1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Bsi bs en 14898 2006 + a1 2007

34 2 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Water Conditioning Equipment Inside Buildings — Active Media Filters — Requirements For Performance, Safety And Testing
Trường học British Standards Institution
Chuyên ngành Water Conditioning Equipment
Thể loại standard
Năm xuất bản 2006
Thành phố Brussels
Định dạng
Số trang 34
Dung lượng 494,98 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 4.1 Materials of construction (10)
  • 4.2 Working conditions (10)
    • 4.2.1 Working temperature (10)
    • 4.2.2 Working flow (10)
  • 4.3 Filter cartridge replacement (10)
  • 4.4 End connections (10)
  • 4.5 Backflow prevention (10)
  • 4.6 Exchange indicator (10)
  • 5.1 Pressure strength of the filter housing (11)
  • 5.2 Dynamic pressure test of housing (11)
  • 5.3 Dynamic pressure test of cartridge (11)
  • 5.4 Pressure drop (11)
  • 5.5 Substance reduction performance (11)
    • 5.5.1 Performance claims (11)
    • 5.5.2 Chlorine reduction (11)
    • 5.5.3 Organic chemical reduction (11)
    • 5.5.4 Odour and flavour reduction (12)
    • 5.5.5 Inorganic chemical reduction (12)
  • 6.1 Static pressure test of filter housing (12)
    • 6.1.1 Principle (12)
    • 6.1.2 Procedure (12)
  • 6.2 Dynamic water pressure test of housing (13)
    • 6.2.1 Principle (13)
    • 6.2.2 Procedure (13)
  • 6.3 Dynamic pressure test of cartridge (14)
    • 6.3.1 Principle (14)
    • 6.3.2 Procedure (14)
  • 6.4 Pressure drop (15)
    • 6.4.1 Principle (15)
    • 6.4.2 Procedure (15)
  • 6.5 Chlorine reduction (17)
    • 6.5.1 Test equipment (17)
    • 6.5.2 Reagents (17)
    • 6.5.3 Analytical methods (17)
    • 6.5.4 Test conditions (17)
    • 6.5.5 Procedure (18)
    • 6.5.6 Sampling (18)
    • 6.5.7 Acceptance criteria (19)
    • 6.5.8 Expression of results (19)
    • 6.6.3 Analytical methods (20)
    • 6.6.4 Test conditions (20)
    • 6.6.5 Procedure (23)
    • 6.6.6 Sampling (23)
    • 6.6.7 Acceptance criteria (23)
    • 6.6.8 Expression of results (23)
  • 7.1 Technical documents (24)
  • 7.2 Marking (25)
  • 7.3 Labelling (25)
    • 7.3.1 Filter housing (25)
    • 7.3.2 Filter cartridge (25)
  • 7.4 Packaging (25)

Nội dung

EN 14898 2006+A1 2007 64 e stf BRITISH STANDARD BS EN 14898 2006 +A1 2007 Water conditioning equipment inside buildings — Active media filters — Requirements for performance, safety and testing The Eu[.]

Materials of construction

Active media shall conform to the requirements for water extractable substances in EN 12903, EN 12904,

EN 12905, EN 12906, EN 12907, EN 12909, EN 12910, EN 12911, EN 12912, EN 12913, EN 12914, EN 12915-1,

EN 13752, EN 13753, EN 13754, EN 14368 or EN 14369, if and as appropriate.

Working conditions

Working temperature

The filter shall be designed to operate to the requirements of this standard at:

 minimum ambient air and water temperatures of not less than 5 °C;

 maximum water temperature of at least 30 °C;

 maximum ambient air temperature of at least 30 °C.

Working flow

Performance tests shall be performed at the maximum of the working flow range stipulated by the manufacturer

If a filter system lacks a flow regulator, the manufacturer must include instructions in the operating manual to help users adjust the flow, ensuring it remains within the maximum working flow range.

