5.1.2.10 Coupling

attenuation Type II ≥ 55 dB, 30 MHz ≤ f ≤100 MHz; 55 - 20*log500 MHz (f/100), 100 MHz ≤ f ≤

Type III ≥ 40 dB, 30 MHz ≤ f ≤ 100 MHz

40 - 20 log (f /100 dB), 100 MHz ≤ f ≤ 500 MHz 5.1.2.11 Transfer

impedance Not applicable NOTE See also Table A.1, proposed table for data cable current, voltage and power ratings

a For the measurements the test sample having a round trip loss ≥ 40 dB at any measured frequency shall be used

b The values in the table are for information only The formula given shall be used to determine compliance, rounded to one decimal place

c The attenuation shall meet values adjusted for temperature of 0,2 % per degree rise from 20 °C to 40 °C and 0,4 % per degree rise for the temperature range 40 °C to 60 °C

d No measurement of ACR-F and PSACR-F is required when FEXT is above 70 dB

e Values between 1 MHz and 4 MHz are for information only

f ELFEXT had been replaced by ACR-F

Trang 12

sheath markings

EN 50289-3-8

Marking shall remain legible

10 cycles Force: 4 N 5.2.6 Simulated installation

testing of the cable 5.2.6.1 Simulated installation

testing of the cable

EN 50289-3-9:2001, Clause 4

Single Bend

4 X diameter / 4 strokes Near end Crosstalk, Return Loss and Characteristic Impedance and Coupling Attenuation (u/c) shall remain within the specified limits

5.2.6.2 Simulated installation

testing of the cable

EN 50289-3-9:2001, Clause 8

“S” Bend

8 X diameter / 100 m / 1 cycle / 120° / 1 m/s Near end Crosstalk, Return Loss and Characteristic Impedance and Coupling Attenuation (u/c) shall remain within the specified limits

5.2.7 Tensile performance

EN 50289-3-16 combined with 5.2.6

Load shall be 25 N per pair (i.e.100 N 4 Pair)

Near end Crosstalk, Return Loss and Characteristic Impedance and Coupling Attenuation (u/c) shall remain within the specified limits