Filter cartridge replacement

Any tools necessary for routine maintenance shall not come into contact with the water intended for human consumption Any special tools shall be provided by the equipment supplier

The system shall be designed, and suitable instructions provided, such that contamination of the treated water supply is avoided during the filter cartridge change procedure.

End connections

All fittings provided with the filter for connecting to existing pipework must meet the relevant European Standards, and for point-of-entry installations, the minimum size should be DN 15.

Backflow prevention

Backflow prevention shall be provided in accordance with the national implementation of EN 1717.

Exchange indicator

An active media filter system must include a cartridge exchange indicator that provides guidance on the remaining lifespan of the filter element based on its filtration capacity Additionally, it should clearly state the maximum duration after which the cartridge needs to be replaced.

Pressure strength of the filter housing

When subjected to a hydraulic test as defined in 6.1, there shall be no visible leakage or damage.

Dynamic pressure test of housing

While subject to a cyclic pressure test as described in 6.2, the filter housing shall show no visible signs of leakage or damage

In the case of a capsule type filter, this test shall be omitted but the dynamic pressure test as described in 6.3 shall be completed.

Dynamic pressure test of cartridge

While subject to a cyclic pressure test as described in 6.3, the filter cartridge shall show no visible signs of leakage or damage.

Pressure drop

When subjected to the maximum of the working flow range as described in 6.4, the filter, with a clean element, shall not develop a pressure drop higher than the manufacturer’s declared value.

Substance reduction performance

Performance claims

The filter manufacturer may assert any or all performance claims outlined in this clause; however, if multiple substance performance claims are made, the rated capacity will correspond to the lowest capacity specific to any one substance.

Chlorine reduction

When tested in accordance with 6.5, the reduction in chlorine achieved shall be categorized as follows:

Organic chemical reduction

The unit must achieve a minimum reduction of 90% for specified chemical parameters when tested according to section 6.6, starting from an influent concentration that is 10 times the regulated value or the World Health Organization (WHO) Guidelines value While trihalogenmethanes (THM) can use chloroform as a surrogate, specific tests must be conducted for each substance that the manufacturer claims to reduce Claims for the reduction of generic groups of organic chemicals, such as pesticides and polycyclic aromatic hydrocarbons (PAH), are not permitted under this standard, except for THMs.

The protocols outlined in section 6.6 can be modified to assess the reduction of substances not explicitly addressed by the performance requirements of this standard, as detailed in Annex C It is important to note that claims regarding the reduction of these substances are distinctly separated from claims of conformity to this standard, as referenced in section 7.1.

Odour and flavour reduction

The unit must demonstrate the ability to lower geosmin levels from 0.15 àg/l to 0.015 àg/l and reduce 2,4,6-trichlorophenol levels from 20 àg/l to 2 àg/l, as per the testing requirements outlined in section 6.6 It is important to note that separate claims regarding odour or flavour reduction are not allowed for compliance with this standard.

Inorganic chemical reduction

When tested in accordance with 6.6, the unit shall meet the criteria given in Table 1 for any or all of the substances tested

Determinant Concentration units Influent concentration C i Effluent percentage reduction

Carbonate hardness is measured at 300 ± 30 mg/l as CaCO3 To ensure that excessive nitrite formation does not occur, filtered water samples must be analyzed for both nitrite and nitrate.

The protocols outlined in section 6.6 of this standard can be modified to assess the reduction of substances that are not explicitly addressed by the performance requirements It is important to note that claims regarding the reduction of these substances are distinctly separate from claims of compliance with this standard.

Static pressure test of filter housing

Principle

The filter is mounted in a test rig and a water pressure 1.5 times the maximum working pressure is applied for

10 min The filter is examined for visible evidence of leakage or damage.

Procedure

To install the filter, set it up in a test rig as illustrated in Figure 1, ensuring the pressure gauge is positioned at the outlet of the test specimen Verify that the outlet pressure meets the specified value and flush the system with water to eliminate any trapped air in the filter Gradually increase the water pressure to 1.5 times the maximum working pressure at a rate of at least 0.1 MPa/s, and maintain this pressure for 10 minutes, with a tolerance of ±2 minutes Finally, inspect the filter for any visible signs of leakage or damage.

2 Stop valve/ Solenoid valve 5 Test specimen

Dynamic water pressure test of housing

Principle

The empty filter housing is mounted in a test rig and subjected to 200 000 load cycles with pressure varying from

150 kPa to 1,3 times the maximum working pressure at a frequency of 15 min -1 The filter housing is examined for visible evidence of leakage or damage.

Procedure

Position the filter in an appropriate test rig and subject it to 200,000 load cycles, with water pressure fluctuating between 150 kPa and 1.3 times the maximum working pressure at a frequency of (15 ± 2) min\(^{-1}\) Each phase of pressure increase, hold, and decrease must be carefully timed.

(1 ± 0,2) s The pressure shall be measured at the outlet of the filter Maintain the water temperature of the system at (20 ± 3)°C Examine the filter for visible evidence of leakage or damage

The filter used for the test described in 6.2 shall not be used for subsequent testing

Dynamic pressure test of cartridge

Principle

The filter cartridge, installed in a test rig, undergoes 20,000 load cycles with pressure fluctuations ranging from 150 kPa to 1.3 times the maximum working pressure at a frequency of 6 cycles per minute Following this rigorous testing, the cartridge and seals are thoroughly inspected for any signs of physical damage.

Procedure

 Position the filter with cartridge installed in a test rig (see Figure 1)

The test involves applying 20,000 load cycles with water pressure fluctuating between 1.3 times the maximum working pressure and 150 kPa The pressure increase and hold time at 1.3 times the maximum working pressure should each be (2.5 ± 0.2) seconds Additionally, the pressure decrease from 1.3 times the maximum working pressure to 150 kPa, along with the hold period at 150 kPa, should total (5 ± 0.2) seconds.

 Maintain the water temperature of the system at (20 ± 3) °C After the completion of 20 000 load cycles, remove the cartridge and examine it for visible evidence of leakage or damage

 The filter used for the test described in 6.3 shall not be used for subsequent testing

Pressure drop

Principle

The filter is installed in a test rig to record differential pressure at various flow rates, creating a pressure drop curve This test is repeated without the filter cartridge, allowing for the calculation of the differential pressure curve by subtracting the results of the cartridge-removed test from those with the cartridge in place However, for filters with capsule cartridges, the test without the cartridge is not conducted, and the pressure drop is reported for the entire system instead.

Procedure

The test rig, illustrated in Figure 4, requires the filter to be connected following the manufacturer's provided instructions It is essential to install the filter between two pressure measurement sensors linked to appropriately sized manometers with an error limit of 2 kPa; alternatively, a differential pressure gauge can be utilized.

 If the appliance to be tested is fitted with a shut-off valve, open it fully

 Adjust the flow rate by means of the regulating valve installed downstream of the filter Maintain the water temperature of the system at (20 ± 3) °C

 Measure the differential pressure at a number (e.g 10) of flow rates in order to generate a pressure drop curve (curve A in Figure 5)

1 Regulating valve 4 Differential pressure gauge

2 Flow meter 4’ Alternatively: two pressure gauges

3 Sensors for pressure measurement 5 Appliance under test

Figure 4 — Flow rate/pressure loss test rig

X Flow rate, in m 3 /h A Differential pressure across the housing and cartridge

Y Pressure drop, in kPa/10 B Differential pressure across the empty housing

C Differential pressure across the cartridge

Figure 5 — Pressure drop as function of flow rate

For point of entry units, the nominal flow rates shall not be lower than those specified in Table 2

Table 2 — Flow rate values (point of entry only)

0,35 0,63 1,0 1,6 2,53 3,89 6,67 10 15,56 a These flow rates correspond to a superficial linear velocity of approx 2 m/s

For point of use units the pressure drop shall be documented at the maximum working flow rate specified by the manufacturer.

Chlorine reduction

Test equipment

A test rig must be utilized that can deliver the maximum working flow range and corresponding static pressures specified by the manufacturer Two identical units should be tested simultaneously in parallel For reference, an example system is provided in Annex A.

NOTE The raw water supply may be directly from the mains or from a batch tank.

Reagents

All reagents shall be of a recognised analytical grade and the water used to prepare reagent solutions shall conform to grade 2 in accordance with EN ISO 3696

Aqueous solution of sodium hypochlorite (NaClO) containing approximately 12 % by mass of available chlorine

Dissolve (3,5 ± 0,1) g sodium thiosulfate pentahydrate (!Na2S2O3 ã 5 H2O") in water and dilute to 1 l in a volumetric flask Store this solution at (4 ± 1) °C in the absence of light.

Analytical methods

Water analyses shall be conducted using the following methods:

 free available chlorine : EN ISO 7393-1

Test conditions

Mains supply water shall be used, adjusted as necessary to the following characteristics:

 conductivity : from 300 àS/cm 2 to 750 àS/cm 2

Chlorinated test water shall be adjusted to the following characteristic:

 free available chlorine (as Cl 2 ) : (1,0 ± 0,1) mg/l

Add sodium hypochlorite solution (6.5.2.2) to achieve the specified free available chlorine concentration

For testing water from a batch tank, it is essential to perform superchlorination and subsequent dechlorination to ensure the required level of free available chlorine is met If a stable free chlorine residual cannot be achieved, the specified procedure must be followed.

To prepare the test water, add sodium hypochlorite to achieve a total chlorine concentration of at least 5 mg/l If using storage tanks with lids, let the water stand for a minimum of 2 hours; for a flow-through system, utilize a static mixer and a holding tank to ensure a 5-minute residence time After chlorination, dechlorinate the water by adding sodium thiosulfate solution, where 2 ml neutralizes 1 mg/l of free chlorine per liter Verify that all free chlorine has been removed before chlorinating to the required influent challenge concentration of 1.0 mg/l by adding sodium hypochlorite to the tank or through injection.

The water pressure used for the test shall be not less than 410 kPa

The ambient air temperature throughout the test shall be (20 ± 5) °C.

Procedure

 Install two identical systems into the test rig referred to in 6.5.1 in accordance with the manufacturer’s instructions

 Condition the systems in accordance with the manufacturer’s instructions using the test water defined in 6.5.4.1.1

 Start the flow of chlorinated challenge water and regulate the flow to the maximum of the working flow range by adjusting the control valve downstream of the filter unit

 Set the timer on the solenoid valves to operate on a 50 % on 50 % off basis, with a cycle time of 60 min, 16 h/d with an 8 h overnight stagnation

 Operate the system to the end of the filter rated capacity.

Sampling

 Collect the first influent challenge and product water samples starting during the “on” portion of the cycle after the passage of 10 unit volumes of the influent challenge

 Sample the influent and effluent from each filter at 10 % increments between 10 % and 100 % of the rated capacity of the filter for chlorine reduction

 Note the temperature and flow rate of each product sample as it is taken

 Take samples of influent and product water simultaneously

 Analyse each influent and product sample for free available chlorine within 5 min of taking the sample

 To verify compliance with the test water requirements (see 6.5.4.1), analyse the first and final influent sample for pH, turbidity and conductivity for each batch tank

Laboratories must ensure that the challenge water meets the necessary concentration levels prior to commencing testing If the concentrations are not adequate, adjustments to the water composition should be made to achieve the required standards.

Acceptance criteria

To meet the required standard, each test filter must demonstrate a percent reduction efficiency of free available chlorine that is equal to or greater than the claimed efficiency or the minimum specified in section 5.5 for the stated chlorine reduction rating.

Expression of results

For an example test result sheet, see Annex B

6.6 Chemical and odour/flavour reduction

A test rig capable of providing the specified flow rates and static pressures shall be used Two identical units shall be tested in parallel Annex A gives an example system

All reagents shall be of a recognised analytical grade and the water used to prepare reagent solutions shall conform to grade 2 in accordance with EN ISO 3696

Dissolve (65,6 ± 0,1) g calcium chloride dihydrate (!CaCl2 ã 2 H2O") in water and dilute to 1 l in a volumetric flask

Dissolve (38,0 ± 0,1) g magnesium sulfate heptahydrate (!MgSO4 ã 7 H2O") in water and dilute to 1 l in a volumetric flask

Dissolve (67,2 ± 0,1) g sodium hydrocarbonate (NaHCO3) in water and dilute to 1 l in a volumetric flask

Dissolve (6,52 ± 0,01) g potassium nitrate (KNO 3 ) in water and dilute to 1 l in a volumetric flask

6.6.2.6 Metals volumetric flask, using a further 400 ml water to rinse the glass beaker Then fill up to the mark with water The stock solution can be stored for 6 months

Table 3 — Preparation of metals stock solutions

Metal Salt Mass to be dissolved g

Solution containing 100 mg/l 2,4,6-trichlorophenol (2,4,6-Cl3C6H2OH) in water

Dilute 5 ml of 2,4,6-trichlorophenol stock solution (6.6.2.7.1) to 100 ml with water in a volumetric flask Prepare this solution immediately before use

Solution containing 1 mg/l geosmin in water

Dilute 5 ml of geosmin stock solution (6.6.2.7.3) to 100 ml with water in a volumetric flask Prepare this solution immediately before use.

Analytical methods

Water analyses shall be conducted using the following methods:

Organic chemicals dissolved in water shall be analysed using methods that meet the specification in Annex 3 of 98/83/EC ![2]".

Test conditions

 conductivity : from 300 àS/cm 2 to 750 àS/cm 2

6.6.4.1.2 Organic chemical and odour/flavour challenge

 Add the organic chemical to be tested to the general test water (6.6.4.1.1) to achieve a concentration equal to

10 times the regulated value (see ![2]")

 If the organic chemical does not have a regulated value, use a concentration 10 times the WHO Guideline value (see ![3]")

 For the odour/flavour test, geosmin and 2,4,6-trichlorophenol shall be tested separately Geosmin shall be spiked at a concentration of 0,15 àg/l and 2,4,6-trichlorophenol at 20 àg/l

NOTE 1 Annex C gives guidance on selecting spiking concentrations for chemicals that do not have regulated or guideline values

NOTE 2 The removal of several chemicals may be simultaneously tested using a mixture spiked into the test water, provided that there is no reaction that would invalidate the individual result

NOTE 3 Presence of TOC in the water supply may adversely affect organic chemical reduction

Two basic challenge water preparations are specified: a) To test metal reduction Each metal element shall be tested at two pH levels b) To test nitrate and carbonate hardness reduction

For other inorganic chemicals, add the inorganic chemical to be tested to the general test water (6.5.4.1.1) to achieve a concentration equal to 10 times the regulated value (see ![2]")

If the inorganic chemical does not have a regulated value, use a concentration 10 times the World Health Organization Guideline value (see ![3]")

NOTE 1 Annex C gives guidance on selecting spiking concentrations for chemicals that do not have regulated or guideline values

NOTE 2 The removal of several chemicals (but not metals) may be simultaneously tested using a mixture spiked into the test water, provided that there is no reaction that would invalidate the individual result

6.6.4.1.3.2 Challenge water for metal reduction (except for lead pH 8,5)

To prevent interference among various metals in the challenge water, it is essential to test each element individually The mains supply water should be utilized and modified as needed to meet the specifications outlined in Table 4.

Table 4 — Characteristics for challenge water for metal reduction

Characteristic Low pH High pH (except for lead) pH 6,5 ± 0,25 8,5 ± 0,25

Hardness (20 ± 10) mg/l as CaCO3 (150 ± 50) mg/l as CaCO3

Alkalinity (20 ± 10) mg/l as CaCO3 (175 ± 75) mg/l as CaCO3

Polyphosphate < 0,5 mg/l as P < 0,5 mg/l as P

Add 1 ml of the respective metal stock solution (6.6.2.6) per litre of challenge water to achieve the specified concentration in the challenge water

6.6.4.1.3.3 Challenge water for lead pH 8,5 testing

For lead reduction testing, utilize freshly prepared, deionised reverse osmosis water with a hardness of (150 ± 10) mg/l as CaCO3 and an alkalinity of (100 ± 10) mg/l CaCO3, achieved by adding 2.5 ml of each specified stock solution per litre of challenge water Adjust the pH to 8.5 ± 0.25 using sodium hydroxide or concentrated hydrochloric acid After mixing for 10 minutes, incorporate 1 ml of lead stock solution per litre of challenge water and stir for 1 hour prior to use Ensure to stir for at least 5 minutes every hour during the test and prepare fresh test water daily.

6.6.4.1.3.4 Challenge water for carbonate hardness and nitrate reduction

Spike the general test water (6.6.4.1.1) to achieve the following target concentrations:

 hardness : 300 mg/l as CaCO3 Add equal volumes of the calcium and magnesium stock solutions

(6.6.2.2 and 6.6.2.3) Addition of 1 ml of each solution per litre of challenge water will increase hardness by 60 mg/l CaCO3

 alkalinity : 200 mg/l as CaCO3 Addition of 1 ml of stock solution (6.6.2.4) per litre of challenge water will increase alkalinity by 40 mg/l CaCO3

 nitrate : 200 mg/l as NO3 Addition of 1 ml of stock solution (6.6.2.5) per litre of challenge water will increase the nitrate concentration by 40 mg/l

The water pressure used for the test shall be not less than 410 kPa

The ambient temperature throughout the test shall be (20 ± 5) °C.

Procedure

 Install two identical systems into the test rig referred to in 6.5.1 in accordance with the manufacturer’s instructions

 Condition the systems in accordance with the manufacturer’s instructions using the test water defined in 6.6.4.1.1

 Start the flow of challenge water and regulate the flow to the maximum of working flow range by adjusting the control valve downstream of the filter unit

 Set the timer on the solenoid valves to operate on a 50 % on 50 % off basis, with a cycle time of 60 min, 16 h/d with an 8 h overnight stagnation

 Operate the system to the end of the filter rated capacity.

Sampling

 Collect the first influent challenge and product water samples starting during the “on” portion of the cycle after the passage of 10 unit volumes of the influent challenge

 Sample the influent and effluent from each filter at 10 % increments between 10 % and 100 % of the rated capacity of the filter for the substance-specific organic chemical reduction

 Note the temperature and flow rate of each product sample as it is taken

 Take samples of influent and product water simultaneously

 To verify compliance with the test water requirements (see 6.6.4.1), analyse the first and final influent sample for the specified parameters for each batch tank

NOTE 1 Adequate precaution should be taken throughout the test to ensure that loss or degradation of the spiked chemical does not affect the result

NOTE 2 Laboratories should satisfy themselves that the challenge water meets all of the required concentrations before testing is started If it does not then the water composition should be adjusted until the required concentrations are met.

Acceptance criteria

To meet the standard, the average percent reduction efficiency of each specific organic chemical by the test filter must be at least equal to the claimed efficiency and must also meet the minimum requirements outlined in sections 5.5.3, 5.5.4, or 5.5.5, depending on the claimed reduction rating Additionally, no individual result should fall below this threshold.

90 % of the minimum specified in 5.5.3, 5.5.4 or 5.5.5.

Expression of results

For an example test result sheet, see Annex B

7 Technical documents, marking, labelling and packaging

Technical documents

Active media filter units shall be accompanied by a technical product description with comprehensive instructions for installation, operation, maintenance and service

Instructions for filters with replaceable filter cartridges shall provide the following information:

For proper installation of the filter in compliance with European Standards, a comprehensive list of necessary components must be provided, clearly indicating which items are included with the product and which are not It is essential to recommend the inclusion of a pressure reducing valve if the supply pressure is at risk of exceeding the maximum rated pressure Additionally, the installation instructions should specify the requirements for backflow prevention applicable in the country of sale.

 recommendations on siting of system for safe and effective operation;

 recommendations for orientation for ease and safety of maintenance;

 frequency of filter cartridge replacement;

 opening and draining of filter;

 removal and disposal of filter cartridge;

 correct and hygienic insertion of replacement filter cartridge;

The instruction manual shall include a pressure drop chart up to 100 kPa

When the supply pressure may exceed the unit's maximum pressure rating, it is essential to consider installing a pressure reducing or limiting valve The manufacturer or supplier must provide clear installation instructions for the pressure reducing valve and highlight the potential flow reduction effects associated with these devices.

The instruction manual must state that the rated capacities provided are based on specific test conditions Actual in-service capacity may vary, being either higher or lower, influenced by factors such as influent water quality, flow rate, influent water pressure, and the continuity of flow.

In the absence of a flow regulation device, the instruction manual must offer guidance on managing the flow rate through the filter when the supply pressure exceeds the maximum specified working flow range set by the manufacturer.

Claims regarding filter rated capacity must rely on the lowest substance-specific rated capacity value Additionally, any claims about the reduction of substances not explicitly addressed by the performance requirements of this European Standard must be distinctly separated from claims of conformity with the Standard Such claims should be supported by tests conducted in accordance with the guidelines outlined in Annex C.

To maintain optimal treated water quality, it is essential to replace the cartridge after a designated time period following its installation, regardless of its current condition.

Marking

The direction of flow of the water through the filter housing shall be permanently and clearly marked on the filter housing It shall be visible after installation.

Labelling

Filter housing

A label shall be permanently fixed to the filter housing and be clearly legible in operation after the filter has been installed It shall include, as a minimum, the following information:

 manufacturer’s or supplier’s or importer’s name and contact details;

 working flow range, in l/h, for a specified pressure drop, in kPa;

 maximum and minimum working pressures, in kPa;

 maximum and minimum water temperature, in °C;

 filter type/designation (part number).

Filter cartridge

The filter cartridge packaging shall provide the following information:

 maximum differential pressure, in kPa;

 frequency of filter cartridge replacement

The filter cartridge label shall clearly specify the manufacturer, filter type and designation of the housing(s) for which the filter element meets the requirements of this standard.

Packaging

Example of test rig for substance reduction testing

TEST WATER Start Final pH

Percent Reduction Flow rate (l/min)

This standard addresses the application of active media filters for the supplementary treatment of water supplies that have been previously treated to comply with the European Directive on drinking water quality.

Manufacturers and suppliers of equipment may seek to reduce specific substances to improve aesthetic qualities and provide protection against occasional fluctuations in water quality.

The assessment of substance removal involves using challenge water spiked to contain ten times the regulated value or, in the absence of such a value, the WHO Guideline value For chemicals lacking both regulated and Guideline values, a concentration must be established that poses no significant health risk to consumers over a lifetime of exposure, based on toxicity data and WHO calculation methods This evaluation should be performed by an independent and competent institute, separate from the filter manufacturer, with testing conducted using the chemical spiked at ten times the determined health-based concentration.

This annex provides crucial guidelines for the installation, operation, maintenance, and repair of active media filters, translating the general requirements outlined in EN 15161 into specific directives tailored for these filters.

Proper operation and maintenance of the device are crucial for ensuring effective and hygienic performance Devices that meet this European Standard must include all necessary information and instructions for their operation and maintenance The following details are required as a minimum, but this list is not exhaustive and does not replace the supplier's instructions.

According to this European Standard, the term "supplier" refers to the organization named on the product being sold, which may or may not be the actual manufacturer.

Choosing the right device that meets performance expectations and is suitable for the installation site is crucial Key installation and operation requirements should be provided at the point of purchase through brochures, specification sheets, or clear labeling on the product packaging This information must outline installation limitations regarding dimensional and environmental conditions, such as ambient temperature Additionally, it should offer guidance on the frequency of maintenance and accessibility needs, as well as specify water supply requirements, including pressure limitations and pipe sizes, along with the proximity to essential services like electric power and drainage facilities.

The installation instructions included with the device must feature a comprehensive list of all components provided, as well as any additional items required for a successful installation, such as a pressure reducing valve Furthermore, the specifications of these supplementary components should be clearly outlined.

The assembly instructions must provide a step-by-step procedure for connecting the components to the water supply and any additional services needed Clear guidelines should specify the dimensional and orientation requirements necessary for positioning the device and its accessories, ensuring sufficient access for operation and maintenance at the selected installation site.

In addition, the installation instructions shall include a checklist to ensure that the device is located:

 in a suitable location (e.g clean, well ventilated, adequately illuminated and protected against pests, frost, physical damage, chemical damage) within the domestic water distribution system;

 as close as possible to the existing distribution system and to other necessary services;

 avoiding or minimising dead-legs that can encourage stagnation

NOTE Drinking water for cleaning purposes and appropriate waste disposal facilities should be available

The device as supplied shall be labelled, with a durable waterproof label mounted on, or close to, the device, with the information required in accordance with 7.3.1

The instructions shall contain a procedure for putting the device into service including as a minimum:

 initial filling and pressurisation of the system;

 flushing requirements (time and/or volume);

 setting-up , e.g flow rate adjustment (in the absence of flow regulation);

 performance check (using control kit, if provided)

The instructions shall provide advice on checking performance and, where a control kit is provided, detailed instructions on the use of the kit and interpretation of the results

When commissioning is performed by a third party, it is essential that they provide the owner with all printed instructions for device use, including testing procedures, frequency, and actions based on testing results Additionally, the third party must hand over the updated logbook and any control kit supplied for monitoring the device's performance.

NOTE 1 Depending on the intended application of the active media filters, the control kit could include one or more of the following:

 free and total chlorine measurement;

In its most basic form, a logbook can be a single adhesive-backed sheet that attaches to the device, allowing for at least the recording of cartridge change dates.

To ensure optimal performance of the device during daily operations, users should follow a checklist that outlines essential procedures and checks This checklist must include, at a minimum, clear instructions for routine assessments.

 to be alert to the treated water quality with respect to the treatment expectations (e.g taste, odour, visible quality of the treated water);

In order to maintain optimum performance of the device, the instructions shall include procedures and checks to be made at specified time intervals, including instructions:

 to carry out the replacement procedure of the active media cartridge in accordance with the instructions (to include dismantling, cartridge disposal, cleaning, reassembly, preconditioning etc., as appropriate);

 to record on the logbook the date of the active media cartridge replacement;

 to inspect the disassembled system for signs of leakage or damage;

 to call for repair in the event that any defect or failure is noticed (e.g taste, odour, colour in the treated water)

The instructions shall provide guidance on the hygiene precautions necessary for any maintenance operations that require dismantling of the system

NOTE An example of good practice is as follows:

Hygiene is crucial during maintenance operations that involve dismantling the system and exposing water contact parts to prevent contamination It is recommended to use disposable gloves to avoid personal contamination, and any tools that may touch wetted parts should be cleaned and disinfected according to the provided instructions Additionally, the spent cartridge must be disposed of carefully, while the replacement cartridge should remain sealed in its protective wrapping until it is needed.

Regular maintenance and prompt replacement of consumable components are crucial for optimal device performance Neglecting to replace a worn-out or clogged cartridge can lead to decreased efficiency in achieving the specified parameters and reduced flow rates.

Consistent usage of the water system is crucial to prevent off-tastes in treated water To maintain water quality, it is essential to flush the system before reuse if it has been inactive for several weeks or longer.

Ngày đăng: 14/04/2023, 08:14